PowerMax OV 140 P Series, 140 Series, 155x Series, OV 140 CP, SS 140 P Installation And Servicing Instructions

...
Publication No. P443 - 12/05
BAXI POTTERTON BROWNEDGE ROAD BAMBER BRIDGE PRESTON PR5 6SN (Technical Helpline) TEL 0870 606 0955 (Service) TEL 0870 606 0933 FAX 0870 606 0966 (Spares) TEL 0870 6060454
“Powermax” is a trademark of Baxi Group Ltd
The code of practice for the installation, commissioning
& servicing of central heating systems
Guide to Panel Removal
Auto vent access
Main power supply
cable entry
Upper front panel and
retaining screw
Lower front panel
(2 screws)
Lifting and plumbing
access each side
External controls
cable entry
Top panel
Plinth (4 screws)
MAIN POWER SUPPLY
CABLE ENTRY
TRANSIT SCREW
EXTERNAL CONTROLS
(AND IMMERSION
HEATER CABLE ENTRY)
PLUMBING ACCESS
EACH SIDE
LIFTING AND PLUMBING
ACCESS EACH SIDE
AUTO VENT ACCESS
TOP PANEL
(2 SCREWS)
FRONT PANEL (2 SCREWS)
PLINTH (4 SCREWS)
Guide to panel removal
140
155
xx
SAFETY NOTICE
In your own interest and that of safety, it is the law that all gas appliances are installed and serviced by competent persons in accordance with Gas Safety (Installation and Use) Regulations 1998. This appliance requires annual checking or servicing and this should be entrusted to a CORGI Registered Installer. All CORGI Registered Installers carry a CORGI ID card and have a registration number. Both should be recorded in your central heating log book. You can check your installer is CORGI registered by calling 01256 372300.
INSTALLATION AND SERVICING INSTRUCTIONS
TO BE LEFT WITH BOILER - READ THESE INSTRUCTIONS BEFORE INSTALLING OR LIGHTING THE BOILER
The code of practice for the installation, commissioning
& servicing of central heating systems
140 and 155
xx
POWERMAX OPEN VENT MODELS :
OV 140 P OV 155x P WITH FITTED PUMP OV 140 CP OV 155x CP WITH FITTED PUMP & PROGRAMMER
POWERMAX SEALED SYSTEM MODELS :
SS 140 P SS 155x P WITH FITTED PUMP SS 140 CP SS 155x CP WITH FITTED PUMP & PROGRAMMER
2
THIS APPLIANCE IS FOR USE WITH NATURAL GAS ONLY.
Contents
Section Page
1. Safety Regulations 2
2. Description 2-3
3. Natural Gas Supply 3
4. Electric Supply 3
5. Siting the Appliance 3-4
6. Flueing Options 4-5
7. Ventilation Requirements 6
8. Technical Data 6
9. Installing the Appliance 6-7
10. Electrical Connection to the Appliance 8 Wiring Diagrams 9
11. Water Supply / Primary System 10-11
12. Commissioning 14-15
13. Servicing Instructions 16-18
14. Fault Finding 12
15. Functional Flow Diagrams 13
16. Short List of Spare Parts 19
17. Installing an Extended Balanced Flue 20-21
18. List of Extended Flue Components 22
19. Optional Immersion Heater 23
This appliance must be installed by a competent person in accordance with the Gas Safety Regulations and these instructions. Installers must be CORGI Registered. Failure to install appliances correctly could lead to prosecution.
This appliance must be installed in accordance with the relevant requirements of the current Gas Safety (Installation and Use) Regulations 1998, Local Building Regulations, Building Standards (Scotland) Regulations, Current IEE Wiring Regulations Health and Safety Document No. 635 “The Electricity at Work Regulations 1989” and the Byelaws of the Local Water Undertaking.
The installation must also comply with the relevant recommendations of the following British Standards:
Baxi supports the Benchmark initiative and the aims of the programme. Benchmark has been introduced to improve the standards of installation and commissioning of central heating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency.
1. SAFETY REGULATIONS
POWERMAX –
HIGH PERFORMANCE HOT WATER AND HEATING
Installation and Servicing Instructions
Powermax 140 and 155x are combination boilers in which the gas burner heats the contents of a built-in thermal store. This heated water is used as ‘primary’ water and circulated, as required, to the radiators. Domestic hot water (‘secondary’ water) is heated by a heat exchanger and delivered via a thermostatic blending valve which prevents the hot water exceeding 60°C. The flow rate is governed to a maximum of 12 litres per minute (140) and 18 litres per min (155
x.
