Power One AURORA PVI-10.0/12.5-OUT-xx, AURORA PVI-3600-OUTD-IT Operation And Installation Manual

Page 1
AURORA
Photovoltaic Inverters
INSTALLATION AND OPERATOR'S
Model number: PVI-10.0/12.5-OUT-xx PVI-3600-OUTD-IT Rev. 1.2
®
Page 2
Operation and installation manual Page 2 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
REVISION TABLE
Document
Revision
Author Date Change Description
1.0 Federico Mastronardi
21/07/2008 First release
1.1 Federico Mastronardi
06/08/2008 - Removed paragraphes on
display menù
- Updated text
- Updated paragraph 2.2
1.2 Federico Mastronardi
01/09/2008 - Updated automatic cut-out size
(pag.26)
- Updated output values
SAVE THESE INSTRUCTIONS !
IMPORTANT SAFETY INSTRUCTIONS
POWER-ONE: Reproduction and disclosure, even partially, of the contents of this
manual are strictly forbidden without prior authorization of Power­One.
Page 3
Operation and installation manual Page 3 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important safety and operational instructions that must be accurately understood and followed during the installation and maintenance of the equipment. To reduce the risk of electrical shock hazards, and to make sure the equipment is safely installed and commissioned, special safety symbols are used in this manual to highlight potential safety risks and important safety information. The symbols are:
WARNING: the paragraphs highlighted by this symbol contain processes and instructions that must be absolutely understood and followed to avoid potential danger to people.
NOTE: the paragraphs highlighted by this symbol contain processes and instructions that must be rigorously understood and followed to avoid potential damage to the equipment and negative results.
The equipment is provided with several labels, some of them with a yellow background, which are related to safety issues. Make sure to read the labels and fully understand them before installing the equipment. The symbols are:
Equipment grounding conductor (Main grounding protective earth, PE)
Alternate Current (AC) value
Direct Current (DC) value
Phase
Grounding (Earth)
Page 4
Operation and installation manual Page 4 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
IMPORTANT SAFETY INFORMATION AND SAFETY STANDARD
FOREWORD
¾ The installation of Aurora must be performed in full compliance with national and
local standards and regulations.
¾ AURORA features no spare parts.
For any maintenance or repair please contact the nearest authorized repair center. Please contact your reseller if you need to know the nearest authorized repair center.
¾ Read and understand all the instructions contained in this manual and become
familiar with the safety symbols in the relevant paragraphs before you install and commission the equipment.
¾ The connection to the distribution grid must be done only after receiving approval
from the distribution utility as required by national and state interconnection regulations, and can be done only by qualified personnel.
¾ Keep the whole surface of the photovoltaic panel covered with material opaque to
solar radiation before connecting panel to equipment; this will ensure that no dangerous high voltage is present at AURORA connection cables.
GENERAL
During inverter operation, some parts could be live, some not properly insulated and, in some cases, some parts can move or rotate, or some surfaces may be hot. Unauthorized removal of the necessary protections, improper use, wrong installation or wrong operation may lead to serious damage to people and objects. Transport, handling, installation, start-up and maintenance must be performed by qualified and trained personnel (all accident prevention rules in force in the user's country must be observed! ! !). According to these basic safety rules, qualified and trained people have skills for the assembling, start-up and operation of the product, as well as the necessary requirements and qualifications to perform such operations.
Page 5
Operation and installation manual Page 5 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
ASSEMBLY
Devices shall be assembled and cooled according to the specifications mentioned in the relevant literature. In particular, during transport and handling, parts shall not be bent and/or the insulation distances shall not be changed. Devices shall not get in contact with any electronic components or connection terminals. Electrical parts must not be mechanically damaged or broken (potential health risk).
ELECTRICAL CONNECTION
When working with the inverter energized, comply with all prevailing national regulations on accidents prevention. Electrical connections shall be carried out in accordance with the applicable regulations, such as conductor sections, fuses, PE connection.
OPERATION
Systems with inverters shall be provided with further control and protective devices in compliance with the corresponding prevailing safety rules, such as those relating to the compliance with technical equipment, accident-preventing regulations, etc. Any calibration change shall be made using the operational software. After disconnecting the inverter from distribution grid, wait for capacitors to discharge before servicing/touching any live part and electric connection. Comply with all corresponding marks and symbols present on each device. During operation, make sure that all covers and doors are closed.
MAINTENANCE AND SERVICING
Comply with manufacturer's instructions.
SAVE ALL DOCUMENTS IN A SAFE PLACE !
Page 6
Operation and installation manual Page 6 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
PVI-10.0/12.5-OUTD-xx
This document applies to the above-mentioned inverters only.
Fig.1 - Product label
The product label on the inverter provides the following information:
1) Manufacturing Part Number
2) Model Number
3) Serial Number
4) Week/Year of Manufacture
Page 7
Operation and installation manual Page 7 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
TABLE OF CONTENTS:
1 FOREWORD ............................................................................ 10
1.1 PHOTOVOLTAIC ENERGY ............................................................... 10
2 DESCRIPTION OF THE SYSTEM ....................................... 11
2.1 KEY ELEMENTS OF A PHOTOVOLTAIC SYSTEM: “STRINGS” AND
“ARRAYS” ......................................................................................................... 11
2.2 AVAILABLE VERSIONS............................................................................ 14
2.3 DATA TRANSMISSION AND CHECK......................................................... 16
2.4 AURORA TECHNICAL DESCRIPTION..................................................... 16
2.5 PROTECTIVE DEVICES............................................................................. 18
2.5.1 Anti-Islanding.................................................................................... 18
2.5.2 Ground fault of the photovoltaic panels ............................................ 18
2.5.3 Further Protective Devices................................................................ 18
3 INSTALLATION...................................................................... 19
3.1 PACKAGE INSPECTION............................................................................ 19
3.2 INSPECTING PACKAGE CONTENTS........................................................... 20
3.3 SELECTING THE PLACE OF INSTALLATION .............................................. 21
3.4 WALL MOUNTING................................................................................... 22
3.5 BEFORE PERFORMING THE ELECTRICAL CONNECTIONS .......................... 25
3.6 ELECTRICAL CONNECTIONS ................................................................... 28
3.7 PROCEDURE FOR GAINING ACCESS TO INTERNAL TERMINAL BOARDS
BY REMOVING THE FRONT PANEL ......................................................................... 33
3.8 CHANGING THE LITHIUM BATTERY OF THE TYPE CR2032 ...................... 34
3.9 CHANGING THE MEMORY ....................................................................... 34
3.10 CHANGING THE RS485 PIGGYBACK BOARD ........................................... 35
4 START-UP ................................................................................ 36
5 MONITORING AND DATA TRANSMISSION................... 37
5.1 USER INTERFACE MODE.......................................................................... 37
5.2 TYPES OF AVAILABLE DATA ................................................................... 39
5.2.1 Real-time operation data ................................................................... 39
5.2.2 Data stored inside the unit................................................................. 40
5.3 LED INDICATORS ................................................................................... 41
5.4 ERROR CODES AND MESSAGES ............................................................... 44
Page 8
Operation and installation manual Page 8 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5 LCD .......................................................................................................47
5.5.1 System connection to the grid .............................................................47
5.5.2 Error Messages ..................................................................................49
5.5.3 First stage, checking the various electrical parameters.....................49
5.5.4 Main menu..........................................................................................53
5.5.5 Statistics .............................................................................................53
5.5.5.1 Lifetime ...................................................................................54
5.5.5.2 Partial....................................................................................... 54
5.5.5.3 Today....................................................................................... 54
5.5.5.4 Last 7 days............................................................................... 55
5.5.5.5 Last Month...............................................................................55
5.5.5.6 Last 30 days.............................................................................55
5.5.5.7 Last 365 days...........................................................................55
5.5.5.8 User period .............................................................................. 56
5.5.6
Settings...............................................................................................57
5.5.6.1 Address ....................................................................................57
5.5.6.2 Display set ...............................................................................58
5.5.6.3 Service ..................................................................................... 59
5.5.6.4 New password ......................................................................... 59
5.5.6.5 Cash ......................................................................................... 59
5.5.6.6 Time......................................................................................... 59
5.5.6.7 Language .................................................................................60
5.5.6.8 START voltage........................................................................60
5.5.6.9 Alarm.......................................................................................60
5.5.6.10 Remote control....................................................................61
5.5.6.11 UV Prot.time.......................................................................62
5.5.6.12 Alarm Message ...................................................................62
5.5.7
Info .....................................................................................................63
6 DATA COMMUNICATION AND CHECK ......................... 64
6.1 CONNECTION THROUGH RS-485 SERIAL PORT OR WITH RJ12
CONNECTORS ........................................................................................................ 64
6.1.1 RS-485 Serial Port..............................................................................64
6.1.2 RJ12 Connectors ................................................................................65
6.1.3 Daisy chain .........................................................................................66
6.2 ACCURACY OF MEASURED VALUES.........................................................68
7 TROUBLESHOOTING........................................................... 70
Page 9
Operation and installation manual Page 9 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
8 SPECIFICATIONS .................................................................. 72
8.1 INPUT VALUES........................................................................................ 72
8.2 OUTPUT VALUES .................................................................................... 75
8.3 GRID PROTECTION FEATURES................................................................. 76
8.4 GENERAL FEATURES .............................................................................. 76
8.5 POWER DERATING ................................................................................. 77
8.6 NOTE ABOUT THE DIFFERENTIAL PROTECTION BUILT IN THE P
OWER-ONE AURORA INVERTERS........................................................................ 79
Page 10
Operation and installation manual Page 10 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
1 FOREWORD
This document contains a technical description of AURORA photovoltaic inverter so as to provide the installer and user all the necessary information about installation, operation and use of AURORA.
