Read these instructions carefully and look at the equipment to become familiar with
the device before trying to install, operate, or maintain it. The following special
messages appear throughout this bulletin to warn of potential hazards.
!
Used where there is a hazard of severe bodily injury or death. Failure to
follow a “DANGER” instruction
!
Used where there is a hazard of bodily injury or death. Failure to follow a
“WARNING” instruction can result in death or bodily injury.
!
Used where there is a hazard of equipment damage. Failure to follow a
“CAUTION” instruction can result in damage to equipment.
FCC NOTICE: This equipment complies with the requirements in Part 15 of FCC
rules for a Class A computing device. Operation of this equipment in a residential
area may cause unacceptable interference to radio and TV reception, requiring the
operator to take whatever steps are necessary to correct the interference.
DANGER
will
result in death or
WARNING
CAUTION
severe
bodily injury.
PLEASE NOTE: Electrical equipment should be serviced only by qualified electrical
maintenance personnel, and this document should not be viewed as sufficient for
those who are not otherwise qualified to operate, service, or maintain the equipment
discussed. Although reasonable care has been taken to provide accurate and
authoritative information in this document, no responsibility is assumed by Square D
for any consequences arising out of the use of this material.
TECHNICAL SUPPORT
For technical support, contact the
Power Monitoring and Control Systems Technical Support Center.
Hours are 7:30 A.M. to 4:30 P.M., Central Time, Monday through Friday.
www.powerlogic.comBBS: (615) 287-3414
Fax: (615) 287-3404Phone: (615) 287-3400
POWERLOGIC, POWERLINK, Square D, and are Registered Trademarks of Square D Company.
System Manager is a trademark of Square D.
Other names are trademarks or service marks of their respective companies.
1998 Square D. All rights reserved. This bulletin may not be copied in whole or in part, or transferred
to any other media without the written permission of Square D Company.
Register your Power Meter
Please fill out, detach, and mail the postage paid card below. Fill out
only one registration card, even if you have purchased multiple
POWERLOGIC Power Meters.
D-1:Power Meter System Wiring Connections ............................................... 75
H-1:Maximum Distances of 2-Wire Modbus or Jbus
Comms Link at Different Baud Rates................................................... 103
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 1—Introduction
CHAPTER 1—INTRODUCTION
WHAT IS THE POWER METER?
The POWERLOGIC Power Meter is a compact, low-cost power meter for
basic industrial power monitoring applications. The power meter has been
designed for ease of installation in industrial retrofit applications. Power
meter applications include new equipment such as switchboards,
panelboards, and Low Voltage Drawout (LVDO) feeders, and it can be used
in POWERLINK installations for metering the main. Additionally, the power
meter can be used for Motor Control Centers (MCCs) and busway.
The power meter can be purchased with an optional display for local display
and setup. Also, the display can be purchased separately to be used as a
power meter programmer. The display fits standard 4-1/4" (108 mm)
ammeter and voltmeter cutouts. It connects to the power meter by a cable
that supplies both communications and power.
All power meter modules can be mounted up to 50 feet (15.2 m) from the
display. You can mount them on an enclosure floor or wall, on a horizontal
35 mm DIN rail, or directly behind the display on the panel door.
The power meter is completely supported in POWERLOGIC System Manager
Software releases SMS-3000, SMS-1500 and PMX-1500, including setup and
resets. SMS-770/700 v. 2.23 and EXP-550/500 v. 1.23 provide limited support,
including real-time and historical data monitoring and PC-based alarming
and trending.
Some of the power meter’s features include:
• ANSI C12.16 Revenue Accuracy
• True RMS Metering (31st Harmonic)
• Accepts Standard CT and PT Inputs
• Direct Connect up to 600 V
• Fits Standard 1% Ammeter/Voltmeter Mounting Holes
• Optional Display to View Meter Values
• Power Quality Readings—THD (Voltage and Current)
• On-board Clock/Calendar
• Easy Setup through Remote Display (Password Protected)
• RS-485 Communications Standard
• System Connections
– 3-Phase, 3-Wire Delta (Metered or Calculated B Phase)
– 3-Phase, 4-Wire Wye
• Operating Temperature Range (0°C to +60°C)
1998 Square D All Rights Reserved1
Power MeterBulletin No. 3020IM9503R6/98
Chapter 1—IntroductionDecember 1998
Table 1-1 below summarizes the power meter instrumentation common to all
three models. Table 1-2 describes the three power meter models and accessories. You can assemble custom length cables using the components specified
in Table 1-3. Table 1-4 compares features of those models.
Table 1-1
Summary of Power Meter Instrumentation
Real-Time Readings
• Current (per phase)
• Voltage (L-L, L-N)
• Real Power (per phase and 3Ø total)
• Reactive Power (per phase and 3Ø total)
• Apparent Power (per phase and 3Ø total)
• Power Factor, true (per phase, 3Ø)
• Frequency
Energy Readings
• Accumulated Energy, real 3Ø total
• Accumulated Energy, reactive 3Ø total
• Accumulated Energy, apparent 3Ø total
Table 1-2
Class 3020 Power Meters and Accessories
TypeDescription
PM-600Instrumentation, 0.3% accuracy
PM-620PM-600 features, plus date/time stamp, THD/thd,
neutral current, demand values
PM-650PM-620 features, plus alarms, min/max values,
data and event logs
PMD-32Power Meter Display (optional) with 1-ft. (0.3 m) cable
SC-1044-ft (1.2 m) cable (optional)
SC-11212-ft. (3.7 m) cable (optional)
SC-13030-ft. (9.1 m) cable (optional)
Table 1-3
Components for Assembling Custom Length Cables
DescriptionMfr./Part NumberQuantity
➀ Assemble with manufacturer’s recommended crimping tool.
2 1998 Square D All Rights Reserved
Olflex 602604
or50-ft. (15.2 m)
Unitronic 190Maximum Length
(4-wire/26 AWG)
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 1—Introduction
Table 1-4
Power Meter Feature Comparison
FeaturePM-600PM-620PM-650
Full Instrumentation✘✘✘
RS-485 Communications Port✘✘✘
Wiring Diagnostics✘✘✘
ANSI C12.16 Accuracy✘✘✘
Current Demand (per phase, neutral)✘✘
Power Demand (3-phase total, present)✘✘
Peak Power & Current Demand✘✘
Date/Time Stamping✘✘
THD or thd (Voltage and Current)✘✘
Calculated Neutral Current✘✘
Onboard Alarms✘
Min/Max Readings✘
Predicted Power Demand✘
Data Log✘
Event Log✘
Demand Interval Synch to Comms✘
Rolling Block Demand✘
USING THIS BULLETIN
This document provides the information required to install and operate the
power meter. The document consists of a table of contents, chapters, several
appendices, and an index. To locate information on a specific topic, refer to
the table of contents or the index.
Notational Conventions
This document uses the following notational conventions:
•Procedures. Each procedure begins with a statement of the task, followed
by a numbered list of steps. Procedures require you to take action.
•Bullets. Bulleted lists, such as this one, provide information but not
procedural steps. They do not require you to take action.
•Cross-References. Cross-references to other sections in the document
appear in boldface. Example: see Power Meter Connections in Chapter 3.
Not Covered in this Bulletin
Some of the power meter’s features, such as PC-based logging, onboard
logging for the PM-650, trending, and PC-based alarming, must be set up
using POWERLOGIC application software. For instructions on setting up
these features, refer to the application software instruction bulletin.
Note: The PM-650 is supported by POWERLOGIC System Manager Software
(SMS)-3000 v. 3.1 (and higher).
1998 Square D All Rights Reserved3
Power MeterBulletin No. 3020IM9503R6/98
Chapter 1—IntroductionDecember 1998
4 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 2—Safety Precautions
CHAPTER 2—SAFETY PRECAUTIONS
DANGER
!
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.
• Only qualified electrical workers should install this equipment.
Such work should be performed only after reading this entire set
of instructions.
• The successful operation of this equipment depends upon proper
handling, installation, and operation. Neglecting fundamental
installation requirements may lead to personal injury as well as
damage to electrical equipment or other property.
• Before performing visual inspections, tests, or maintenance on this
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized,
tested, grounded, and tagged. Pay particular attention to the design
of the power system. Consider all sources of power, including the
possibility of backfeeding.
Failure to observe these precautions will result in death, severe
personal injury, or equipment damage!
1998 Square D All Rights Reserved5
Power MeterBulletin No. 3020IM9503R6/98
Chapter 2—Safety PrecautionsDecember 1998
6 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 3—Hardware Description
CHAPTER 3—HARDWARE DESCRIPTION
DISPLAY
The optional power meter display is designed for maximum ease of use. The
display has the following modes of operation:
• Setup—for setting up power meter
• Resets—to perform resets of peak demands
min/max
• Alarm Log➁—displays and acknowledges onboard alarms
• Alarm Setup
• Min/Max
➁
—for setting up onboard alarms
➁
—displays minimum and maximum values
For details on how to use the optional display, see Chapter 7—DisplayOperation.
➀ When used with PM-620 and PM-650.
➁ When used with PM-650.
1998 Square D All Rights Reserved7
Power MeterBulletin No. 3020IM9503R6/98
Chapter 3—Hardware DescriptionDecember 1998
Figure 3-1 shows the power meter display. Display components are listed
below:
➀ 2-Line Liquid Crystal Display. For local display of metered values.
➁ Arrow Buttons. Press to move through meter display screens. In Setup,
Resets, and Diagnostic modes, press to change values and, on the PM-650
only, Alarm Setup and Alarm Log.
➂ Mode Button. Press to scroll through the available modes.
➃ Contrast Button. Press to change the contrast of the display.
➄ Select Button. Press to select modes and Setup, Resets, and Diagnostic
values. On the PM-650 only, use this button to select Alarm values.
➀
➁
➂
➃
Mode
Select
Power Meter
Figure 3-1: Power meter display components
➄
8 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 3—Hardware Description
The display connects to the power meter via the display cable. One display
communications port is located on the back of the display (figure 3-2, below).
The other display communications port is located on the meter connections
end of the power meter (figure 3-3).
Display
Communications
Port (Terminal 23)
Display Front
Display Back
Figure 3-2: Power meter display, front and back
1998 Square D All Rights Reserved9
Power MeterBulletin No. 3020IM9503R6/98
Chapter 3—Hardware DescriptionDecember 1998
POWER METER CONNECTIONS
Figure 3-3 shows the front of the power meter and the label on the terminal
shield. Identified parts are as follows:
➀ 3-Phase Voltage Inputs
➁ Control Power Terminals
➂ KYZ Pulse Output
➃ 3-Phase Current Inputs
➄ Display Communications Port
➅ RS-485 Communications Terminals
Note: See Chapter 5—Wiring for wiring instructions.
➀
➁
➃
➅
Va VbVc Vn
G
➂
L
2
L
1
Ia– Ib– Ic–
➄
IN+
IN–
OUT+
OUT–
SHLD
Figure 3-3: Front of power meter and terminal shield label
Ia+ Ib+ Ic+
K
Y
Z
10 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 4—Installation
CHAPTER 4—INSTALLATION
DANGER
!
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.
Only qualified electrical workers should install and wire this equipment.
Perform such work only after reading this complete set of instructions.
Failure to observe these precautions will result in death or severe
personal injury!
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
When mounting the power meter module, provide the following clearances
(from enclosure walls or other objects): terminal end: 4" (102 mm); vented
sides: 3" (76 mm). No clearance is necessary on the non-vented sides.
Failure to observe this precaution can result in equipment damage.
POWER METER/DISPLAY MOUNTING OPTIONS
There are several options for mounting the power meter module and display:
•display mounted on front of a power equipment panel; power meter
module mounted on back of panel (figure 4-1, page 15)
•display mounted on front of panel; power meter mounted remotely inside
of equipment, with the terminals
–up, mounted to bottom (floor) of equipment, or
–perpendicular, mounted on side pan (figure 4-2, page 17)
•display mounted on front of panel, with the power meter module mounted
on a 35 mm DIN rail (figure 4-4, page 19)
•no display; power meter mounted in one of the above locations
Mounting instructions for each of these options are described in this section.
When choosing a mounting location, consider the following:
•Allow for easy access to the meter connections end (where terminals are
located) of the power meter module.
•Allow extra space for all wires, shorting blocks, or other components.
1998 Square D All Rights Reserved11
Power MeterBulletin No. 3020IM9503R6/98
Chapter 4—InstallationDecember 1998
•Be sure that ambient conditions fall within the acceptable range: operating
temperature 0°C to +60°C, relative humidity 5–95%, non-condensing.
Note: Always refer to local and state electrical safety standards before mounting the
power meter or display.
MOUNTING THE DISPLAY
The display can be mounted in the following locations:
•in a standard 1% ammeter/voltmeter panel cutout
•on an equipment panel where it will be necessary to cut a hole before
mounting the display
Table 4-1 below shows possible locations for mounting the display.
