This symbol indicates the presence of dangerous voltage within and
outside the product enclosure that may constitute a risk of electric
shock, serious injury or death to persons if proper precautions are not
followed.
Caution
This symbol alerts the user to the presence of hazards that may cause
minor or moderate injury to persons, damage to property or damage
to the device itself, if proper precautions are not followed.
Note
This symbol directs the user’s attention to important installation,
operating and maintenance instructions.
Installation Considerations
Installation and maintenance of the ION 8000 series meter should only be
performed by qualified, competent personnel that have appropriate training and
experience with high voltage and current devices. The meter must be installed in
accordance with all Local and National Electrical Codes.
DANGER
Failure to observe the following instructions may result in severe injury or death.
During normal operation of the ION 8000 series meter, hazardous voltages are
present on its terminal strips, and throughout the connected potential
transformer (PT), current transformer (CT), digital (status) input, control power
and external I/O circuits. PT and CT secondary circuits are capable of generating
lethal voltages and currents with their primary circuit energized. Follow
standard safety precautions while performing any installation or service work
(i.e. removing PT fuses, shorting CT secondaries, etc.).
The terminal strips on the meter base should not be user-accessible after
installation.
Do not use digital output devices for primary protection functions. These
include applications where the devices perform energy limiting functions or
provide protection of people from injury. Do not use the ION 8000 series in
situations where failure of the devices can cause injury or death, or cause
sufficient energy to be released that can start a fire. The meter can be used for
secondary protection functions.
Do not HIPOT/Dielectric test the digital (status) inputs, digital outputs, or
communications terminals. Refer to the label on the ION 8000 series meter for
the maximum voltage level the device can withstand.
CAUTION
Observe the following instructions, or permanent damage to the meter may occur.
Network Compatibility Notice for the Internal Modem
Theinternalmodeminmetersequippedwiththisoptioniscompatiblewiththe
telephonesystemsofmostcountriesintheworld,withtheexceptionofAustralia
andNewZealand.Useinsomecountriesmayrequiremodificationoftheinternal
modem’sinitializationstrings.Ifproblemsusingthemodemonyourphone
system
Power Measurement Ltd. (“Power Measurement”) reserves the right to make changes in the
device or its specifications identified in this document without notice. Power Measurement
advises customers to obtain the latest version of the device specifications before placing
orders to verify that the information being relied upon by the customer is current.
Regardless of whether any remedy set forth herein fails of its essential purpose, except to
the extent the following limitation is prohibited by applicable law, Power Measurement
shall not, in any event or under any legal claim or theory (whether based on contract,
indemnity, warranty, tort (including negligence and strict liability) or otherwise), be liable
to the original purchaser or any other person or entity for special, indirect, incidental,
punitive, liquidated, special or consequential damages whatsoever with respect to any
purchased product, including, without limitation, business interruption, loss of use, profit
or revenue, even if Power Measurement has been advised of the possibility of such
damages. To the extent that a limitation or exclusion of consequential damages are
prohibited by applicable law, then Power Measurement’s liability shall be limited to twice
the amount of the relevant purchased product. Not to limit the foregoing, a) Power
Measurement shall not be liable for any claim (other than a claim solely for the breach of one
of the above Warranties that is made in accordance with the above described procedures)
made by the original purchaser, its employees, agents, or contractors for any loss, damage,
or expense incurred due to, caused by, or related to any purchased product; and b) the
above Warranties are the original purchaser's exclusive remedy and Power Measurement
hereby expressly disclaims all other warranties, express or implied, including, without
limitation, warranties of non-infringement and the implied warranties of merchantability
and fitness for a particular purpose.
These limited Warranties shall not apply to any product that has been subject to alteration,
accident, misuse, abuse, neglect or failure to exactly follow Power Measurement's
instructions for operation and maintenance. Any technical assistance provided by Power
Measurement's personnel or representatives in system design shall be deemed to be a
proposal and not a recommendation. The responsibility for determining the feasibility of
such proposals rests with the original purchaser and should be tested by the original
purchaser. It is the original purchaser’s responsibility to determine the suitability of any
product and associated documentation for its purposes. The original purchaser
acknowledges that 100% "up" time is not realizable because of possible hardware or
software defects. The original purchaser recognizes that such defects and failures may cause
inaccuracies or malfunctions. Only the terms expressed in these limited Warranties shall
apply and no distributor, corporation or other entity, individual or employee of Power
Measurement or any other entity is authorized to amend, modify or extend the Warranties
in any way.
The information contained in this document is believed to be accurate at the time of
publication, however, Power Measurement assumes no responsibility for any errors which
may appear here and reserves the right to make changes without notice.
Power Measurement, ION, ION Enterprise, MeterM@il, WebMeter and “drive energy
performance” are either registered trademarks or trademarks of Power Measurement. All
other trademarks are property of their respective owners.
ION 8300™, ION 8400™ and ION 8500™ meters provide revenue-accurate, true
RMS measurements of voltage, current, power and energy, and are complemented
by extensive I/O capabilities, comprehensive logging, and advanced power quality
measurement and compliance verification functions. The meters come with an
extensive selection of pre-configured data screens and measurements, so you can
use the meters “out of the box” or customize them to fit your unique requirements.
ION 8000 series meters give you the tools to manage complex energy supply
contracts that include commitments to power quality. You can also integrate the
meters with ION® software or other energy management, SCADA, automation
and billing systems, via Internet communications and multiple industry-standard
communication channels and protocols including MV90.
The Meter is Factory-Configured and Ready to Operate ................................13
Page 7
ION 8000 Series Meters ION 8000 Series User Guide
ION 8000 Series Meters
ION 8300, ION 8400 and ION 8500 meters are suited to a wide range of
applications. The meters can be used as stand-alone devices, but their extensive
capabilities are fully realized when used as part of an enterprise energy
management (EEM) system.
Whether your company is an energy supplier, service provider or consumer, an
EEM system gives you the real-time information and control needed to take
control of energy cost, quality and reliability across your entire enterprise. It gives
you an integrated solution to managing new billing structures, distributed
generation, energy purchasing, energy cost control, and operational efficiency
while maximizing uptime. Systems can span widely dispersed geographic
locations and multiple points within each site. A single, shared system delivers a
broad range of functionality that can satisfy the needs of many different groups
within your enterprise.
ION® technology uniquely delivers the benefits of enterprise energy management
through an efficient, economical, and scalable architecture using web-enabled
software and intelligent metering and control devices. ION systems place
intelligence everywhere it’s needed, delivering information and control to
everyone that needs it, wherever they are. This gives all parties the necessary
information to make the best energy decisions, and the control to act on them. A
single, shared system delivers a broad range of functionality that can satisfy the
needs of many different groups within an enterprise, while integrating seamlessly
with existing systems.
ION Enterprise™ is a powerful web-ready software suite that can process,
analyze, store, and share information from across your entire organization. Its
compatibility and flexibility means you can introduce individual components, at a
pace you decide, while maintaining your original investments. You can access
information and alarms from any workstation, pager, PDA, or cell phone locally or
around the world, in the format you require. You can also perform coordinated
load and equipment control functions, either manually or automatically. ION
software collects data automatically from ION meters and third-party devices, so
you can manage a single site or a global network of devices. ION software and
hardware products reduce cost of installation and ownership by leverage existing
corporate networks and popular networking technologies, including serial,
wireless, modem, Ethernet and Internet links.
A wide selection of ION intelligent metering and control devices are available,
with choices to meet the specific needs of various key points within an enterprise.
Devices offer a range of high accuracy metering, power quality and reliability
analysis, data and event logging, alarming, control and communications.
This manual discusses ION 8000 series meter default functionality, as well as
features and applications. Throughout the manual, the term “meter” refers to all
three meter models. All differences between the models, such as a feature specific
to one model, are indicated with the appropriate model number.
Page 8Chapter 1 - Introduction
ION 8000 Series User GuideION 8000 Series Meters
These meters can be used effectively in numerous energy supply-side (utility) and
demand-side applications. Some common meter applications are:
Revenue metering
Substation automation
Power quality monitoring (with Flicker)
Commercial/industrial operations metering
Demand and power factor control
SCADA (supervisory control and data acquisition)
Distributed generation (generator) monitoring and control
Chapter 1 - Introduction Page 9
ION Meter in Enterprise Energy Management Systems ION 8000 Series User Guide
ION Meter in Enterprise Energy Management Systems
Applications that include the meter typically require additional equipment.
Display and analysis software tools are almost always used to manage, interpret
and distribute the data measured or logged by a meter. There are usually a variety
of tools used, and often these tools are connected using different communications
standards and protocols. In many cases, a meter must also provide control
capabilities and device-level data sharing.
The meter can adapt to many situations. Advanced communications allow data to
be shared simultaneously across multiple networks, built-in I/O provides
monitoring and control capabilities, and a variety of display and analysis tools can
be used to monitor your power system.
Data Display and Analysis Tools
Not only does the meter’s front panel allow meter configuration and data display,
but the meter also integrates seamlessly with display and analysis software
available from Power Measurement. ION Enterprise software is the network and
device configuration software that also lets you analyze and monitor your system
and produce reports for any department in an organization. Furthermore, you can
use data acquired by the meter in a variety of third-party systems. ION software is
designed to make use of all the available advanced capabilities.
Page 10Chapter 1 - Introduction
ION 8000 Series User GuideData Display and Analysis Tools
The Front Panel
Local monitoring and standalone applications are facilitated by the meter’s front
panel interface. The front panel combines real-time display features with limited
device configuration functions. The front panel is often used in combination with
an ION software system, providing an interface for field personnel.
WebMeter® Internal Web Server Feature
An on-board Web server combined with an Ethernet port provides quick and easy
access to real-time energy and basic power quality information without special
software: this is WebMeter functionality. The built-in web pages display a range of
energy and basic power quality information through the web-enabled device;
these pages even support basic meter configuration tasks.
MeterM@il® Internal Email Server Feature
Configure the meter to automatically email high-priority alarm notifications or
scheduled system-status update messages to anyone, anywhere within the facility
or around the world. Specify the type of event that triggers an email alert, such as
power quality disturbances or logged data at any pre-determined interval, and
have your ION software administrator program the meter to respond with a
MeterM@il message when these events occur. MeterM@il messages can be
received like any email message over a workstation, cell phone, pager, or PDA.
XML Compatibility
The meters can exchange information using industry-standard XML format. This
simple machine-readable format supports easy integration with custom reporting,
spreadsheet, database, and other applications.
ION Enterprise™ Software
The complete ION Enterprise software package enables the meter to be part of a
fully networked information system with other meters and local and wide-area
computer networks. ION Enterprise is recommended for all power monitoring
systems where advanced analysis and control capabilities are required.
ION Enterprise provides tools for managing your power monitoring network,
logging data, analyzing real-time and logged data, generating power system
reports, and creating custom functionality at the meter level.
ION Enterprise also offers two ways to remotely view information through a web
browser: the WebReach™ component of ION Enterprise, and Microsoft Terminal
Services.
WebReach only requires an URL to display a meter’s real-time data and select
views of historical and waveform data from a web browser; there is no client
machine configuration. WebReach is a data display application; there is no
control functionality available through it.
Microsoft Terminal Services enable full ION Enterprise functionality, including
control features. Some client machine configuration is required.
Chapter 1 - Introduction Page 11
Communications Methods ION 8000 Series User Guide
ION Setup™ Software
ION Setup is a meter configuration tool designed specifically to configure and test
meters. ION Setup offers an intuitive graphical interface for performing basic
meter setup, installing templates into meters, viewing real-time and reset
accumulated values, verifying meter calibration and measurements, and setting
up advanced security.
MV90
MV90 software (by Utility Translation Systems) is a multi-vendor translation
system that can collect and analyze data from a variety of different brands of
meters. One of the unique features of MV90 is its ability to log some information
coming from several different brands of meters, each with unique database
formats. MV90 manipulates this data without extensive knowledge of the device
of origin. This is done by using TIM modules; each TIM module acts as a protocol
translator specific to a device type, and it will convert some pre-defined data from
a meter to the MV90 database format. The TIM module used for ION meters is
called TIM_ION.
Communications Methods
The meter can be integrated into various industry-standard networks. Data that is
measured by the meter can be made available to other devices using the Modbus
Master, Modbus RTU, Modbus TCP, and DNP 3.00 protocols, as well the MV-90
translation system. You can also configure the meter to import data from devices
on these networks. With these advanced communications functions, the meter
operates in most existing power monitoring systems. Any data display and
analysis software that works with Modbus RTU or DNP 3.00 devices will also
function with the meter.
The standard meter includes a selectable RS-232/RS-485 port (the factory default is
RS-232), a high-speed RS-485 port, and an IrDA optical port for communications
in the field. Order options include a 10Base-T Ethernet port or 10Base-FL fiberoptic port, and a 33.6 kbps internal modem (both FCC and CTR-21 compliant).
Depending on the hardware options purchased, up to four separate ports can
communicate simultaneously.
Digital and Analog I/O Options
The meter has digital inputs and outputs for a variety of applications.
Additionally, a LED on the front panel is configured for energy pulsing. An
optional I/O Expander product option is also available for digital and analog
communication. There is separate I/O Expander documentation that accompanies
this option.
Onboard I/O
The meter contains four Form C digital outputs and three Form A digital inputs.
They can be used for monitoring breaker trips or send KYZ pulsing information to
third-party system equipment.
Page 12Chapter 1 - Introduction
ION 8000 Series User GuideDigital and Analog I/O Options
Expanded I/O
The I/O Expander option extends the meter’s I/O capabilities. The digital I/O
Expander model provides four Form A digital outputs, four Form C digital
outputs, and eight Form A digital inputs. The analog I/O Expander model replaces
the four form A digital outputs with analog outputs.
The Meter is Factory-Configured and Ready to Operate
Even though the meter is fully customizable, it is shipped from the factory with
many pre-configured functions. Once you have performed the installation and
basic setup, all of the basic measurements, energy calculations and recording
functions are ready to operate right out of the box. You may find that the factory
configuration aptly serves your purposes, allowing you to forego additional
configuration.
Chapter 1 - Introduction Page 13
Using this Guide ION 8000 Series User Guide
Using this Guide
This User’s Guide is directed at three types of user: the typical user or operator, the
system administrator, and the advanced user. You might not fit into any of these
groups directly, or perhaps you are both an operator and an administrator. These
classifications are intended to make this guide easier to navigate with respect to
which information is appropriate to your needs.
Typical User or Operator
Most users simply want to display the data provided by the factory-configured
meter. These users want fast access to data through the front panel, ION software,
or a third-party protocol such as Modbus or DNP.
System Administrator or Manager
Some users need to make minor adjustments so that their meters “fit” their power
systems: data recording intervals, demand sub-intervals and other parameters
may need to be set before the meter’s setup is complete. These users will use the
front panel, or ION software to change settings in the device’s operating software.
(ION Enterprise is highly recommended.)
Advanced User or Systems Integrator
Advanced users may want to make use of the flexibility and power provided by
the device’s operating software. These users will need to become familiar with the
ION architecture, and the ION software tools used to customize the device’s
operation.