1.1 PHOTOVOLTAIC ENERGY
Industrialized countries (greater energy consumers) have been experimenting energy­saving methods and reduced pollutant levels for many years thanks to the energy­conversion process. This may be possible through a shrewd and rational consumption of well-known resources, and also by looking for new forms of clean and not exhaustible energy. Regenerating sources of energy are fundamental to solve this problem. Under these circumstances, solar energy exploitation to generate electrical (photovoltaic) energy is becoming more and more important world-wide. Photovoltaic energy, in any case, is of great advantage to the environment because the radiated energy we receive from the sun is transformed directly into electrical energy without any combustion process and without producing any pollution.
Page 11
Operation and installation manual Page 11 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
2 DESCRIPTION OF THE SYSTEM
The AURORA inverter is capable of feeding a power grid using the power generated by photovoltaic panels. Photovoltaic panels transform the sun-radiated energy into electrical energy in the form of direct (DC) current (through a photovoltaic field, also known as PV generator). In order to utilize this energy and feed it back to the distribution grid, this energy shall be turned into alternating (AC) current. Aurora does this conversion, also known as DC to AC inversion, in a very efficient way, without using rotating parts but just static power electronic devices. When used in parallel with the grid, the alternate current generated by the inverter is directly fed to the household distribution circuit, which is in its turn also connected to the public power distribution grid. The solar energy system powers all connected electric items: lighting, household appliances, etc. When the photovoltaic system is not generating sufficient energy, the power required to ensure proper operation of connected loads is taken from the public power grid. While if the produced energy is too much, it is directly fed to the grid, thus becoming available to other users. According to national and local standards and regulations the produced energy can be sold to the grid or credited to the user against future consumption, thus granting a great saving of money.
2.1 Key elements of a photovoltaic system: “STRINGS” and “ARRAYS”
The so-called STRINGS technology has been developed in order to reduce the installation costs of a photovoltaic system as much as possible. These costs are mainly related to the wiring operations on inverter DC side and the consequent distribution on the AC side. A photovoltaic panel is composed of many photovoltaic cells assembled on the same mount. A STRING is composed of a certain number of panels electrically connected in series. An ARRAY is composed by one or more strings connected in parallel. Larger photovoltaic systems may be implemented by using several arrays connected to one or more AURORA inverters. The greater the number of panels in each string, the lower the cost and the less complex the wiring connections of the system.
Page 12
Operation and installation manual Page 12 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig.2 - Array Composition
WARNING: Aurora DC voltage input shall not exceed 850 Vdc or
damages to the equipment could result. Overvoltage up to 900 Vdc is allowed for 2 hours per day. At any rate, exceeding 850 Vdc input causes an alarm warning by AURORA.
NOTE: The minimum input voltage required to start up AURORA is 200 Vdc; a certain voltage is required to start the grid connection sequence (can
be set from 250 Vdc to 500Vdc) and default setting is 360 Vdc. Once connected, Aurora will transfer power to the distribution grid for any input DC voltage value, between 70% of set starting voltage and 850 Vdc.
Page 13
Operation and installation manual Page 13 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
The total current of an array must also be within the capability limits of the inverter. For AURORA, the maximum current from any input can never exceed 18 Adc. AURORA PVI-10.0/12.5-OUTD-xx models can serve two separate arrays. If the photovoltaic system exceeds the capacity of a single inverter, it is possible to add more AURORA inverters to the system and connect every one of them to a suitable section of the photovoltaic field on Dc side, as well as to distribution grid on Ac side. Each Aurora inverter will work independent of the others and will output to the grid the maximum power available from its own section of the photovoltaic panels. There are several factors and considerations to be taken into account when designing a photovoltaic system, such as the type of panels, available room, location, long-term target output, etc. The system configurator available on Power-One's web site at www.power-one.com
may help in sizing a photovoltaic system.
Fig.3 - Simplified diagram of a photovoltaic system
AC disconnect
DC disconnect
Page 14
Operation and installation manual Page 14 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
2.2 Available versions
PVI-10.0/12.5-OUTD PVI-10.0/12.5-OUTD-FS
Models ending by FS-IT are supplied with built-in DC switch 1000V, 25A and protection fuses as shown in Fig.3B.
Fig.3A - Inverter function chart with no built-in DC switch.
Page 15
Operation and installation manual Page 15 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig.3B - Inverter function chart with built-in DC switch and fuses.
DC/AC
Inverter
A
C
Output
+ PV Input 1
- PV In
p
ut 1
+ PV In
p
ut 2
- PV Input 2
DC
PVI-10.0-OUTD-FS / PV I - 12 .5-OUTD-FS
- PV Input
- PV Input
- PV Input
+ PV Input + PV In
p
ut
+ PV In
p
ut
- PV Input
- PV Input
- PV Input
+ PV Input + PV In
p
ut
+ PV In
p
ut
MPPT 1
MPPT 2
10A - 900V
N
U V
W
Page 16
Operation and installation manual Page 16 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
2.3 Data Transmission and Check
When more than one inverter is used, remote monitoring can be implemented through a sophisticated communication system based on an RS-485 serial interface. An optional Aurora Easy-Control system is also available for remote monitoring via the Internet, analog modem or GSM digital modem.
2.4 AURORA Technical Description
Figure 4 shows a block diagram of AURORA. The main blocks are Dc-Dc input converters (also called “boosters”) and the output inverter. Both DC-DC converters and output inverter operate at a high switching frequency to enable a compact design and relatively low weight. This version of AURORA does not include a transformer, i.e. with no galvanic insulation between input and output. Without the transformer, conversion system efficiency is further enhanced. Moreover AURORA is equipped with protections to guarantee safe operation and compliance with safety standards, even without the transformer, as described in the paragraph about protections.
Fig.4 - Block diagram of AURORA
Page 17
Operation and installation manual Page 17 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
The block diagram shows model AURORA PVI-10.0/12.5-OUTD-xx with its two input Dc-Dc converters and each converter is dedicated to a separate array with independent Maximum Power Point Tracking (MPPT) control. This means that the two arrays can be installed in different positions and orientations. Each array is controlled by an MPPT control circuit. In the wind version, the two converters are connected in parallel to rectifier output. Thanks to its high efficiency and generously sized heat sink, the AURORA inverter provides maximum power operation in a broad range of ambient temperatures. The inverter is controlled by two independent DSPs (Digital Signal Processors) and one central microprocessor. Connection to the distribution grid is then monitored by two independent computers, complying with the electrical standards both concerning system power supply and safety. AURORA operating system communicates with the relevant components to analyse data. This process ensures optimal performance levels of the whole units, as well as a high efficiency under all insolation and load conditions, always in full compliance with the applicable directives, standards and regulations.
Page 18
Operation and installation manual Page 18 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
2.5 Protective devices
2.5.1 Anti-Islanding
When the local power distribution grid fails due to a fault or when the equipment is shut down for maintenance operations, Aurora shall be physically disconnected under safety conditions, so as to protect the people working on the grid, in full compliance with the applicable prevailing national standards and regulations. To avoid any possible islanding operation, Aurora is provided with an automatic disconnection protective system called “Anti-Islanding”. The AURORA PVI-10.0/12.5-OUTD-xx
model is equipped with a state-of-the-art
anti-islanding protection system certified to the following standards and regulations:
¾ CEI 11-20 and ENEL DK-5940 Regulation (in Italy)
2.5.2 Ground fault of the photovoltaic panels
This version of AURORA shall be used with panels connected in a “floating” way, i.e. with positive and negative terminal not connected to the ground. A top-notch ground fault protection circuit constantly monitors the ground connection and turns off AURORA when a ground fault is detected, indicating ground fault condition through a red LED on the front panel. AURORA inverter is equipped with a terminal for system ground lead; please refer to section 3.6 (step 3) for further details.
NOTE: For more details of AURORA shutdown or possible causes of malfunction, please refer to sections 5.3 and 5.4
2.5.3 Further Protective Devices
Aurora is equipped with additional protections to guarantee safe operation under any circumstances. The protections include:
¾ constant monitoring of grid voltage to ensure that voltage and frequency remain
within the specified operational limits (in accordance with DK5940);
¾ inner temperature control to automatically limit the power any time this is
necessary to avoid unit overheating (heatsink temperature 70°C [158°F]).
Many control devices are fitted to AURORA making its structure redundant, but at the same time ensuring a perfect and fully safe operation.
Page 19
Operation and installation manual Page 19 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3 INSTALLATION
WARNING: The electrical installation of AURORA must be performed in
compliance with applicable local and national standards and laws.
WARNING: The connection of AURORA to the electrical distribution grid must be performed only after receiving authorization from the utility that operates the grid.
3.1 Package Inspection
NOTE: The distributor delivered your AURORA to the carrier safely
packaged and in perfect condition. Upon acceptance of the package, the
carrier assumes responsibility for its safe delivery. In spite of careful handling, transport damage to package or its content is always a possibility.
The customer is encouraged to perform the following checks:
¾ Inspect the shipping box for apparent damage, such as holes, cracking or any sign
of possible damage to its contents.
¾ Describe any damage or shortage on the receiving documents and have the
carrier sign his/her full name.
¾ Open the shipping box and inspect the contents for internal damage. While
unpacking, be careful not to discard any equipment, parts or manuals. If any damage is detected, call the delivering carrier to determine the appropriate action. Save all shipping material for the event the carrier sends an inspector to verify damage!