Table 4-1
Typical Locations for Mounting Display
Equipment TypeMounting Location
QED SwitchboardsDisconnect Door
POWER-ZONE
HVL and VISI/VAC
Metal-Clad and Substation CBsStandard Relaying Locations
ISO-FLEX
Model 6 MCCsMain Meter Location or Auxiliary Section
III SwitchgearMain Instrument Compartment Door
Switchgear9-inch Front Panel or Instrument Door
Medium Voltage MCCsLow Voltage Door
In Existing 1% Ammeter/Voltmeter Cutout
To mount the display in a standard 1% ammeter/voltmeter cutout, follow
these steps:
1. Turn off all power supplying the equipment before working on it. Following all safety precautions, remove the existing ammeter/voltmeter.
2. Position the display against the front of the panel. From the other side of
the panel, line up the mounting holes in the panel with the mounting holes
in the display (see figure 4-1, page 15).
HAZARD OF EQUIPMENT DAMAGE.
Use only the power meter display mounting screws included in the mounting hardware kit. Use of any other screws for display mounting voids the
warranty and may damage the display.
Failure to observe this precaution can result in equipment damage.
12 1998 Square D All Rights Reserved
CAUTION
!
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 4—Installation
3a. If a power meter will be attached to the display, insert display mounting
screws into only the top two holes; tighten until approximately 1/4" of
each screw protrudes from the panel. See Directly Behind the Display,
page 14, for remaining instructions. Begin with step 3.
b. If a power meter will not be attached directly to the display (behind the
panel door), insert one display mounting screw (included in hardware kit)
through each of the four mounting holes. Tighten all screws to 6–9 lb-in
(0.7–1.0 N•m).
On Panel Without Existing 1% Ammeter/Voltmeter Cutout
To mount the display on a panel without an existing cutout for an
ammeter/voltmeter, follow these steps:
1. Turn off all power supplying the equipment before working on it. Follow
all safety precautions.
2. Tape the template shipped with the display to the panel in the desired
location; make sure the template is level. (Hole positions and dimensions
are shown in figure 4-3, page 17.) Make sure no wires or equipment on the
other side of the panel will be damaged, then drill through the panel at the
4 holes marked A on the template. Use a 3/16" drill bit.
Drill or punch a hole 2 to 4 inches (51–102 mm) in diameter through the
3.
panel at the center of the template (center of hole is marked on the template).
4. Position the display against the front of the panel. From the other side of
the panel, line up the mounting holes in the panel with the mounting holes
in the display.
5a. If a power meter will be attached directly to the display, insert screws
into only the top two holes; tighten until approximately 1/4" of each screw
protrudes from the panel. See Directly Behind the Display, page 14, for
remaining instructions. Begin with step 3.
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
Use only the power meter display mounting screws included in the mounting hardware kit. Use of any other screws for display mounting voids the
warranty and may damage the display.
Failure to observe this precaution can result in equipment damage.
b. If a power meter will not be attached directly to the display (behind the
panel door), insert one display mounting screw (included in hardware kit)
through each of the four mounting holes. Tighten all screws to 6–9 lb-in
(0.7–1.0 N•m). Note: See CAUTION statement above.
1998 Square D All Rights Reserved13
Power MeterBulletin No. 3020IM9503R6/98
Chapter 4—InstallationDecember 1998
MOUNTING THE POWER METER
Power meter mounting options are described in this section.
DANGER
!
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.
Only qualified electrical workers should install and wire this equipment.
Perform such work only after reading this complete set of instructions.
Failure to observe these precautions will result in death or severe
personal injury!
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
When mounting the power meter module, provide the following clearances
(from enclosure walls or other objects): terminal end: 4" (102 mm); vented
sides: 3" (76 mm). No clearance is necessary on the non-vented sides.
Failure to observe this precaution can result in equipment damage.
Directly Behind the Display
To mount the power meter directly behind the display, follow these steps:
1. Turn off all power supplying the equipment before working on it. Follow
all safety precautions.
2. Mount the display. See Mounting the Display, page 12, for instructions.
3. Plug one end of the 1-foot communications cable provided with the
display into the display communications port (terminal 23, figure 4-1) on
the back of the display.
4. Hook the power meter mounting feet onto the top two display mounting
screws protruding from the back of the door or panel. Route the cable to
the right (hinged side) so it is not pinched between the power meter
module and the panel (figure 4-1).
14 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 4—Installation
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
Use only the power meter display mounting screws included in the mounting hardware kit. Use of any other screws for display mounting voids the
warranty and may damage the display.
Failure to observe this precaution can result in equipment damage.
5. Using the screws in the display hardware kit, secure the power meter to
the display through the bottom two mounting feet holes. Tighten all
screws to 6–9 lb-in (0.7–1.0 N•m).
6. Plug the other end of the communications cable into the display
communications port (terminal 22, figure 4-1) on the power meter.
Display
Panel
Display Communications
Port (Terminal 23)
Panel with
Existing Cutout
Display Cable
SC-101
Display Communications
Port (Terminal 22)
Top View
After Mounting
Figure 4-1: Mounting power meter and display on panel with existing ammeter/voltmeter cutout
1998 Square D All Rights Reserved15
Power MeterBulletin No. 3020IM9503R6/98
Chapter 4—InstallationDecember 1998
Remote Mounting
To mount the power meter remotely (inside an enclosure), follow these steps:
DANGER
!
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.
Only qualified electrical workers should install and wire this equipment.
Perform such work only after reading this complete set of instructions.
Failure to observe these precautions will result in death or severe
personal injury!
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
When mounting the power meter module, provide the following clearances
(from enclosure walls or other objects): terminal end: 4" (102 mm); vented
sides: 3" (76 mm). No clearance is necessary on the non-vented sides.
Failure to observe this precaution can result in equipment damage.
1. Turn off all power supplying the equipment before working on it. Follow
all safety precautions.
2. Select a mounting location on the floor or wall of the enclosure, ensuring
that there are adequate clearances, that the terminals are accessible, and
that the location complies with local and state electrical codes.
3. Tape the template shipped with the module to the panel in the desired
location (see figure 4-2, page 17); make sure the template is level. (Hole
positions and dimensions are shown in figure 4-3, page 17.) Make sure no
wires or equipment on the other side of the panel will be damaged, then
drill through the panel at the 4 holes marked A on the template. Use a
3/16" drill bit.
4. Place the power meter mounting feet holes over the drilled holes and
secure the power meter to the enclosure panel using No. 6 (maximum)
screws or bolts suitable for the panel. Tighten to 6–9 lb-in (0.7–1.0 N•m).
16 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 4—Installation
Template
Panel
Figure 4-2: Mounting power meter on panel with no existing cutout
1.6875
43
2" to 4" Hole
51–102
3.375
86
1.6875
43
Dual Dimensions:
Inches
Millimeters
4 Holes
0.1875 (5 mm)
3.375
86
Note: The dimensions and positions of the 4 display holes shown above are identical for the power meter module.
Figure 4-3: Panel mount for the power meter display
1998 Square D All Rights Reserved17
Power MeterBulletin No. 3020IM9503R6/98
Chapter 4—InstallationDecember 1998
DIN Rail Mounting
To mount the power meter onto 35 mm DIN rail, follow these steps:
DANGER
!
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.
Only qualified electrical workers should install and wire this equipment.
Perform such work only after reading this complete set of instructions.
Failure to observe these precautions will result in death or severe
personal injury!
1. Turn off all power supplying the equipment before working on it. Follow
all safety precautions.
2. Mount a piece of 35 mm DIN rail in the desired location. Note: The DIN railmust be horizontal. Position the power meter in front of and slightly above
the DIN rail (figure 4-4).
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
When mounting the power meter module, provide the following clearances
(from enclosure walls or other objects): terminal end: 4" (102 mm); vented
sides: 3" (76 mm). No clearance is necessary on the non-vented sides.
Failure to observe this precaution can result in equipment damage.
3. Slip the two DIN rail hooks, located on the power meter case, onto the
upper edge of the rail.
4. Rotate the power meter down and press it against the 35 mm DIN rail
until the power meter snaps into place.
18 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 4—Installation
DIN Rail Hooks
DIN Rail Clip
Side View
Side View
After Installation
DIN Rail
Figure 4-4: Mounting power meter on 35 mm DIN rail
1998 Square D All Rights Reserved19
Power MeterBulletin No. 3020IM9503R6/98
Chapter 4—InstallationDecember 1998
20 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 5—Wiring
CHAPTER 5—WIRING
DANGER
!
HAZARD OF PERSONAL INJURY OR DEATH.
Only qualified electrical workers should install and wire this equipment.
Such work should be performed only after reading this complete set of
instructions. Follow proper safety procedures regarding CT secondary
wiring. Never open circuit the secondary of a CT.
Failure to observe this precaution will result in death or severe
personal injury!
WIRING CTs, PTs, AND CONTROL POWER
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
External fusing (customer-supplied) is
required
for control power inputs.
Failure to observe this precaution can result in equipment damage.
The power meter supports a variety of 3-phase power system wiring
connections, including 3-wire delta, and 4-wire wye. Table 5-1 lists some
of the most widely used system connections. Additional system connections
are shown in Appendix D.
Table 5-1
System Connection Types
System TypeSys ID # CTs # PTs➀PT Conn.CurrentsVoltagesFigure #
3Ø, 3W Delta3020 or 2Open Delta A, B➁, CA-B, C-B, C-A
Calculated B5-4
3∅, 3W Delta3130 or 2Open Delta A, B, CA-B, C-B, C-A
Metered B Phase
➂
3∅, 4W Wye4030 or 3Wye-WyeA, B, C, N
A-N, B-N, C-N5-6,
A-B➃, B-C➃, C-A
➁
➁
5-3,
5-5
➃
5-7
➀ PTs not required at 600 volts (line-to-line) or below.
➁ Calculated.
➂ Calculated, PM-620 and PM-650.
➃ Line-to-line voltage in the 4-wire mode is calculated and fundamental only.
1998 Square D All Rights Reserved21
Power MeterBulletin No. 3020IM9503R6/98
Chapter 5—WiringDecember 1998
Control Power Transformer (CPT) Sizing
If you are using control power transformers (CPTs), refer to table 5-2 below. It
shows CPT sizing for various quantities of power meter modules.
Table 5-2
Control Power Transformer Sizing
Number ofSize of
Power Meter ModulesCPT
1–10100 VA
11–20150 VA
21–30200 VA
31–40250 VA
Control Power Fuses
The control power input(s) of each power meter module must be individually
fused under all circumstances. When using a control power transformer
where the secondary is 120 Vac, or when deriving control power from
metering potential transformers, use a standard 250 V, 100 mA, fast-acting
fuse. If control power is derived directly from the line voltage (600 V or less),
each power meter module control input must be fused using a 1/2 amp
Bussman FNQ-R fuse (or equivalent).
Metering Potential Transformers (PTs)
No potential transformers are required on the voltage metering inputs for
wye-connected and ungrounded delta circuits with line-to-line voltages of 600
V or less; connect the voltage metering inputs directly to the line voltages.
However, for power systems with voltages higher than 600 V line-to-line, or
corner-grounded delta circuits, potential transformers must be used. To set up
the appropriate voltage range, see page 50.
CE Compliance
To comply with CE Electromagnetic Compatibility Requirements, the power
meter must be installed in a metallic enclosure, i.e., switchgear. Install the
clamp-on ferrite provided in the hardware kit around all three control power
input leads close to the power meter (figure 5-1). To open the clamp-on ferrite
prior to installation, follow the instructions in figure 5-2.
For CE compliance, a Merlin Gerin Disconnect Breaker Type P25M #21104 or
IEC 947 equivalent must be connected directly to the metering voltage and
control power inputs (figure 5-1). Note: The disconnect switch must be placed
within reach of the power meter and labeled “Disconnect Switch for Power Meter.”
22 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 5—Wiring
Note: The disconnect
breaker
must
be
installed here
If control power is derived
from the metering voltage
source, no additional
disconnect device is
necessary.
However, if control
power is derived from
a separate source (
not
jumpered from
metering voltage as
shown), an
additional
disconnect breaker
must
be installed here
between the control
power terminals and the
control power source
(See inset box at right
for detail of additional
disconnect breaker.)
Metering Voltage Source
Disconnect
Breaker
Clamp-On
Ferrite
KYZ
Voltage
Control
Power
L
1
L
2
Current
Display
Comms
Port
Comms
Note: See figures 5-3 through 5-8 for possible system connections.
Figure 5-1: Clamp-on ferrite and disconnect breaker for CE compliance (4-wire system shown)
2
1
To open the clamp-on ferrite prior to installation, follow these steps:
1. Using a small screwdriver or similar device, gently pry open the ferrite case at
location ➀ above.