Symbols
The following symbols are used in this manual to warn you about the risk of
injury, damage to the equipment, inconvenience if the proper procedure is not
followed, or additional information you may want to consider.
CAUTION
This symbol alerts you to things that may cause loss of data, damage to your computer or your device.
DANGER
This symbol alerts you to things that may cause serious injury to a person. Only qualified, properly trained
personnel should perform these procedures.
NOTE
A note provides you with additional information that you might want to consider.
TIP
This symbol draws your attention to information that will help you perform a task more quickly or easily.
Page 14Chapter 1 - Introduction
ION 8000 Series User GuideUsing this Guide
Terminology
Clear: Place the mouse cursor over the check box for the specified
option, then click the mouse button so that the check mark is
removed from the check box.
Click:Place the mouse cursor over the specified option or button,
then press and release the mouse button.
Double-click:Place the mouse cursor over the specified option or button,
then press and release the mouse button twice.
Drag:Hold down the mouse button while moving the mouse cursor
to the appropriate location, then release the button.
Enter:Type the information, then press the ENTER or RETURN key.
Point: Position the mouse pointer over a submenu or menu
command. For example, point to the File menu.
Press: Press the specified key or key combination on your keyboard,
for example, press CTRL+ALT+DEL.
Select:Place the mouse pointer over the check box for the specified
option, then click the mouse button so that an X or check mark
appears in the check box.
Or:
Place the mouse pointer over the specified box or button, then
click the mouse button.
Type:Type the information. Do not press the Enter or Return key.
PDF Documents
This manual is also provided in PDF (Portable Document Format) at our website:
www.pwrm.com.
Use Acrobat
printing the manual, please print the entire manual, including the copyright and
disclaimer statements.
The PDF files for all Power Measurement products are available from the Power
Measurement web site. Each Power Measurement device has installation
information and a user's guide to teach you about the features of your device.
®
Reader® to view and print the PDF version of the manual. When
ION meters are programmed using ION modules that are linked to create
unlimited custom functionality. Your meter has many pre-configured modules
that provide most functionality that you need. If you want to extend or customize
the functionality of your meter consult the online ION Reference for general
information and ION module descriptions. For information on configuring
features search the technical notes.
Chapter 1 - Introduction Page 15
Getting More Information ION 8000 Series User Guide
Getting More Information
Additional information is available from Power Measurement. Check our web site
at www.pwrm.com, contact your local Power Measurement representative, or
contact Power Measurement directly (contact information is provided on the first
page of this document). Documents that are related to the installation, operation
and application of the meter are as follows:
Installation Guide
This brief guide is shipped with each meter. It details the mounting, wiring and
basic setup of the device.
Online ION Setup Help
This online reference has in-depth information on installation, setup and security
of ION Setup. It also contains detailed descriptions of ION meter configurations
using the Setup Assistant.
ION Reference
This online reference contains detailed descriptions of all modules in an ION
meter.
ION Enterprise Getting Started Guide
This guide explains the installation and configuration of the ION Enterprise
software suite.
Online ION Enterprise Help
Each ION Enterprise software component has an in-depth online help system.
Technical Notes
Technical notes are available from our website. These documents are regularly
updated with new and revised content and features.
Application Notes
Online application notes offer detailed, high-level descriptions of real-world
situations, where Power Measurement’s ION devices and ION software provide
beneficial solutions.
Before You Can Use this Guide
By the time you are ready to use this guide, your meter should be installed, basic
setup should have been performed, and communications/basic operation should
have been verified. If the unit is not yet installed and operational, refer to the
Installation Guide that shipped with the meter.
Page 16Chapter 1 - Introduction
2Front Panel
The front panel of the ION 8000 series provides a user-friendly interface from
which you can view system data or configure meter settings. A scrollable display
and three distinct modes (NORM, ALT and TEST) provide easy access to a full
range of functions through a simple three-button keypad.
This chapter describes the front panel and explains how to use it to display data,
perform tests, and set up basic configuration options.
Basic Setup Menu ..................................................................................................30
Demand Setup Menu ............................................................................................ 31
COM Ports Setup Menu ....................................................................................... 31
Network Setup Menu ........................................................................................... 33
Format Setup Menu .............................................................................................. 35
Display Setup Menu ..............................................................................................35
Security Menu ........................................................................................................36
Page 17
Front Panel Features ION 8000 Series User Guide
Front Panel Features
The front panel of the ION 8000 series includes a liquid crystal display with
detailed graphics and text, Up and Down arrow buttons to aid in screen navigation
and basic setup procedures, as well LED pulsers to aid in testing the meter. This
section outlines the features available on the front panel of the meter.
Status bar
Optical port
Navigation buttons
Watt LED
ALT/Enter button
VAR LED
Main display
Meter label
Demand reset switch
The meter’s display can show numeric data screens, event logs, phasor diagrams,
bar graphs and harmonics histograms. As the graphic above illustrates, the display
screen is divided into two sections: the main display area and the status bar.
The main display area presents meter data and status information; the status bar
provides time, date, phase, quadrant, and mode information. During normal
operation, the main display area automatically cycles through a series of several
displays. If you prefer, you can use the Up or Down arrow buttons to step
manually through these displays. By default, the automatic scrolling will resume
60 seconds after you have pressed a button.
TIP
To adjust the contrast, hold down the Up and Down arrow buttons simultaneously. When the contrast
reaches the desired level, release the buttons.
Page 18Chapter 2 - Front Panel
ION 8000 Series User GuideFront Panel Features
LED pulsers
Two LED pulsers located near the top of the front panel represent WATT - to the
left - and VAR - to the right.
These LEDs are preconfigured for energy pulsing. The adjacent smaller infrared
outputs are connected to the LEDs and pulse at the same rate. Pulse rates can be
adjusted by re-configuring the Calibration Pulser module; for a detailed
description of LED pulsers operation, refer to “Energy Pulsing with LEDs” on
page 137).
Demand reset switch
Located on the front of the meter's external cover assembly, the Demand Reset
switch resets the peak demand values logged in the meter. This switch can be
activated with the cover on or off. When the ION 8000 series meter is in TEST
mode, the Demand Reset switch resets the test demand parameters.
In most applications, the Demand Reset switch is sealed with an anti-tamper
mechanism; a through-hole in the switch can accommodate either an external seal
or a locking mechanism. See “Anti-Tamper Sealing Methods” on page 70 for a
discussion of Anti-Tamper sealing.
The ION setup register labeled Demand Lockout Time sets the minimum time
allowed between consecutive demand resets; the meter ignores any attempts to
reset the demand outside the bounds of the register. The default value for the
Demand Lockout time is 25 days. For details on the Demand Lockout Time setup
register, refer to “Demand and Peak Demand Module Overview” on page 119.
Navigation buttons
The navigation buttons are the Up and Down arrow buttons and the round
Alt/Enter button. Pressing the Up or Down arrow buttons to manually scroll back
or forth through the available displays temporarily halts the display screen’s
automatic scrolling function. Pressing Alt/Enter toggles between NORM and ALT
display modes. The automatic scrolling function restarts 60 seconds after a button
was last pressed.
Hold the Alt/Enter button for approximately three seconds to display the Setup
menu. You can then use the navigation buttons to view the device's configuration
or edit communication settings. See “Setup Menus” on page 30 for further
instruction on modifying the device's configuration using the front panel buttons.
Optical port
An optical port facilitates infrared communication with the device. For details on
how to configure and use this port, see “Configuring the Optical Port” on page 81.
Chapter 2 - Front Panel Page 19
Front Panel Features ION 8000 Series User Guide
Master Reset button
WATT
MASTER
RESET
TEST
MODE
VAR
You must remove the meter cover and its label to access the Master Reset button;
it is a pin-hole located in the lower left of the faceplate (it is labeled “Energy Reset”
on some meters). This button is recessed to prevent accidental activation. For
instructions on removing the meter cover, see “Performing a Master Reset from the
front panel” on page 182.
Use the Master Reset button to delete most accumulated values and all derived
revenue measurements from the meter.
To use the Master Reset button:
1.Remove the cover assembly.
2.Using a pin or similar instrument, press and hold the Master Reset button until
the “Master Reset in Progress” message is displayed on the front panel.
CAUTION
After initiating a Master Reset, wait until the “Master Reset Completed” message appears on the front
panel (or about two minutes, depending on your firmware). This allows the meter to completely reset
parameters. This is especially important if you are powering down the meter after a Master Reset.
Hardware-Locked Meters and Master Reset
Master reset is not accessible via software in a hardware-locked ION 8000 series
meter, whether the meter is in TEST, ALT or NORM mode. To perform a master
reset on a hardware-locked meter, you must remove the front cover and press the
master reset button.
With a meter that is not hardware-locked, you can perform a Master Reset via
software. It does not have to be in TEST mode.
Parameters affected by a Master Reset
The Master Reset button resets many of the device's measurements and logs. The
mode that the meter is in (NORM mode or TEST mode - see “Modes of Operation”
on page 25) defines the values that will be reset.
NORM or ALT mode
In NORM or ALT mode, the following parameters are reset to zero:
Energy and Demand
Peak Demand
Loss Calculation
Power Quality disturbance counters
Time of Use
Page 20Chapter 2 - Front Panel
ION 8000 Series User GuideFront Panel Features
ENERGY
The following are cleared:
Event Log
All Data Recorders
All Waveform Recorders
TEST mode
All TEST mode Energy and Demand measurements are set to zero.
TEST mode button
WATT
ENERGY
RESET
TEST
MODE
VAR
The TEST mode button is located under the meter's external cover assembly; it
places the meter into TEST mode. While in TEST mode, the meter ceases
accumulation of billable quantities; energy and demand measurements are
accumulated in TEST mode registers.
Refer to “TEST mode” on page 26 for more details on this mode of operation.
Chapter 2 - Front Panel Page 21
Display Screen Types ION 8000 Series User Guide
Display Screen Types
The front panel displays measurements, configured settings and configuration
data in a variety of forms. The types of display screens are described below. For
information on customizing the display on your meter, see “Configuring Front
Panel Displays” on page 163.
The status bar
The status bar runs along the bottom of the front panel display and contains
information about the following settings:
Date and time (in 24 hour format).
Voltage phases present. The labels and rotation of phases correspond to the
configuration of the power monitoring system. AB BC is for Delta configuration
(35S forms), ABC is four wire Wye configurations (9S/36S forms).
Quadrant where the system power factor resides.
Mode (NORM, ALT or TEST).
Time remaining in the Rolling Block Demand interval. If the interval has
counted to zero the letters EOI (End Of Interval) appear on the status bar. If the
interval is counting down then a time remaining indicator appears.
Main display
Status bar
Numeric displays
All NORM mode data and some of the ALT mode display screens use numeric
displays. Numeric displays show up to four parameters at a time. If no numeric
values are available for a parameter, N/A is displayed.
The front panel automatically scales the units for basic measurements (i.e. voltage,
current and power parameters). For example, a measurement of 2,000 Watts is
displayed as 2 kW. A measurement of 2,000,000 Watts is displayed as 2 MW. The
meter makes these conversions using your PT and CT Ratios.
Page 22Chapter 2 - Front Panel
ION 8000 Series User GuideDisplay Screen Types
The meter only performs these automatic units if the measurement is derived
solely from the Power Meter module’s output.
Nameplate display and event log
Nameplate displays and event logs appear in ALT mode and are organized in
tabular format. Nameplate displays show owner, meter and power system details:
The Event Log displays recent high priority events. You must use ION software to
retrieve all logged data:
Histogram displays
Harmonic content is displayed in histogram format. The 2nd to the 63rd harmonics
st
(31
on the ION 8300 meter) are displayed in the histogram. The total harmonic
distortion (THD) is displayed above the histogram.
Chapter 2 - Front Panel Page 23
Display Screen Types ION 8000 Series User Guide
Phasor diagram displays
Phase information can be displayed in phasor diagram format. Phasor diagrams
are accompanied by tables that show phase, voltage and current magnitudes. In
cases where a phase vector is too small to be represented graphically, it is shown
as a table entry only.
Disk simulator
This display simulates the behavior of a mechanical watt-hour meter indicating
power received or delivered by the direction of the pulse.
Time and date
This displays supports time and date formats, enabling displays with nothing but
date and/or time and/or time remaining in the current interval.
Time-stamped values
Up to three timestamped parameters can display on the same screen. The
timestamp indicates the time that the displayed parameter was last updated.
Page 24Chapter 2 - Front Panel
ION 8000 Series User GuideModes of Operation
Modes of Operation
The ION 8000 series has three modes of operation: NORM, ALT and TEST. Both
NORM and ALT are display modes, providing various power system data and
meter properties screens. TEST mode is used to perform diagnostics and verify the
meter’s calibration and function.
NOTE
If your meter has the optional hardware lock, you must remove the meter’s cover to put it into TEST mode.
Refer to “Meter Security Features” on page 50 for more information.
Basic operation (NORM mode)
The ION 8000 series meter defaults to NORM mode when powered up, and
remains in this mode until you manually switch to ALT or TEST.
NOTE
You can customize NORM mode display screens and alter the front panel’s scrolling characteristics by
editing the configuration of the meter’s Display and Scroll modules – refer to “Display Setup Menu” on
page 35 for more details.
If you have a meter without the hardware lock, all of the settings available in the
panel Setup menu can be changed while the meter is in NORM mode, provided
you have the correct password. If you have a hardware-locked meter, only the
basic communications parameters in the COM Setup menu can be changed in
NORM mode. (You must enter TEST mode to change other meter parameters on
the hardware-locked meter — refer to “Additional Revenue Metering Security” on
page 69 for more details.)
ALT mode
ALT mode provides scrolling display screens that show power system data, billing
information (including extensive Time of Use data) and meter properties such as
Nameplate information.
ALT mode screens are described in “ALT mode default display screens” on
page 168.
Switching to ALT mode
Press the Alt/Enter button to switch to ALT
to switch back to NORM mode at any time. If no buttons are pressed, the meter
automatically reverts to NORM mode after five minutes. As with any mode,
pressing any button temporarily suspends display screen scrolling, allowing you
to press the Up or Down arrow buttons to manually browse the available screens.
mode. Press the Alt/Enter button again
Chapter 2 - Front Panel Page 25
Modes of Operation ION 8000 Series User Guide
TEST mode
TEST mode is typically used for verifying meter calibration and function. The
meter is usually reading data from a test power supply while these functions are
performed.
All of the billing quantities that are recorded when the meter is in NORM and ALT
mode will stop accumulating when the meter is switched to TEST mode — the data
is sent to special TEST mode registers instead. The values accumulated in these test
registers are displayed on the front panel (and in Vista software).
The regular NORM/ALT mode billing registers are unaffected while the meter is
in TEST mode; accumulation of this data continues as soon as you exit TEST mode.
All test registers are reset to zero when you exit TEST mode.
For detailed information on TEST mode, see “Switching to TEST Mode” on
page 175.
NOTE
The meter will always return to NORM mode when you exit TEST mode, even if you entered TEST mode
from ALT mode.
Page 26Chapter 2 - Front Panel
ION 8000 Series User GuideConfiguring the Meter with the Front Panel
Configuring the Meter with the Front Panel
With the meter’s front panel, you can navigate through different menus to perform
basic setup on your meter.