¾ If the inspection reveals damage to the inverter call your local supplier or the
authorized distributor. They will determine if the equipment should be returned for repair. They will also provide instructions on how to get the equipment repaired;
¾ It is the customer's responsibility to file a claim with the carrier. Failure to file a
claim with the carrier may void all warranty service rights for any damage;
¾ Carefully store away AURORA original packaging since it shall be used in case
it is necessary to ship it for repair.
Page 20
Operation and installation manual Page 20 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3.2 Inspecting package contents
Description Quantity (No.)
AURORA inverter 1
Bag containing: 5 screws 6.3x70, 5 blocks SX10, 5 washers M6, 1 fairlead M20, 1 fairlead M40, 2 cables AWG12 for jumpers, 1 seal type 36A3M20, 1 cylinder TGM58, 1 wrench Torx20, 1 nut 1143M40N, 6 Male MULTICONTAC counterparts, 6 Female MULTICONTAC counterparts. 6 Multicontact positive caps and 6 Multicontact negative caps, already assembled to the inverter
1
One copy of this manual 1
One certificate of warranty 1
CD-ROM with communication software 1
Page 21
Operation and installation manual Page 21 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3.3 Selecting the place of installation
Place of installation should be selected based on the following considerations:
¾ AURORA shall be set at a suitable height from the ground to enable easy readout
view of the display and the state LEDs.
¾ Select a well ventilated place sheltered from direct sun radiation. Choose a place
that allows unobstructed air flow around the unit.
¾ Allow sufficient room around the unit to enable easy installation and removal of
the object from its mounting surface.
¾ Hardware and software maintenance is mostly done from the front panel. It is then
necessary to easily gain access to this side, or you will have to remove the unit from its mounting surface.
The following figure shows the recommended minimum clearances around the inverter:
Fig.5 - Place of installation - Minimum clearances around AURORA
200mm (8”)
150mm (6”)
Page 22
Operation and installation manual Page 22 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3.4 Wall mounting
AURORA shall be mounted in a vertical position, as shown in figure 6. In the package you will find a kit consisting of 5 steel screws 6.3x70 (with 5 M6 washers) and 5 blocks SX10 necessary to fasten the metal bracket onto a wall. Screws and blocks can be fitted into the 3 holes provided onto the metal bracket (Part C) and then into the two holes available on inverter bottom (Part B)
WARNING: fasten bracket horizontally on wall, its side provided with springs shall be facing up, while the side with mounting holes shall be facing down.
The diameter of the holes to be drilled on the wall is 10 mm, and minimum depth is 75mm. Installer shall use suitable mounting material, according to the wall material. It is recommended to always use stainless steel screws.
Fasten AURORA to springs (Part D) located on bracket top part, by means of the metal mount fastened to inverter back plate top part. This metal plate features some drafts at the point where bracket springs fasten (Part A). Once inverter top part is fixed, fasten the bottom part by fitting the screws in the provided holes.
AURORA FRONT END AURORA BACK
Part A
Part B
Page 23
Operation and installation manual Page 23 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig.6 - AURORA wall-mounting
NOTE: Ensure Aurora is not exposed to direct sun radiation or other external
heat sources, including heat from units below it (see fig.7). Indeed, the heat generated by the inverters of the bottom rows could increase ambient temperature to the detriment of the inverters located in the top rows. At temperature above 50°C, output power of the top row units could be derated.
Derating is more marked in case of high output power and high ambient
temperature. For proper cooling, make sure to install AURORA so as to allow unobstructed air flow (for instance, never with the front panel facing a solid surface).
Part A
Part C
Part D
Part B
Part D
Part C
Page 24
Operation and installation manual Page 24 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
RECOMMENDED POSITION
Fig.7 - Recommended installation layout of Aurora inverters
NOTE: Although the unit can also be installed in a slanted position (see fig.
8), pay utmost attention since in this case performance could be reduced (Derating), due to worse heat sinking.
WARNING: Unit surface may become very hot to the touch during operation. DO NOT touch unit surface to avoid severe burns.
Fig.8 - Mounting in slanted position
Deratin
g
- 5 °
0
°
Deratin
g
Derating
NO Deratin
g
Page 25
Operation and installation manual Page 25 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3.5 Before performing the electrical connections
WARNING: The electrical connections can be made only after AURORA
is firmly secured to the wall.
WARNING: The connection of AURORA to the electrical distribution grid must be performed by qualified operators and anyway only after receiving authorization from the utility that operates the grid.
WARNING: For a step-by-step description of the correct procedure, please read - and closely follow - the instructions provided in this section (and its subsections) and all safety warnings. Any operation non-complying with the instructions below could lead to operator/installer hazards and to equipment damage.
WARNING: Always respect the nominal ratings of voltage and current specified in section 8 (Technical Data) when designing your system. Please observe these considerations when designing the photovoltaic field:
¾ Maximum DC voltage input to each MPPT circuit: 850 Vdc. ¾ Maximum DC current input to each MPPT circuit: 18 Adc under any
condition.
WARNING: Check the National and local standard regulations to make sure your electrical installation design is in compliance with them.
NOTE: As shown in the standard assembly diagram (see Fig. 9), a
disconnect (thermal automatic cut-out) shall be installed on Ac output section, in-between AURORA and the distribution grid. The features of such a disconnect or automatic cut-out are 25 A and 440 V. It is possible to use a three-pole device (if the inverter is in three wire reading mode) or a four-wire device (if the inverter is in four wire reading mode).
Page 26
Operation and installation manual Page 26 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig.9 - Connection diagram
WARNING: When disconnecting AURORA from the grid, always open the
AC disconnect before the DC disconnect.
WARNING: When selecting the power supply cables for AURORA connection, please carefully consider nominal operating voltage, insulation voltage, maximum operating temperature, current density and flammability
rating. All of these values must comply with the maximum current density ratings required by applicable local rules.
A key consideration in cable selection is cable loss, as exceeding loss will lead to derating.
For connection to the distribution grid, maximum cross-section of leads to be mounted to terminal boards is 16 sq. mm for stiff cables and 10 sq. mm for Bowden cables. Supplied M40 fairlead diameter is within the range 19mm – 28mm.
Page 27
Operation and installation manual Page 27 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
On inverter bottom you can find, from right to left (see Fig. 10):
¾ 2 holes plugged off with sealed caps. Removing them you can gain access to the
connectors for data serial transmission, through RS485 line. A hole for input serial cable and the other one for the output cable (if any) (for connecting many inverters in a daisy-chain configuration, see Chapter 6).
¾ 2 holes plugged off with sealed caps. Remove them to route wires for remote
control / alarm warnings.
¾ 1 hole plugged off with sealed cap. Remove it to route a PE ground cable other
than the five-pole cable for AC connection (if any).
¾ Label for AC grid connection
Fig. 10 - Connections available on inverter bottom and relevant marking
WARNING: When making the electrical connections follow this exact
procedure to avoid exposure to dangerous voltages. Each step of the
procedure is explained in the following paragraphs. To disconnect AURORA, follow “Step 1/5 and 2/5”, and then disconnect both AC and DC connectors.
Page 28
Operation and installation manual Page 28 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3.6 Electrical Connections
Step 1/5: Open grid disconnect (Ac)
Step 2/5: Open photovoltaic field disconnect (Dc)
Step 3/5: Open the front panel removing the 6 safety bolts
Step 4/5: Connect AURORA to Ac grid disconnect
WARNING: use suitable low-impedance cables to connect AURORA to
AC disconnect.
WARNING: AURORA inverter shall be connected to AC disconnect by means of a five-pole cable: three phase cables, one neutral cable and a yellow-green cable for ground (PE).
1) Lay out the cable between AURORA and the AC disconnect
2) connect the three-pole cable to Aurora by means of the fairlead on the
mechanical parts
3) Connect the 5 cables as follows:
- Terminal for Protective Earth PE
- terminal R for Line R,
- terminal S for Line S.
- terminal T for Line T.
- terminal N for neutral.
Fig.11 - Terminal board for AC cables connections
Page 29
Operation and installation manual Page 29 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
WARNING: Do not reverse any phase and neutral as this might make the system unsafe to run and cause malfunctioning.
NOTE: If you have installed a meter between the AC disconnect and AURORA, follow the same procedure outlined above when connecting the
meter.
Step 5/5: Connect AURORA to Dc photovoltaic field disconnect
Power-One warmly recommends to use two separate arrays any time that it is possible, each one having a current capacity of less than 18 Adc, and to connect each array to an input section of AURORA inverter.
WARNING: Ensure that photovoltaic field voltage polarity matches the “+” and “-” symbols. Before connecting Aurora with the photovoltaic field, Power-One recommends to check, using a proper gauge, that the polarity
value and the voltage allowed value between positive and negative contacts are correct.
Follow this procedure to connect each single array:
1) Lay down the positive cable across DC connection device and
AURORA.
2) Fit cable end into counterpart of Multicontact connector (not supplied).
3) Connect the positive cable to AURORA.
4) Lay down the negative cable across DC connection device and
AURORA.
5) Fit cable end into counterpart of Multicontact connector (not supplied).
6) Connect the negative cable to AURORA.