2. Flip open the top of the ferrite case in the direction shown (➁).
3. After routing control leads through the middle of the ferrite, snap the ferrite
case closed; make sure you do not crimp the control wires when closing
the ferrite case.
Figure 5-2: Opening the clamp-on ferrite
1998 Square D All Rights Reserved23
Power MeterBulletin No. 3020IM9503R6/98
Chapter 5—WiringDecember 1998
AØ
BØ
Line
CØ
VDS
Fuses
Top
Voltage
Load
KYZ
Control
Power
Comms
Current
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L or an external
source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
90–300 Vdc
Installation Category II
For ungrounded delta systems only.
Figure 5-3: 3-phase, 3-wire delta direct voltage connection with 2 CTs
24 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 5—Wiring
AØ
Line
BØ
CØ
Load
CDS
Fuse
VDS
Fuses
Fuses
CPT
(120 or 240 Vac
Secondary,10 VA)
Comms
Fuses
Voltage
Control
Power
Current
Open Delta
PT Connection
(120 V Secondaries)
Top
KYZ
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L or an external
source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
Installation Category II
Figure 5-4: 3-phase, 3-wire delta with 2 PTs and 2 CTs
90–300 Vdc
1998 Square D All Rights Reserved25
Power MeterBulletin No. 3020IM9503R6/98
Chapter 5—WiringDecember 1998
AØ
BØ
Line
CØ
Load
CDS
Fuse
VDS
Fuses
CPT
(120 or 240 Vac
Secondary, 10 VA)
Comms
Fuses
Voltage
Control
Power
Current
Open Delta
PT Connection
(120 V L-N
Secondaries)Fuses
Top
KYZ
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L or an external
source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
Installation Category II
Figure 5-5: 3-phase, 3-wire delta with 2 PTs and 3 CTs
26 1998 Square D All Rights Reserved
90–300 Vdc
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 5—Wiring
AØ
Line
BØ
CØ
Load
N
VDS
Fuses
Top
KYZ
Voltage
Control
Power
Comms
Current
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L, or L-N, or an
external source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
Installation Category II
Figure 5-6: 3-phase, 4-wire wye, ground and direct voltage connection, with 3 CTs
90–300 Vdc
1998 Square D All Rights Reserved27
Power MeterBulletin No. 3020IM9503R6/98
Chapter 5—WiringDecember 1998
AØ
BØ
Line
CØ
N
Load
CDS
Fuse
Fuse
VDS
Fuses
CPT
(120 or 240 Vac
Secondary , 10 VA)
Comms
Fuses
Top
Voltage
Control
Power
Current
Wye PT
Connection
(120 V L-N
Secondaries)
KYZ
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L, or L-N, or an
external source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
Installation Category II
Figure 5-7: 3-phase, 4-wire wye, ground connection, with 3 PTs and 3 CTs
28 1998 Square D All Rights Reserved
90–300 Vdc
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 5—Wiring
Top
KYZ
Voltage
DC Control
Power 125/250
Vdc Nominal
Control
Power
Comms
Current
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L, or L-N, or an
external source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
90–300 Vdc
Installation Category II
Figure 5-8: DC control power wiring
1998 Square D All Rights Reserved29
Power MeterBulletin No. 3020IM9503R6/98
Chapter 5—WiringDecember 1998
Typical power meter module wire routing is shown in figure 5-9 below.
➀
➂
➁
➀ 3-Phase Voltage Inputs
➁ Control Power Terminals
➂ KYZ Output
➃ 3-Phase Current Inputs
➄ Communications Connection
to Display
➅ RS-485 Communications Terminals
Figure 5-9: Power meter wire routing
!
HAZARD OF ELECTRICAL SHOCK, BURN, OR EXPLOSION.
• Before removing the terminal shield or making connections, turn off
all power supplying this equipment.
• Refer to the terminal identifications label on the terminal shield for
proper wiring polarities.
➅
➃
DANGER
➃
➄
• Refer to page 22 for CPT and fuse recommendations.
• Snap terminal shield into closed position before turning power on.
Failure to observe these precautions will result in death or severe
personal injury!
To wire the power meter, follow these steps:
1. Strip 0.25" (6 mm) of insulation from the end of all wires. Using a suitable
crimping tool, attach the spade connectors (in hardware kit) to the voltage
and current input wires (up to 12 AWG) as shown in figure 5-9.
30 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 5—Wiring
2. Connect the spade connectors to the 3-phase voltage input terminals
(➀, figure 5-9) and the 3-phase current input terminals (➃, figure 5-9).
Tighten the terminal block screws to 9 lb-in (1.0 N•m).
3. Insert 14 AWG control power wires into the control power terminal block
as shown in figure 5-9. Derive control power from one of these sources:
– a stable ac source
– phase voltage inputs
– dc power source
Tighten terminal screws to 4 lb-in (0.45 N•m).
4. Ground the power meter. See Grounding the Power Meter in this chapter
for instructions.
5. If all wiring is complete, snap the terminal shield into the closed position.
CAUTION
!
HAZARD OF EQUIPMENT DAMAGE.
External fusing is required when bringing line voltages to the power
meter or other metering device.
Failure to observe this precaution can result in equipment damage.
Deriving Control Power from Phase Voltage Inputs
Whenever possible, derive power meter control power from a stable voltage
source. If such a source is unavailable, the power meter can derive control
power from the metered circuit up to 600 V, or from its phase PT inputs. Due
to the wide range of permissible control power inputs, the power meter can
accept either L-N or L-L control power inputs up to 600 V.
DANGER
!
HAZARD OF ELECTRICAL SHOCK, BURN, OR EXPLOSION.
• Turn off all power supplying this equipment before opening the
terminal shield or making connections.
• Snap terminal shield into closed position before turning power on.
Failure to observe these precautions will result in death or severe
personal injury!
1998 Square D All Rights Reserved31
Power MeterBulletin No. 3020IM9503R6/98
Chapter 5—WiringDecember 1998
Note: Before wiring, see fuse recommendations on page 22.
Follow these steps to derive control power from phase PT inputs:
1. Connect the Va terminal (terminal 9) to the L1 terminal (terminal 6).
2. For L-N control power (see figure 5-6, page 27), connect the Vn terminal
(terminal 12) to the L2 terminal (terminal 7). For L-L control power (see
figure 5-3, page 24), connect the Vb terminal (terminal 10) to the L2
terminal (terminal 7).
3. If all wiring is complete, snap the terminal shield into the closed position.
GROUNDING THE POWER METER
For optimal grounding, connect the power meter to a true earth ground.
To ground the power meter, follow these steps:
1. Connect the ground terminal (terminal 8) to a true earth ground, using
#14 AWG wire.
2. After grounding, snap the terminal shield into the closed position.
Note: The power meter must be grounded as described in these instructions.
Failure to properly ground the power meter may induce noise on the power
conductor.
32 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 5—Wiring
SOLID-STATE KYZ PULSE OUTPUT
DANGER
!
HAZARD OF ELECTRICAL SHOCK, BURN, OR EXPLOSION.
• Turn off all power supplying this equipment before opening the
terminal shield or making connections.
• Snap terminal shield into closed position before turning power on.
Failure to observe these precautions will result in death or severe
personal injury!
The KYZ output can be wired to a 2-wire or 3-wire pulse receiver. To wire
to a 2-wire pulse receiver, use the K and Y terminals only (figure 5-10). When
wiring the KYZ pulse output, use 14 to 18 AWG wire. Strip 0.25" (6 mm) of
insulation from the end of each wire being connected to the KYZ connector.
Insert the wires into the KYZ output terminal block. Tighten the terminal
block screws to 5–7 lb-in (0.56–0.79 N•m).
Note: Set up the KYZ by using either the Setup mode on the power meter display or
the setup screen in SMS-3000, SMS-1500, or PMX-1500 software. See page 65 for
instructions for determining the pulse constant.
19
K
Y
Z
K
Y
Z
20
21
19
20
21
2-Wire Pulse
Receiver
3-Wire Pulse
Receiver
Figure 5-10: KYZ pulse output
1998 Square D All Rights Reserved33
Power MeterBulletin No. 3020IM9503R6/98
Chapter 5—WiringDecember 1998
For the PM-650 only, the KYZ output can also be wired as an alarm contact
(figure 5-11). When wiring the KYZ output, use 14 to 18 AWG wire. Strip 0.25"
(6 mm) of insulation from the end of each wire being connected to the KYZ
connector. Insert the wires into the KYZ output terminal block. Tighten the
terminal block screws to 5–7 lb-in (0.56–0.79 N•m).
120 Vac
10 A Fuse
Load
Load
Figure 5-11: Typical KYZ output connection for use as an alarm contact
L
N
N
34 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 6—Communications
CHAPTER 6—COMMUNICATIONS
PROTOCOLS
POWERLOGIC Power Meters can communicate using three different protocols:
• POWERLOGIC
• Modbus
• Jbus
During setup, select which protocol will be used.
Descriptions of the connections that can be used with each protocol follow.
Note: For 2-wire Modbus and Jbus information, see Appendix H—2-Wire Modbus
and Jbus.
POWERLOGIC PROTOCOL COMMUNICATIONS WIRING
POWERLOGIC devices are equipped with RS-485 communications. You can
daisychain up to 32 POWERLOGIC (or Power Monitoring and Control
System [PM&CS]) compatible devices to a single communications port. This
document refers to a chain of PM&CS devices connected by communications
cable as a communications link.
A PM&CS communications link can consist of up to 32 PM&CS-compatible
devices connected to a communications port on one of the following:
• Personal computer
• POWERLOGIC Network Interface Module (PNIM)
• SY/MAX programmable controller
• POWERLOGIC Ethernet Gateway
• Other host devices with a POWERLOGIC-compatible port
Figures 6-1 through 6-3 show power meters (other PM&CS-compatible
devices can be substituted) connected in typical systems. The accompanying
text describes important considerations for each connection alternative.
The figures also show the placement of communications adapters and
terminators. For additional information on using the communications adapter
and terminator, see Terminating the Communications Link, and Biasing theCommunications Link in this chapter.
1998 Square D All Rights Reserved35
Power MeterBulletin No. 3020IM9503R6/98
Chapter 6—CommunicationsDecember 1998
Connecting to a Personal Computer via POWERLOGIC Communications
•Connect up to 32 PM&CS devices to a personal computer (figure
6-1). See Length of the Communications Link in this chapter for distance
limitations at varying baud rates.
•PM&CS devices can be connected to a SY/LINK card installed in the
personal computer. To do this, connect the PM&CS devices to the
RS-422 port (female DB-9 connector) of the SY/LINK card.
•PM&CS devices can be connected to a serial communications port on the
personal computer. To do this, the PM&CS devices must be connected to
an RS-232-to-RS-422/RS-485 converter, which is connected to the personal
computer. POWERLOGIC offers a converter kit for this purpose (Class
3090 Type MCI-101; refer to the instruction bulletin included with the
MCI-101 for connection instructions).
Remote PC
MCTAS-485
(or MCT-485
with Terminal
Block)
1–32 Devices (Power Meters and Other Power
Monitoring & Control System Compatible Devices)
Belden 8723
(or equivalent)
Figure 6-1: Power meters connected to a personal computer via SY/LINK card
Connected to
RS-422 Port
of SY/LINK Card
MCA-485
CAB-107
36 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 6—Communications
Connecting to a POWERLOGIC Network Interface Module (PNIM)
Using POWERLOGIC Communications
•Connect up to 32 PM&CS devices to a PNIM. See Length of the Communications Link in this chapter for distance limitations at different baud rates.
•Connect PM&CS devices to PNIM port 0 (top RS-485 port) only.
•Configure PNIM port 0 for “POWERLOGIC” mode (see side of PNIM for
instructions on setting dip switches).
•Configure the baud rate of PNIM port 0 to match the baud rate of the
PM&CS devices on the communications link.
• Refer to the PNIM instruction bulletin for detailed instructions on
configuring the PNIM.
PNIM
SY/MAX
CLASS 8030
TYPE CRM-565
NETWORK
R x Ø
T x Ø
R x 1
T x 1
NET RxERROR
NET TxERROR
POWER
NETWORK
INTERFACE
NUMBER
——
2
8
NETWORK
INTERFACE
NUMBER
Ø1 —
C
O
M
M
1——
C
O
M
M
SY/NET
NETWORK
INTERFACE
SY/NET
PC with SY/LINK Card
MCTAS-485
(or MCT-485
with Terminal
Block)
Belden 8723
(or equivalent)
Only Connect
Power Meters
to Top Port (Port 0)
of PNIM
MCA-485
CAB-107
(Belden 9463 or equivalent)
1–32 Devices (Power Meters and Other Power
Monitoring & Control System Compatible Devices)
Figure 6-2: Power meters connected to a PNIM
1998 Square D All Rights Reserved37
Power MeterBulletin No. 3020IM9503R6/98
Chapter 6—CommunicationsDecember 1998
Connecting to a SY/MAX Programmable Controller
Using POWERLOGIC Communications
•Connect up to 32 PM&CS devices to a programmable controller. See
Length of the Communications Link in this chapter for distance limitations at different baud rates.