Status bar
Optical port
Navigation buttons
Watt LED
ALT/Enter button
VAR LED
Main display
Meter label
Demand reset switch
Accessing the Setup Menu
To access the Setup menu, press and hold the front panel's Alt/Enter button while
the meter is displaying power system data. Within the Setup menu is a list of submenus that contain the meter’s configurable settings. Setup menu items are
described in “Front Panel Features” on page 18.
Press the Up or Down arrow buttons to navigate through the menu. Highlight a
menu item and press the Alt/Enter button. When you se lect a n item from the Se tup
menu, you will be presented with another menu of the settings in the meter. You
may need to penetrate several layers of menus to access the setting you want to
change.
Chapter 2 - Front Panel Page 27
Configuring the Meter with the Front Panel ION 8000 Series User Guide
The following diagram shows how the buttons are used to navigate the menus:
The settings contained in the Setup menu are described below.
Basic Setup: changes basic settings in the power measurement system
configuration.
Demand Setup: Rolling Block/Sliding Window and Thermal Demand settings.
COM1 Setup: RS-232/RS-485 multiplexed port setup.
COM2 Setup: RS-485 port or optional modem setup.
COM3 Setup: optical port setup.
COM4 Setup: settings for the optional RS-485 port - only available for
ION 8500 / ION 8400 meters with the optional modem.
Network Setup: settings for the optional Ethernet 10Base-T port.
Format Setup: customizes the style and values appearing on the display screens
Display Setup: customizes display appearance, update time, and demand lockout
time.
Security: allows you to modify your password, disable the password, or disable
meter configuration with a web browser.
Each of these settings are discussed in turn in “Setup Menus” on page 30.
Page 28Chapter 2 - Front Panel
ION 8000 Series User GuideConfiguring the Meter with the Front Panel
Returning to Previous Setup Screens
Use the Up or Down arrow buttons to scroll through the menu items. When the
setting you want to change is highlighted, press the Alt/Enter button.
To return to a previous screen, highlight the RETURN menu item and then press
the Alt/Enter button.
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
BASIC SETUP
RETURN
VOLTS MODE
PT PRIMARY
Configuring Parameters Using the Navigation Buttons
Use the Up or Down arrow buttons to change the value (if numeric) or the setting
(if enumerated) of the highlighted parameter.
CONFIRM CHANGE
YES
NO
To change the position of the cursor, press the Up or Down arrow buttons for
about one second. The Up arrow button moves the cursor one position to the left,
and the Down arrow button moves the cursor one position to the right. Once you
have the value you want, press the Alt/Enter button to select it.
NOTE
When setting Ethernet values (IP address, default gateway, etc.), press the Up arrow button to insert
additional digit spaces. Press the Down arrow to remove digit spaces (see “Network Setup Menu” on
page 33 for more information).
OUT OF RANGE screen
When editing numeric data the numbers below MIN and MAX indicate valid entry
bounds. If you enter a value outside valid bounds, you will be presented with an
OUT OF RANGE screen. You may then either return to the register you were
editing, or choose to exit.
Confirming Configuration Changes
The CONFIRM screen appears whenever you attempt to change the meter’s
settings through the front panel. This allows you to abort an unwanted
configuration change. The front panel also informs you when an entry is out of
range. In either case, you must press the Alt/Enter button to return to the previous
setup screen.
Chapter 2 - Front Panel Page 29
Setup Menus ION 8000 Series User Guide
Setup Menus
The following sections describe settings for the Demand Setup, COM Setup and
Network Setup menus. Security setup is also discussed.
Setup menus can be accessed with ION software or with the meter’s front panel.
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
BASIC SETUP
VOLTS MODE
PT PRIMARY
PT SECONDARY
Basic Setup Menu
The Basic Setup menu lets you set volts mode, potential transformer (PT) and
current transformer (CT) ratios and various other settings (such as I4 and voltage
and current polarities) so that you can ensure that your meter is adequately set for
your application.
To access the Basic Setup menu with the meter’s front panel:
1.Press and hold the Alt/Enter button on the front panel of the meter. After
about three seconds the Setup screen appears.
2.Use the Up or Down arrow buttons to navigate to the
the Alt/Enter button.
3.Press the Up or Down arrow buttons to navigate to the appropriate menus
(VOLTS MODE, PT PRIMARY, PT SECONDARY, CT PRIMARY,
CT SECONDARY).
Many of the settings will be configured when the meter is initially put into service
(the device will not operate properly until Volts mode and PT and CT ratios are
set), but some settings may need to be changed to refine the device’s operation.
NOTE
If you have a hardware-lockable ION 8000 Series meter, you must put the device into TEST mode prior
to making changes to the Basic Setup parameters. For TEST mode information, see “TEST mode” on
page 26.
BASICSETUP menu. Press
The functions of the setup registers in the Basic Setup menu are as follows:
Basic Setup
Menu Item
Volts mode*The power system’s configuration and supported Form Factor
CT Primary5The Current Transformer’s primary winding rating
CT Secondary5The Current Transformer’s secondary winding rating
I4 Primary5The Current Transformer’s primary winding rating for I4
I4 Secondary5The Current Transformer’s secondary winding rating for I4
VA PolarityNORMALThe polarity of the Potential Transformer on V1
VB PolarityNORMALThe polarity of the Potential Transformer on V2
VC PolarityNORMALThe polarity of the Potential Transformer on V3
Page 30Chapter 2 - Front Panel
Default
Value
Function
ION 8000 Series User GuideSetup Menus
IA PolarityNORMALThe polarity of the Current Transformer on I1
IB PolarityNORMALThe polarity of the Current Transformer on I2
IC PolarityNORMALThe polarity of the Current Transformer on I3
I4 PolarityNORMALThe polarity of the Current Transformer on I4
Phase RotationABCThe expected rotation of the voltage phases (ABC or ACB)
8500 SETUP
BASIC SETUP
DEMAND SETUP
COM1 SETUP
DEMAND SETUP
RETURN
SWD SUBINTERVAL
SWD # SUBINTERVLS
Demand Setup Menu
You can access the Demand Setup menu with ION software or with the meter’s
front panel.
To view the Demand Setup menu with the meter’s front panel, press and hold the
Alt/Enter button, and press the Up or Down arrow buttons to highlight Demand
Setup, and then press the Alt/Enter button.
The Demand Setup menu accesses the global settings for all of the revenue related
Rolling Block (Sliding Window) Demand and Thermal Demand functionality in
the ION 8000 series meter. The settings provided in the Demand Setup menu
control the timing of these demand calculations. The following setup registers and
their default settings are displayed:
Setup Register
SWD SubInterval900 sSpecifies the number of seconds in the Rolling Block sub-interval
SWD # SubIntervals1Sets the number of sub-interval in the Rolling Blocks
SWD Pred Resp70Specifies the speed of the predicted demand output
TD Interval900 sSets the number of seconds in the thermal demand interval
TD Tim Const90Sets the rate of the thermal demand output response
Default
Val ue
Function
NOTE
Refer to “Sliding Window Demand Module Settings” on page 117 and “Thermal Demand Module
Settings” on page 118 for complete details about Sliding Window Demand and Thermal Demand
modules.
8500 SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
Chapter 2 - Front Panel Page 31
COM1 SETUP
RETURN
PROTOCOL
BAUD RATE
COM Ports Setup Menu
You can access the COM Ports Setup menu with ION Setup software or with the
meter’s front panel. See “Communications Options” on page 73 for more
information.
To make changes to communications settings with the meter’s front panel, hold
down the Alt/Enter button for three seconds to enter the Setup menu, then press
the Down arrow button to select the COM Setup you want. Depending upon the
Setup Menus ION 8000 Series User Guide
communications options ordered with your meter, the parameter settings
available are as follows:
Menu ItemDescription
COM1 SetupSettings for the selectable RS-232 or RS-485 communications port. The COM1 communications channel may be used by
the ION 8300 meter optional Ethernet if COM2 has the internal modem option or dedicated RS-485.
COM2 SetupSettings for the dedicated RS-485 or optional modem port. The COM2 communications channel may be used by ION
8300 meter optional Ethernet if COM1 has selectable RS-232 or RS-485.
COM3 SetupSettings for the optical communications port.
COM4 Setup
Network Setup
The optional COM4 RS-485 port is only available for the ION 8500 / ION 8400 meters with the optional modem. The
COM4 communications channel is also used by the Ethernet option, so COM4 RS-485 is not available when the
Ethernet option is selected.
Settings for the Ethernet communications port.
For the ION 8500 / ION 8400 meters, the optional Ethernet port shares the COM4 communications channel with the
optional COM4 RS-485 communications, so Ethernet is not available when COM4 RS-485 is enabled.
For ION 8300 meters, the optional Ethernet port shares the COM1 or COM2 communications channel, so Ethernet may
not be available if both of these ports have other options.
NOTE
For hardware-lockable meters, you do not need to be in TEST mode to alter these COM port settings.
Serial COM Settings
There are three main parameters that you must set or verify if your meter is
connected to a serial network (including modem communications): Unit ID, BaudRate, and Protocol.
NOTE
Other parameters such as TRANSMITDELAY, are used in advanced configuration or fine-tuning your system.
Settings for the parameters mentioned above are commonly required to get your meter communicating.
You can access serial COM settings with ION Setup software, or with the meter’s
front panel. To navigate to the Unit ID, baud rate, and protocol settings using the
meter’s front panel:
1.Press and hold the Alt/Enter button on the front panel of the meter. After
about three seconds the Setup screen appears.
2.Use the Up or Down arrow buttons to navigate to the COM port you want to
configure. Press the Alt/Enter button.
Press the Up or Down arrow buttons to navigate to PROTOCOL, UNIT ID and
BAUD RATE menus. The default configurations are listed in the following COM
Setup menu for COM1 (selectable RS-232 or RS-485), COM2 (RS-485 or optional
modem), COM3 (optical port) and COM4 (optional RS-485 with optional modem
for ION 8500 and ION 8400 meters only).
Sets the ION 8000 series’ Unit ID;
a unique Unit ID is required for each device (including all
the devices on a ModemGate or EtherGate serial loop)
The communications mode selected:
COM1: RS-232 or RS-485
COM3: IRDA optical port or internal modem
‘RTS/CTS’ or ‘RTS with Delay’;
this setting is located in the COM1 Hardware sub-menu
The number of rings during defined answer hours – Valid
entries for this register are 0-255 rings; an entry of 0 rings
will disable answering
Time Synchronization and Timekeeping
2
for further details on using the meter’s time
ION
9600 bps
COM1: Unit ID is based
on the serial number.
COM2: 101
COM3: 102
COM1: RS-485
COM3: Modem
‘RTS with Delay’
1
*
8500 SETUP
COM3 SETUP
NETWORK SETUP
FORMAT SETUP
NETWORK SETUP
RETURN
IP ADDRESS
MASK
Network Setup Menu
There are two main parameters that you must set or verify if your meter is
connected to an Ethernet network: IP address and Subnet mask address.
NOTE
There are other parameters, such as IPBOOT, GATEWAYADDRESS and SMTPADDRESS, that are used in
advanced configuration or in fine tuning your system. The parameters discussed here are the most
common parameters required to get your meter communicating.
The default configurations for the network settings are as follows:
SettingDescriptionDefault
IP BootP
Option
IP AddressSets the IP Address for the meter
A BootP server automatically sets the IP Address,
Subnet Mask, Gateway, & SMTP Mail Server IP Address
– see your Network Administrator to determine if BootP
is used
Manual
If a BootP server has been correctly set up, the IP Address number
appears.
If no BootP server has been set up (e.g. you wish to configure
settings through the front panel) then the default is None.
Chapter 2 - Front Panel Page 33
Setup Menus ION 8000 Series User Guide
SettingDescriptionDefault
Subnet Mask
Gateway
SMTP
Address
Used if subnetting applies to your network
– see your Network Administrator to determine if
Subnet Mask is used
Used in multiple network configurations
– see your Network Administrator to determine if
Gateway is used
Sets the IP Address for the SMTP Mail Server that is
configured to forward mail from the meter to the final
destination
– see your Network Administrator to determine if the
SMTP Mail Server is used
Network settings can be configured in one of two ways: automatically with BootP,
or manually through the front panel.
Configuring Network Settings Through the Front Panel
To configure network settings through the meter’s front panel or with ION
software, the BootP setting must to set Manual (the default).
CAUTION
Configuring the IP Address, Subnet Mask, and Gateway registers incorrectly can cause network
disruptions. See your network administrator for more information.
If a BootP server has been correctly set up, and Subnet Mask is
used, then the Subnet Mask address number appears. If Subnet
Mask is not used, then the default is None.
If no BootP server has been set up (e.g. you wish to configure
through the front panel) then the default is None.
If a BootP server has been correctly set up, and Gateway is used,
then the Gateway address number appears. If Gateway is not
used, then the default is None.
If no BootP server has been set up (e.g. you wish to configure
through the front panel) then the default is None.
If a BootP server has been correctly set up, and an SMTP Address is
used, then the SMTP Address address number appears. If an SMTP
Address is not used, then the default is None.
If no BootP server has been set up (e.g. you wish to configure
through the front panel) then the default is None.
Typically, your Network Administrator will provide you with the appropriate IP
Address for the meter. The Subnet Mask and Gateway settings are only required
if you have communications between multiple Ethernet networks and if
subnetting is implemented.
Use the Navigation buttons to edit the values of the network settings so that they
match your system addresses. As you configure the network addresses, the front
panel automatically discards unnecessary leading zeroes from each three-digit
grouping. The hidden leading zeroes appear (and disappear again) as you move
the position of cursor across the network address.
89.123.40.
0
56
In the example above, the highlighted zero is discarded as soon as you change the
position of the cursor.
Page 34Chapter 2 - Front Panel
ION 8000 Series User GuideSetup Menus
8500 SETUP
NETWORK SETUP
FORMAT SETUP
DISPLAY SETUP
8500 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
FORMAT SETUP
RETURN
PHASE LABELS
PF SYMBOL
DISPLAY SETUP
RETURN
UPDATE RATE
CONTRAST
Format Setup Menu
Format Setup contains the following values that set labeling and formatting
preferences.
Menu ItemDescription
Phase Labels
PF Symbol
Digit Group
Date Format
Show DST
Volts Decimal,
Current Decimal,
and Power Decimal
ABC, 123, RWB, RYB, XYZ, or RST
Power Factor Symbols can be: LD/LG, +/-, or CAP/IND.
Numbers of three digits or greater can be grouped in any of the following
three formats: 1000.0 (no commas, no spaces) or 1,000.0 (commas, no
spaces) or 1 000.0 (no commas, spaces).
The date can be expressed in any of three formats: DD/MM/YYYY, YYYY/
MM/DD, and MM/DD/YYYY.
You can choose to display Daylight Savings Time (DST) or not.
You can have voltage, current, and power measurements shown to one, two,
or three decimals of accuracy. The default value is two decimals of accuracy.
Display Setup Menu
You can configure the following display preferences within Display Setup.
Menu ItemDescription
Update Rate
Contrast
Backlight Timeout
DMD Lock
TEST mode TO
The front panel can update its data from every one to every six seconds. The
default update time is one second.