Page 30
Operation and installation manual Page 30 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
WARNING: In some cases the system could consist of one array only. In such a case, if array power output is lower than maximum capacity of one
AURORA section (see specifications chart) and if array current capacity is below 18 Adc, the array could be connected just to IN1 section. To avoid any problems when assessing panels electric insulation features, it is recommended to short-circuit the inputs of the second section (IN2), by connecting a cable to the relevant terminals inside inverter board, as shown in Fig. 13. To gain access to the board you shall remove the panel on Aurora front
Fig.12 - Connections available on a brand new unit
Page 31
Operation and installation manual Page 31 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig.13 - Connections necessary for short-circuiting channel 2
WARNING: While, if array power output or current capacity exceed
maximum capacity of an inverter input section, it is necessary to connect in
parallel the two sections by wiring two jumpers across terminal board terminals; it is possible to reach it after removing the cover, as described under 3.7. The cables to make said jumpers, of 6 sq. mm cross-section (AWG10) shall be connected across –IN1 and –IN2 terminals for the negative, and across +IN1 and +IN2 terminals for the positive, respectively, as shown in Fig.14. Moreover, it is necessary to set up the inverter to work with two sections connected in parallel (one string), by positioning the switch indicated in fig. 15 to “PAR” position
Page 32
Operation and installation manual Page 32 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig.14 - Connection/set-up of the two channels in parallel
Fig.15 - Connection/set-up of the two channels in parallel
Page 33
Operation and installation manual Page 33 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3.7 Procedure for gaining access to internal terminal boards by removing the
front panel
WARNING: Shock hazard! Before removing the panel, disconnect
AURORA at both the AC and DC side and allow at least 5 minutes for the internal capacitors to discharge.
Loosen the 6 screws shown in figure 16 using the supplied torx screwdriver and remove the front panel.
Fig.16 - AURORA with front panel
After putting back the panel, tighten the screws to at least 1.5Nm (13.2 in-lbs) to ensure sealing.
1
3
2
4
5
6
Page 34
Operation and installation manual Page 34 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3.8 Changing the lithium battery of the type CR2032
Aurora contains a lithium battery of the type CR2032. When battery is nearly flat a message is displayed on LCD to warn about battery state. Remove Aurora front panel (see fig.16) and this battery is in view. The battery can not
be inserted straight onto its mount, you need to fit it from the side (side A), tilted by about 30°. The component will settle into battery mount until finding its correct position.
Fig.17 - AURORA battery
WARNING: This component should only be replaced by qualified
personnel.
3.9 Changing the memory
All log data about system production are stored in this memory. Should it be necessary to change the inverter, it is possible to simply remove the memory from the old unit and installed into the new one. In this way you lose no data and can save the present and future daily information See fig.18
Fig. 18 - Inverter memory
Side A
Slide in tilted by about 30°
Page 35
Operation and installation manual Page 35 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
WARNING: This component should only be replaced by qualified personnel.
WARNING: Ensure to correctly insert memory connector pins into the connector welded onto board.
3.10 Changing the RS485 Piggyback board
It is possible to change the RS485 communication board. This board is mounted on the logic board in a Piggyback position.
Fig. 19 - RS485 board and arrow on board for assembly purposes
WARNING: This component should only be replaced by qualified
personnel.
WARNING: Ensure to correctly insert piggyback board connector pins into the connector welded onto board. Two arrows are printed on these
parts and indicate correct installation
Page 36
Operation and installation manual Page 36 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
4 START-UP
WARNING: Do not place any items on AURORA during operation.
WARNING: When the inverter is operating, do not touch the heat sink since
some parts may become very hot and cause burns.
Set up AURORA as follows:
1) Set the DC disconnect (for photovoltaic panels), outside of the inverter, to ON.
2) Set the AC disconnect (for distribution grid), outside of the inverter, to ON. The two devices can be closed using any sequence, there is no priority order.
3) After turning on these two switches, grid voltage and frequency parameters are checked and shall stay within operating range set by DK5940; if no failure arise from this check routine, the inverter starts the grid connection sequence. These steps are indicated by the green LED flashing, corresponding to the POWER indication, located on top of the display. This check routine could last for several minutes (minimum 30 seconds to maximum a few minutes), depending on grid conditions. During this routine, the LCD displays three pages in a sequence:
“Measuring Riso…” , connection in progress, with progress bar.
Grid voltage value and indication of whether within specified range or
not.
Grid frequency value and indication of whether within specified range or
not.
4) After this connection sequence, AURORA is activated and signals correct operation by a buzzer and the green LED that turns on steady. This means that solar radiation is sufficient to output power into the grid.
5) If grid check was negative, the unit shall repeat again the procedure until all parameters: voltage and frequency values as well as grid configuration are within specified range. During this stage, the green LED flashes.
Page 37
Operation and installation manual Page 37 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5 MONITORING AND DATA TRANSMISSION
5.1 User interface mode
AURORA inverter generally does not require any inspection since it works in automatic mode. When solar radiation is not sufficient to output power to the grid (for example at night) AURORA automatically disconnects, and sets to standby mode. The operating cycle is automatically resumed when solar radiation is sufficient. In this case the LEDs will indicate this state. AURORA inverter can give information about its operation by means of:
¾ LEDs ¾ LCD displaying operating data ¾ Data transmission via dedicated RS-485 serial line. Data can be collected by a PC
or data logger provided with an RS-485 port. When using the RS-485 line, it could be useful to use the serial interface converter AURORA RS-485/RS232 model number PVI-RS232485. It is equally possible to use an optional data logger AURORA Easy Control.
Page 38
Operation and installation manual Page 38 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig. 20 - Data Transmission Options
Page 39
Operation and installation manual Page 39 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.2 Types of available data
AURORA gives two types of data, readable through the suitable interface software.
5.2.1 Real-time operation dat a
Real-time operation data can be transmitted on request through communication lines and are not recorded inside the inverter. To transmit data to a PC, you can use the software AURORA Communicator, available free of charge on your installation CD (please check on www.power-one.com
for upgrades).
Available data are:
¾ Grid voltage (phase R, S and T) ¾ Grid current (phase R, S and T) ¾ Grid frequency ¾ Power output to the grid ¾ Voltage of photovoltaic field ¾ Current of photovoltaic field ¾ Heatsink temperature ¾ Serial no. Code ¾ Week of manufacture ¾ Firmware Rev. index ¾ Daily Energy
¾ System leakage current ¾
Total Energy
¾
Partial Energy
¾ Grid average voltage of the last 10 min. (phase R, S and T) ¾ Insulation resistance ¾ Date, Time ¾ Daily Peak Power ¾ Absolut Peak Power-One ¾ Clock State ¾ E
2
PROM memory state
Page 40
Operation and installation manual Page 40 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.2.2 Data stored inside the unit
AURORA stores the following data:
¾ Total counter for grid connection time ¾ Total counter for power output to grid ¾ Partial power counter (uses the same start time as partial time counter) ¾ Energy output to grid every 10 seconds in the last 8640 units of 10 seconds (on
average, recording covers more than 2 days)
¾ Partial counter for grid connection time (counter start time can be reset by means
of the software AURORA Communicator)
¾ Last 100 changes to grid connection parameters, with the indication of the
parameter code and new value. The first three types of data are displayed on the LCD and on RS-485 interface, while all the other types can only be viewed through the RS-485.
Page 41
Operation and installation manual Page 41 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.3 LED indicators
Next to the display there are three LEDs: the first on the left (POWER) indicates that the inverter works normally, the central one (FAULT) indicates a fault, while the one on the right (GFI) indicates a failure to the ground.
1. The green “Power” LED indicates that AURORA works correctly.
When the unit is started this LED flashes during grid check routine. If a valid grid voltage is detected, the LED stays on permanent, as far as there is enough solar radiation to activate the unit. If it is not so, the LED will go on flashing until solar radiation is sufficient for unit activation. At this stage, the LCD shows the message “Waiting sun….”
2. The yellow “FAULT” LED indicates that AURORA has detected a fault. The
problem is displayed.
3. The red “GFI” (ground fault) LED indicates that AURORA has detected a fault to
ground in photovoltaic field DC side. When this fault is detected, AURORA immediately disconnects from grid and the LCD shows the relevant error warning. AURORA stays in this state until the operator presses ESC to restart the grid connection sequence. If AURORA can not reconnect to the grid it is necessary to contact the authorised repair center to find and remove the cause of the fault.
Fig.21 - LED layout
The following chart shows all possible combination of LEDs activation according to AURORA operating state.
Page 42
Operation and installation manual Page 42 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Legend:
LED on
LED flashing
LED off
Any of the above
LED STATUS OPERATING STATUS COMMENTS
1
green: yellow: red:
AURORA automatic switch-off
Input voltage below 70% of the start-up voltage set for both inputs
2
green: yellow: red:
AURORA start-up, loading settings and waiting for grid check routine
It is a transition state due to the routine checking for all required operating conditions
3
green: yellow: red:
AURORA is powering the grid
The machine works normally (constant voltage or maximum power point tracking)
4
green: yellow: red:
Failure in the insulation system
Ground leakage detected
5
green: yellow: red:
Failure – fault!!! Fault can be internal
or an external failure, see warning on the LCD
6
green: yellow: red:
Internal ventilation failure
This condition indicates a failure of the internal ventilation.
7
green: yellow: red:
Grid disconnection Indicates that grid
connection is missing
Page 43
Operation and installation manual Page 43 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
NOTE: Not only each inverter state is signalled through the relevant LED
that comes on or flashes, but the AURORA LCD also displays a message that identifies the operation in progress or the detected fault/failure (see following paragraphs).
G Y R
1) Night-time mode
AURORA has switched off for the night; this happens when input
power is too low to power the inverter.
G Y
R
2) AURORA initialisation and grid check
The machine is initialising: inverter input power is sufficient;
AURORA checks that the required conditions for start-up are true (e.g.: input voltage, insulation leakage value, etc.) and starts grid check routine.
G Y
R
3) AURORA is powering the grid
Once all self-tests on electronic and safety parts are completed, the
machine starts grid connection sequence.
As already stated, in this stage AURORA automatically tracks and
analyses the maximum power point (MPPT) available from photovoltaic field.