A fully pre-mixed burner is used to ensure that the gas is burned cleanly and efficiently. Ignition is fully automatic and the ignition controller incorporates a flame safety device.
A small diameter twin pipe flue system has been designed for a length of up to 9.0 metres (including a balanced flue terminal) through which to draw inlet air and expel exhaust gases. The standard terminal suits a wall thickness of 200mm to 500mm.
The appliance thermostat maintains the thermal store at about 80°C and this stored water is circulated through radiators via a pump inside the casing. A cold start thermostat prevents the pump from operating until working temperature (approx. 60°C) is attained.
For summer operation the central heating can be switched off by the user.
CP models come fitted with both CH pump and an electronic 7-day, 3-event programmer. Provision is made for fitting both room and frost thermostats if required.
Installation of Sealed System models only may fall within the scope of the Building Regulations 1992 (Part G). These require that installation of an ‘unvented’ system shall only be carried out by a competent person as defined in the Approved Document G3. The above requirements do not apply to a Powermax installed as part of an open vented system.
Take particular care to avoid damaging outer panels, switches, programmer etc. Trucking must be done from the rear.
Store the appliance under cover in dry conditions.
Handling and Storage
Operation
2. DESCRIPTION
BS6891:1988
Specification for low pressure gas pipework in domestic premises
BS5440:Part 1:1999 Specification for installation of flues
BS5440:Part 2:2000 Specification for installation of ventilation for gas appliances (except that compartment ventilation is amended as in section 7 of these Instructions).
BS5546:1990 Specification for installation of gas hot water supplies
BS5449:1990 Specification for forced circulation hot water central heating systems
BS6798:1987 Specification for installation of gas fired hot water boilers of rated input not exceeding 60kW
3
These boilers require a natural gas supply of 1.6 to 2.0 cubic metres per hour. Gas supply pipework of not less than 22mm diameter should be run to the appliance and to within 300mm of the gas valve (gascock) and should be installed in
accordance with BS6891:1988. (i.e. The pressure drop
between meter and appliance not to exceed 1mbar).
The gas connection to the appliance is Rp
1
/2 (1/2 in B.S.P.) Entry
holes are provided through the controls chassis. The complete installation must be tested for soundness and
purged as described in the above standard and in accordance with Corgi recommendations.
The appliance requires a 230V ~ 50Hz single phase 3A fused electrical supply which must be installed in accordance with the current IEE Wiring Regulations and any Local Regulations which apply. Detailed wiring instructions are given in Section 10. Power consumption is approximately 140W for the appliance, with the Central heating pump rated at an additional 40W to 88W depending upon pump speed.
WARNING : THIS APPLIANCE MUST BE EARTHED
Note: This appliance may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring Regulations, and in Scotland, the electrical provisions of the Building Regulations with respect to the installation of the appliance in a room or internal space containing a bath or shower. Where a room­sealed appliance is installed in a room containing a bath or shower, any electrical switch or appliance control, utilising mains electricity should be so situated that it cannot be touched by a person using the bath or shower.
4. ELECTRIC SUPPLY
3. NATURAL GAS SUPPLY
The appliance must be installed on a flat floor capable of supporting the weight of the unit when full of water – up to 185kg. It should be sited to minimise the length of flue and to avoid long hot water pipe runs. The extended flueing capability enables the appliance to be sited well away from an outside wall, thus installation in a first floor cupboard or compartment, basement, utility room or kitchen are all feasible locations. The appliance must not be sited outside or in any outhouse where it could be exposed to the weather. The location chosen must permit the provision of a satisfactory external flue termination. The location must also provide adequate space for servicing and air circulation. If floor settlement is likely due to the weight of the appliance, ensure that pipework design is able to accommodate this.
When using an extended flue system it is essential to fit protective ducting (such as that supplied in the extended flue kits) in order to prevent direct contact with the hot flue pipe.