•Connect PM&CS devices to the RS-422 port of the programmable
controller.
•The programmable controller must contain a program to access
POWERLOGIC device data.
•Configure the baud rate of the programmable controller’s port to match
the baud rate of the POWERLOGIC devices on the communications link.
•Refer to the programmable controller instruction manual for detailed
instructions on configuring the programmable controller.
Note: PM&CS devices can be connected to other manufacturers’ systems using
available communication interfaces. For further information, contact the
POWERLOGIC Technical Support Center.
MCTAS-485
(or MCT-485
with Terminal
Block)
1–32 Devices (Power Meters and Other Power
Monitoring & Control System Compatible Devices)
Belden 8723
(or equivalent)
Connect Power Meters
to RS-422 Port of
Programmable
Controller
MCA-485
CAB-107
Programmable
Controller
SY/MAX
400
MODEL
PROCESSOR
RUN
HALT
MEMORY
FORCE
I/O
BATTERY
LOW
WRITE
PROTECT
BATTERY
INSTALLED
DATE
RUN
PROGRAM
RUN
HALT
DISABLE
OUTPUTS
PRGMR
CHNL 1
COMM
CHNL 2
Figure 6-3: Power meters connected to a SY/MAX programmable controller
38 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 6—Communications
MODBUS RTU PROTOCOL
Alternately, power meters can communicate using the Modbus RTU protocol.
Using 4-wire Modbus, you can daisychain up to 32 power meters to a single
communications port. When using 2-wire Modbus communications, a
maximum of 16 power meters can be daisychained to a single communication
port.
Note: See Appendix H for 2-wire Modbus wiring and distance limits.
A power meter Modbus communications link can be connected to a communications port on any of the following:
•personal computer
•Modicon programmable controller
•other host devices with a Modbus-compatible port
JBUS PROTOCOL
Jbus is the third protocol by which power meters can communicate. When
using 4-wire Jbus, up to 32 power meters can be daisychained from a single
communications port. For 2-wire Jbus, a maximum of 16 power meters can be
daisychained.
Note: See Appendix H for 2-wire Jbus wiring and distance limits.
You can connect a power meter Jbus communications link to any host device
with a Jbus-compatible port.
1998 Square D All Rights Reserved39
Power MeterBulletin No. 3020IM9503R6/98
Chapter 6—CommunicationsDecember 1998
CONNECTING TO A PC USING MODBUS OR JBUS COMMUNICATIONS
• Connect up to 32 Modbus or Jbus devices to a personal computer (figure
6-4). See Length of the Communications Link in this chapter for distance
limitations at varying baud rates.
• Power meters configured for Modbus or Jbus can be connected to a serial
communications port on the personal computer. To do this, the power
meters must be connected to an RS-232-to-RS-422/RS-485 converter, which
is connected to the personal computer. POWERLOGIC offers a converter
kit for this purpose (Class 3090 Type MCI-101; refer to the instruction
bulletin included with the MCI-101 for connection instructions).
MCTAS-485
(or MCT-485
with
Terminal
Block)
Belden 8723
(or equivalent)
MCA-485
RS-232/
RS-485
Converter
1–32 Devices (Power Meters and
Other Modbus- or Jbus-Compatible Devices)
Figure 6-4: Power meters connected to a personal computer via serial port
CAB-108
CAB-104
Modbus Host
40 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 6—Communications
LENGTH OF THE COMMUNICATIONS LINK (POWERLOGIC, MODBUS, OR JBUS)
The length of the communications link cannot exceed 10,000 feet (3,048 m).
This means that the total length of the communications cable from the PNIM,
personal computer, or PLC, to the last device in the daisychain, cannot exceed
10,000 feet. The maximum distance may be shorter, depending on the baud
rate. Table 6-1 shows the maximum distances at different baud rates.
Table 6-1
Maximum Distances of Comms Link at Different Baud Rates
Baud
Rate
120010,000 ft. (3,048 m)10,000 ft. (3,048 m)
240010,000 ft. (3,048 m)5,000 ft. (1,524 m)
480010,000 ft. (3,048 m)5,000 ft. (1,524 m)
960010,000 ft. (3,048 m)4,000 ft. (1,219 m)
192005,080 ft. (1,548 m)2,500 ft. (762 m)
1–16 devices17–32 devices
Maximum Distances
Note: See Appendix H for 2-wire Modbus and Jbus wiring distance limits.
DAISYCHAINING PM&CS DEVICES (POWERLOGIC, MODBUS, OR JBUS)
Note: To daisychain the power meter with other PM&CS, Modbus, or Jbus devices, use
a communications cable containing two twisted-shielded pairs (Belden 8723 or
equivalent). Strip back the cable sheath 2" (51 mm) on each end of the cable, and strip
back the insulation 0.25" (6 mm) from the end of each wire. Then follow daisychaining
instructions in this section. Torque terminal block screws to 5–7 lb-in (0.56–0.79 N•m).
Each communicating power meter has a 5-position plug-in RS-485 terminal
block for connection to a PM&CS, Modbus, or Jbus communications link. On
all PM&CS devices, the terminals are labeled IN+, IN-, OUT+, OUT-, and
SHLD. On the power meter, the IN+, IN-, OUT+, OUT-, and SHLD terminals
are numbered 5, 4, 3, 2, and 1, respectively.
To daisychain a power meter to another PM&CS, Modbus, or Jbus device,
wire the power meter’s RS-485 communications terminals to the matching
communications terminals of the next device (wire the IN+ terminal of the
power meter to the IN+ terminal of the next device, wire IN- to IN-, OUT+ to
OUT+, OUT- to OUT-, and SHLD to SHLD). See figure 6-5.
If the power meter is the last device on the daisychain, use a terminator at the
end of the link. See Terminating the Communications Link in this chapter
for instructions. If the power meter is the first device on the daisychain,
connect it to the PNIM, personal computer, or programmable controller using
a CAB-107 or equivalent cable and a Multipoint Communications Adapter.
See Biasing the Communications Link in this chapter for instructions. See
Appendix C for the CAB-107 pinout.
1998 Square D All Rights Reserved41
Power MeterBulletin No. 3020IM9503R6/98
tible Devi
tible Devi
tible Devi
Chapter 6—CommunicationsDecember 1998
To RS-485
Terminals of
Next Device
Power Meter
or Other PM&CS-
Compatible, Modbus,
or Jbus Device
ce
IN+
IN+
IN-
IN–
OUT+
OUT+
OUT-
OUT–
SHLD
SHLD
Power Meter
or Other PM&CS-
Compatible, Modbus,
compa
or Jbus Device
cecompa
IN+
IN+
IN-
IN–
OUT+
OUT+
OUT-
OUT–
SHLD
SHLD
Power Meter
or Other PM&CS-
Compatible, Modbus,
or Jbus Device
cecompa
IN+
IN+
IN-
IN–
OUT+
OUT+
OUT-
OUT–
SHLD
SHLD
To RS-485
Terminals of
Next Device
Belden 8723 (or equivalent) Comms Wire
(two twisted pairs with shield)
Figure 6-5: Daisychaining the RS-485 communications terminals
BIASING THE COMMUNICATIONS LINK (POWERLOGIC, MODBUS, OR JBUS)
For proper RS-485 communications performance, the communications link
must be biased (figure 6-6) using a POWERLOGIC Multipoint Communications Adapter (Class 3090 Type MCA-485). The adapter is placed between the
first device on the link and the communications port of a PNIM, SY/LINK
card, or other host device.
Power Meter
Belden 8723
IN+
➄
IN–
➃
OUT+
➂
OUT–
➁
SHLD
➀
Green
White
Red
Blue
Shield
IN+
IN–
OUT+
OUT–
SHLD
20
21
22
23
24
CAB-107
MCA-485
RS-485
Terminals
5-Position
Terminal Block
Figure 6-6: Connecting the power meter as the first
device on a PM&CS or Modbus communications link
To bias the communications link, refer to figure 6-6 and follow these steps:
1. Install the 5-position terminal block in a convenient location.
Note: The CAB-107 cable is 10 feet (3 m) long. If the terminal block must be
located farther than 10 feet from the host device, build a custom cable using Belden
8723 cable and a male DB-9 connector. See the CAB-107 pinout, page 74.
2. Plug the male end of the Multipoint Communications Adapter (MCA-485)
into the communications port of the PNIM, SY/LINK board, or other host
device.
To Comm
Port of
Host Device
Note: When connecting to a PNIM, connect the power meter to the top RS-422
port, labeled port 0. This port must be configured for POWERLOGIC mode.
42 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 6—Communications
3. Carefully mark the flying leads on the CAB-107 as indicated in table 6-2
below. For example, mark the green wire, labeled 20, as “IN+”; mark the
white wire, labeled 21, as “IN–”; and so on.
4. Attach the male DB-9 connector on the CAB-107 to the multipoint
communications adapter.
5. Connect the CAB-107 spade connectors to the 5-position terminal block.
See figure 6-8, page 45, for terminal identification.
6. Cut a length of Belden 8723 (or equivalent) cable that is long enough to
reach from the terminal block to the first power meter. Strip back the
cable sheath 1-1/4" (32 mm) from both ends.
7. On one end of the Belden 8723 (or equivalent) cable, carefully strip .25"
(6 mm) of insulation from the end of each wire to be connected. Using a
suitable crimping tool, securely attach a forked terminal (spade connector) to each wire.
8. Connect the cable end with attached spade connectors to the terminal
block. See figure 6-8, page 45, for terminal identification. Tighten all
terminal screws to 6–9 lb-in (0.68–1 N•m).
9. On the other cable end, carefully strip .4"–.45" (10–11 mm) of insulation
from the end of each wire to be connected.
10. Connect this end of the Belden 8723 (or equivalent) cable to the power
meter RS-485 terminals; see figure 6-8, page 45, for communications
terminal identification.
Be sure to connect the terminal accepting the IN–
wire on the CAB-107 to the IN– terminal on the power meter, the terminal
accepting the IN+ wire on the CAB-107 to the IN+ terminal on the power
meter,
and so on. Tighten the RS-485 terminal screws to 5–7 lb-in
(0.56–0.79 N•m).
Note: An alternative to using a terminal block and a CAB-107 is to build a
custom cable using Belden 8723 cable (or equivalent) and a male DB-9 connector.
When building a cable, follow the CAB-107 pinout shown in Appendix C.
1998 Square D All Rights Reserved43
Power MeterBulletin No. 3020IM9503R6/98
Chapter 6—CommunicationsDecember 1998
Terminating the Communications Link (POWERLOGIC, Modbus, or Jbus)
For proper RS-485 communications performance, terminate the last device on
a PM&CS or Modbus communications link. To terminate the last device, use a
POWERLOGIC Multipoint Communications Terminator.
Terminate the power meter using one of the following methods:
•MCTAS-485. This terminator plugs directly into the power meter communications port (RS-485 terminals in figure 6-7 below).
•Terminal block and MCT-485. In this method, communications wires route
from the last power meter on a daisychain to a 5-position terminal block. A
terminator attaches to the terminal block. See figure 6-8.
Figures 6-1 to 6-4 show the terminator applied in typical systems.
Power Meter
(If Last Device in Daisychain)
MCTAS-485
In+
In–
Out+
Out–
Shield
RS-485
Terminals
To Next Device on Daisychain
Belden 8723
Figure 6-7: Terminating power meter with MCTAS-485
44 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 6—Communications
Terminal Block
Power Meter
(If Last Device in Daisychain)
In+
In–
Out+
Out–
Shield
MCT-485
In+
RS-485
Terminals
In–
Out+
Out–
Shield
Belden 8723
To Next Device on Daisychain
Figure 6-8: Terminating power meter with terminal block and MCT-485
1998 Square D All Rights Reserved45
Power MeterBulletin No. 3020IM9503R6/98
Chapter 6—CommunicationsDecember 1998
46 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 7—Display Operation
CHAPTER 7—DISPLAY OPERATION
INTRODUCTION
This chapter tells how to set up the power meter from the display only. You
can also set up the power meter using POWERLOGIC SMS-3000, SMS-1500,
or PMX-1500 software. Refer to the software instruction bulletin(s) for specific
instructions.
MODES
The power meter has the following modes. Each mode is detailed in
this section.
•Summary
•Power
•Energy
•Demand
•Power Quality
•Min/Max
•Alarm Setup
•Alarm Log
➀
➀
➁
➁
➁
•Setup
•Resets
•Diagnostics
➀ PM-620 and PM-650.
➁ PM-650 only.