A front panel display contrast level can be set from zero to nine where higher
numbers represent a sharper level of contrast. The default level is five. The
contrast level may be adjusted at any time by pressing and holding down
both Up and Down arrow buttons simultaneously.
This selection allows you to make the backlight turn off automatically after
zero to 7200 seconds (two hours). The default is 300 seconds (five minutes).
If this value is set to 0 (zero), the backlight will always be on.
Demand lockout time (in seconds) controls the minimum allowable time
between consecutive demand resets. You may select values from 0 (disabled)
to 5184000 (60 days). The default is 216000 (25 days).
If there are no front panel key presses, the meter will exit TEST mode
automatically; the TEST mode time-out setting defines how long the meter
remains in TEST mode before switching to norm mode. While in TEST mode,
the value on the bottom right of the status bar indicates the amount of time
before TEST mode times out. The default TEST mode time-out value is 30
minutes.
Chapter 2 - Front Panel Page 35
Setup Menus ION 8000 Series User Guide
8500 SETUP
DISPLAY SETUP
SECURITY
RETURN
SECURITY
RETURN
MODIFY PASSWD
DISABLE SECURITY
Security Menu
The settings in the front panel Security menu item allow you to:
modify the existing meter password or reset it to the factory default.
disable the password security check.
enable web browser configuration on the meter.
You require the valid password to enter the Security Settings menu. The default
password is 0 (zero).
See “Meter Security Features” on page 50 for more details.
NOTE
The password enables users to change the configuration of the meter. It is recommended that you change
your password from the default when you put the meter into service
If you have not yet entered your password, the meter’s front panel requires that
you enter it before you can view the Security Setup menu. Use the Navigation
buttons to enter numerical data. If you enter an incorrect password, the front panel
will display an “invalid password” message and you will have to try again.
Modify Password Sub-Menu
Use this sub-menu to change the password, or to reset the password to the factory
default (0).
From the meter’s front panel select S
appear: M
M
ODIFY PASSWORD, or the Down button to select FACTORY DEFAULT.
ODIFY PASSWORD or FACTORY DEFAULT. Use the Up button to select
ECURITY, then MODIFY PASSWORD. Two choices
Changing a password
To change the value of a highlighted digit, use the Up or Down arrow buttons.
To change the position of the cursor one space to the left, press the Up arrow
button for about one second.
To change the position of the cursor one space to the right, press the Down
arrow button for about one second.
When the correct password is displayed press Alt/Enter.
Disable Security Sub-Menu
Use this sub-menu to enable and disable password security on the ION 8000 series.
Disabling the password allows changes to all the meter’s settings through the front
panel without a security check.
CAUTION
Non-secure access to critical settings in the meter, such as PT and CT ratios, is not advisable. It is highly
recommended that any ION 8000 series in the field have the password security check enabled.
Page 36Chapter 2 - Front Panel
ION 8000 Series User GuideSetup Menus
When you re-enable password security, the password is reset to the factory default
of 0 (zero). You should re-enter a custom password at this point.
Disabling the Password Security Check is necessary to write to the meter when it
is a Modbus Slave device. Refer to “The Meter as Modbus Slave” on page 97 for
details about configuring your ION 8000 series for third-party systems.
Web Config
Use this setting to enable/disable web browser configuration of the meter. See
“Enabling and Disabling Web Config Access” on page 55 for more details.
Chapter 2 - Front Panel Page 37
3Templates and Firmware
Your meter comes installed with a pre-configured default template. This template
contains various frameworks which provide all the power measuring and
analyzing functionality of the meter. Templates and frameworks can be used
immediately without any user configuration (“right out of the box”). They can also
be customized, reconfigured, and pasted from one meter to another.
For more information on templates, frameworks and ION modules, see the
ION Reference.
Your meter’s operating system is known as firmware. When newer firmware is
available for your meter, simply upgrade to the latest version for all the added
features and functionality.
The Factory module displays firmware version, serial number and other device
information in read-only setup registers (read-only registers can be viewed but not
changed).
Factory Module Settings
The device information provided is as follows:
Setup RegisterDescription
Device TypeA device type identifier (e.g. “8500” for the ION 8500)
ComplianceA statement of whether the device is ION compliant or not
OptionsShows model number of meter
RevisionThe meter’s firmware version
Serial NumThe meter’s serial number
ION VersionThe ION version supported by the device
TemplateThe name of the template (framework) installed on the device at the factory
Nom FreqThe expected frequency of the power system being monitored
The Factory module also contains numerous read-only setup registers that hold
the calibration constants used at the factory.
How to TAG Your Meter
Three configurable setup registers are provided for you to enter your company
name and other text information you want stored in the meter:
Owner - This is a text register for storing user information (e.g. company name); it
can be up to 255 characters in length.
Tag 1 - This is a text register for storing user information (e.g. device location); it
can be up to 15 characters in length.
Tag 2 - This is a text register for storing user information (e.g. device number or
identifier); it can be up to 15 characters in length
Page 40Chapter 3 - Templates and Firmware
ION 8000 Series User GuideRestoring the Factory Configuration
Restoring the Factory Configuration
If you have made changes to the default functionality and want to return to the
factory configuration, you can re-initialize the factory configuration in the meter
using ION software. The basic setup of the device can be retained, so the meter
does not need to be taken out of service for a long period of time.
NOTE
If you restore the factory configuration, all custom features you have created are lost.
Using Designer
1.Display the meter’s main Configuration screen in Designer.
2.Choose Select All from the Edit menu, then press Delete.
The confirmation dialog box appears explaining that some modules will not be
deleted (core modules cannot be deleted — scroll down in the dialog to see
which standard modules will be deleted).
3.Click OK on the confirmation dialog box.
After a brief wait the modules are deleted, and the main meter Configuration
screen is blank except for the Frameworks folder in the Advanced Setup area.
(The Frameworks folder contains the folder of Core modules which cannot be
deleted.)
4.Choose Select All from the Edit menu to select the Frameworks folder. This
selects all subfolders and modules within the folder.
5.In the Edit menu, choose Paste from Framework, then select the appropriate.fwn
file from the folder \ION Enterprise\config\fmwk\nd\. Click OK.
The Factory module’s Default Template register tells you the filename for the
default factory framework. (For details about framework files, contact Customer
Service or visit the Support area of the Power Measurement web site.)
6.Click Open. The Paste Summary window appears.
7.Click on the first module, scroll down to the last module, hold the Shift key and
click on the last module. This selects all of the modules.
8.While holding the Shift key, click on the check box to the left of the module name
so you see a lock icon with a green check mark.
CAUTION
Persistent modules can be overwritten in Designer. When pasting a default framework onto a meter, use
lock-paste on the Persistent modules, not free-paste. A list of Persistent modules is available from
Customer Service.
9.Check “Maintain external inputs” and click OK on the confirmation dialog box.
A message appears indicating that Designer is pasting modules. All modules are
selected when the paste is complete. Click anywhere in the background of the
node diagram to deselect all of the modules.
Chapter 3 - Templates and Firmware Page 41
Restoring the Factory Configuration ION 8000 Series User Guide
10. Click the Power Meter shortcut in the Basic Configuration area to select it. Once
selected, click Reset in the Designer toolbar, or select Reset from the Edit menu.
This reverts the Power Meter to the settings it had before you deleted any
modules (retaining the basic setup you previously had).
11. Choose Send & Save from the File menu. The factory configuration is now
restored and any custom functionality you created is removed.
NOTE
The time required to complete steps 3, 5, and 11 may vary depending on your connection and the meter
configuration.
Using ION Setup
1.Download your device’s latest template from http://www.pwrm.com/
support/downloads/. Save the .DCF file in the .../ION Setup/TEMPLATE
folder for easy access.
2.Connect to your meter in ION Setup, using Basic Mode.
3.Navigate to Setup Assistant > Template.
4.Click the Send to Meter tab and click the Send button.
5.Select the .DCF file from the TEMPLATE folder and click OK.
Page 42Chapter 3 - Templates and Firmware
ION 8000 Series User GuideUpgrading Your Meter
6.The Template Paste Options screen appears. Select the check boxes for the
settings you wish to retain (not overwrite) and click OK.
Rapid Meter Programming pastes the template onto your meter. A dialog box
confirms the paste was successful.
Upgrading Your Meter
See the Upgrading ION Device Firmware technical note for details.
Chapter 3 - Templates and Firmware Page 43
4Basic Setup
This chapter explains how to perform basic meter setup via the front panel or via
ION software.
Basic configuration of the meter is provided by the Power Meter module. The
Power Meter module is the main connection between the power system
measurements and all other ION modules in the device. This module reports the
values for all voltage, current and power measurements. The Power Meter
module’s setup registers describe details of the power system being monitored.
Many of the Power Meter module’s setup registers are configured when the meter
is initially put into service, although the device cannot operate properly until the
Volts Mode and PT and CT ratios are set. Some registers may need to be changed
to refine the device’s operation. See the ION Reference for more details on the Power
Meter module.
Configuring Basic Setup
Use the front panel or ION software to perform basic meter setup.
Using the Front Panel
The Basic Setup menu item provides access to the following power system settings.
MenuSettingDescriptionRange (Values)Default
9S 4W-WYE/DELTA
Volts ModeThe power system’s configuration – WYE, DELTA, etc.
PT PrimaryThe Potential Transformer’s primary winding voltage rating1 to 999,999,999120
PT SecondaryThe Potential Transformer’s secondary winding voltage rating1 to 999,999,999120
CT PrimaryThe Current Transformer’s primary winding current rating1 to 999,999,9995
CT SecondaryThe Current Transformer’s secondary winding current rating1 to 999,999,9995
I4 CT PrimaryPrimary rating for the I4 current transformer (if available)1.0 - 999,999.005
I4 CT SecondarySecondary rating for the I4 current transformer (if available)1.0 - 999,999.005
VA PolarityThe polarity of the Potential Transformer on VANormal or InvertedNormal
Basic Setup
VB PolarityThe polarity of the Potential Transformer on VBNormal or InvertedNormal
VC PolarityThe polarity of the Potential Transformer on VCNormal or InvertedNormal
IA PolarityThe polarity of the Current Transformer on IANormal or InvertedNormal
IB PolarityThe polarity of the Current Transformer on IBNormal or InvertedNormal
IC PolarityThe polarity of the Current Transformer on ICNormal or InvertedNormal
I4 PolarityThe polarity of the Current Transformer on I4Normal or InvertedNormal
The Basic Setup Assistant helps you configure the Power Meter module:
1.Open ION Setup and connect to your meter, using Basic Mode.
Page 46Chapter 4 - Basic Setup
ION 8000 Series User GuideConfiguring Basic Setup
2.In the Setup Assistant, navigate to Basic Setup and click on the PT/CT Ratios tab.
3.Configure each register as required by selecting the parameter and clicking Edit.
Using Designer
Open your meter in Designer and navigate to the Basic Configuration Framework.
Right-click on the Power Meter module to edit.
Chapter 4 - Basic Setup Page 47
Power Meter Module Settings ION 8000 Series User Guide
Power Meter Module Settings
Setup
Register
Volts mode
PT Prim
1
PT Sec
CT Prim
1
CT Sec
V4 Prim
1
V4 Sec
I4 CT Prim
I4 CT Sec
I5 CT Prim
I5 CT Sec
FunctionDefault
1
The power system’s configuration – WYE, DELTA, Single, etc4W-WYE
1
The Potential Transformer’s primary winding rating for V1, V2 and V3120
The Potential Transformer’s secondary winding rating for V1, V2 and V3120
1
The Current Transformer’s primary winding rating for I1, I2 and I35
The Current Transformer’s secondary winding rating for I1, I2 and I35
1
The Potential Transformer’s primary winding rating for V4120
The Potential Transformer’s secondary winding rating for V4120
1
The Current Transformer’s primary winding rating for I45
1
The Current Transformer’s secondary winding rating for I45
1
The Current Transformer’s primary winding rating for I55
1
The Current Transformer’s secondary winding rating for I55
Vn PolarityThe polarity of the Potential Transformer on VnNormal
In PolarityThe polarity of the Current Transformer on InNormal
Phase OrderThe expected rotation of the voltage phases (ABC or ACB)ABC
Phase Lbls
The phase label format assigned to the outputs (ABC, RST, XYZ, RYB,
RWB or 123)
ABC
1
The registers are typically set when the device is commissioned. Changing the values of these registers
while the device is in service is not recommended.
Once basic setup is performed (i.e. the PT/CT and Volts mode settings), the meter
operates properly. Typically there is no need to make further changes to the Power
Meter module’s setup registers.
Page 48Chapter 4 - Basic Setup
5Security
ION 8000 series meters offer Standard and Advanced meter security. Standard
security is enabled by default from the factory; procedures for changing these
security settings using the front panel and ION software are detailed in this
chapter. Advanced security, which allows up to 16 users, each with unique access
privileges, is discussed as well. This chapter also details some security features
available for revenue meters.
Meter Security Features ION 8000 Series User Guide
Meter Security Features
Your meter includes the following security features:
Standard meter security
Anytime you make configuration changes to your meter you must enter a
password. See “Standard Meter Security” on page 51.
Advanced meter security
Available only on the ION 8000 series meter, this level of security allows
configuration of up to 16 users, each with unique access rights to the meter. See the
topic “Configuring Advanced Meter Security” on page 61.
Revenue meter security
Your revenue meter can be protected by anti-tamper sealing. See “Additional
Revenue Metering Security” on page 69.
Software security
ION software security brings access-level security to the meter. With ION
software, you can configure multiple users with different passwords and specify
access rights. ION software security only applies to users who are accessing the
meter via ION software.
For more information on ION software security, refer to the ION Security technical
note.
Page 50Chapter 5 - Security
ION 8000 Series User GuideStandard Meter Security
Standard Meter Security
Standard meter security is enabled by default on all ION 8000 series meters; all
configuration functions in the front panel are password-protected. The password
is factory-set to 0 (zero).
If you make configuration changes to the meter via the front panel, the meter
prompts you for its password before accepting any configuration changes.
Similarly, if you make any configuration changes via ION software you are
prompted by the meter for its password (in addition to the password used to
access ION software). Once you enter the correct meter password and confirm the
new configuration, the change is set on the meter.
Configuring standard meter security using the front panel
Note that the front panel will prompt you for the meter password before you make
your first configuration change. You will not need to re-enter the password for
each subsequent change. However, if you perform no additional configuration
changes for five minutes, you will need to re-enter the Setup menu and provide the
valid meter password to resume making changes. This is because the meter returns
from setup mode to data display mode after five minutes of inactivity.
The meter password allows access to the meter's configuration through
ION software and the front panel. The default password is 0 (zero).
This section describes the password security options available to front panel users.
Step by step instructions are provided on the following procedures:
1.Entering the meter password
2.Changing the meter password
3.Disabling (and Enabling) the password security check
This section also presents security precautions to consider when configuring time
synchronization and third party protocols.
Entering the Password
The first time you try to make a change to any setting, you will be presented with
the password screen (shown below). After you have entered the correct password,
you will not have to re-enter it for other any other changes unless you exit the
configuration session.