G Y
R
4) Faulty insulation to ground
AURORA indicates that too low insulation leakage resistance was
detected.
The problem could be connected to an insulation fault in the
connection between photovoltaic field inputs and ground.
WARNING: it is extremely dangerous to personally try to fix the
fault. Carefully follow the instructions below; contact a qualified operator if you do not have the required training and experience to work in safe conditions.
How to proceed after an insulation fault warning
When the red LED turns on, try first of all to reset the warning by means of the multifunction ESC button, on the side of the LCD. If AURORA correctly reconnects to the grid, failure cause was temporary. It is recommended to have the system inspected by a specialized technician if this type of malfunction occurs quite often. If AURORA does not reconnect to the grid, it is necessary to set AURORA in safety conditions and cut power both on the DC side and the AC side, then contact the authorised repair centre to have the system repaired.
Page 44
Operation and installation manual Page 44 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
G Y
R
5) Failure-Fault Warning
Any time AURORA control system detects a failure or fault of
monitored system operation, the yellow LED turns on steady and the
LCD displays a message indicating the problem found.
G Y
R
6) Internal ventilation failure
Indicates that internal ventilation is not working properly. This should
not give any problems since the fan is only triggered in case of high
temperature and high output power.
G
Y R
7) Grid disconnection
When the system is duly activated and operating, and grid connection
is suddenly missing, for any reason, the yellow LED immediately turns
on steady and the green one flashes.
5.4 Error codes and messages
System status is identified through Warning messages or Errors appearing on the LCD. The tables below summarize the two types of messages that can be displayed.
MESSAGES indicate AURORA current state, they are not caused by a failure and do not require any action. They will no longer be displayed when normal conditions are restored. See W strings in the table below.
ALARM messages identify a possible fault of the equipment or of the connected parts. These messages will disappear as soon as the causes are removed, except for ground insulation faults in the photovoltaic field, which have to be corrected by qualified personnel. Usually, when an error message appears, an action is needed. This action will be managed as much as possible by Aurora or, in case this is not possible, Aurora will supply all the necessary helping information to the person who will have to carry out the maintenance operations to fix the fault on the equipment or system. See E strings in the table below.
Page 45
Operation and installation manual Page 45 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Message Error
Warning
Error
Type
Description
Sun Low W001 // Input Voltage under threshold
Input power below threshold (when off)
Input OC // E001 Input Overcurrent
Input UV W002 // Input Undervoltage
Input OV // E002 Input Overvoltage
Int.Error // E003 No parameters
No parameters
Bulk OV // E004 Bulk Overvolt ag e Int.Error // E005 Communication Error
Communication Error
Out OC // E006 Output Overcurrent Int. Error // E007 IGBT Sat Sun Low W011 // Bulk Undervoltage
Int.Error // E009 Internal Error
Internal Error
Grid Fail W003 // Grid Fail
Grid parameters incorrect
Int.Error // E010 Bulk Low Int.Error // E011 Ramp Fail
DC/DC Fail // E012 DcDc Error revealed by inverter
Inverter detected a DcDc failure
Wrong Mode // E013 Wrong Input setting (Single instead of dual)
Wrong input setup (single instead of dual)
Over Temp. // E014 Overtemperature
Excessive internal temperature
Cap. Fault // E015 Bulk Capacitor Fail
Bulk capacitors fault
Inv. Fail // E016 Inverter fail revealed by DcDc
Inverter failure detected by DcDc
Int.Error // E017 Start Timeout
Ground F. // E018 I leak fail
Leakage current error l
Page 46
Operation and installation manual Page 46 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Message Error
Warning
Error Type
Description
Int.Error // E019 Ileak Sensor fail
Leakage current error
Int.Error // E020 DcDc relay fail
DcDc relay fail
Int.Error // E021 Inverter relay fail
Inverter relay fail
Int.Error // E022 Autotest Timeout Int.Error // E023 Dc-Injection Error Grid OV W004 // Output Overvoltage Grid UV W005 // Output Undervoltage Grid OF W006 // Output Overfrequency Grid UF W007 // Output Underfrequency
Z Grid HI W008 // Z grid out of range
Impedance out of range
Int.Error // E024 Unknown Error
Internal Error
--------- // E025 Riso Low (Lo g Only)
Low insulation leakage (log only)
Int.Error // E026 Vref Error
Reference voltage error (VRef)
Int.Error // E027 Vgrid Measures Fault
Wrong grid voltage reading (VGrid)
Int.Error // E028 Fgrid Measures Fault
Wrong grid frequency reading (FGrid)
Int.Error // E029 Zgrid Measures Fault
Wrong grid impedance (ZGrid)
Int.Error // E030 Ileak Measures Fault
Wrong leak current reading (ILeak)
Int.Error // E031 Wrong V Measure
Wrong voltage reading V
Int.Error // E032 Wrong I Measure
Wrong current reading I
Fan Fail W010 // Fan Fail (No disconnection)
Fan failure (Log Only)
Int.Error // E033 UnderTemperature
Internal temperature
Page 47
Operation and installation manual Page 47 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Message Error
Warning
Error
Type
Description
// E034 Interlock Fail (Not Used) // E035 Remote Off
Remote switch-of f
// E036 Vout Avg
Average output voltage out of range
W012 // Clock Battery Low (No disconnection)
Clock battery low (not wor ki ng )
W013 // Clock Failure (No disconnection)
Faulty clock (not working)
5.5 LCD
5.5.1 System connection to the grid
The two-line Liquid Crystal Display is located on the front panel and shows:
9 Inverter operating status and statistics; 9 Service messages for operator; 9 Alarm messages and fault indications.
During regular operation, the display will cycle through available data. Screen pages change every 5 seconds, or you can manually scroll through them by pressing UP (2
nd
key on display) and DOWN (3
rd
key on display).
1) When the inverter is started, the two pages below are displayed:
2) While waiting for the connection, the following pages could be displayed:
- When system is checking grid connection “Missing Grid”, the yellow LED next to
the display is steady on and the green LED is flashing.
- When waiting for the sun, “Waiting Sun”, the green LED is steady on.
- When the conditions “Missing Grid” and “Waiting Sun” are met the inverter
connection occurs.
POWER-ONE
Initialing… Please wait
Missing Grid Waiting Sun
Page 48
Operation and installation manual Page 48 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
3) Indicates the number of seconds left before completing the check on voltage and frequency values measured at output. As far as the Italian rules are concerned, maximum time for these checks is 20 seconds while according to German standards it is 30 seconds.
4) Displays instant output voltage and gives information on whether this reading is within the allowed range.
5) Displays instant output frequency and gives information on whether this reading is within the allowed range.
6) If instant voltage reading -step 4)- and frequency reading -step 5)- are out of allowed range, the display will cycle through the following pages
-
Next connections (page 3)
- Vgrid (page 4)
- Fgrid (page 5)
7) Instant value for insulation leakage
Meas. Riso ……………………… In range
Fout 50,17 Hz In ran
g
e
Vout 233,8 V In ran
g
e
Next connections: 2 secs
Page 49
Operation and installation manual Page 49 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5.2 Error Messages
After the connection is established, the inverter runs a test cycle; if wrong values are found, the cycle is interrupted and an error code is displayed. To acknowledge the error, please refer to the chart under section 5.4. To customise the message to be displayed follow the programming procedure explained in section 5.5.6.15 “Alarm Message”. Until the error is rectified, the display will cycle through the following screens:
Once the error has been removed, the inverter resets all functions in progress and restarts the connection (section 5.5.2 System connection to the grid, item 2).
- Missing grid
- Waiting sun
5.5.3 First stage, checking the various electrical parameters
GENERAL ISSUES ABOUT THE USE OF DISPLAY KEYS:
During regular operation, the display will cycle through available data. Screen pages change every 5 seconds, or you can manually scroll through them by pressing UP (2
nd
key on display) and DOWN (3
rd
key on display).
In all cases, to go back to previous menu just press ESC (1
st
key on display).
Fig.22
Fig.23
Auto-scroll is indicated by 2 arrows in the top left corner of the display (Fig. 22). Scrolling can be locked by pressing
ENTER (4
th
key on display) and the lock symbol
is displayed (Fig.23).
Custom msg………
Type OUTD Part No………
S/N ………..…….. Firmware………… In ran
g
e
ERROR Code ……..
Page 50
Operation and installation manual Page 50 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
1A) If the procedures explained under section 5.5.1 gave positive outcome, the system continues with more check routines. The display will cycle through the following 13 pages, as described under “GENERAL ISSUES ABOUT THE USE OF DISPLAY
KEYS”.
2A) indicates the inverter serial number and revision index of loaded firmware.
3A)
E-day: Daily quantity of energy produced. $-day: Energy saved for the day. The value is expressed in the set currency.
4A)
E-tot: Total energy produced since installation E-par
: Partial energy produced since selected period
5A)
P-out: measured instant output power On display second line is the highest temperature of the 2 values: T-inv: inverter heatsink temperature T-boost. Heatsink temperature 6A)
Ppk: peak power maximum value reached since “partial” function was activated
Ppk W P
pk
-Day ………...W
Type OUTD PN------------
S/N--------- xxxxxx FW rel. C.0.1.1
E-day 0 Wh $-da
y
0.0 EU
R
E-tot ------------­E-
p
ar 0 KWh
P-out 0 W T-boost - °C
Page 51
Operation and installation manual Page 51 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Ppk Day: indicates peak power maximum value reached during the day. Count is reset when unit is switched off.