1998 Square D All Rights Reserved47
Power MeterBulletin No. 3020IM9503R6/98
Chapter 7—Display OperationDecember 1998
Accessing a Mode
To access a mode, refer to figure 7-1 while following these steps:
1. Press the Mode button until the desired mode appears (➀, figure 7-1).
2. Press Select to enter the desired mode.
3. For Setup, Resets, Diagnostics, Alarm Log**, or Alarm Setup** modes,
press the Select button to select a field (➁), and move through screens in
that mode.
For Summary, Power, Energy, Demand*, Power Quality* (PQ), and
Min/Max** modes, press Select to enter a display mode, then use the arrow
buttons to move through the display screens (➂).
➡
➀
➡
Setup
Resets
Diagnostics
Summary
Power
Energy
Demand
Power Quality*
Min/Max**
Alarm Setup**
Alarm Log**
➁
▼
➁
▼
➁
▼
➂
▼
Figure 7-1: Navigating power meter parameters
➂
▼
➂
▼
➂➂
▼
▼
➂
▼
➁
▼
➁
* PM-620 and PM-650.
** PM-650 only.
48 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 7—Display Operation
Setup Mode
The Setup mode lets you configure the following parameters:
•Protocol
•Device Address
•Baud Rate
•Parity (even or none)
•CT Primary
•CT Secondary
•Voltage Range
•PT Primary
•PT Secondary
•System Type
•Frequency
•Power Demand Interval
➀
•KYZ Mode
•Pulse Constant
•THD/thd
➁
➀
You can also set the date➀, time➀, master password, and reset password.
➀ PM-620 and PM-650.
➁ The pulse constant parameter is displayed only when the KYZ mode is enabled (KWH, KVAH, or KVARH
energy mode).
1998 Square D All Rights Reserved49
Power MeterBulletin No. 3020IM9503R6/98
Chapter 7—Display OperationDecember 1998
Note: Because the power meter can directly meter up to 600 V line-to-line without
using potential transformers, you must specify the appropriate voltage range during
the setup procedure. To determine what voltage range to enter during setup, find your
system voltage in table 7-1 below. Enter the corresponding voltage range.
If your specific system voltage is not listed, use the next highest voltage range. If your
system voltage is greater than 600 V
or 347 V
L-L
, then you must use PTs and
L-N
select 208/120 V as the voltage range.
Table 7-1
Selecting Voltage Ranges for System Types
System Voltage
4-wire:
208/120 V208/120 V
480/ 277 V480/277 V
600/347 V600/347 V
>600/347 V208/120 V with PTs ➀
3-wire (Delta)➁:
➀ Note: Set PT ratios.
➁ For 3Ø, 3-wire delta corner-grounded applications, install two line-to-line rated PTs. Set the
voltage range to 208/120 V with PTs.
Resets Mode
The Resets mode allows you to reset energy, demand
values
➃
Set Power Meter
Voltage Range To:
240 V480/277 V
480 V480/277 V
600 V600/347 V
>600 V208/120 V with PTs ➀
➂
, and min/max
. See Performing Resets, page 54, for more information.
Diagnostics Mode
The Diagnostics mode displays the model number and serial number of your
power meter, as well as firmware versions and a read-only register interface.
For more information, see Viewing Diagnostic Information, page 55.
Display Modes
The display modes—Summary, Power, Energy, Demand
and Min/Max
➂ PM-620 and PM-650.
➃ PM-650 only.
➃
—each display information indicated by their titles.
50 1998 Square D All Rights Reserved
➂
, Power Quality➂,
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 7—Display Operation
How the Buttons Work
The buttons on the power meter display (figure 7-2) function differently in
Setup, Resets, Diagnostics, Alarm Log➀, and Alarm Setup➀ than they do in
the display modes.
Mode
Button
This button lets you scroll through available modes. You can also use this
button to exit a mode after making all desired changes. For example, after
making all desired changes in Setup mode, press the Mode button. The power
meter then prompts you to accept or reject your changes.
Arrow Buttons
Use these buttons to increase or decrease the displayed parameter. Also, use
these buttons to toggle between Yes and No when required.
Select
Button
This button allows you to enter a selected mode and scroll through fields
within that mode. Also use this button as an “Enter” key to accept a new
configuration value and move to the next field.
Mode
Figure 7-2: Power meter display buttons
Select
Contrast Button
This button allows you to adjust the contrast of the display screen.
➀ PM-650 only.
1998 Square D All Rights Reserved51
Power MeterBulletin No. 3020IM9503R6/98
Chapter 7—Display OperationDecember 1998
SETTING UP THE POWER METER
To set up the power meter, follow these steps:
1. Press the Mode button until “Mode: Setup” is displayed on the screen.
2. Press the Select button. At the “Enter Password“ prompt, press the up
arrow button once to enter the default password 0 (if you have set up a
different password, use that instead).
3. Press Select until the desired setup parameter is displayed. Change the
value using the up and down arrow buttons.
4.
Repeat step 3 until all desired changes are made. Table 7-2 below shows setup
parameters, the factory default for each, and the allowable range of values.
5. After making all desired changes, press the Mode button. The display reads
“Save Changes? NO.”
6. To reject changes, press the Select button once.
7. To accept changes, press an arrow button to change from “NO” to “YES.”
Then press the Select button.
8. The power meter accepts the setup changes and restarts.
Table 7-2
Factory Defaults for Power Meter Setup Parameters
ParameterAllowed ValuesDefault
ProtocolPOWERLOGIC,POWERLOGIC
Modbus, or JBus
Network Address0 to 1991
Baud Rate1200–192009600
Parityeven, noneeven
CT Primary (3-Phase)1 to 32,7675
CT Secondary1, 55
Voltage Range ➀208/120 V,208/120 V
480/277 V,
600/347 V
PT Primary
3-Phase1 to 1,700,000120
PT Secondary100, 110, 115, 120120
System Type40, 4-wire;40, 4-wire
31, 3-wire (3 CT);
30, 3-wire (2 CT)
Frequency (Nominal)50, 60 Hz60 Hz
Demand Interval (Power) ➁1 to 60 min.15
KYZ ModekWH,kWH
KYZ Disabled ➂,
kVAH,
kVARH
Alarm Mode ➃
Pulse Constant
(WH/Pulse Output [KVARH, KVAH])0 to 327.67 kWH0
THD ➁THD (United States)THD (United States)
thd (European)
Password (Master and Reset)0 to 99980
➀ See note on voltage range selection, page 50.
➁ PM-620 and PM-650.
➂ PM-600 and PM-620.
➃ PM-650 only.
52 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 7—Display Operation
Start
Press the
button until “Setup”
is displayed.
Select
choose Setup.
Use the arrow
buttons to display the
password. Then press
the
Press the
to move to the parameter
to be changed.
Use the arrow
buttons to change
Mode
Press the
button to
Select
button.
Select
the value.
button
Do you want
to change
another
parameter?
NO
Press the
button once.
Do you want
the changes?
Mode
to accept
YES
Press
arrow ▲ button.
Press the
Select
button.
Power Meter accepts
changes and restarts.
YES
NO
Press the
Select
button.
Display returns
to mode list.
Figure 7-3: Power meter setup flowchart
1998 Square D All Rights Reserved53
Power MeterBulletin No. 3020IM9503R6/98
Chapter 7—Display OperationDecember 1998
PERFORMING RESETS
➀
To reset energy, demand
, and min/max➁ values using the display, follow
these steps:
1. Press the Mode button until “Resets” is displayed.
2. Press the Select button to enter the Resets mode. The display shows the
password prompt.
3. Use the arrow buttons to enter the Reset Password; press the Select button.
4. Press the Select button to find the value you want to reset.
5. Press either arrow key to change from “no” to “yes.”
6. Repeat steps 4 and 5 until all desired resets have been made.
7. After enabling all desired resets, press the Mode button. The display reads
“RESET NOW? NO.”
8. To reject resets, press the Select button once.
9. To accept resets, press either arrow button to change “NO” to “YES.”
Then press the Select button. You’ll see a brief message: “Resetting, Please
Wait…” as the changes are made.
➀ Demand values available on models PM-620 and PM-650.
➁ Min/max values available on model PM-650 only.
54 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 7—Display Operation
VIEWING DIAGNOSTIC INFORMATION
To view diagnostic information via the display, follow these steps:
1. Press the Mode button until “Diagnostics” is displayed.
2. Press the Select button to enter the Diagnostics mode. As you continue to
press the Select button, you’ll scroll through these screens: Model Number,
Serial Number, and four F/W (firmware operating) Version screens.
3. Press the Select button again to go into the register read-only screen.
4. Press the arrow keys to scroll through available registers.
5. Press the Modes button to return to the modes list.
Refer to Appendix F—Register List for additional register information.
USING DISPLAY MODES
The general procedure for displaying data is as follows:
1. Press the Mode button to scroll to one of the six available display modes
➀
(Summary, Power, Energy, Demand
, Power Quality➀, or Min/Max➁).
2. Press the Select button to select a mode.
3. Press arrow buttons to scroll through metered values.
SETTING UP ONBOARD ALARMS (PM-650 ONLY)
To set up alarming via the display, follow these steps:
1. Press the Mode button until “Alarm Setup” is displayed.
2. Press the Select button to enter the Alarm Setup mode. The display shows
the password prompt.
3. Use the arrow buttons to enter the password (factory default = 0); press the
Select button.
4. Use the arrow keys to scroll through the available alarms. When you reach
the desired alarm, press the Select button.
5. Press either arrow key to change from “Disabled” to “Enabled”; press the
Select button.
6. The display shows the appropriate scale factor for the pickup value.
Multiply the desired pickup value by the scale factor shown on the screen
(see Scaling Alarm Setpoints in Appendix I—Alarm Setup for an
explanation of scale factors); press the Select button.
7. Use the arrow keys to increase or decrease the displayed value until the
desired scaled pickup value is reached; press the Select button.
➀ PM-620 and PM-650.
➁ PM-650 only.
1998 Square D All Rights Reserved55
Power MeterBulletin No. 3020IM9503R6/98
Chapter 7—Display OperationDecember 1998
8. Use the arrow keys to increase or decrease the displayed value until the
desired pickup delay is reached; press the Select button.
9. The display shows the appropriate scale factor for the dropout value.
Multiply the desired dropout value by the scale factor shown on the
screen; press the Select button.
10. Use the arrow keys to increase or decrease the displayed value until the
desired scaled dropout value is reached; press the Select button.
11. Use the arrow keys to increase or decrease the displayed value until the
desired dropout delay is reached; press the Select button.
12. Use the arrow keys to select either “Output: Enabled” or “Output:
Disabled”; press the Select button.
Note: The output selection is not available if the KYZ output has been enabled in
the Setup mode.
13. Repeat steps 4–12 above for each additional alarm that you’d like to set
up.
14. Press the Mode button.
15. To save the changes you’ve just made, press the up arrow button to
change from “No” to “Yes.” Then press the Select button.
To discard the changes, press the Select button while “No” is displayed.
The Power Meter will reset.
VIEWING ACTIVE ALARMS (PM-650 ONLY)
To view the active alarms, follow these steps:
1. Press the Mode button until “Alarm Log” is displayed.
2. Press the Select button to enter the alarm log.
3. Use the arrow keys to scroll through the alarms. The last 10 alarms are
listed, starting with the most recent alarm. Alarms that are currently active
will flash. To acknowledge the alarms, press the Mode key.
4. Use the arrow keys to change from “No” to “Yes.”
5. Press the Select button. The screen will flash “Acknowledging Alarms.”
The Power Meter returns to “Alarm Log” mode.
56 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 8—Metering Capabilities
CHAPTER 8—METERING CAPABILITIES
REAL-TIME READINGS
The power meter measures currents and voltages and reports rms values
for all three phases and a calculated neutral current➀. In addition, the power
meter calculates true power factor, real power, reactive power, and more.
Table 8-1 lists the real-time readings and their reportable ranges.
Table 8-1
Real-Time Readings
Real-Time ReadingReportable Range
Current
Per-Phase0 to 32,767 A
Neutral ➀0 to 32,767 A
Voltage
Line-to-Line, Per-Phase0 to 3,276,700 V
Line-to-Neutral, Per-Phase0 to 3,276,700 V
Real Power
3-Phase Total0 to +/- 3,276.70 MW
Per-Phase0 to +/- 3,276.70 MW
Reactive Power
3-Phase Total0 to +/- 3,276.70 MVAr
Per-Phase0 to +/- 3,276.70 MVAr
Apparent Power
3-Phase Total0 to 3,276.70 MVA
Per-Phase0 to 3,276.70 MVA
Power Factor (True)
3-Phase Total–0.200 to 1.000 to +0.200
Per-Phase–0.200 to 1.000 to +0.200
Frequency
50/60 Hz45.00 to 66.00 Hz
MIN/MAX VALUES (PM-650 ONLY)
The power meter stores the following minimum and maximum values in
nonvolatile memory:
•Frequency
•Current Phase A, B, C, and Neutral
•Voltage Phase A, Phase B, Phase C, A–B, B–C, C–A
•Power Factor Phase A, Phase B, Phase C, 3-Phase
•kW Phase A, Phase B, Phase C, 3-Phase Total
•kVAr Phase A, Phase B, Phase C, 3-Phase Total
➀ PM-620 and PM-650.