ENTER PASSWD
MIN:
00000000
HOLD ARROW KEY TO ADVANCE CURSOR
00000000
MAX:
99999999
Chapter 5 - Security Page 51
Standard Meter Security ION 8000 Series User Guide
NOTE
Once the correct password is entered, you will not have to re-enter the password for any other changes
unless you exit configuration.
To enter the password:
1.To change the value of the highlighted digit, use the arrow buttons. The up
arrow increments the number and the down arrow decrements it.
2.To change the position of the cursor, hold down an arrow button for about one
second. The up arrow moves the cursor left one position, and the down arrow
moves the cursor right one position.
3.Once you have the value you want, press the Alt/Enter button.
Changing the Password
By default, the password is set to 0 (zero) in the factory. The password may be
changed to any eight-digit number. It is highly recommended that you change the
password from the default value. To change the password:
1.Hold down the Alt/Enter button to access the Setup menu.
2.Scroll through the menu items using the arrow buttons, highlight SECURITY.
3.Press the Alt/Enter button to select SECURITY.
Ia
Ib
Ic
In
18:30:00 1999.06.01 ABC Q1 NORM5:00mEOI
2401.1
2951.3
2291.7
102.1
kA
kA
kA
kA
Press and Hold
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
Press
SECURITY
RETURN
MODIFY PASSWD
DISABLE SECURITY
4.You will be prompted to enter the current meter password (see “Entering the
Password”, above). Once you enter the password, you are presented with the
“MODIFY PASSWD” screen, as seen below:
MODIFY PASSWD
MIN:
00000000
HOLD ARROW KEY TO ADVANCE CURSOR
00000000
MAX:
99999999
5.To change the value of the highlighted digit, use the arrow buttons. The up
arrow increments the number and the down arrow decrements it.
6.To change the position of the cursor, hold down an arrow button for about one
second. The up arrow moves the cursor left one position, and the down arrow
moves the cursor right one position.
Page 52Chapter 5 - Security
ION 8000 Series User GuideStandard Meter Security
7.Once you have the value you want, press the Alt/Enter button. You will be
prompted for your current password before the new password is saved.
Enabling & Disabling the Password Security Check
Disabling the password allows changes to all the meter's settings through the front
panel without a security check. This procedure may only be necessary if the
communications interface you are using does not support the meter’s security
protocols.
CAUTION
Non-secure access to critical settings in the meter, such as PT and CT ratios, is not advisable. It is highly
recommended that any ION 8000 series devices in the field have the password security check enabled.
Disabling the Password Security Check
Follow these steps to disable the password security check:
1.Press the Alt/Enter button to enter the Setup menu. Scroll down the menu with
the arrow button. Press Alt/Enter again when SECURITY is highlighted.
2.Enter the valid meter password at the password prompt. You are then presented
with the Security menu.
3.Scroll down and highlight the DISABLE SECURITY menu item and press the
Alt/Enter button.
Ia
Ib
Ic
In
18:30:00
2401.1
2951.3
2291.7
102.1
1999.06.01 ABC Q1 NORM
EOI
kA
kA
kA
kA
Press and Hold
Press
Press
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
Press
SECURITY
RETURN
MODIFY PASSWD
DISABLE SECURITY
4.Select PROCEED, then select YES at the following prompt.
DISABLE SECURITY
PROCEED
RETURN
A message appears on screen notifying you of how to re-enable password
security (refer to "Enabling the Password Security Check", below). Your meter’s
password is now disabled; changes to settings in the meter do not require a valid
password.
Press and Hold
CONFIRM CHANGE
YES
NO
5.Press the Alt/Enter button to return to the Setup menu.
Chapter 5 - Security Page 53
Standard Meter Security ION 8000 Series User Guide
Enabling the Password Security Check
When you re-enable the password security, you are required to enter a new
password. To re-enable password security:
1.Press and hold down the Alt/Enter button to enter the Setup menu. Scroll
down the menu and select SECURITY.
2.From the Security menu, select MODIFY PASSWD, and press the Alt/Enter
button. The Modify Password Screen appears.
3.The message FAC DEFAULT appears in the middle of the Modify Password
screen. If you want to use the factory default password, press the Alt/Enter
button. If you want to set the password to a different eight-digit number, use the
instructions in Changing the Password above.
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
Press
DISABLE SECURITY
SECURITY
RETURN
MODIFY PASSWD
Press
MODIFY PASSWD
FAC DEFAULT
Press
CONFIRM CHANGE
YES
NO
4.Once you have entered your new password, press the Alt/Enter button.
5.Select YES to confirm the change and return to the Setup menu.
The password security check is re-enabled, and all changes to the device's
configuration require the new meter password.
Resetting the Password
NOTE
If you forget your password, and your meter has the Password Security check enabled, you must remove
the meter's outer cover to put the device into TEST mode.
In the event that you forget or lose your meter password, you can reset the
password to the factory default value of 0 (zero). Resetting the password requires
that the meter be in TEST mode (Refer to “Switching to TEST Mode” on page 175
for details on invoking TEST mode).
If your meter has the Password Security check disabled, you can invoke TEST
mode using ION software. If the password security check is enabled (or you have
the hardware-locked option) you will have to remove the meter's outer cover to
access the TEST Mode button.
Follow these instructions to reset the password to the factory default:
1.Put the device into TEST mode (either through communications or by pressing
the TEST Mode button. Refer to “Switching to TEST Mode” on page 175 for
details).
2.Once the device is in TEST mode, press and hold down the Alt/Enter button and
Demand Reset buttons simultaneously.
Page 54Chapter 5 - Security
ION 8000 Series User GuideStandard Meter Security
A message appears on screen: PASSWORD RESET PASSWORD SET TO
DEFAULT. Password Security is now enabled; the meter password is 0 (zero).
Enabling and Disabling Web Config Access
By default, remote configuration of the device via web browser is enabled. Follow
these steps to enable or disable your meter’s web configuration access.
1.Press the Alt/Enter button to enter the Setup menu. Scroll down the menu with
the arrow button. Press Alt/Enter again when SECURITY is highlighted.
2.Enter the valid meter password at the password prompt. You are then presented
with the Security menu.
3.Scroll down and highlight the WEB CONFIG menu item and press the Alt/Enter
button.
4.Select “Enabled” or “Disabled” as appropriate.
5.Confirm the change and select RETURN to go back to the Setup Menu.
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
Press
SECURITY
RETURN
WEB CONFIG
RETURN
Press
WEB CONFIG
Disabled
Enabled
Press
CONFIRM CHANGE
YES
NO
Time Synchronization Security Considerations
Depending on ION software settings, a workstation that connects to an
ION 8000 series device may send a time synchronization signal and synchronize
the meter's internal clock with the workstation's clock. This could cause overlaps
in the Demand intervals, and timestamps in the data logs may not be accurate.
Chapter 5 - Security Page 55
Standard Meter Security ION 8000 Series User Guide
Ensure that the TimeSynch Source setup register in the Clock module is set to a
secure communications port. By default, the Time Synch Source setup register in the
Clock module is set to COM3 - the optical port. Time synchronization broadcasts
will only be accepted through the optical port in this configuration. The following
example is from the Clock module’s Time Synch Source setup register as seen in
ION Setup.
Ensure that time synchronization is disabled on all other ports. Use ION software
to disable time synchronization on a communications port; refer to ION Enterprise
on-line help.
Configuring standard meter security in ION Setup
1.Launch ION Setup with Supervisor authority.
2.Connect to the appropriate meter.
3.Once connected, double-click the Setup Assistant and select the Security
heading.
4.Make sure the Standard tab is selected
.
Page 56Chapter 5 - Security
ION 8000 Series User GuideStandard Meter Security
5.Click Password. The following dialog box appears:
6.Type a new numeric password and confirm by re-typing the password in the
fields.
Configuring standard meter security in Designer
1.Launch Designer software with Supervisor access.
2.Select Options > Show Toolbox if the toolbox is not displayed.
3.From the Options menu, select Change Standard Meter Security...
4.Enter the meter password when prompted. You must enter the existing meter
password before you can change security settings (the default is zero).
Chapter 5 - Security Page 57
Scenarios for Standard Security - Front Panel Security Enabled ION 8000 Series User Guide
5.Type a new numeric password and confirm by re-typing the password in the
fields (see image below). If you are sure you want to disable Standard security,
click the Disable Standard Meter Security check box.
CAUTION
Do not disable security unless it is absolutely necessary. Disabling Standard security leaves your meter
configuration open to tampering (intentional or unintentional) through communications and the front
panel.
Scenarios for Standard Security - Front Panel Security Enabled
1. Access through the front panel display
With the Front Panel Security enabled and Front Panel Programming set to
"Allowed", you can read metering data from the display. To configure meter
parameters, you must enter the numeric password.
If Front Panel Security is disabled and Front Panel Programming is set to
"Allowed", you can read metering data from the display and configure or make
changes without entering in a password.
If Front Panel Programming is set to "Disallowed", you can read metering data
from the display, but you cannot access any of the configuration screens from the
front panel display.
2. Access through software talking ION protocol with ION
Setup and/or ION Enterprise on ANY comm port (serial,
modem, optical and Ethernet)
If you are communicating through ION protocol (and have Front Panel Security
enabled) with the appropriate software access, you can read and configure meter
parameters. When you attempt to write or configure any parameter, you must
enter in the numeric password.
Page 58Chapter 5 - Security
ION 8000 Series User GuideScenarios for Standard Security - Front Panel Security Enabled
3. Access through Modbus on ANY comm port (serial, modem,
optical and Ethernet)
On ION meters, Modbus implementation consists of two parts:
i.Modbus Data
Includes the Modbus Slave ION modules.
These modules are configurable as to what data is available and where in
the range of Modbus registers this data is placed.
ii.Modbus Setup
Also referred to as the Modbus Map (see Power Measurement’s
“Modbus Protocol” document).
Uses fixed functionality and register mapping.
4. Accessing the Modbus data section with Standard Security
When accessing the Modbus Data section with Standard Security enabled, you:
Can read from the data section at all times.
Can write to the data section if the Modbus Slave Module is set to "Unsigned
16Bit Input Mode", and the Front Panel Security is disabled or the password is
set to zero.
Cannot write to the data section if the Front Panel Security is enabled and the
password is set to a non-zero value.
5. Accessing the Modbus setup section with Standard Security
When accessing the Modbus Setup Section with Standard Security enabled, you:
Can read from the setup section at all times.
Can write to the setup section if the Front Panel Security is disabled or the
password is set to zero.
Cannot write to the setup section if the Front Panel Security is enabled and set to
a non-zero value.
Time syncs are considered to be a Modbus Setup parameter and follow the same
rules above for writing a time sync to the meter. Also, the ION Clock Module must
have its Time Sync Source setup register set to the appropriate communication port.
The Modbus Slave module and the Clock module setup registers are only
accessible via ION protocol. Their settings are therefore protected by the security
settings on the ION device.
Chapter 5 - Security Page 59
Scenarios for Standard Security - Front Panel Security Enabled ION 8000 Series User Guide
6. Access through DNP 3.0 on ANY serial, modem or optical
communication port
NOTE
Currently there is no Ethernet support for DNP 3.0 on ION meters.
If you are communicating through DNP 3.0 protocol over any serial, modem or
optical port (and Front Panel Security is enabled), you can read data from the
default DNP 3.0 Map without having to enter the numeric password.
If the DNP 3.0 Map is changed to expose control and setup parameters, then you
could write to the custom DNP 3.0 Map. The DNP 3.0 Map can only be changed by
using ION Setup or ION Enterprise and then the customer must know the numeric
password. Time syncs can be sent to the meter in this mode.
7. Access through a standard browser on an Ethernet port via
HTTP protocol
If the Front Panel Security is enabled and Webserver Configuration Access is
enabled then you will be prompted for the password by your web browser before
being allowed to make any configuration changes to the meter. If the Front Panel
Security is not enabled, then you will be able to make configuration changes
without having to supply the password.
If Webserver Configuration Access is disabled, you can only read data. The default
Webserver pages contain real-time data only.
8. Access through FACTORY protocol on a Telnet connection via
Ethernet or HyperTerminal on a serial, modem, or optical
port
If the Front Panel Security is enabled, you must enter the numeric password to log
into the Factory protocol. If Front Panel Security is disabled, logging in via Factory
protocol does not require a password.
Once logged in, you can change the following:
1.IP Boot Option - BOOTP or Manual
2.IP Address
3.Subnet Mask
4.Gateway
5.Reset Battery Counters
6.Enable/Disable Front Panel Security
If you wish to change additional configuration settings beyond the above list,
contact Power Measurement.
Page 60Chapter 5 - Security
ION 8000 Series User GuideConfiguring Advanced Meter Security
Configuring Advanced Meter Security
Advanced meter security is available on ION 8000 series meters. This level of
security allows configuration of up to 16 users, each with unique access rights to
the meter. Access rights consist of the following levels where you can:
Read: view any parameter except the security configuration.
Peak Demand Reset: perform a reset of peak demand values (for example,
sliding window demand for kW, kVAR, kVA etc.).
Timesync: set the time on the meter.
Full Meter Configuration: configure any programmable register on the meter
except for registers related to the security setup, registers that result in a demand
reset, or actions that place the meter in test mode.
TEST Mode: put the meter into test mode.
Advanced Security Configuration: configure Advanced security for the meter,
full meter configuration must also be set to YES.
When configuring users, in most cases you must set Read access to YES. However,
you can set up a user without read access; for example, you may want to create a
user who can only timesync the meter. In some cases (such as Advanced security
configuration access) you must set multiple access options to YES. When you are
configuring Advanced security, the software rejects unacceptable or unsafe user
configurations.
NOTE
Use only ION Enterprise or ION Setup v1.1 to configure Advanced security. ION Setup has a Setup
Assistant that guides you through Advanced security setup.
Chapter 5 - Security Page 61
Configuring Advanced Meter Security ION 8000 Series User Guide
Entering an advanced security user name and password
When you attempt to view data or make a change to a meter that has advanced
security enabled, you are prompted for a user name and password.
.
1.Enter the valid Advanced security user name.
NOTE
User names are fixed as USER1 through to USER16.
2.Enter the appropriate password and click OK.
Configuring advanced security using ION Setup
If you are using ION Setup software follow the instructions below.
1.Launch ION Setup with Supervisor access.
2.Connect to the meter you want to configure with Advanced security.
3.Once connected, double-click the Setup Assistant in the right-hand column of
the Network Viewer.
4.Select the Security heading in the left-hand column of the Setup Assistant. Click
the Advanced Setup tab.
5.Click the SOP1 Enable Advanced Security listing. Click Edit.
Page 62Chapter 5 - Security
ION 8000 Series User GuideConfiguring Advanced Meter Security
6.Select the Enabled setting. You will be prompted with the following warning
screen. Click Yes.
Configuring advanced users with ION Setup
1.Click the Advanced Users tab in the Security setup screen.
2.Click the Add User button. ION Setup automatically adds a new user.
3.Select the new user listing and click Edit. The following dialog box appears:
Use the available settings to configure access levels for the new user. Passwords
can also be changed from this screen.
4.Click Send to send the changes to the meter.