General requirements for cupboard/compartment installations, including airing cupboards, are given in BS6798. Specific requirements for Powermax installations are given below. a The compartment must be ventilated at high and low
level in accordance with BS5440:Part 2 and Section 7 of these instructions.
b The compartment shall be a fixed rigid structure large
enough to allow it and the boiler to be inspected and serviced. A minimum width between the door jambs of 550mm (21in) must be provided.
c Internal surfaces should be non-combustible or lined
with non-combustible material. Examples of non­combustible materials having a fire resistance of not less than 0.5 hour are plaster skimmed plasterboard, and fireproof boarding. The floor need not be lined. Doors or shelves made from combustible material, e.g. wood must be at least 75mm from the front or top of the boiler.
d The door of an understairs cupboard shall have a
BS476:Part 8 fire resistance of not less than 0.5 hour; and air vents must be direct to outside air.
e The flue pipe must be protected by the ducting supplied
by Baxi UK or by another no less suitable non­combustible enclosure.
f Householders should be discouraged from storing
clothes etc on the boiler itself. A removable shelf at least 75mm above the boiler is acceptable.
Detailed recommendations for flueing are given in BS5440:Part 1. The following notes are intended to give general guidance. The appliance must be installed so that the flue terminal is exposed to the external air, preferably on a clear expanse of wall. Acceptable positions are indicated in Fig.5.1.
Avoid positions where the terminal is adjacent to projections; particularly immediately under a balcony, inside a re-entrant position, or immediately adjacent to a drain pipe.
If the appliance is fitted under a ventilator or opening window, the terminal must be at least 300mm (12in) from any part of the window or ventilator, and in accordance with BS5440:Part 1.
Requirements for horizontal balanced flue terminations
Compartment Installation
Flue Protection
General
5. SITING THE APPLIANCE
Powermax Sealed System Schematic
AIR VENT
PRESSURE
RELIEF
CH FLOW
CH RETURN
GAS
CH
FLOW
CH
RETURN
FLUECOMBUSTION AIR
BLENDING VALVE DHW
COLD MAIN
4
Where the lowest part of the terminal is less than 2m (6ft) above the level of any ground, balcony, flat roof or place to which people have access, the terminal must be protected by a guard of durable material. A Terminal Guard Kit is available as an optional extra Part No. P210 from Baxi UK. The guard requires a flat wall surface of approximately 450mm diameter,concentric with the terminal assembly.
The exhaust flue pipe of the terminal must not be closer than 25mm(1in) to combustible material. Additional clearance must be provided when passing the flue through timber walls.
Advice on gas installations in timber framed buildings is contained in an IGE technical publication available from the Institution of Gas Engineers, 21 Portland Place, London W1N 2AF.
Several flueing systems are available. ALL are ‘room sealed’ and a choice of terminals is offered:
1. Horizontal balanced flue terminal.
2. Vertical balanced flue terminal.
3. Ridge tile terminal (unbalanced)
4. Mini terminal balanced flue systems
All terminals can be sited up to 7.0m from the boiler. In some circumstances, a horizontal terminal can be sited 9.0m from the boiler – See below. Flue systems are supplied in kits, or components can be ordered individually-see list in section 17.
Before starting an installation, check that the correct flue kit has been supplied with the boiler.
The efficient operation of Powermax will naturally give rise to condensation in the flue gases and pluming will be visible during adverse atmospheric conditions. In installations with long flue runs some condensate may be discharged from the terminal. The terminal must, therefore, be sited to avoid nuisance from either phenomenon.
Visible Pluming
6. FLUEING OPTIONS
Use Kit P260 for installations where the flue passes through the wall immediately behind the appliance. The terminal is suitable for a thickness of 200mm to 500mm as shown in Fig.6.1. An 800mm wall liner P337 can be ordered separately. Step-by-step instructions are given in Section 9.
Kits are supplied as follows with components also available separately.
Kit No.
The maximum length of each air/flue pipe must not exceed 5m (including a Horizontal BF Terminal) when the maximum of 4 air pipe bends and 3 flue pipe bends is used – see Fig 6.3.
The pipes can leave the boiler horizontally to right or left, or rearwards, or vertically upwards.
There is no minimum length. If fewer bends are used between the appliance and the flue
terminal, the maximum length of straight pipe can be increased if required – see table below.
Kit P242 allows the flue to terminate at an approved (gas vent) Ridge Tile Terminal with combustion air being drawn from a ventilated loft space or from a second ridge terminal. The inlet terminal must be not less than 300mm above the top surface of the ceiling insulation.The air inlet pipework must be at least
1.5m long and not less than half the flue length. Full fixing instructions are supplied in each kit.