1998 Square D All Rights Reserved57
Power MeterBulletin No. 3020IM9503R6/98
Chapter 8—Metering CapabilitiesDecember 1998
•kVA Phase A, Phase B, Phase C, 3-Phase Total
•THD/thd Current Phase A, Phase B, Phase C
•THD/thd Voltage Phase A, Phase B, Phase C
You can view these values using the power meter display, and reset them
using the Reset mode (see Performing Resets in Chapter 7).
Using POWERLOGIC application software you can:
•view all min/max values
•upload min/max values from the power meter and save them to disk
•reset min/max values
For instructions on viewing, saving, and resetting min/max data using
POWERLOGIC software, refer to the instruction bulletin included with the
software.
POWER FACTOR MIN/MAX CONVENTIONS
All running min/max values, with the exception of power factor, are arithmetic minimums and maximums. For example, the minimum phase A–B
voltage is simply the lowest value in the range 0 to 3,276,700 V that has
occurred since the min/max values were last reset. In contrast, power factor
min/max values—since the meter’s midpoint is unity—are not true arithmetic
minimums and maximums. Instead, the minimum value represents the
measurement closest to –0 on a continuous scale of –0 to 1.00 to +0. The
maximum value is the measurement closest to +0 on the same scale.
Figure 8-1 shows the min/max values in a typical environment, assuming a
positive power flow. In figure 8-1, the minimum power factor is –.7 (lagging)
and the maximum is .8 (leading). It is important to note that the minimum
power factor need not be lagging, and the maximum power factor need not be
leading. For example, if the power factor values ranged from –.75 to –.95, then
the minimum power factor would be –.75 (lagging) and the maximum power
factor would be –.95 (lagging). Likewise, if the power factor ranged from +.9
to +.95, the minimum would be +.95 (leading) and the maximum would be
+.90 (leading).
See Changing the VAR Sign Convention in Appendix E for instructions on
changing the sign convention over the communications link.
58 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 8—Metering Capabilities
Minimum
Power Factor
-.7 (lagging)
LAG
(-)
.4
.2
Figure 8-1: Power factor min/max example
Maximum
Power Factor
.8
.8 (leading)
.6
+0
LEAD
(+)
.4
.2
Range of Power
Factor Values
Unity
1.00
.8
.6
-0
Quadrant
2
WATTS NEGATIVE (–)
VARS NEGATIVE (–)
P.F. LEADING (+)
Reverse Power Flow
WATTS NEGATIVE (–)
VARS POSTIVE (+)
P.F. LAGGING (–)
Quadrant
3
WATTS POSITIVE (+)
VARS NEGATIVE (–)
P.F. LAGGING (–)
Normal Power Flow
WATTS POSITIVE (+)
VARS POSTIVE (+)
P.F. LEADING (+)
REACTIVE
POWER
Quadrant
1
REAL
POWER
Quadrant
4
Figure 8-2: Default VAR sign convention
1998 Square D All Rights Reserved59
Power MeterBulletin No. 3020IM9503R6/98
Chapter 8—Metering CapabilitiesDecember 1998
REACTIVE
POWER
Quadrant
2
WATTS NEGATIVE (–)
VARS POSITIVE (+)
P.F. LEADING (+)
Reverse Power Flow
WATTS NEGATIVE (–)
VARS NEGATIVE (–)
P.F. LAGGING (–)
Quadrant
3
Quadrant
1
WATTS POSITIVE (+)
VARS POSITIVE (+)
P.F. LAGGING (–)
Normal Power Flow
WATTS POSITIVE (+)
VARS NEGATIVE (–)
P.F. LEADING (+)
Quadrant
4
REAL
POWER
Figure 8-3: Alternate VAR sign convention
60 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 8—Metering Capabilities
ENERGY READINGS
The power meter provides 3-phase total energy values for kWh, kVARh, and
kVAh (table 8-2). These values can be displayed on the power meter display,
or read over the communications link. In the default mode (unsigned), the
power meter accumulates energy as positive, regardless of the direction of
power flow (i.e., the energy value increases, even during reverse power flow
as in a tie breaker application).
Using POWERLOGIC
System Manager Software SMS-3000, SMS-1500, or
PMX-1500, the power meter can be configured to accumulate kWh and
kVARh in one of three additional modes: signed, energy in, and energy out.
In signed mode, the power meter considers the direction of power flow,
allowing the accumulated energy magnitude to both increase and decrease.
The power meter can also be configured to accumulate kWh and kVARh as
either energy into the load only or energy out of the load only. The default
accumulation mode is unsigned (absolute).
The power meter also calculates a 3-phase total apparent energy value. All
energy values are stored in nonvolatile memory.
Table 8-2
Energy Readings
Energy Reading, 3-PhaseReportable Range
Accumulated Energy
Real (Signed/Absolute/In/Out)0 to 9,999,999,999,999,999 Wh
Reactive (Signed/Absolute/In/Out)0 to 9,999,999,999,999,999 VARh
Apparent0 to 9,999,999,999,999,999 VAh
1998 Square D All Rights Reserved61
Power MeterBulletin No. 3020IM9503R6/98
Chapter 8—Metering CapabilitiesDecember 1998
POWER ANALYSIS VALUES
The power meter provides power analysis values that can be used to detect
power quality problems, diagnose wiring problems, and more. Table 8-3
summarizes the power analysis values.
Table 8-3
Power Analysis Values
ValueReportable Range
THD-Voltage, Current (per phase) ➀0 to 3,276.7%
Fundamental Voltages (per phase) ➁
Magnitude0 to 3,276,700 V
Angle0.0 to 359.9°
Fundamental Currents (per phase) ➁
Magnitude0 to 32,767 A
Angle0.0 to 359.9°
➀ PM-620 and PM-650.
➁ Via communications only.
THD—Total Harmonic Distortion (THD) is a quick measure of the total
distortion present in a waveform. It provides a general indication of the
“quality” of a waveform. Power meter models PM-620 and PM-650 use the
following equation to calculate THD:
2
2
2
+
H
3
4
1
x
100%
THD =
H
2
++
H
H
thd—An alternate method for calculating Total Harmonic Distortion, used
widely in Europe. Power meter models PM-620 and PM-650 use the following
equation to calculate thd:
2
2
2
+
H
3
4
x
100%
thd =
++
H
2
Total rms
H
62 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 8—Metering Capabilities
DEMAND READINGS (PM-620 AND PM-650 ONLY)
Power meter models PM-620 and PM-650 provides both current and power
demand readings (table 8-4).
Table 8-4
Demand Readings
Demand ReadingReportable Range
Demand Current, Per-Phase & Neutral
Present0 to 32,767 A
Peak0 to 32,767 A
Demand Real Power, 3Ø Total
Present0 to +/-3,276.70 MW
Peak0 to +/-3,276.70 MW
Demand Reactive Power, 3Ø Total
Present0 to +/-3,276.70 MVAr
Peak0 to +/-3,276.70 MVAr
Demand Apparent Power, 3Ø Total
Present0 to 3,276.70 MVA
Peak0 to 3,276.70 MVA
Predicted Real Power Demand ➀➁0 to ±32,767 kW➂
Predicted Reactive Power Demand ➀➁0 to 32,767 kVAr ➂
Predicted Apparent Power Demand ➀➁0 to 32,767 KVA ➂
➀ PM-650 only.
➁ Via communications only.
➂ 3-phase total.
Demand Power Calculation Methods
To be compatible with electric utility billing practices, the power meter
provides the following types of demand power calculations:
•Sliding Block Interval Demand (PM-620 and PM-650 only)
•Block Interval Demand with Rolling Subinterval (PM-650 only)
•Synch to Comms (PM-650 only)
Block interval demand can be set up using the power meter display. Block
interval demand with a subinterval and sync to comms must be set up over
the communications link. A brief description of these three demand power
calculations follows.
Sliding Block Interval Demand
The block interval demand mode supports a sliding block interval calculation.
The default interval is 15 minutes.
In the sliding block interval mode, you can select a demand interval from 1 to
60 minutes in 1-minute increments. (The demand interval is set in the Setup
Mode. See Chapter 7 for details.) If you specify an interval of 1 to 15 minutes,
the demand calculation updates every 15 seconds on a sliding window basis.
1998 Square D All Rights Reserved63
Power MeterBulletin No. 3020IM9503R6/98
Chapter 8—Metering CapabilitiesDecember 1998
If the interval is between 16 and 60 minutes, the demand calculation updates
every 60 seconds on a sliding window basis. The present demand value
displayed by the power meter is the value for the last completed interval.
Block Interval Demand with Subinterval Option (PM-650 Only)
When using POWERLOGIC software, you must select both a block interval
and a subinterval length. The default subinterval length is 0 minutes. At this
default setting, the sliding block interval calculation described above is
performed. If you set the subinterval to the value of the block interval, a fixed
block calculation is performed and the demand calculation is updated every
interval. If you set the subinterval to a value other than 0 or the block interval
value, the power meter performs a rolling block demand calculation and
updates the demand calculation at every subinterval.
Synch to Comms (PM-650 Only)
If you set the demand to 0 using POWERLOGIC software, the synch to
comms demand calculation is used. See Appendix E for more information.
Predicted Demand (PM-650 Only)
Predicted demand is the average rate of power use during the most recent
one-minute interval. It is called predicted demand because the best estimate
of future power use is the power used in the most recent past.
The power meter calculates predicted demand for kW, kVAr, and kVA,
updating the readings every 15 seconds. The predicted demand value does
not predict the outcome of the present demand interval. Rather, since it
represents only the most recent 1 minute interval, it is more responsive to
recent increases or decreases in power than the present demand calculation.
Peak Demand
The power meter maintains, in nonvolatile memory, a “peak demand” for
each average demand current and average demand power value. It also stores
the date and time of each peak demand. In addition to the peak demand, the
power meter stores the coinciding average (demand) 3-phase power factor.
The average 3-phase power factor is defined as “demand kW/demand kVA”
for the peak demand interval.
Peak demand values can be reset using the power meter display, or over the
communications link using POWERLOGIC application software. To reset
peak demand values using the power meter display, see Performing Resets
on page 54.
64 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 8—Metering Capabilities
KYZ PULSE OUTPUT
This section describes the power meter’s pulse output capability. For wiring
instructions, see Chapter 5—Wiring. The KYZ output is a Form-C contact
with a maximum rating of 96 mA.
Calculating the Pulse Constant
This section shows an example of how to calculate the pulse constant (in this
case, a watthour-per-pulse value). To calculate this value, first determine the
highest kW value you can expect and the required pulse rate. In this example,
the following assumptions are made:
• The metered load should not exceed 1500 kW.
• The KYZ pulses should come in at about two pulses per second at full
scale.
Step 3: Round to the nearest hundredth, since the power meter accepts
0.01 kWH increments.
Ke = 0.21 kWH/pulse
Summary:
• 3-wire basis—0.21 kWH/pulse will provide approximately 2 pulses per
second at full scale.
• 2-wire basis—0.11 kWH/pulse will provide approximately 2 pulses per
second at full scale. (To convert to the kWH/pulse required on a 2-wire
basis, divide Ke by 2. This is necessary since the power meter Form-C relay
generates two pulses—KY and KZ—for every pulse that is counted on a
2-wire basis.)
1998 Square D All Rights Reserved65
Power MeterBulletin No. 3020IM9503R6/98
Chapter 9—Onboard AlarmingDecember 1998
CHAPTER 9—ONBOARD ALARMING (PM-650 ONLY)
The power meter 650 has 30 alarm conditions available onboard, including
over/under conditions and unbalance conditions (See Alarm Conditions andAlarm Codes in Appendix I for a complete list of alarm conditions.) The
power meter maintains a counter for each alarm to keep track of the total
number of occurrences.
These alarm conditions are tools that enable the power meter to execute tasks
automatically. Using POWERLOGIC application software, each alarm
condition can be assigned one or more of the following tasks:
•Force data log entries in the data log file
•Operate the KYZ relay output
SETPOINT-DRIVEN ALARMS
All of the alarm conditions require that you define the following setpoints:
•Pickup Setpoint
•Pickup Delay (in seconds)
•Dropout Setpoint
•Dropout Delay (in seconds)
For instructions on setting up alarm/relay functions from the power meter
display, see Setting Up Onboard Alarms on page 55.
66 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 9—Onboard Alarming
Figure 9-1 below illustrates how the power meter 650 handles setpoint-driven
alarms.