Configuring advanced security using ION Enterprise
If you are using Designer software follow the instructions below.
1.Launch Designer software with Supervisor access. From the File menu choose
Open... and select the meter you want to configure with Advanced security.
2.If the toolbox is not displayed, choose Options from the main menu and select
Show Toolbox.
3.If you do not want to allow front panel programming using the Standard
security meter password then double-click on the Display Options module and
change the Front Panel Programming register to disallow.
Chapter 5 - Security Page 63
Device Security Access for ION Services ION 8000 Series User Guide
NOTE
If you allow front panel programming when you set up Advanced security, the meter password (used in
Standard security) is still active through the front panel. You may need to allow front panel programming
if someone installs the meter in the field and needs to make setup modifications. Once the meter is
installed, you can disallow front panel programming so that Advanced security user names and
passwords must be used to view or change meter information.
4.Double-click on the Meter Security Setup folder.
For each user you want to configure, drag out a Security User module from the
Toolbox, and modify the appropriate access level setup registers.
5.Click the Change Password button at the bottom left of the module setup screen
to configure a password. The default password is zero (0).
Click OK when you have configured the users.
6.Right-click on the Security Options module.
7.Double-click on any setup register and use the drop-down menu to change the
register setting or label.
You must set the ‘Enable Advanced Security’ register to Enabled. Refer to the
Security Options module description in the ION software online help for more
details.
8.From the File menu choose Send & Save. Advanced security is now enabled on
the meter.
Device Security Access for ION Services
Many ION Services need constant access to your network’s ION devices. These
services include the ION Log Server, the VIP and Site Server that perform the
following type of functions:
ServiceFunction
ION Log Server
VIP
Site ServerBroadcasts time signals to the meter.
When Advanced meter security is enabled, these services may not have sufficient
access rights to perform their operations. You must specify a user with sufficient
access rights for these services.
NOTE
You may want to configure a separate user for accessing services. If you observe trouble with ION
software accessing the meter, it is likely that these services either do not have access rights or the original
user name and password have changed.
Reads the ION meter Data Recorder or waveform modules and can
automatically rearm recorders that are configured as Stop-When-Full
Can be configured to read from a meter or perform control action
using Distributed Control.
Page 64Chapter 5 - Security
ION 8000 Series User GuideDevice Security Access for ION Services
Allowing ION Services access to advanced security enabled meters (ION Enterprise)
1.Launch the Management Console and click Devices on the Management
Console’s System Setup Pane.
2.Highlight the ION device (or select multiple devices) with Advanced security
enabled, right-click and select Security... The following window displays.
3.Select t he user name yo u wa nt fro m the drop dow n menu. Once yo u select a user
the Change Password button is active. Click the check box if you want to allow
this user to send time synchronization signals to the meter. Click OK.
4.Enter the valid password, re-type the password to confirm and click OK.
Allowing ION Services access to Standard security enabled meters (ION Enterprise)
1.Launch the Management Console and click Devices on the Management
Console's System Setup Pane.
2.Highlight the ION device (or select multiple devices) with Standard security
enabled, right-click and select Security....
3.Select Standard Security from the drop down menu. Click the check box if you
want to allow this user to send time synchronization signals to the meter. Click
OK.
4.Enter the valid meter password for Standard Security, re-type the password to
confirm, and click OK.
Allowing ION Services access to advanced security enabled meters (ION Setup)
1.Launch ION Setup and connect to the appropriate meter.
2.Once connected, open the Setup Assistant and select Security from the left-hand
column. Make sure Advanced Security is enabled in the Setup Assistant.
Chapter 5 - Security Page 65
Scenarios for Advanced Security - Front Panel Security Enabled ION 8000 Series User Guide
3.Select the user name you want from the available list. Click the Edit button. The
following window appears:
4.Click Time Sync Access from the available settings list. If you want to allow this
user to send time synchronization signals to the meter, ensure the setting reads
Yes. To change the setting, click the Edit button and make the appropriate
changes.
Scenarios for Advanced Security - Front Panel Security Enabled
1. Access through the front panel display
With both Advanced Security and Front Panel Security enabled, you can read the
metering data on the display. To configure/write to the meter, enter the numeric
password. Advanced Security does not add additional security when accessing the
meter through the front panel.
2. Access through software talking ION protocol with
ION Setup and/or ION Enterprise on ANY comm port (serial,
modem, optical and Ethernet)
With Advanced Security enabled and communicating through ION protocol on
any communication port, you must enter a username and password in order to
read or configure/write the meter. Advanced Security blocks access to the device
if you do not know the correct username and password. If you know the username
and password, and the username is assigned the proper access, then you can read
and configure/write (depending on the assigned user-access rights) data within
the meter. Refer to page 61 for details on setting up Advanced Security and how to
assign user access rights.
3. Access Through Modbus on ANY comm port (serial, modem,
optical and Ethernet)
On ION meters, Modbus implementation consists of two parts:
i.Modbus Data
Page 66Chapter 5 - Security
ION 8000 Series User GuideScenarios for Advanced Security - Front Panel Security Enabled
Includes the Modbus Slave ION modules.
These modules are configurable as to what data is available and where in
the range of Modbus registers this data is placed.
ii.Modbus Setup
Also referred to as the Modbus Map (see Power Measurement’s
“Modbus Protocol” document.
Uses fixed functionality and register mapping.
From an Advanced Security point of view, however, the Modbus Data and Setup
sections operate somewhat differently.
When accessing the Modbus Data Section with Advanced Security Enabled, you:
Can still read from the data section at all times.
Can write to the data section if the Modbus Slave Module is set to "Unsigned
16Bit Input Mode", and the "Modbus Map Access" is set to "Yes".
Cannot write to the data section if "Modbus Map Access" is set to "No".
When accessing the Modbus Setup Section with Advanced Security Enabled, you:
Can read from and write to the data section if "Modbus Map Access" is set to
"Yes".
Cannot read from or write to the data section if "MODBUS Map Access" is set to
"No".
You can write a time sync only if "MODBUS Map Access" and "Allow Broadcast
Time syncs" are both set to "Yes", and the ION Clock Module's "Time Sync Source"
setup register is set to the appropriate communication port.
Since the Modbus Map Access, the Modbus Slave module, and the Clock module
setup registers are only accessible via ION protocol, their settings are protected by
the security settings on the ION device.
4. Access through DNP 3.0 on ANY serial, modem or optical
port
NOTE
Currently there is no Ethernet support for DNP 3.0 on ION meters.
With Advanced Security enabled and communicating through DNP 3.0 protocol
over any serial, modem or optical port, you can read from the default DNP 3.0
Map. If the DNP 3.0 Map is changed to expose control and setup parameters, then
you can write to the custom DNP 3.0 Map. Any changes to the DNP 3.0 Map or the
Security Options Module can only be changed by using ION Setup or
ION Enterprise and the customer must know the proper Advanced Security
username and password. Time syncs can be sent to the meter in this mode without
having to enter in a username and password.
Chapter 5 - Security Page 67
Scenarios for Advanced Security - Front Panel Security Enabled ION 8000 Series User Guide
5. Access through a standard browser on an Ethernet port via
http protocol
If Advanced Security is enabled and the Web Access Read Security setup register
in the Security Options Module is set to YES, you must enter in the proper
Advanced Security username and password before gaining read access to the
device through a standard browser. If you have the proper username and
password, the next level of security is the Webserver Configuration Access setting.
If the Webserver Configuration Access disabled, you can only read metering data.
If the Web Access Read Security setup register is set to NO, then you will be able
to read web pages on the device without having to provide an Advanced Security
username and password. However, if you attempt to make configuration changes,
you will be prompted for the Advanced Security username and password.
6. Access Through FACTORY protocol on a Telnet connection via
Ethernet or HyperTerminal on a serial, modem, or optical
port
Advanced Security does not affect the Factory protocol. Therefore, if Front Panel
Security is enabled, you will have to enter the password to log into the Factory
protocol. If the Front Panel Security is disabled you can log into the Factory
protocol without supplying a password.
Once logged in, you can change the following:
1.IP Boot Option - BOOTP or Manual
2.IP Address
3.Subnet Mask
4.Gateway
5.Reset Battery Counters
6.Enable/Disable Front Panel Security
If you wish to change additional configuration settings beyond the items listed
above, you must contact Power Measurement.
Page 68Chapter 5 - Security
ION 8000 Series User GuideAdditional Revenue Metering Security
Additional Revenue Metering Security
To meet government regulations and utility security requirements, the revenue
meter incorporates additional security systems:
a hardware-locked security system that prevents modification of revenue
quantities after the meter is sealed.
a traditional anti-tamper mechanical seal on the meter base unit.
Hardware Lock Security Option
The hardware-locked security feature is an ordering option for some ION 8000
series meters. This hardware lock is factory set; to make configuration changes to
billing parameters on a hardware-locked meter, you must first place the meter in
TEST mode. The TEST mode button is located under the anti-tamper sealed outer
cover. This button cannot be activated remotely with a Hardware Lock meter.
Press this button to
enter TEST Mode
4WY
W
TEST
MODE
SHIFT
UP
SHIFT
DOWN
ALT /
ENTER
DEMAND
RESET
The Hardware Lock Option can be combined with Advanced Security and the
Front Panel Security to offer the highest level of security. Once the TEST button is
activated, all rules above for Advanced and Standard Security still apply. When
the TEST Button is not activated, no changes to the locked parameters can be made.
Those parameters that are not locked are outside the revenue metering space.
However if Advanced Security and Front Panel Security are enabled, the unlocked
portion of the meter is secured by the rules for Advanced and Standard Security.
In certain countries the meter is no longer revenue certified if the hardware lock is
broken.
kW, kVAR, kVA Thermal and Sliding Window demand min and max values.
Digital Outputs controlling the energy pulsing applications.
All Power system settings, including PT and CT ratios.
Chapter 5 - Security Page 69
Anti-Tamper Sealing Methods ION 8000 Series User Guide
Locked Module Listings
For a complete list of locked modules specific to your meter and its firmware,
please download the ION Device Templates help file from the Power Measurement
website.
Anti-Tamper Sealing Methods
The ION 8000 series meter uses the following anti-tamper sealing methods.
Demand Reset Switch Seal
The Demand Reset switch located on the front panel may be sealed by a wire seal
or lock inserted through the side of the switch. This seal does not have to be broken
to remove the meter's cover.
Socket Seals
A standard ANSI C12.7 type socket-sealing ring may be in place to hold the meter
to the socket. When removing the outer cover, the sealing ring must first be
removed. Some socket sealing rings facilitate wire seals.
Outer Cover Seals
The outer cover of the meter is factory sealed to its backplate with a T-type seal.
Depending on the installation, this seal may be inaccessible after the meter is
installed until you remove the device from the socket.
Socket.
Outer cover.
Demand Reset
Switch seal.
Outer cover
T-t y pe s e a l .
Socket sealing
ring.
Page 70Chapter 5 - Security
6Communications
This chapter includes general instructions for connecting and configuring all the
communication ports on your meter.
For specific installation steps and meter specifications, consult your ION 8000 Installation Guide.
The ModemGate Protocol .................................................................................... 91
Page 71
Communications Overview ION 8000 Series User Guide
Communications Overview
The following illustration shows all the possible connections to the
communications card.
Socket or switchboard meter connections
Optional Ethernet:
FL Fiberconnectors.
Optional Ethernet: RJ45
connector. See
“Configuring Ethernet
Connections” on page 83.
ANSI C12.13 Type II
Magnetic Optical
Communications
Coupler. The optical
communications
port is located on
the front panel. See
“Configuring the
Optical Port” on
page 81.
Optional Modem:
RJ11 or RJ31 male
connector. See
“Internal Modem
Connections” on
page 88.
Optional communications
break-out cable for serial
communications. Ordered
separately.
COM1: RS-232 or RS-485.
COM2 or COM4: RS-485,
depending on the order
option. See
“Communications Break-out
Cable” on page 80.
Serial COMs and
Expanded I/O: Molex
Micro-Fit 24 pin male
connector. See
“Communications
Options” on page 73.
Optional IRIG-B
GPS Time Synch.
Optional I/O Expander for serial
communications (and expanded I/O).
Ordered and shipped separately. For
more information, see the ION 8000
I/O Expander
Series
Serial COMs
COM1: RS-232
or RS-485.
COM2 or
COM4: RS-485,
depending on
the ordering
option.
documentation.
Expanded I/O
Eight Form A digital
inputs.
Four Form C digital
outputs (mechanical
relays).
Four Form A digital
outputs or four analog
outputs.
Page 72Chapter 6 - Communications
ION 8000 Series User GuideCommunications Options
Communications Options
ION 8000 Series meters have numerous communication possibilities depending on
your ordering preferences. Not all models can have exactly the same
communications options. Refer to the Power Measurement website for the latest
ordering options and documentation. All communications ports can be used
simultaneously.
COM PortAvailable ConnectionsStandard/Option
1Selectable RS-232/RS-485 portStandard
RS-232
RS-485
Optical Port
Ethernet
1
Fibre
EtherGate
Internal Modem
Modem-Gate
2
3ANSI 12.13 Type II optical portStandard
4
1
Optional on ION 8400/ION 8500 meters only. ION 8300 meters do not have a COM4 port.
2
Optional on ION 8000 series socket meters only.
High-speed RS-485 port - OR - 33.6 kbps
internal modem
Ethernet 10Base-T
Fiber 10Base-FL
1
2
Standard
Option
NOTE
Socket meters are available with either Fiber or Ethernet, not both.
In addition to standard communications, these ordering options are available:
ION 8500/ION 8400
COM1COM2COM3COM4NetworkIRIG-B
Not available if the
internal modem option
is present on this port.
Not available if the
internal modem option
is present on this port.
– Only available if the
internal modem is ordered
for COM2.
– Not available with
Ethernet.
available on all
ION 8000
series meters.
Not available if the RS485 option is present
on COM4.
Available with Onboard
I/O provided no
Outage Dialback is
present.
1
Socket only.
Chapter 6 - Communications Page 73
Communications Options ION 8000 Series User Guide
Optional Switchboard Breakout Panel
Connector TypeAvailableComments
RS-485YesCaptured wire
RS-232YesDB9
RJ31 Modem (option)No
ModemYes
EthernetYes
FiberNoSocket option only
Onboard I/O expansionYesIf meter has optional onboard expansion I/O card
IRIG-BYesIf meter has optional IRIG-B feature
Auxiliary PowerYesIf meter includes one of the Auxiliary Power Options
NOTE
COMs on the I/O box are not connected. Use the RS-485 and RS-232 provided on the breakout panel.
RS-232
RS-485
Optical Port
Ethernet
1
Fibre
EtherGate
Internal
Modem
ModemGate
ION 8300
COM1COM2COM3NetworkIRIG-B
Not available if Ethernet
ordered with internal modem
option on COM2
(Ethernet uses COM1)
Not available if Ethernet
ordered with internal modem
option on COM2
(Ethernet uses COM1)
– Not available if internal
modem option on this port
– Not available if Ethernet option
ordered with selectable RS-232
and RS-485 on COM1 (Ethernet
available on all
ION 8000 series
meters.
uses COM2)
– Uses COM1 when internal
modem option on COM2
– Uses COM2 when
selectable RS-232 and RS485 on COM1
Available with Onboard I/O
provided no Outage
Not available if internal modem
Dialback is present.
option on this port
1
Socket only
Page 74Chapter 6 - Communications
ION 8000 Series User GuideCommunications Options
NOTE
The ION 8300 meter Ethernet option can share a communications channel with COM1 or COM2,
depending on the ordering options. There is no COM4 port.