Additional components may be specified up to the maximum indicated in the diagram and the table opposite.
Combustion air may be drawn from a ventilated roof space or from a compartment or duct which is permanently ventilated direct to outside air. The effective open area of the vent must not be less than 160cm
2
(25in2).
When combustion air is drawn from a roof space or compartment or duct, that area must be effectively sealed from the remainder of the dwelling. A tight fitting trap door or similar is acceptable.
Ridge Tile Terminal
Fig. 6.5
Extended Balanced Flue Systems
Fig. 6.3
Balanced Flue Terminal
1m Sideways horizontal balanced flue P261
3m Extended horizontal balanced flue P263
5m Extended horizontal balanced flue P265
7m Extended horizontal balanced flue P267
9m Extended horizontal balanced flue P269
Refer to Section 17 for step-by-step fixing instructions.
MAX. No OF BENDS MAXIMUM PIPE
(90° OR 135°) LENGTH
Air Inlet Exhaust Flue Total Air/Flue inc. Horizontal Trml.
4 3 7 5.0m each 3 2 5 7.0m each 2 1 3 9.0m each
Lagging is recommended when the flue pipe exceeds 3m. The insulation used must be non-combustible and suitable for operating at temperatures up to 200°C. Class ‘O’ foil backed glass wool or mineral wool insulation wrapped tightly around the flue pipe will help to reduce pluming. It is not necessary to insulate the air inlet pipes.
Flue Pipe Insulation
Fig. 6.1
‘T’ WALL THICKNESS = 200mm MIN 500mm MAX
Terminal position Min. distance A: Directly below an openable window or other opening, e.g. an air brick 300mm B: Below gutters, soil pipes or drain pipes 75mm C: Below eaves 200mm D: Below balconies or car port roof (not illustrated) 200mm E: From vertical drain pipes and soil pipes 75mm F: From internal or external corners 300mm G: Above ground or balcony level 300mm H: From a surface facing a terminal 600mm I: From a terminal facing a terminal, or from an opening in a car port into 1200mm
dwelling (not illustrated) 1500mm J: Vertically from a terminal on the same wall 300mm K: Horizontally from a terminal on the same wall 300mm L: Between ridge terminals (if combustion air is drawn from second terminal) 300mm M: Between vertical terminal and wall 300mm NB: Terminals located less than 2m above ground level must be protected by a terminal
guard P210
Fig. 5.1
J
IMPORTANT Any flue pipework in a horizontal plane MUST run downwards AWAY from the boiler by 5mm per metre. To prevent water accumulation there must be no sags or dips in the pipework.
6
5
Fig. 6.2 Mini terminal flue system
Example of rearwards flueing to achieve minimum 300mm distance between terminals
Maximum permitted flue run of 9.0m total length (including one 90° bend and one 170° offset Bend in the flue pipe).
Fig. 6.3
Typical routeing of extended balanced flue
Fig. 6.5 Typical routeing of ridge terminal flue kit
Note that
the length of
the air inlet
pipe must not
be less than
0.5 x length of flue pipe
1.5 TO 4.0 METRES
1.5 TO 5.0 METRES [STANDARD KIT]
1.5 TO 7.0 METRES
[EXTENDED]
Vertical RS Flue System
The Powermax Vertical RS flue system offers an unobtrusive balanced flue terminal as an option for both pitched and flat roofs.
The vertical roof terminal Part No. P230 provides a combined air intake and combustion gas outlet in a concentric arrangement. Below the roof the terminal changes into a twin pipe system. Separate roof flashing units should be ordered (specified) for pitched or flat roofs. Roof pitches from 15° to 55° are catered for by selecting one of three pitched roof flashing units.
P231 for pitches 15° to 25° P232 for pitches 25° to 45° P233 for pitches 35° to 55° P236 for flat roofs
To connect the Powermax to the vertical terminal a kit Part No. P246 is required. This contains a range of extension air/flue pipes and bends to enable the terminal to be sited up to 2.5m from the appliance. The maximum overall length of the
complete flue system must not exceed the limits indicated for extended balanced flue systems, however the length of the
vertical terminal itself can be disregarded. Complete fixing instructions are provided in each kit.
The Mini Terminal Flue system provides an alternative arrangement to the standard (140mm diameter) balanced flue terminal. Separate 65mm diameter air inlet and flue terminal assemblies can be positioned in different locations on the same wall subject to similar wind conditions. See Fig. 6.2.