Max2
Max1
Pickup Setpoint
Dropout Setpoint
∆T
Pickup Delay
∆T
Dropout Delay
EV1EV2
Alarm Period
EVI— Power meter 650 records the date/time that the pickup setpoint and time delay were satisfied, and
the maximum value reached (Max1) during the pickup delay period (∆T). Also, the power meter
performs any tasks—forced data log entries, relay output operations—assigned to the event.
EV2— Power meter 650 records the date/time dropout setpoint and time delay were satisfied, and the
maximum value reached (Max2) during the alarm period.
Figure 9-1: How the power meter handles setpoint-driven alarms
Figure 9-2 shows the event log entries for figure 9-1 displayed by
POWERLOGIC application software.
Max1
EV1
EV2
SETPOINT-CONTROLLED RELAY FUNCTIONS
The KYZ output can be used to operate an alarm horn or bell to annuciate
the alarm condition or as an input into a building management system.
For instructions on wiring the KYZ output as an alarm contact, see
Chapter 5—Wiring.
Max2
Figure 9-2: Sample event log entries
1998 Square D All Rights Reserved67
Power MeterBulletin No. 3020IM9503R6/98
Chapter 9—Onboard AlarmingDecember 1998
Undervoltage
•Pickup and dropout setpoints are entered in volts. Very large values may
require scale factors. Refer to Appendix I—Alarm Setup.
•The per-phase overvoltage alarm occurs when the per-phase voltage is
equal to or above the pickup setpoint for the specified pickup delay period
(in seconds).
•When the overvoltage alarm occurs, the power meter operates the KYZ
output (if the output is enabled).
•The relay remains closed until the overvoltage alarm clears. The alarm
clears when the phase voltage remains below the dropout setpoint for the
specified dropout delay period.
Unbalance Current:
•Pickup and dropout setpoints are entered in tenths of percent, based on the
percentage difference between each phase current with respect to the
average of all phase currents. For example, enter an unbalance of 16.0%
as 160.
•The unbalance current alarm occurs when the phase current deviates from
the average of the phase currents, by the percentage pickup setpoint, for
the specified pickup delay (in seconds).
•When the unbalance current alarm occurs, the power meter operates the
KYZ output (if the output is enabled).
•The relay remains closed until the unbalance current alarm clears. The
alarm clears when the percentage difference between the phase current
and the average of all phases remains below the dropout setpoint for the
specified dropout delay period.
Unbalance Voltage
Pickup and dropout setpoints are entered in tenths of percent, based on the
percentage difference between each phase voltage with respect to the average
of all phase voltages. For example, enter an unbalance of 16.0% as 160.
•The unbalance voltage alarm occurs when the phase voltage deviates from
the average of the phase voltages, by the percentage pickup setpoint, for
the specified pickup delay (in seconds).
•When the unbalance voltage alarm occurs, the power meter operates the
KYZ output (if the output is enabled).
•The relay remains closed until the unbalance voltage alarm clears. The
unbalance voltage alarm clears when the percentage difference between
the phase voltage and the average of all phases remains below the dropout
setpoint for the specified dropout delay period.
68 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Chapter 10—Logging
CHAPTER 10—LOGGING (PM-650 ONLY)
ALARM LOG
The PM-650 has an alarm log viewable only from the power meter display.
The alarm log stores the last 10 alarms that occurred and indicates whether
each of those alarms has been acknowledged. The alarm log and event log are
two separate logs.
EVENT LOG
Power meter model 650 also provides an event log to record onboard events.
(An event occurs when the pickup or dropout setpoint of an alarm is reached;
see Chapter 9 for more information.) The event log holds a user-configurable
number of alarm events in FIFO (first-in-first-out) or Fill/Hold order. The
event log is factory pre-configured to hold 20 events. Using POWERLOGIC
application software, you can upload the event log for viewing, save it to disk,
and clear the power meter’s event log memory.
DATA LOG
The PM-650 is equipped with nonvolatile memory for storing meter readings
at regular intervals. One data log is provided for user configuration. The
following items can be configured for the data log file:
•Logging interval—1 minute to 24 hours in 1 minute increments
•Offset time
•First-In-First-Out (FIFO), or Fill & Hold
•Values to be logged
The data log is pre-configured to log each of the following hourly:
•Per-phase quantities: present current demand (including neutral) and
line-to-line voltages
•3-phase quantities: true power factor, kW demand total, kVAr demand
total, and kVA demand total
For instructions on setting up and clearing data log files, refer to the POWERLOGIC application software instruction bulletin.
ALARM-DRIVEN DATA LOG ENTRIES
Using POWERLOGIC application software, you can select an alarm condition
such as “Overcurrent Phase A” and set up the power meter to force data log
entries into the log file each time the alarm condition occurs.
STORAGE CONSIDERATIONS
The PM-650 has 1K of nonvolatile memory allocated for the event log and the
data log. See Appendix J—Calculating Log File Size for additional information on the event and data logs.
1998 Square D All Rights Reserved69
Power MeterBulletin No. 3020IM9503R6/98
Appendix A—SpecificationsDecember 1998
APPENDIX A—SPECIFICATIONS
Metering Specifications
Current Inputs
Current Range ..................................................................................... 0–10.0 A ac
Nominal Current............................................................................................ 5 A ac
Voltage Inputs
Voltage Range (line to line) ................................................................. 35–600 Vac
Voltage Range (line to neutral) ............................................................ 20–347 Vac
Nominal Voltage (typical)................................... 208/120, 480/277, 600/347 Vrms
Frequency Range (50/60 Hz)..................................................................... 45 to 66 Hz
Harmonic Response—Voltage, Current
Frequency 45–65 Hz ....................................................................... 31st harmonic
Input Impedance ............................................................. Greater than 2 megohms
➀ Any CT secondary currents less than 20 mA are reported as zero.
➁ From 20% nominal current to 150% nominal current.
➂ For readings less than 20% nominal, add ±0.05 full scale error.
➃ Satisfies applicable ANSI C12.16 revenue accuracy requirements.
70 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix A—Specifications
Electrical Fast Transient ....................................................... IEC 1000-4-4 Level 4
Immunity to Surge ................................................................ IEC 1000-4-5 Level 4
Safety ........................................................................... CSA, UL 508, CE, EN61010-1
1998 Square D All Rights Reserved71
Power MeterBulletin No. 3020IM9503R6/98
Appendix B—DimensionsDecember 1998
APPENDIX B—DIMENSIONS
3.81
6.08
154
4.75
121
96.7
4.50
114
3.63
92
4.50
114
Inches
Millimeters
4.50
114
1.26
32
Figure B-1: Dimensions of power meter and display
72 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix C—Communication Cable Pinouts
APPENDIX C—COMMUNICATION CABLE PINOUTS
CAB-107
Power Meter
Terminal
Male DB-9
Connector
IN- (4)—White1
TXA—White1
TXB—Green2
RXA—Black3
IN+ (5)—Green2
OUT- (2)—Black3
OUT+ (3)—Red4
5
6
7
Shield—Shield9
8
SHLD (1) Shield9
CC-100
11
22
33
44
55
66
77
88
99
CAB-108
RXB—Red4
5
6
7
8
CAB-102, CAB-104
22
33
44
55
66
77
88
2020
2222
1998 Square D All Rights Reserved73
Power MeterBulletin No. 3020IM9503R6/98
Appendix D—Additional Wiring DiagramsDecember 1998
APPENDIX D— ADDITIONAL WIRING DIAGRAMS
DANGER
!
HAZARD OF ELECTRICAL SHOCK, BURN, OR EXPLOSION.
• Turn off all power supplying this equipment before opening the
terminal shield or making connections.
• Close and snap the terminal shield before turning power on.
Failure to observe these precautions will result in death or severe
personal injury!
SUPPORTED WIRING CONNECTIONS
Table D-1 on the following page describes various power systems supported
by the power meter. The table also shows which power meter system type
should be used (system I.D.) and how the power meter should be wired.
Figures D-1, D-2, and D-3 show CT, PT, and control power wiring. See
Chapter 5 for other wiring diagrams.
To comply with CE, see CE Compliance, page 22.
74 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix D—Additional Wiring Diagrams
2Ø, 3W wye,401Ø, 3W1. Jumper input of phase not being metered
groundedfigure D-1to neutral voltage input.
neutral
Power MeterWiring for
System I.D.➀Power Meter
figure 5-3,
5-4, or 5-5
figure 5-6
or 5-7
Notes
Connect GND to neutral voltage terminal.
Line to neutral voltage may be unbalanced
due to potential difference between GND
at transformer & GND at meter.
3Ø, 4W403Ø, 4W1.
open delta,figure D-2
grounded2.
mid-tappower meter.
3Ø, 3W open30 or 313Ø, 3W delta 1. Wire grounded corner into B phase
delta, cornerfigure 5-4voltage input.
groundedor 5-5
1Ø, 3W401Ø, 3W1. B phase readings will be zero.
groundedfigure D-12.
mid-tappower meter.
1Ø, 2W401Ø, 3W1. Use only L
groundedfigure D-12. B & C phase readings will be zero.
end of phase3.
mid-tappower meter.
30 or 313Ø, 3W delta 1. For ungrounded delta systems only.
figure 5-3
Per phase power factor will be determined
with respect to neutral.
Always use 480/277 voltage range on the
power meter.
Per phase power factor will be determined
with respect to neutral.
Always use 480/277 voltage range on the
Always use 208/120 voltage range on the
-N PT and L1 CT.
1
Always use 208/120 voltage range on the
➀ System type as shown on power meter setup screen.
➁ For 3Ø, 3W delta corner-grounded applications, install two L-L rated PTs as shown in figures 5-4 and 5-5.
1998 Square D All Rights Reserved75
Power MeterBulletin No. 3020IM9503R6/98
Appendix D—Additional Wiring DiagramsDecember 1998
L1
Line
L2
N
VDS
Fuses
Top
Voltage
Control
Power
Load
KYZ
Comms
Current
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L, or L-N, or an
external source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
90–300 Vdc
When configuring the power meter, set system type to 4-wire (40) and
PT ratio to 120:120.
Installation Category II
Figure D-1: 240/120 V 1-phase, 3-wire direct voltage connection with 2 CTs
76 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix D—Additional Wiring Diagrams
AØ
BØ
Line
CØ
N
VDS
Fuses
Top
Load
KYZ
Voltage
Control
Power
Comms
Current
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L, or L-N, or an
external source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
90–300 Vdc
Use at 480/277 volt range for 240/120 V and 480/240 V systems.
Use system type 40.
Installation Category II
Figure D-2: 3-phase, 4-wire delta with 3 PTs and 3 CTs
1998 Square D All Rights Reserved77
Power MeterBulletin No. 3020IM9503R6/98
Appendix D—Additional Wiring DiagramsDecember 1998
AØ
BØ
Line
CØ
N
Load
CDS
Fuse
Fuse
VDS
Fuses
CPT
(120 or 240 Vac
Secondary,
Projected 10 VA)
Comms
Fuses
Top
Voltage
Control
Power
Current
Wye PT
Connection
(120 V L-N
Secondaries)
KYZ
Display
Communications
Port
Note: Control power can be drawn from fused voltage inputs L-L, or L-N, or an
external source. See page 22 for CPT and fuse recommendations.
Control power range: L1-L2 90–600 Vrms
Installation Category II
Figure D-3: 3-phase, 4-wire wye, 3-wire load with 3 PTs and 2 CTs
78 1998 Square D All Rights Reserved
90–300 Vdc
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix E—Using the Command Interface
APPENDIX E—USING THE COMMAND INTERFACE
RESETTING DEMAND AND ENERGY VIA COMMUNICATIONS
Using System Manager Software (SMS-3000, SMS-1500, or PMX-1500), you can
reset Peak Demand Currents, Peak Demand Powers, Min/Max and the associated power factors. You can also clear accumulated energies. If you are not
using one of these software packages, you can perform these functions via
communications by entering the desired command code (see below) to register
7700.
Command
CodeDescription
4110Reset min/max (PM-650 only)
5110Reset peak demand currents
5120Reset peak demand powers and associated average power factors
6210Clear all accumulated energies
CHANGING THE VAR SIGN CONVENTION
The power meter offers two VAR sign conventions (see figures 8-2 and 8-3
in Chapter 8). The procedures below tell how to change the sign convention
via communications.
To change to the alternate sign convention, complete the following steps:
1. (SY/MAX or POWERLOGIC protocol only) Read register 7715.
2. Read register 2028, the value of the system password.
3. Write the value in register 2028 into register 7721.
4. Write the decimal value 2020 into register 7720.
5. Change to binary mode and read register 7755.
6. Change bit 0, the least significant or right-most bit, to a 1 and write the
new value back to register 7755.
7. Change back to decimal mode and read register 2028.
8. Write the value of register 2028 into register 7721.
9. Write the decimal value 2050 into register 7720. The changes are saved and
the power meter resets.