7A)
Vout R: measured instant value for the phase R voltage Vout Avg R: phase R voltage average value calculated in the last 10 minutes of inverter operation
The same page is then available for phase S and phase T.
8A)
Iout R: measured instant value for the phase R current Fout: measured instant value for the phase R frequency
The same page is then available for phase S and phase T.
9A)
Vin 1: instant value for the input voltage, measured at input 1 Iin 1: instant value for the input current, measured at input 1
10A)
Vin 2: instant value for the input voltage, measured at input 1 Iin 2: instant value for the input current, measured at input 1
When channels are connected in parallel, the previous two pages are summarised in one single page indicating the reading of Vin and Iin values.
Vin 2 0 V
I in 2 0.0 A
Vin 1 0 V
I in 1 0.0 A
Iout R 0.8 A Fout 50.18 Hz
Vout R 197 V Vout Av
g
R 0 V
Page 52
Operation and installation manual Page 52 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
11A)
Pin 1: instant value for the channel 1 input power Pin 2: instant value for the channel 2 input power
When channels are connected in parallel, the previous page only indicates Pin, without making the difference between input channels.
12A)
Riso: measured insulation leakage value. This parameter, unlike the other parameters described so far, is not an instant reading; this measurement is only taken upon inverter start-up. Ileak: measured leakage current value.
13A)
If all previous steps are OK, the inverter specified this on display first line, together with current date and time. In case of malfunction of the clock or other inverter parts that are “not vital for inverter operation” (the unit can still produce power), the problem will be displayed on display second line, instead of date and time. The error messages can be as follows:
- CLOCK FAIL indicates clock fault, contact assistance
- BATTERY LOW battery flat
- CLOCK FAIL is displayed when unit is first switched on or after changing the battery.
- FAN FAIL: contact the assistance
- MEMORY FAIL: Collected data are no longer stored. It is necessary to contact the assistance for servicing.
Inverter OK
Wed 17 Ma
y
11 23
Riso 0.0 Mohm Ileak 73 mA
Pin 1 0 W Pin 2 0 W
Page 53
Operation and installation manual Page 53 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5.4 Main menu
Once the above grid connection stages and electrical parameters check are completed, it is now possible to gain access to new pages that allow you to monitor inverter operation from various viewpoints. Press ESC (1
st
key on display) to open 3 new pages:
GENERAL ISSUES ABOUT THE USE OF DISPLAY KEYS:
- Press UP (2
nd
key on display) and DOWN (3rd key on display) to swap from one item
to another.
- Press ESC (1
st
key on display) to go back to previous session described under section
5.5.3.
- Press ENTER (4
th
key on display) to open sub-menu of the selected option.
5.5.5 Statistics
Select the STATISTICS menu and the following sub-menu will be displayed:
5.5.6
The display only shows 2 lines, use the side keys to scroll among the items or open every sub-menu of these items, as described under 5.5.3 GENERAL ISSUES ABOUT THE USE OF DISPLAY KEYS. Selected item is highlighted by an arrow on the left side, as shown below:
Lifetime
1.1.1
Par tial
1.1.2
Info Settings Statistics
Page 54
Operation and installation manual Page 54 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5.6.1 Lifetime
Select "Lifetime" to view the following information:
Time: Lifetime operation time E-tot: Lifetime energy output Val.: Money earned CO2: Quantity of CO2 saved if compared to fossil fuel
5.5.6.2 Partial
Select Partial to view the following information:
Time: Total operation time since counter was last reset * E-par: Total energy output since counter was last reset* PPeak: peak power value measured since “partial” counter was activated Val.: Money earned since counter was last reset* CO2: Quantity of CO2 saved if compared to fossil fuel since count was reset*
* All counters of this menu can be reset by pressing and holding ENTER (4
th
key on
display) for more than 3 seconds. After this time, you will hear 3 beeps.
5.5.6.3 Today
Select Today to view the following information:
E-day: Total energy output during the day Ppeak: Peak power achieved during the day.
E-day KWh Ppeak W Val. EUR CO2 Kg
Time h E-par KWh Ppeak W Val. EUR CO2 Kg
Time h E-tot KWh Val. EUR CO2 Kg
Page 55
Operation and installation manual Page 55 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Val.: Money earned during the day CO2: Quantity of CO2 saved if compared to fossil fuel in the current day
5.5.6.4 Last 7 days
Select Last 7 days to view the following information:
E-7d: Total energy output during the last 7 days Val. : Money earned during the last 7 days CO2: Quantity of CO2 saved if compared to fossil fuel in the last 7 days
5.5.6.5 Last Month
Select Last Month to view the following information:
E-mon: Total energy output during the month Val.: Money earned during the month CO2: Quantity of CO2 saved if compared to fossil fuel in the current month
5.5.6.6 Last 30 days
Select Last 30 Days to view the following information:
E-30d: Total energy output during the last 30 days Val. : Money earned during the last 30 days CO2: Quantity of CO2 saved if compared to fossil fuel in the last 30 days
5.5.6.7 Last 365 days
Select Last 365 Days to view the following information:
E-365d: Total energy output during the last 365 days Val. : Money earned during the last 365 days
E-365d KWh Val. EUR CO2 K
g
E-30d KWh Val. EUR CO2 Kg
E-mon KWh Val. EUR CO2 Kg
E-7d KWh Val. EUR CO2 Kg
Page 56
Operation and installation manual Page 56 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
CO2: Quantity of CO2 saved if compared to fossil fuel in the last 365 days
5.5.6.8 User period
Using this function you can measure accumulated energy saving in a given period. From “User period” page, press ENTER to open the following sub-menu:
Use keys on the display to set start and end date of the period to be considered:
¾ Use ENTER to move to the next field (from left to right) ¾ Use ESC to go back to the previous field (from right to left) ¾ Press ESC repeatedly to go back to the previous menus, as described under
5.5.3
Set date as follows:
¾ Press DOWN to scroll numbers backwards (from 31 to 1) ¾ Press UP to scroll numbers forward (from 1 to 31)
Set month as follows:
¾ Press DOWN to scroll months backwards (from December to January) ¾ Press UP to scroll months forwards (from January to December)
Should you set a wrong date, the following message will be displayed:
ERROR! Wrong date
Start 23 June End 28 August
User period
Page 57
Operation and installation manual Page 57 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5.7 Settings
Select SETTINGS from the Main menu (section 5.5.4) to display the initial screen (password screen):
The default password is 0000. The password may be modified using the display keys:
¾ Use ENTER to move to the next digit (from left to right) ¾ Use ESC to go back to the previous digit (from right to left) ¾ Press ESC repeatedly to go back to the previous menus, as described under
5.5.3
¾ Press DOWN to scroll numbers backwards (from 9 to 0) ¾ Press UP to scroll numbers forward (from 0 to 9)
After entering the correct password, press ENTER to gain access to the information contained in this section:
The display only shows 2 lines, use the side keys to scroll the items or open every sub­menu of these items, as described under 5.5.4 GENERAL ISSUES ABOUT HOW
TO READ THE DISPLAY.
An arrow on the left side of the display highlights your current selection. Select the item you need and press ENTER to open the corresponding sub-menu.
5.5.7.1 Address
Address Display Set Service New PW Cash Time Language Vstart Alarm Remote Control UV Prot.time Alarm Message
Password
****
Page 58
Operation and installation manual Page 58 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Use this function to set addresses for the communication of each single inverter connected to the system onto RS485 line. Available address numbers are from 2 to 63. Press UP or DOWN to scroll available numbers. If you do not want to manually set the address for each and every inverter, you can select the AUTO function that will automatically set them and match them to the inverters.
5.5.7.2 Display set
Use this function to set display features:
1) Light: display light setting:
- Press MODE to set display backlighting. After selecting Mode with the arrow, press ENTER to open the corresponding sub­menu. The page is like this:
ON: Light always on OFF: Light always off
AUTO: Automatic light control. Light turns on any time you press any key and stays on for 30 sec, then gradually turns off.
2) Contrast: display light contrast Display lighting scale is from 0 to 9.
ON OFF Auto
Mode Intensit
y
Light Contrast Buzzer
New Address
Auto
New Address
63
AUTO
2 3 ….. ….. 62 63 AUTO
Page 59
Operation and installation manual Page 59 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
To select the number, press UP and DOWN to scroll and then press ENTER to confirm.
3) Buzzer: key tone control Select: ON: key tone is on OFF: key tone is off
5.5.7.3 Service
It is a function available only to installers. A special password is necessary that is supplied by Power-One.
5.5.7.4 New password
Use this function to change the default password 0000. To set system password, use the keys on display as follows:
¾ Use ENTER to move to the next digit (from left to right) ¾ Use ESC to go back to the previous digit (from right to left) ¾ Press ESC repeatedly to go back to the previous menus, as described under
5.5.3
¾ Press DOWN to scroll numbers backwards (from 9 to 0) ¾ Press UP to scroll numbers forward (from 0 to 9)
5.5.7.5 Cash
This function is about money gained thanks to power output.
Name: set desired currency, using keys as previously explained. Euro is the default setting. Val/KWh: indicates the cost of 1 KWh in the set currency. 0.50 Euro is the default setting.
5.5.7.6 Time
Enter this section to edit time or date.
Time 14:21 Date 17 Ma
y
2006
Name EUR Val/KWh 00.50
Page 60
Operation and installation manual Page 60 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5.7.7 Language
Set German or English.
5.5.7.8 START voltage
Start-up voltage can be set according to the photovoltaic field. Voltage range is 250V to 500V. Aurora default setting is 360V. You can edit this parameter using the keys on display. Press ENTER to display the following page.
Select one of the two lines by pressing ENTER to set the start voltage for the two channels, individually.