They are available in a small range of colours chosen for their compatibility with typical external building materials.
Code. A Matt Black
(standard finish)
D Red Brick
B Stone
(also suitable for yellow stock brick)
E Slate
C Light Brick F White Each terminal requires a hole of 65mm diameter to be core
drilled through the external wall. Flue kits are available as listed below. Each kit contains all the
components needed for a complete system including full fixing instructions.
Kit No.
* For sideways flueing
WARNING – The flue pipe becomes very hot when appliance is working. Householders should be warned not to touch exposed pipe e.g. beyond protective duct within loft. The flue pipe should be insulated or ducted if accidental contact is likely.
Description
MINI TERMINAL FLUE
P231/232/233
P230
P236
P234
Fig.6.6 VERTICAL FLUE COMPONENTS
FLUEING RESTRICTIONS – RIDGE TILE TERMINAL
Number of Bends Pipe Length
Application Components 90° or 135° (metres)
Standard Air Inlet 2 1.5 minimum Kit Flue 3 1.5 minimum
Extended Air Inlet 2-3 1.5 to 4.0 Inlet & Flue 3 max 1.5 to 7.0 Flue
1m Mini Terminal BF kit* P271
3m Mini Terminal BF kit P273
5m Mini Terminal BF kit P275
7m Mini Terminal BF kit P277
9m Mini Terminal BF kit P279
300
170 OFFSET
BEND P320
90 BENDS P358
SHORT EXTENSION P338
MINIMUM EFFECTIVE AREA OF COMPARTMENT AIR VENTS 140 155
xx
Position of opening Ventilated to Area of each vent
High and Low Level Room 54cm
2
60cm
2
High and Low Level Outside 27cm
2
30cm
2
6
7. VENTILATION REQUIREMENTS
a When the appliance is installed in a room or habitable
internal space, there are no specific ventilation requirements.
b When the appliance is installed in a compartment it is
essential that permanent high and low vents are provided for the circulation of cooling air. Purpose made vents must have a non-adjustable free area not less than the minimums specified in the table below.
8. TECHNICAL DATA
Guidance on where to locate the appliance is given in Sections 5, 6 and 7. In some instances it will be advantageous to pre-plumb pipework or to pre-fix terminal, air/flue pipes and duct.
1. Move appliance to where it is accessible for flue preparation. For a guide to removing panels, see back page. Remove 2 screws at bottom of front cover, pull forward from bottom, gently ease downwards to free location studs.
140: The lid is retained by 3 screws, 2 in the front edge under
the timer control panel and a third transit screw in the back of the lid. The lid can be eased upwards from the rear and pulled gently forwards and away from the control panel. The transit screw can be discarded if access is restricted.
155x: Remove recessed screw at top of switch panel and keep
safe. Lift off upper front cover. The top panel is retained by 4 studs: gently ease upwards to remove. The plinth cover is retained with 4 screws and 2 screws retain the rear section.
2. Carefully set aside the outer covers. Remove small press-out panel(s) either side of casing for plumbing connection (and flue/air pipes) as necessary. The hand hold cut outs in the side panels also provide convenient plumbing access. The cut out in the base allows pipework to be brought up from floor level, see Plumbing Guide on page 23, but the pipes must not obstruct service access to the sump. See Fig. 11.1.
3. Connect one end of electricity supply cable to the user terminal in accordance with sections 4 and 10. The cable must be routed via the anchorage and through the bushing in LH side panel. See Fig. 9.6.
4. Flueing If installing boiler with vertical RS balanced flue see separate instructions supplied with vertical flue kit. If installing boiler with an extended horizontal balanced flue go to Section 17 of these instructions. If installing boiler with a Ridge Tile Terminal or Mini Terminals, see separate instructions supplied with each kit. The standard flue kit P260 contains the following components, See Fig.9.2 1 x flue terminal assembly. complete with sealing ring 1 x wall liner 1 x flexible duct AIR INLET ONLY 2 x worm drive clips Note: The flue terminal assembly MUST be installed horizontally. The unit is floor standing and a vertical flat area of wall is required 1100mm or 1260mm high x 550mm wide. If unit is being raised above floor level, allow for this in marking position of flue liner.