IRIG-B GPS Time Synchronization
IRIG-B cannot be configured via the meter’s front panel. See the IRIG-B Product
Option document for configuration procedures.
Communications Accessories
The following accessories are currently available as separate products:
I/O Expander
The I/O Expander connects with the male Molex connector on the meter to provide
I/O capabilities as well as access to standard serial communications ports. Refer to
the I/O Expander Installation Guide for complete details about this device.
Communications break-out cable
The communications break-out cable connects with the male Molex connector on
the meter. This is a pre-made cable that provides access to the standard serial
communications ports on the meter.
Molex extension cables
Depending on your ordering preference, the molex extension cables add either 5
or 15 feet (1.5 or 4.5 meters) to the molex cable on the meter.
Optical probe
The optical probe attaches to the optical port on the front of the meter and allows
on-site communications (e.g. with a laptop computer).
Chapter 6 - Communications Page 75
Serial Connections ION 8000 Series User Guide
Serial Connections
If the meter’s COM1 port is selected as RS-232, you can connect this port to a
remote modem, which in turn is connected to a PC. You must use a null-modem
RS-232 cable to connect the meter to an external modem. One end of the cable must
be equipped with a Micro-Fit 3.0 Molex female connector for mating with the
Molex male connector on the meter.
You can connect many meters’ COM1 ports; they are selected as RS-485 using an
RS-232 to RS-485 converter (such as COM 32 or COM128).
NOTE
You cannot use both RS-232 and RS-485 ports on the meter’s COM1 simultaneously.
Attach the Molex connector
from the meter to a break-out
cable or the I/O Expander.
PC workstation
local
modem
Telephone
Network
Telephone
Network
remote
modem
remote
modem
null–modem
RS-232/RS-485
converter
RS-232
meter with
external modem
RS-485 chain of
meters and external
modem
If your meter is part of an ION Enterprise power-monitoring network, you can
configure your local and remote modems with ION software. You can also use
ION software to schedule regular connection times to collect meter data.
Extension Molex cables with a female Molex connectors are available from your
supplier. Maximum overall cable length is 50 feet (15.2 m). Pin assignments for the
Molex connector are provided in the ION 8000 Installation Guide that ship with the
meter (also available at www.pwrm.com).
Page 76Chapter 6 - Communications
ION 8000 Series User GuideRS-232 Connections
RS-232 Connections
Refer to ION 8000 Installation Guide for the meters’ RS-232 specifications.
Because of the wiring configuration between pins 2 and 3, the meter is considered
a DTE (Data Terminal Equipment) device in all RS-232 connections. In order to
communicate directly to a PC you must use a null modem cable or the optional
break-out cable to mate the pinouts on the PC with the meter. The maximum cable
length is 50 feet (15.2 m).
DB9 Null Modem
Wiring Diagram:
DCE
(computer)
2
3
4
5
6
7
8
2
3
4
5
6
7
8
DTE
(meter)
Communications settings for the RS-232 port are accessible through the front panel
Setup menu (see Chapter 2 - “Using the Front Panel”) and with Designer software.
Computer Connections
5
0
fe
e
t
(1
5
.
2
m
)
m
a
x
R
S
-
2
3
2
Meter Connections
Chapter 6 - Communications Page 77
50 feet (15.2 m) max
RS-232
RS-485 loop
RS-485 Connections ION 8000 Series User Guide
External Modem Connections
R
S
-2
3
2
5
0
fe
e
t
(
1
5
.
2
m
)
m
a
x
NOTE
Optical isolation voltage is 750 V peak for 10 seconds at 62 Hz. There is optical isolation from all other
inputs and outputs except COM1 (RS-485 port).
RS-485 Connections
Refer to the ION 8000 Series Installation Guide for the RS-485 specifications.
If you have not installed the I/O Expander or the communications break-out cable,
a custom cable is required to connect the D+ and D- pins from the male Molex
connector to the RS-485 data bus. The I/O Expander box is wired as a DTE device
and does require a NULL modem cable/adapter to connect to the serial port.
Optical isolation is from all other inputs and outputs (the COM1, RS-485 port is not isolated from the
COM1, RS-232 port). Isolation voltage is 750 V peak for 10 seconds at 60 Hz.
The break-out cable’s twisted pair provide connections for both of the meter’s RS485 serial communications ports. The first set is for COM1 RS-485 connections. The
second set is for either COM2 or COM4 RS-485 communications, depending on the
options ordered for your meter.
The second RS-485 twisted pair connection is either COM2 or COM4 or inactive. The following points
determine their status, however check the communications LEDs on the side of your meter to see which
options are on the meter: If the meter has an optional COM4 port on the meter, then the RS-485 twisted
pair is COM4. If the meter has an internal modem (and no COM4), the pair is inactive. Otherwise, the
pair is COM2.
NOTE
NOTE
Up to 32 devices can be connected on a single RS-485 bus. Use a good quality
shielded twisted pair cable for each RS-485 bus, AWG 22 (0.33 mm
2
) or larger. The
overall length of the RS-485 cable connecting all devices cannot exceed 4000 feet
(1219 m). The RS-485 bus may be configured in straight-line or loop topologies.
Page 78Chapter 6 - Communications
ION 8000 Series User GuideRS-485 Connections
Straight-Line Topology
Wiring color codes for the Molex
cable are provided in the
8000 Installation Guide
ships with the meter and are
available at www.pwrm.com.
ION
that
SHLD
+
SHLD
+
SHLD
+
+
SHLD
+
+
R
T
R
T
Termination
Resistor
RS-232 to
RS-485
Converter
SHLD
SHLD
SHLD
+
+
+
+
SHLD
shield
Loop Topology
SHLD
Termination
Block
RS-232 to
RS-485
Converter
SHLD
SHLD
+
+
SHLD
SHLD
+
SHLD
+
SHLD
+
+
SHLD
+
+
General Bus Wiring Considerations
Devices connected on the bus, including the meter, converter(s) and other
instrumentation, must be wired as follows:
Connect the shield of each segment of the cable to ground at one end only.
Isolate cables as much as possible from sources of electrical noise.
Use an intermediate terminal strip to connect each device to the bus. This allows
for easy removal of a device for servicing if necessary.
Install a ¼ Watt termination resistor (RT) between the (+) and (-) terminals of the
device at each end point of a straight-line bus. The resistor should match the
nominal impedance of the RS-485 cable (typically 120 ohms – consult the
manufacturer’s documentation for the cable’s impedance value).
RS-485 Connection Methods to Avoid
Any device connection that causes a branch in the main RS-485 bus should be
avoided. This includes star and tee (T) methods. These wiring methods cause signal
reflections that may cause interference. At any connection point on the RS-485 bus,
no more than two cables should be connected. This includes connection points on
instruments, converters, and terminal strips. Following this guideline ensures that
both star and tee connections are avoided.
Chapter 6 - Communications Page 79
RS-485 Connections ION 8000 Series User Guide
Avoid 3-way “Star”
connection point
Avoid 3-way “T”
connection point
Communications Break-out Cable
Refer to the ION 8000 Installation Guide for the DB9 serial pin assignments for the
optional break-out cable female DB9 connector. A communications break-out
cable facilitates communications connections by connecting to the Molex male
connector on your meter. The cable splits to a standard DB9 female connector and
two RS-485 shielded, twisted pairs. Cable length is 152 cm (5 feet).
Molex male
from the meter
RS-485
twisted pairs
RS-485 shield
DB9 female
connector
Page 80Chapter 6 - Communications
ION 8000 Series User GuideConfiguring the Optical Port
Configuring the Optical Port
Refer to the ION 8000 Installation Guide for infrared port specifications.
The infrared port available on the ION 8000 Series meters is compatible with
standard magnetic optical communications couplers, or optical probes (ANSI
C12.13 Type II). Optical probes are available from suppliers as a separate product;
contact Power Measurement for a list of suppliers. The original equipment
manufacturer’s warranty will apply (see the technical note Optical Probes for more
detailed information).
Optical probes can communicate real-time measurements via the ION, Modbus
RTU, or DNP 3.0, Factory, or GPS protocols. You can configure the optical port
communications settings with the front panel, with ION Setup, or with the
Designer component of ION Enterprise.
Using the front panel
1.Press and hold the Alt/Enter button for a few seconds. The SETUP MENU will
appear.
2.Use the Up or Down arrow buttons to choose COM3 S
3.Press the Alt/Enter button to access COM3 S
ETUP parameters.
ETUP.
4.Configure the COM3 Baud Rate, Unit ID, and Protocol parameters to match your
communications system.
Ia
Ib
Ic
In
18:30:00 1999.06.01 ABC Q1 NORM5:00mEOI
2401.1
2951.3
2291.7
102.1
kA
kA
kA
kA
Press and Hold
Press
Press
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
Press
COM3 SETUP
RETURN
PROTOCOL
BAUD RATE
Using ION Setup
1.Run ION Setup and connect to the appropriate meter.
2.Select View > Setup Screens. The Setup Assistant appears in the right-hand side
of the Network Viewer. Double-click the Setup Assistant to open.
3.In the Setup screens, select the communications screen. Click the COM3 tab and
configure the Baud Rate, Unit ID, and Protocol parameters to match your
communications system.
Chapter 6 - Communications Page 81
Configuring the Optical Port ION 8000 Series User Guide
To enable communications from the infrared port, you must configure the COM3
Communications module. The Protocol, the Baud Rate and Unit ID setup registers
must properly match your system. If you have the internal modem option, you
must ensure that the Comm Mode setup register is set to select the IrDA port. When
creating an ION site, ensure the RtsCts is disabled (set to No) in the COM3 serial
site.
Refer to the Management Console section of the online ION Enterprise Help for
more details about adding serial sites.
Using ION Enterprise
1.From the Management Console, select (or create) a “direct site” from the
management console.
2.Configure the COM3 communications module (refer to the online ION
Enterprise help for details). Ensure the Protocol, the baud rate, and Unit ID setup
registers must properly match your system.
This is your PC’s
(workstation’s) COM port.
If you are using ION
software, ensure that
RtsCts is disabled for the
infrared port's site in
Management Console.
Page 82Chapter 6 - Communications
ION 8000 Series User GuideConfiguring Ethernet Connections
Configuring Ethernet Connections
This section only applies if your ION 8000 Series meter has the Ethernet option.
Refer to the ION 8000 Series Installation Guide for Ethernet port specifications of the
ION 8000 Series meters.
Ethernet
Connections are made via the RJ45 modular jack on the rear of the unit. Use high
quality Category 3, 4 or 5 UTP cable (RJ-45 female to RJ-45 male) if you require an
extension. This optional Ethernet port is capable of data rates up to 10Mbps, and
supports TCP/IP, ION, Telnet, and Modbus/TCP protocols. The Ethernet port is
controlled by the ETH1 Communications module.
The EtherGate feature provides communications both to an Ethernet connected
device and through that device to a connected serial network (See “Configuring
EtherGate Connections” on page 85).
You can configure the Ethernet Communications module to enable Ethernet
communications using the front panel, ION Setup or ION Designer software. In
each case, you must configure the IP Address, Subnet Mask,Gateway, SMTP Server
and SMTP Connection Timeout to properly match your system.
Using the front panel
1.Select NETWORK SETUP from the ION 8000 Setup menu (hold down the
Alt/Enter key for about 3 seconds and scroll down using the softkeys).
Ia
Ib
Ic
In
18:30:00 1999.06.01 ABC Q1 NORM EOI
2401.1
2951.3
2291.7
102.1
2.Configure the Ethernet Communications module IP Address, Subnet Mask, Gateway,
SMTP Server and SMTP Connection Timeout setup registers to match your
communications system.
kA
kA
kA
Press and Hold
Press
Press
8500 SETUP
COM3 SETUP
NETWORK SETUP
FORMAT SETUP
NETWORK SETUP
RETURN
IP ADDRESS
MASK
Chapter 6 - Communications Page 83
Configuring Ethernet Connections ION 8000 Series User Guide
Using ION Setup
Once you have wired your meter to the Ethernet network and performed basic
setup, add the meter to your ION Setup networking using the Setup Assistant.
1.Run ION Setup.
2.In the Setup Assistant, select the “Communications” screen and click the
“Ethernet” tab.
3.Configure the IP Address, Subnet Mask,Gateway, SMTP Server and SMTP Connection Timeout setup registers to match your communications system.
Using ION Enterprise
After you have wired your meter to the Ethernet network and performed basic
setup, add the meter to your ION Enterprise network using the Management
Console. It is not necessary to add an Ethernet site.
To enable communications through the Ethernet port, you must configure the
Ethernet (Communications) module. Launch Designer and configure the IP Address, Subnet Mask,Gateway, SMTP Server and SMTP Connection Timeout
registers to match your system.
Adding an Ethernet device to your ION Enterprise Network
In the Management Console, the Ethernet Device Options screen appears when
you add an Ethernet device (meter). Use this screen to describe your meter
Ethernet address and other communications information. Be sure to include:
the server computer that communicates with the Ethernet device
Page 84Chapter 6 - Communications
ION 8000 Series User GuideConfiguring EtherGate Connections
the Ethernet device TCP/IP address
Configuring EtherGate Connections
The EtherGate protocol is a powerful communications tool that lets you
communicate to a meter and through a meter simultaneously. When a meter
installed on the Ethernet network has EtherGate enabled, a master device (such as
a workstation running ION Enterprise software) can communicate to the meter,
and through the meter to a serial network of devices wired to the meter’s COM port.
EtherGate is available on serial ports COM1 and COM2 in place of the ION,
Modbus Master, Modbus RTU, or DNP 3.00 protocols. The protocol permits the
direct transfer of data from up to 62 devices (31 devices per COM port).
Each device in the
serial network must
have a unique Unit
ID and operate at
the same baud rate.
Specifying the TCP/IP Port
Ethernet
instructs the ION gateway
meter to:
7801—talk through COM1
7802—talk through COM2
Once you have the chain of serial devices installed, use Designer or the meter’s
front panel to change the COM1 or COM2 Protocol setting to EtherGate. The
transfer of data between protocols is then handled automatically.
Using the front panel
1.Press and hold the Alt/Enter button for a few seconds to reach the Setup
screens.
2.Press the Up or Down arrow buttons to scroll to COM1 Setup (or COM2,
depending on your meter’s options). Press Alt/Enter to go to the COM1 Setup
parameters.
Chapter 6 - Communications Page 85
Configuring EtherGate Connections ION 8000 Series User Guide
3.Scroll to Protocol and press Alt/Enter. Change the port’s Protocol setting to
EtherGate using the Up or Down arrow buttons.