5.5.7.9 Alarm
The inverter features an alarm function that activates opening or closing of a relay contact, access to this relay is ensured by opening the front panel as shown in Fig. 24. For instance, this contact could be used to activate a siren or a visual alarm in case of inverter disconnection from the grid (failed power output) or for any alarm event generated by the system. This function can trigger 2 different alarm modes. Press ENTER to open the corresponding sub-menu:
VStart1
360V
Production Fault
VStart1 VStart2
English Deutsche
Page 61
Operation and installation manual Page 61 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
An arrow on the left side of the display highlights your current selection. After selection, press ENTER to confirm activation of chosen mode.
PRODUCTION: Activates the relay only when inverter is connected to the grid (closing of contact across “N.O.” and “C” terminals) FAULT: triggers relay activation (closing of contact across “N.O.” and “C” terminals) only when an error signal is present, i.e. in case of grid disconnection, except for Input Under Voltage.
Fig. 24 - alarm contacts terminal board
5.5.7.10 Remote control
Use this function to disable inverter manual switch-off. Selecting:
- ENABLE, ON/OFF manual function is active
- DISABLE, ON/OFF manual function is disabled, so that Aurora operation will be only controlled by the external radiation conditions.
Manual ON and OFF input is read on the inverter digital input. When in OFF condition, the display will cycle through the following pages:
Remote ON/OFF
Disable
Remote ON/OFF
Enable
Remote Off Waiting Rem.ON…
….to restart
Page 62
Operation and installation manual Page 62 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
5.5.7.11 UV Prot.time
Use this function to set time for which the inverter stays connected after input voltage drops below Under Voltage limit, set at 70% of selected Vstart. Example: if you set UV Prot.time to 60 seconds, if Vin voltage drops below Vuv (70% of selected Vstart) at 9.00 a.m., the inverter will stay connected to grid (with 0 power) until 9.01 a.m.
Power-One sets this time to 60 seconds. The user can change this setting, from 1 sec to 3600 sec.
5.5.7.12 Alarm Message
The error message to be displayed can be programmed as follows:
Press ENTER to open the corresponding sub-menu
Select the desired function using the suitable arrow, on display left side, move it up or down using UP (2
nd
key) and DOWN (3rd key) keys on display. After selection, press
ENTER (4
th
key) to confirm activation of chosen mode. When opening the ENABLE/DISABLE menu, the following page is displayed. You can use it to enable or disable message customised setting function:
With the arrow pointing at ENABLE MESSAGE, press ENTER to go to the following message writing pages.
Alarm message
Enable / Disable Com
p
ose message
Enable / Disable Com
p
ose message
Enable message Disable messa
g
e
Page 63
Operation and installation manual Page 63 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Select COMPOSE MESSAGE, and write the first line of the message.
Maximum number of positions available is 16. Press 17 times the Enter key to start writing the second line.
To write the message, use the keys on display as follows:
¾ Use ENTER (4
th
key) to move to the next position (from left to right)
¾ Use ESC (1
st
key) to move to the previous position (from right to left)
¾ Press ESC repeatedly to go back to the previous menus, as described under
5.5.3
¾ Use UP (2
nd
key) to scroll numbers, letters and symbols forward (rising order)
¾ Use DOWN (3
rd
key) to scroll numbers, letters and symbols backward
(decreasing order)
5.5.8 Info
From this menu you can view all Aurora data:
¾ Part No. (part number) ¾ Serial No. – Wk – Yr (serial number, week, year) ¾ Fw rel (firmware revision index)
Message row 2:
----------------
Message row 1:
----------------
Page 64
Operation and installation manual Page 64 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
6 DATA COMMUNICATION AND CHECK
6.1 Connection through RS-485 serial port or with RJ12 connectors
6.1.1 RS-485 Serial Port
The RS-485 serial port uses a three-core cable: two signal ones and one for ground connection. This cable is routed through holes, plugged off, located at Inverter bottom (See Fig.25). Supplied cable gland shall be applied in the relevant hole.
Fig.25 - Holes for RS-485 or wiring for RJ12 connectors
To help installation, the inverter features two holes to separate input cable from output cable, if many units are connected in a daisy-chain, as described below.
1st PLUG
2
nd
PLUG
Page 65
Operation and installation manual Page 65 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
After passing through cable gland, the cables shall be connected to RS-485 terminal block, inside the unit; remove the front panel to reach it. Please refer to par.3.7 for details on how to disassemble and correctly reassemble the front cover.
¾ Signal wires shall be connected to +T/R and –T/R terminals ¾ Ground wire shall be connected to RTN terminal
Fig.26 - Connection terminals to RS-485 serial line and S2 switch
6.1.2 RJ12 Connectors
As an alternative, inverters RS485 serial connection, both as single units or as daisy chain, can be performed by means of the RJ12 connectors (See fig. 26).
The wiring is routed through holes, plugged off, located at Inverter bottom (See Fig.25). Input wiring is routed through one hole and links to one of the RJ12 connectors: it makes no difference if its is no.1 or no.2 since they are connected in parallel, and signals are thus the same. The output wiring from the other RJ12 connector goes out from the other hole and reaches the following unit.
RJ12 No.1 RJ12 No.2
Page 66
Operation and installation manual Page 66 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
RJ12 connectors
Pin
#
Signal
Name
Description
1 Not Used
2 +TR
+ Data Line
Required for RS485 communication.
3 +R
Remote Off
Required or Remote OFF control (see chapter
5.5.6.11 for details).
4 -TR
- Data Line
Required for RS485 communication.
5 Not Used
6 RTN
Signal Return
Common reference for logical signals.
6.1.3 Daisy chain
Terminal block RS-485 or RJ12 connectors may be used to connect a single AURORA inverter or multiple AURORA inverters daisy chained together. Up to 32 inverters can be daisy chained. Recommended maximum daisy chain length is 1000 metres. With multiple daisy-chained inverters, each unit must be assigned an address. See paragraph
5.5.6.1 for instructions no how to edit addresses. The line-termination contact of the last inverter in the chain must be activated (switch S2 ­120 TERM in ON position). See fig.24.
Each AURORA unit is shipped with default address two (2) and S1 switch set to OFF. In order to ensure optimal communication on the RS485 line, Power-One recommends connecting Power-One adapter PVI-RS232485 between the first unit in the daisy-chain system and the computer. See fig.25 for further details. Equivalent devices available on the market may also be used for this purpose. Power-One makes no warranties as to proper link operation when such devices are used, as no specific testing has been conducted to establish their functionality for this particular application.
Page 67
Operation and installation manual Page 67 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Please note that - unlike Aurora PVI-232485 - such devices may require implementation of external termination impedance. The following diagram shows how to connect multiple units in a daisy-chain configuration.
Fig.27 - Multiple daisy-chain connection
NOTE
: The RS-485 link supports up to 32 inverters. Choose any given address
between 2 and 63
NOTE
: if one or more inverters are added to the system at a later time, when
an RS-485 link is used, remember to set back to OFF the switch of the inverter that was the last one.
RTN +T/R -T/R
1
s
t
Aurora
2
nd
Aurora
Last Aurora
S2 switch
ON
S2 switch
OFF
RS-485 cable
max. length = 1,000mt
max. inverter nodes = 31
Block Diagram: RS-485 cabling AURORA PVI-12.5 -O U T D
PC with RS232 port
(Sub-D 9 pin male)
PVI-RS232/485
RS485 to RS232
Converter
(Sub-D 9 pin female)
RTN +T/R -T/R
(terminal block)
Data-Logger
RS485 port
RTN
+T/R -T/R
(terminal block)
Off
On
Recommended RS-485 cable t ype:
Æ LiYCY, 2x2x0.5mm (no.2 twisted
pairs) + shield
Æ RS-485 cable (1pair + 1 conductor) +
shield
RTN +T/R -T/R
S2
switch
OFF
RTN
+T/R -T/R
Page 68
Operation and installation manual Page 68 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
6.2 Accuracy of measured values
Any measurement is subjected to error. The charts below specify the following information for each measured item:
¾ unit of measurement; ¾ range; ¾ resolution.
Resolution
Name of
measured
variable
Unit of
measure
ment
Display Meas.
Max. error %
Input voltage PV No.1
VP1 Vdc 1 V 250mV 2%
Input voltage PV No.2
VP2 Vdc 1 V 250mV 2%
Input current PV No.1
IP1 Adc 0.1 A 7mA 2%
Input current PV No.2
IP2 Adc 0.1 A 7mA 2%
Power output PV No.1
Pin1 W 1 W 6W 2%
Power output PV No.2
Pin2 W 1 W 6W 2%
Output voltage Vout V 1 V 200mV 2%
Output current Iout A 0.1 A 20mA 2%
Output power Pout W 1 W 9W 2%
Frequency Freq Hz 0.01 0,01
0.1%
Page 69
Operation and installation manual Page 69 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Resolution
Name of
measured
variable
Unit of
measure
ment
Display Meas.
Max. error %
Accumulated energy
Energy Wh 1 Wh 4%
Time counter Lifetime
hh:mm:ss
1 s 0.2
Partial time counter
Partial Time
hh:mm:ss
1 s 0.2
Page 70
Operation and installation manual Page 70 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
7 TROUBLESHOOTING
AURORA inverters comply with the preset standards for grid operation, safety and electromagnetic compatibility.
Before shipment, the product is inspected and tested to check operation, safety protection devices, performance and an endurance test is conducted.
Together with Power-One quality guarantee, these tests ensure AURORA trouble-free operation.
Nevertheless, in case of inverter malfunction find and fix the fault as follows.