4a Mark off the centre of the 140mm (5
1
/2 in) diameter hole as shown in Fig.9.3 and core drill. If the wall is clad with a combustible material a 25mm (1in) wide area around the flue liner must be removed. Measure the wall thickness and cut the liner to this length.Cut opposite end to lugs.
b Fit the liner through the 140mm (5
1
/2in) diameter hole (lugs inside) and cement into position, making good internal and external rendering. The latter may be done with arm extended through the liner.
c Insert 50mm diameter 90° elbow into flue socket
(vertically rising pipe at the back of the appliance)
9. INSTALLING THE APPLIANCE
140 155x
Nominal Output, kW gross 14.0 16.4 Nominal Input, kW gross 17.1 20.0 Category I2H Gas G 20 Supply Pressure, mbar 20 Gas Rate m
3
/hr 1.6 2.0 Gas Connection Rc 1/2 Air sense/burner pressure
differential -
0.13 ± 0.03mbar.
This is factory set and no
adjustment is intended NOx < 40 ppm – Class 5 CO < 20 ppm
Thermal store capacity 80 100 (primary water) litres
DHW Temperature °C 55-60 maximum DHW Flow Rate, litres per 12 18
minute (maximum) Working Pressures, bar:
Primary SS models 3 max (Design pressure
2.5 to comply with UK Water Regulations)
Primary OV models 1.0 maximum DHW 6.0 maximum DHW 1.5 minimum
Pressure Relief Valve, bar: 3.0 Weight (empty) kg 75 85
Weight (full) kg 155 185 Connections:
CH Flow/Return 22mm Compression DHW Inlet/Outlet 22mm Compression Gas Rc 1/2 Pressure Relief 15mm Tube
(1/2 x 3/4 Tundish
supplied loose)
Electricity Supply: 230V ~ 3A fused supply
Cable Entry Top rear of LH panel
Dimensions, mm
Height 1100 1260 Width 540 Depth 600
Clearance requirements for installation and servicing:
Top 400mm (16 inches) Sides 5mm (10mm (3/8") total) Base and back Nil Front 450mm (18 in) unless
behind an openable door
Flueing:
Flue Types C13 C33 C53
(As flue kit specified) Bal. Flue Terminal 140mm Diameter Mini Flue 65mm Diameter Flue/Air Pipes 51mm Diameter Standard Flue Length 500mm Extended Flues Refer to Section 6
(including packaging)
Fig. 9.3 View on front of boiler
* Normal dimensions - check actual height on appliance.
Allow also for floor unevenness.
7
Fig. 9.1
Fig. 9.2
Flue terminal assembly
Flue liner
Inlet duct
Worm drive clip
Fig. 9.4
Fig. 9.5 Flue terminal assembly
Fig. 9.6 Route for incoming electric cables
Refer to page 23 for detailed wiring instructions.
Optional immersion heater
Refer to Guide diagram on page 23. This can be ordered as a full-size template Part No P3281.
First Fix Plumbing
AIR INLET
140 TOP
RETAINING
SCREWS
(ACCESSIBLE
AFTER
REMOVING
FRONT)
155x PANEL
RETAINING
SCREW
d Measure and cut flue pipes with a hacksaw to a length
as illustrated in fig 9.5. Measure the wall thickness and add 10mm to the flue pipe and 120mm to the air inlet pipe from datums ‘AA’. Remove any burrs from cut ends of tubes. Note: If wall is not truly vertical or appliance is prevented from standing against wall, add stand off
distance to wall thickness measurement.
e
Push fully home ensuring inlet air pipe enters flexible duct and exhaust flue pipe engages socket. Secure inlet pipe with worm drive clip (See Fig.9.4).
f Carefully push appliance into position, entering terminal
into wall liner. If necessary, fit terminal guard.
5. Make gas connection as described in Section 3.
6. Fix feed and expansion cistern or expansion vessel and make water connections as described in Section 11.
7. Test gas pipework for gas soundness in accordance with BS6891 and latest CORGI codes of practice.
TRANSIT SCREW
WALL LINER
FLUE ELBOW
WORM DRIVE CLIPS
Std. Balanced Fue
540
135
135
WALL THICKNESS+120mm*
INLET
EXHAUST
WALL THICKNESS+10mm*
*(+ ANY STAND-OFF DISTANCE BETWEEN APPLIANCE AND WALL)
'A' 'A'
83
)
N
1100(140) 1260(155
)
63
N
948(140) 1123(155
)
N
948(140) 1135(155
  
  
Loading...
+ 16 hidden pages