Ia
2401.1
kA
Press and Hold
2951.3
2291.7
102.1
kA
kA
kA
Press
Press
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
Press
COM1 SETUP
RETURN
PROTOCOL
BAUD RATE
Press
PROTOCOL
FACTORY
ETHERGATE
MODEMGATE
Ib
Ic
In
1999.06.01 ABC Q1 NORM5:00mEOI
18:30:00
NOTE
If you have the optional internal modem then COM2 is not available for EtherGate applications.
Using ION Setup
1.Run ION Setup and connect to the appropriate meter.
2.Select View > Setup Screens and double-click on “Setup Assistant” in the right
side of the Network Viewer.
3.In the Setup screens, select the Communications tab and then select Com1(or
COM2, depending on your meter’s options). Click edit and scroll to EtherGate.
Refer to the EtherGate technical note for complete details on configuring your
meter for EtherGate.
Page 86Chapter 6 - Communications
ION 8000 Series User GuideConfiguring EtherGate Connections
Using ION Enterprise
1.To communicate to the devices on the RS-485 loop, you must use ION
Enterprise software. Use the Management Console to create a Gateway Site.
2.Once you have created a Gateway Site add each of the devices on the RS-485
loop to it (but not the gateway meter itself).
3.When configuring the Gateway Site, enter the IP address of the meter and the IP Service Port to match the COM port you are using:
7801 = EtherGate IP service port on COM1
7802 = EtherGate IP service port on COM2
The Devices list in the Management Console appears as follows:
The devices that reside on the RS-485
loop connected to the ION 8500.
The ION 8500 appears in
the Devices list, because it
must be configured as an
Ethernet device before you
can configure it as an
Ethernet Gateway Site.
From the Type heading in
the Sites window, you can
see the ION 8500 has
been configured as an
Ethernet Gateway Site.
The Gateway Site - set the IP Service Port
7801 for COM1 or 7802 for COM2.
The number following the IP Service Port
number is the device’s unique Unit ID.
NOTE
In the above configuration you communicate with the devices in the RS-485 loop
must add the meter to an additional Ethernet Site to communicate directly to the meter.
Communicating directly TO the meter:
In order to connect directly over Ethernet, you need only provide the meter’s IP
address when prompted by the software.
through
the meter. You
Chapter 6 - Communications Page 87
Internal Modem Connections ION 8000 Series User Guide
Internal Modem Connections
This section only applies if your meter has the 33.6 kbps internal modem option.
Refer to the ION 8000 Series Installation Guide for internal modem specifications.
Telephone Network
The internal modem is accessed through COM2 and supports all standard modem
protocols at transmission rates from 300 bps to 33600 bps (though 300 bps is not
recommended) and can be shared by up to 31 devices on an RS-485 chain. It is
available with a standard six-pin RJ-11 phone plug, or an eight-pin RJ-31. If you
have multiple meters linked on an RS-485 loop, only the first meter requires an
internal modem. This setup is referred to as a ModemGate (see “The ModemGate
Protocol” on page 91).You can configure the settings of the internal modem with
the front panel or with ION software.
To enable communications through the meter’s internal modem, configure the
COM2 communications module Baud Rate, Unit ID, and Protocol setup registers to
properly match your system, and setup the initialization string for the internal
modem must be using the ModemInit register.
NOTE
When the meter is equipped with the ION Alert module, the modem can initiate calls. Paging is supported
through numeric paging and the TAP1 protocol. See the ION Administrator’s Guide for details on
managing modem connections, setting up periodic dial-out and configuring remote site event
notification.
ModemInit Setup Register
The ModemInit string register defines the initialization string for the internal
modem with a maximum of 47 characters. Edit the ModemInit register and enter the
desired initialization string. The string is sent to the modem as soon as you
download the COM1 module. Note that the string is also sent to the modem
whenever the meter is powered up or the baud rate in the COM1 Communications
module is changed. Any changes to the Modem Init or Baud Rate setup registers
while the modem is online causes the modem to disconnect from the phone line.
CAUTION
Changing the
disconnect from the phone line.
Page 88Chapter 6 - Communications
ModemInit
setup register while the internal modem is online causes the modem to
ION 8000 Series User GuideInternal Modem Connections
Modem Initialization Strings
Refer to the Modem AT Commands technical note for a complete list of AT
commands for both Conexant and Multi-Tech modems.
NOTE
The technical note also contains instructions on how you can determine your meter’s modem type based
on the meter’s serial number.
Adjusting the Modem Initialization String for CTR-21 Compliant modems
The table below shows the strings to add to the end of your modem configuration
string setup register for each of three possible problems.
ProblemAdd to Modem Initialization String
Does not answer
(modem does not detect ring tone)
Does not dial
(modem does not detect dial tone)
Does not detect busy signal*NC70
*NC70
In order of preference:
*NC70, *NC70X0, *NC8 (Italy only)
CAUTION
A Conexant Modem does not support Pulse dialing. The Conexant Modem should be the only device on
the telephone line. Attaching devices on the same line may cause one or more of these devices to operate
incorrectly.
If your local modem (not the internal modem) is not already set up, configure it
with the Remote Modem Configuration Utility according to the instructions in the
online help. After the meter is installed and the internal modem is connected to the
telephone network, the COM2 module can be configured using the meter’s front
panel or ION software. To learn how to connect the internal modem to the
telephone network, consult your ION 8000 Installation Guide.
NOTE
The
ION Enterprise Getting Started
managing modem connections, setting up periodic dial-out, and configuring remote site event
notification.
Configuring the COM2 module through the front panel
1.Press and hold the Alt/Enter button and scroll to COM2 Setup.
booklet contains details on: commissioning an ION network,
Chapter 6 - Communications Page 89
Internal Modem Connections ION 8000 Series User Guide
2.Select COM2 Setup to configure the COM2 communications module
Baud Rate,Unit ID, and Protocol setup registers to your communications system.
Ia
Ib
Ic
In
18:30:00 1999.06.01 ABC Q1 NORM5:00mEOI
2401.1
2951.3
2291.7
102.1
kA
kA
kA
kA
Press and Hold
Press
Press
8500 SETUP
RETURN
BASIC SETUP
DEMAND SETUP
COM1 SETUP
COM2 SETUP
COM3 SETUP
FORMAT SETUP
DISPLAY SETUP
SECURITY
Press
COM2 SETUP
RETURN
PROTOCOL
BAUD RATE
Configuring the COM2 module via Designer
Before you can configure the COM2 module in Designer you must add the meter
(with the internal modem) and a modem site to your ION Enterprise network.
Adding a meter and a modem site to your ION Enterprise network
In the Management Console, add the meter with the internal modem, and a
modem site to your ION Enterprise network. Describe how your remote modem
is wired and other communications information on the options screens.
Either before or after adding the Modem Site, you must add a dialout modem to
the server computer. The server computer dialout modem communicates to the
modem at the modem site. See the ION Enterprise Getting Started guide for more
information.
Remote modem telephone
number.
To avoid excessive communication
errors, the baud rate of the modem
site should match the baud rate of
the COM2 port of the meter.
On the Modem Site Options screen, be sure to include:
the server computer that will communicate with the remote modem
the remote modem telephone number
Server computer that
communicates with the
remote modem. Ensure that
the server computer dialout
modem is configured.
Pick a
local
from the drop-down box.
modem type
Page 90Chapter 6 - Communications
ION 8000 Series User GuideInternal Modem Connections
Configuring the COM2 Communications module in Designer
Launch Designer, and configure the COM2 Communications module Baud Rate,
Unit ID, and Protocol setup registers to match your communications system.
Configure the initialization string for the internal modem using the ModemInit
register. Refer to “ModemInit Setup Register” on page 88.
The ModemGate Protocol
ModemGate is a powerful feature that creates a communications connection
between the telephone network and an RS-485 serial network of devices. When
Works tat ion wit h
ION Enterprise
and modem.
you specify the protocol for a meter’s COM port as M
by the meter’s internal modem is automatically transferred to the serial network.
ModemGate is available on either the COM1 or COM4 port (optional on some
meters); you cannot use the protocol on both ports simultaneously.
Telephone Network
ODEMGATE, all data received
Meter with internal
modem on COM2.
The serial network is
connected to COM1.
Each device on the RS-485 loop,
including the gateway meter’s internal
modem, must have a unique Unit ID.
All serial devices must operate at the
same baud rate as the gateway meter.
The baud rate used between connected modems is independent of the internal
baud rate used for communication between the meter and its modem.
Wire a serial connection between one or more meters and the meter COM port
hosting the ModemGate (COM1 or COM4). You can make ModemGate
connections through an RS-232 cable to a single device, or through an RS-485
shielded twisted pair cable to multiple devices. ModemGate connections do not
connect a workstation running ION Enterprise (or other master device) to the
gateway meter’s COM1 or COM4 port, but rather to the gateway meter’s internal
modem port (COM2).
Configuring the meter for ModemGate
1.Install the meter and connect the internal modem.
Chapter 6 - Communications Page 91
Internal Modem Connections ION 8000 Series User Guide
2.Use the front panel or ION software to set up the internal modem and the serial
communications port (COM1 or COM4) that is the ModemGate. The default for
these ports is:
Communications modulesSettingDefault
Comm ModeRS-485
COM1
(Standard RS-232/485 port)
COM2 (Modem Port)
COM4
(Optional dedicated RS-485 port)
Baud Rate 9600
Unit ID100
ProtocolION
Baud Rate9600
Unit ID101
ProtocolION
Modem Init StringsAT&F
Baud Rate9600
Unit ID103
ProtocolION
NOTE
You can enable ModemGate on either COM1 or COM4, not both simultaneously.
3.Set the internal modem COM2 baud rate, Unit ID and protocol. The baud rate
must be the same as the port hosting the gateway and all the devices connected
to the gateway.
4.Set the protocol of the port hosting the gateway to MODEMGATE (either COM1
or COM4). You must also set the baud rate to the same as the modem baud rate
(COM2).
Configuring devices connected to the ModemGate meter
1.Use ION software or the front panel to change and configure settings. Ensure
each device connected to the meter has the same baud rate as the meter
ModemGate port (either COM1 or COM4).
2.Ensure each device connected on the RS-485 network (including the meter
modem) has a unique Unit ID number. Make a record of your changes.
NOTE
In order to configure the dial-in connection the system administrator requires the serial baud rate of the
modem site and a record of the Unit ID numbers for every device.
3.Ensure ‘RS-485’ is selected for connections to multiple devices along the same
bus.
Adding ModemGate meters to the network
1.Once you have created a Modem Site using the Management Console, add the
meter and all devices connected to the ModemGate port.
2.Ensure each meter on the modem Site has a unique Unit ID number (the
technician who installed the meter at the remote site should provide you with
this information).
Page 92Chapter 6 - Communications
ION 8000 Series User GuideInternal Modem Connections
Refer to the ModemGate technical note for complete details on configuring your
meter for ModemGate.
Chapter 6 - Communications Page 93
7Third Party Protocols
This chapter explains how Modbus and DNP 3.0 protocols are implemented on the
ION 8000 series meter.
Using the Front Panel ......................................................................................... 109
Using ION Setup ................................................................................................. 109
Page 95
Overview ION 8000 Series User Guide
Overview
ION 8000 series meters support DNP 3.0, Modbus RTU and Modbus/TCP
protocols.
While your meter is factory configured to send data (acting as Modbus Slave), it is
not ready to receive data as a Modbus Master until you set up the necessary
framework. The meter is also pre-configured to send DNP 3.0 data to a DNP
Master.
NOTE
Changing the default factory third-party protocol frameworks (or creating new frameworks to enable
receive functionality) is an advanced procedure. Refer to the DNP modules and Modbus modules
descriptions in the
and
Modbus and ION Technology
ION Reference
Most Modbus and DNP modules on the meter are factory pre-set and only require
basic configuration, such as communications setup.
, as well as the technical notes
before proceeding.
Multiport DNP 3.0 and ION Technology,
NOTE
Changing these modules from their factory configuration is an advanced setup procedure that requires
an understanding of the protocol, as well as an understanding of the meter’s internal operation. For more
information on your meter and these protocols see the
ION 8000 Series DNP 3.0 Device Profile
.
Communications Protocol Configuration
In order to use the factory Modbus or DNP configuration, you must first assign the
communications channel you want to use. By default, all communications ports
are configured to use the ION protocol. Choose the 3rd-party protocol you want
from the list of available protocols in the Communications module’s Protocol
setup register. See the Communications chapter for instructions.
NOTE
Modbus RTU is available on each of the meter’s communications ports, and multiple ports can
communicate using Modbus simultaneously. Up to three ports can use the DNP 3.00 protocol at any one
time.
Common Modbus Registers
document and the
Page 96Chapter 7 - Third Party Protocols
ION 8000 Series User GuideThe Meter as Modbus Slave
The Meter as Modbus Slave
Your meter can act as a Modbus Slave, using both the Modbus RTU and Modbus/
TCP protocols.
Using the Modbus RTU Protocol
The ION 8000 series meter can act as a Modbus Slave device, making any real-time
data available through the Modicon Modbus RTU protocol. Modbus Master
devices connected to the meter can access (read) this data or write data to your
meter’s ION registers, making device configuration changes and initiating control
actions.
The Factory Modbus Slave Configuration
The meter makes data available to Modbus Master devices using pre-configured
Modbus Slave modules. These modules are linked to other modules in the meter
that provide the energy, power and demand data. Once a communications channel
is configured to use Modbus RTU protocol, the data is available to Modbus Master
devices.
NOTE
Connect to IP Service Port 7701 for Modbus RTU communications over Ethernet. The Modbus Unit ID of
the meter over Ethernet is 100.
Set the COM port
to the Modbus
RTU protocol
Communications Port
Power Meter
ION meter
Vln a
Module
Measured data is
linked to the Modbus
module’s input.
Modbus Slave
Module
Modbus Slave module
outputs data in Modbus
format
As the data available through the Modbus Slave modules is in a specific format,
knowledge of the Modbus protocol and an understanding of the settings used in
the meter are required to interpret the data provided.
40011
Data is available
to Modbus master
devices
Chapter 7 - Third Party Protocols Page 97
Modbus Slave Modules ION 8000 Series User Guide
Changing the Modbus Configuration
If the factory Modbus configuration does not suit your needs, the existing Modbus
Slave modules can be relinked to other parameters that you want to access through
Modbus.
If your Modbus Master device requires data in a format different than that
provided by the factory Modbus configuration, you can edit the setup registers in
the Modbus Slave modules. These setup registers specify the Modbus format,
scaling and base address settings. Refer to the ION Reference for complete details
on the Modbus Slave module.
Modbus Slave Modules
The ION 8000 Series meter has ten Modbus slave modules. Modules 1 - 5 are part
of the original modbus mapping and are preserved for backward compatibility. If
you are using the new Modbus mapping (modules 6 - 10), you can delete modules
1 - 5.
Modbus Slave Module
#
(original mapping)
1Volts/Amps/Freq6Amp/freq/unbal
2Power/PF7Volts
3Min/Max/Demand8kW/kVAr/kVA
4Energy/THD9kWh/kVArh
5Flicker Count10PF/THD/Kfactor
Modbus Slave Module
#
(new mapping)
The settings for your Modbus Slave modules follow.
Page 98Chapter 7 - Third Party Protocols
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.