9 Work in safety conditions as explained under 3.5 and following paragraphs, check
that connections across AURORA, the photovoltaic field and distribution grid are correct.
9 Carefully check which LED is flashing and the text of the displayed warning; then
identify the type of fault, using the instructions given under sections 5.3, 5.4 and
5.5.
If you could not fix the fault using the indications given herein, contact the authorised repair center or the installer (see instructions on the following page).
Page 71
Operation and installation manual Page 71 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Before contacting the authorised repair center, please find and keep at hand the following information and specify them when requesting servicing:
INFO about AURORA
NOTE: Information available from the LCD
9 AURORA Model? 9 Serial Number? 9 Week of manufacture? 9 Which LED is flashing? 9 Is light flashing or steady on? 9 Which warning is displayed?
9 Brief description of malfunction 9 Have you noticed whether malfunction can be reproduced? 9 If so, how? 9 Have you noticed whether malfunction is repeated cyclically? 9 If so, when? 9 Is malfunction present since unit installation? 9 If so, did it get worse? 9 Describe weather condition when malfunction occurs
INFO about the Photovoltaic Field
9 Make and model of the photovoltaic panels 9 System data: - array maximum voltage and current values
- number of strings in the array
- number of panels per string
Page 72
Operation and installation manual Page 72 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
8 SPECIFICATIONS
8.1 Input values
WARNING: the photovoltaic field and system wiring shall be set up so that
PV input voltage is lower than maximum limit, regardless of the model, number and operating conditions of the chosen photovoltaic panels. Since panel voltage also depends on operating temperature, choose the number of panels for each string considering the minimum ambient temperature foreseen for that specific area (see table A).
WARNING: the inverter is equipped with a linear limit of output power, according to input voltage, from 750 Vdc (100% power output) to 850 Vdc (0% power output)
WARNING: photovoltaic panels open-loop voltage depends on ambient temperature (open-loop voltage increases when temperature decreases) and you shall ensure that foreseen minimum temperature for the installation will not make panels exceed maximum voltage limit of 850Vdc. The following table is an example indicating the maximum voltage of each panel for typical panels with 36, 48 and 72 cells, according to the temperature (assuming a nominal open-loop voltage of 0.6Vdc per cell at 25°C and a temperature coefficient of -0.0023V/°C. Thus, the table shows the maximum number of panels that can be connected in series according to the minimum temperature at which system will operate. Please contact panel manufacturer to find the correct temperature coefficient of V
oc
before calculating maximum voltage of
the photovoltaic array.
Page 73
Operation and installation manual Page 73 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Panels w/36 cells Panels w/48 cells Panels w/72 cells
Minimum Panel
Temp.[°C]
Panel voltage
Max number of
panels
Panel voltage
Max number of
panels
Panel voltage
Max number of
panels
25 21.6 39 28.8 29 43.2 19
20 22.0 38 29.4 28 44.0 19
15 22.4 37 29.9 28 44.9 18
10 22.8 37 30.5 27 45.7 18
5 23.3 36 31.0 27 46.5 18
0 23.7 35 31.6 26 47.3 17
-5 24.1 35 32.1 26 48.2 17
-10 24.5 34 32.7 25 49.0 17
-15 24.9 34 33.2 25 49.8 17
-20 25.3 33 33.8 25 50.7 16
-25 25.7 33 34.3 24 51.5 16
Table A
Page 74
Operation and installation manual Page 74 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Description
Value
PVI – 10.0-OUTD-xx
Value
PVI – 12.5-OUTD-xx
Recommended
maximum DC power
11400 W 14300W
Nominal DC power 10400 W 13000 W
Nominal Input
Voltage
580 V
Max. DC Input
Voltage
850 Vdc
Max. Input
Overvoltage
900 Vdc for 2h/day
Input Voltage, MPPT
operatine range
200 Vdc to 850 Vdc
Input Voltage, MPPT
operating range at full
power
from 300 Vdc to 750
Vdc
from 360 Vdc to 750 Vdc
Max. short-circuit
current (of each array)
22 Adc
Max. operating input
current (of each array)
18 Adc
Max. input power (of
each channel)
(1)
6500 W 8000 W
PV ground fault
protection
Supplied ground fault detector and disconnect
Input channel configuration
Two independent MPPT channels with shared negative
poles or
Two channels in parallel
(1)
Total input power shall in any case stay within recommended DC power value
NOTE
: If photovoltaic field connected to the inverter outputs an input
current higher than the maximum one that can be used, the inverter will not
be damaged as far as the input voltage is within allowed range.
Page 75
Operation and installation manual Page 75 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
8.2 Output values
Description
Value
PVI – 10.0-OUTD-xx
Value
PVI – 12.5-OUTD-xx
Nominal output power
10000 W 12500 W
Grid voltage maximum operating range
(2)
from 326 Vrms to 456 Vrms phase-phase
from 188 Vrms to 263 Vrms phase-neutral
Grid voltage nominal
400 Vrms phase-phase
230 phase-neutral
Grid frequency, maximum range
from 47 to 63 Hz
Grid frequency, nominal
50 Hz
Grid frequency, operating range according to DK5940 standard
from 49.72 to 50.28 Hz
Nominal output current per phase
14.5 Arms 18.1 Arms
Max. output current per phase
16.6 Arms 20 Arms
Output Overcurrent Protection
19 Arms 22 Arms
(2)
Depending on nominal voltage selected (using a password protected menu) the minimum operating voltage could reach 311 Vrms phase-phase or 180 Vrms phase­neutral.
Page 76
Operation and installation manual Page 76 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
8.3 Grid protection features
Anti-Islanding
Complying with:
- DK5940 (Italy).
8.4 General features
Description
Value
PVI – 10.0-OUTD-xx
Value
PVI – 12.5-OUTD-xx
Maximum efficiency
97.8% (97.3% Euro Efficiency)
97.8% (97.3% Euro Efficiency)
Internal consumption in standby
12 W
Internal consumption at night
< 1.5 W
Operating environment ambient temperature
from -25°C to +60°C
(*)
Case protection class
IP65 / Nema 4X
Audible noise with inner fan on
< 50 dbA @ 1m
Dimensions (height x width x depth):
650 x 620 x 200 mm
Weight 38 kg
Relative humidity 0 – 100 % dew point
(*)
Full power ensured up to amb.T = 50°C (as far as with unit not under direct solar
radiation)
Page 77
Operation and installation manual Page 77 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
8.5 Power Derating
To allow safe inverter operation both from a thermal and electrical point of view, the unit automatically decreases power input into grid. Derating can occur in two cases:
Power derating due to ambient conditions
Derating entity and the temperature at which derating will start depend on many operating parameters, apart from the ambient temperature. For example they also depend on input voltage, grid voltage and power available from the photovoltaic field. Thus AURORA will derate power during certain periods of the day, according to the value of these parameters. In any case AURORA guarantees maximum power up to 50°C of ambient temperature, as far as not directly under solar radiation.
Power derating due to input power
The chart shows the automatic power derating in case of too high or low input or output voltage.
Fig. 28 - Derating curves for two input channels.
0
2000
4000
6000
8000
10000
12000
14000
0 100 200 300 400 500 600 700 800 900
Input voltage (V)
PVI-10.0-OUTD-xx-IT PVI-12.5-OUTD-xx-IT
Power Output (W)
Page 78
Operation and installation manual Page 78 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Fig. 29 - Derating curves for one input channel.
Power derating conditions due to the ambient conditions and input voltage could also occur at the same time, but power decrease will always refer to the lowest value measured.
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
0 200 400 600 800 1000
Input voltage (V)
Power output (W)
PVI-10.0-OUT-xx-IT PVI-12.5-OUT-xx-IT
Page 79
Operation and installation manual Page 79 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
8.6 Note about the differential protection built in the Power-One Aurora
inverters
Power One Aurora inverters are equipped with a protection device against ground faults, as per the safety standard required in Germany by VDE V 0126-1-1:2006-02 standard (refer to par. 4.7 of the Standard). All Aurora inverters marketed in Europe are equipped with this protection, including the versions coded as “IT”, available for the Italian market. In particular, Power One Aurora inverters are fitted with a redundancy for leakage current reading, sensitive to all current components, be it direct or alternating. Ground leakage current measurement is taken at the same time and separately by 2 different processors: if only one of them detects a failure, protection is triggered, grid is hence disconnected and conversion process is stopped. There is an absolute threshold of 300mA for the total AC+DC leakage current with protection trigger time of max. 300msec. There are also three more trigger levels with threshold set at 30mA/sec, 60mA/sec and 150mA/sec respectively, to manage "quick" variations of the fault current caused by accidental contacts with active leaking parts. Limit trigger times progressively decrease when fault current variation speed increases and, from 300msec/max for a variation speed of 30mA/sec, value decreases to 150msec and 40msec for variation speed values of 60mA and 150mA, respectively. It shall be noticed at any rate that the built-in device only protects the system against ground faults occurring upstream of the inverter AC terminals (i.e. toward photovoltaic system DC side and hence toward the photovoltaic modules). The leakage current that could occur in the AC section, in-between the pickup/input point and the inverter, are not detected and require an external protection device. It is recommended to use a switch with C-class thermal cut-out and nominal current of 40A, differential protection in class A or class AC with trigger current of 300mA so as to avoid any false trigger events of the protection due to the normal capacitive leakage current of the photovoltaic modules.
Page 80
Operation and installation manual Page 80 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
***************CERTIFICATE OF CONFORMITY ************
Page 81
Operation and installation manual Page 81 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Page 82
Operation and installation manual Page 82 of 82 (PVI-10.0/12.5-OUTD-xx Rev:1.2)
Loading...