To return to the default sign convention, complete the following steps:
1. (SY/MAX or POWERLOGIC protocol only) Read register 7715.
2. Read register 2028, the value of the system password.
1998 Square D All Rights Reserved79
Power MeterBulletin No. 3020IM9503R6/98
Appendix E—Using the Command InterfaceDecember 1998
3. Write the value in register 2028 into register 7721.
4. Write the decimal value 2020 into register 7720.
5. Change to binary mode and read register 7755.
6. Change bit 0, the least significant or right-most bit, to a 0 and write the
new value back to register 7755.
7. Change back to decimal mode and read register 2028.
8. Write the value of register 2028 into register 7721.
9. Write the decimal value 2050 into register 7720. The changes are saved and
the power meter resets.
SYNCH TO COMMS (PM-650 Only)
Using command 5910, it is possible to synchronize the demand intervals of
multiple meters on a communications network. For example, a PLC input
could be monitoring the utility revenue meter’s end-of-demand-interval pulse.
The PLC can be programmed to issue command 5910 to multiple meters
whenever the utility meter starts a new demand interval. This technique
causes the demand readings of each meter to be calculated over the same
fixed block interval.
Enter the command code to register 7700 via communications.
Command CodeDescription
5910Start a new demand interval (if demand interval is 0)
80 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix F—Register List
APPENDIX F—REGISTER LIST
Reg. No. ➀Register NameUnitsRange
REAL TIME METERED VALUES
1000Update Interval1000ths0 to 10,000
of a second
1001Frequency.01 Hertz/Scale4500 to 6600
Factor F(45–66Hz) Range
1002Unused
1003Current, Phase AAmps/Scale0 to 32,767
Factor A
1004Current, Phase BAmps/Scale0 to 32,767
Factor A
1005Current, Phase CAmps/Scale0 to 32,767
Factor A
1006 ➁Current, CalculatedAmps/Scale0 to 32,767
NeutralFactor A
1007–Unused
1009
1010Current Unbalance, Phase APercent in 10ths0 to ±1000
1011Current Unbalance, Phase BPercent in 10ths0 to ±1000
1012Current Unbalance, Phase CPercent in 10ths0 to ±1000
1013Current Unbalance, WorstPercent in 10ths0 to ±1000
1014Voltage, PhaseVolts/Scale0 to 32,767
A to BFactor D
1015Voltage, PhaseVolts/Scale0 to 32,767
B to CFactor D
1016Voltage, PhaseVolts/Scale0 to 32,767
C to AFactor D
1017Unused
1018Voltage, PhaseVolts/Scale0 to 32,767
A to NeutralFactor D
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-620 and PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
1998 Square D All Rights Reserved81
Power MeterBulletin No. 3020IM9503R6/98
Appendix F—Register ListDecember 1998
Reg. No. ➀Register NameUnitsRange
1019Voltage, PhaseVolts/Scale0 to 32,767
B to NeutralFactor D
1020Voltage, PhaseVolts/Scale0 to 32,767
C to NeutralFactor D
1021Reserved
1022Voltage Unbalance, Phase A-BPercent in 10ths0 to ±1000
1023Voltage Unbalance, Phase B-CPercent in 10ths0 to ±1000
1024Voltage Unbalance, Phase C-APercent in 10ths0 to ±1000
1025Voltage Unbalance, L-L WorstPercent in 10ths0 to ±1000
1026Voltage Unbalance, Phase APercent in 10ths0 to ±1000
1027Voltage Unbalance, Phase BPercent in 10ths0 to ±1000
1028Voltage Unbalance, Phase CPercent in 10ths0 to ±1000
1029Voltage Unbalance, L-N WorstPercent in 10ths0 to ±1000
1030Reserved
1031True Power Factor,In 1000ths–100 to +1000
Phase Ato +100
1032True Power Factor,In 1000ths–100 to +1000
Phase Bto +100
1033True Power Factor,In 1000ths–100 to +1000
Phase Cto +100
1034True Power Factor,In 1000ths–100 to +1000
3-Phase Totalto +100
1035–Unused
1038
1039Real Power,kW/Scale0 to ±32,767
Phase AFactor E
1040Real Power,kW/Scale0 to ±32,767
Phase BFactor E
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
for the Modbus offset of one. Regard all registers as holding registers where a
82 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix F—Register List
Reg. No. ➀Register NameUnitsRange
1041Real Power,kW/Scale0 to ±32,767
Phase CFactor E
1042Real Power,kW/Scale0 to ±32,767
3-Phase TotalFactor E
1043Reactive Power,kVAr/Scale0 to ±32,767
Phase AFactor E
1044Reactive Power,kVAr/Scale0 to ±32,767
Phase BFactor E
1045Reactive Power,kVAr/Scale0 to ±32,767
Phase CFactor E
1046Reactive Power,kVAr/Scale0 to ±32,767
3-Phase TotalFactor E
1047Apparent Power,kVA/Scale0 to +32,767
Phase AFactor E
1048Apparent Power,kVA/Scale0 to +32,767
Phase BFactor E
1049Apparent Power,kVA/Scale0 to +32,767
Phase CFactor E
1050Apparent Power,kVA/Scale0 to +32,767
3-Phase TotalFactor E
1051 ➁THD/thd% in 10ths0 to 10,000
A Current
1052 ➁THD/thd% in 10ths0 to 10,000
B Current
1053 ➁THD/thd% in 10ths0 to 10,000
C Current
1054Reserved
1055 ➁THD/thd% in 10ths0 to 10,000
A Voltage
1056 ➁THD/thd% in 10ths0 to 10,000
B Voltage
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-620 and PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
1998 Square D All Rights Reserved83
Power MeterBulletin No. 3020IM9503R6/98
Appendix F—Register ListDecember 1998
Reg. No. ➀Register NameUnitsRange
1057 ➁THD/thd% in 10ths0 to 10,000
C Voltage
1058–Unused
1077
1078A CurrentAmps/Scale0 to 32,767
FundamentalFactor A
RMS Magnitude
1079A Current10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1080B CurrentAmps/Scale0 to 32,767
FundamentalFactor A
RMS Magnitude
1081B Current10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1082C CurrentAmps/Scale0 to 32,767
FundamentalFactor A
RMS Magnitude
1083C Current10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1084–Unused
1087
1088A VoltageVolts/Scale0 to 32,767
FundamentalFactor D
RMS Magnitude
1089A Voltage10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1090B VoltageVolts/Scale0 to 32,767
FundamentalFactor D
RMS Magnitude
1091B Voltage10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-620 and PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
84 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix F—Register List
Reg. No. ➀Register NameUnitsRange
1092C VoltageVolts/Scale0 to 32,767
FundamentalFactor D
RMS Magnitude
1093C Voltage10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1094A-B VoltageVolts/Scale0 to 32,767
FundamentalFactor D
RMS Magnitude
1095A-B Voltage10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1096B-C VoltageVolts/Scale0 to 32,767
FundamentalFactor D
RMS Magnitude
1097B-C Voltage10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1098C-A VoltageVolts/Scale0 to 32,767
FundamentalFactor D
RMS Magnitude
1099C-A Voltage10ths of0 to 3,599
FundamentalDegrees
Coincident Angle
1200 ➁Minimum Update IntervalIn 1000ths of a second0 to 10,000
1201 ➁Minimum FrequencyHertz/Scale Factor F4500 to 6600
1202 ➁Reserved
1203 ➁Minimum Current, Phase AAmps/Scale Factor A0 to 32,767
1204 ➁Minimum Current, Phase BAmps/Scale Factor A0 to 32,767
1205 ➁Minimum Current, Phase CAmps/Scale Factor A0 to 32,767
1206 ➁Minimum Current Neutral, CalculatedAmps/Scale Factor A0 to 32,767
1207 ➁Reserved
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
1998 Square D All Rights Reserved85
Power MeterBulletin No. 3020IM9503R6/98
Appendix F—Register ListDecember 1998
Reg. No. ➀Register NameUnitsRange
1208 ➁ Reserved
1209 ➁ Reserved
1210 ➁ Minimum Current Unbalance, Phase APercent in 10ths0 to ±1000
1211 ➁ Minimum Current Unbalance, Phase BPercent in 10ths0 to ±1000
1212 ➁ Minimum Current Unbalance, Phase CPercent in 10ths0 to ±1000
1213 ➁ Minimum Current Unbalance, WorstPercent in 10ths0 to ±1000
1214 ➁ Minimum Voltage, Phase A to BVolts/Scale Factor D0 to 32,767
1215 ➁ Minimum Voltage, Phase B to CVolts/Scale Factor D0 to 32,767
1216 ➁ Minimum Voltage, Phase C to AVolts/Scale Factor D0 to 32,767
1217 ➁ Reserved
1218 ➁ Minimum Voltage, Phase AVolts/Scale Factor D0 to 32,767
1219 ➁ Minimum Voltage, Phase BVolts/Scale Factor D0 to 32,767
1220 ➁ Minimum Voltage, Phase CVolts/Scale Factor D0 to 32,767
1221 ➁ Reserved
1222 ➁ Minimum Voltage Unbalance, Phase A-BPercent in 10ths0 to ±1000
1223 ➁ Minimum Voltage Unbalance, Ph. B-CPercent in 10ths0 to ±1000
1224 ➁ Minimum Voltage Unbalance, Ph. C-APercent in 10ths0 to ±1000
1225 ➁ Minimum Volt. Unbalance, Worst L-LPercent in 10ths0 to ±1000
1226 ➁ Minimum Voltage Unbalance, Ph. APercent in 10ths0 to ±1000
1227 ➁ Minimum Voltage Unbalance, Ph. BPercent in 10ths0 to ±1000
1228 ➁ Minimum Voltage Unbalance, Ph. CPercent in 10ths0 to ±1000
1229 ➁ Minimum Volt. Unbalance, Worst L-NPercent in 10ths0 to ±1000
1230 ➁ Reserved
1231 ➁ Minimum True Power Factor, Phase AIn 1000ths-100 to +1000 to +100
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
86 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix F—Register List
Reg. No. ➀Register NameUnitsRange
1232 ➁Minimum True Power Factor, Phase BIn 1000ths–100 to +1000 to +100
1233 ➁Minimum True Power Factor, Phase CIn 1000ths–100 to +1000 to +100
1234 ➁Minimum True Power Factor, TotalIn 1000ths–100 to +1000 to +100
1235 ➁Reserved
1236 ➁Reserved
1237 ➁Reserved
1238 ➁Reserved
1239 ➁Minimum Real Power, Phase AkW/ Scale Factor E0 to ±32,767
1240 ➁Minimum Real Power, Phase BkW/ Scale Factor E0 to ±32,767
1241 ➁Minimum Real Power, Phase CkW/ Scale Factor E0 to ±32,767
1242 ➁Minimum Real Power, TotalkW/ Scale Factor E0 to ±32,767
1243 ➁Minimum Reactive Power, Phase AkVAr/Scale Factor E0 to ±32,767
1244 ➁Minimum Reactive Power, Phase BkVAr/Scale Factor E0 to ±32,767
1245 ➁Minimum Reactive Power, Phase CkVAr/Scale Factor E0 to ±32,767
1246 ➁Minimum Reactive Power, TotalkVAr/Scale Factor E0 to ±32,767
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
1998 Square D All Rights Reserved87
Power MeterBulletin No. 3020IM9503R6/98
Appendix F—Register ListDecember 1998
Reg. No. ➀Register NameUnitsRange
1247 ➁Minimum Apparent Power, Phase AkVA/Scale Factor E0 to ±32,767
1248 ➁Minimum Apparent Power, Phase BkVA/Scale Factor E0 to ±32,767
1249 ➁Minimum Apparent Power, Phase CkVA/Scale Factor E0 to ±32,767
1250 ➁Minimum Apparent Power, TotalkVA/Scale Factor E0 to ±32,767
1251 ➁Minimum THD/thd Current, Phase APercent in 10ths0 to 10,000
1252 ➁Minimum THD/thd Current, Phase BPercent in 10ths0 to 10,000
1253 ➁Minimum THD/thd Current, Phase CPercent in 10ths0 to 10,000
1254 ➁Reserved
1255 ➁Minimum THD/thd Voltage, Phase APercent in 10ths0 to 10,000
1256 ➁Minimum THD/thd Voltage, Phase BPercent in 10ths0 to 10,000
1257 ➁Minimum THD/thd Voltage, Phase CPercent in 10ths0 to 10,000
1258 ➁Reserved
1259 ➁Reserved
1400 ➁Maximum Update IntervalIn 1000ths of a second0 to 10,000
1401 ➁Maximum FrequencyHertz/Scale Factor F4500 to 6600
1402 ➁Reserved
1403 ➁Maximum Current, Phase AAmps/Scale Factor A0 to 32,767
1404 ➁Maximum Current, Phase BAmps/Scale Factor A0 to 32,767
1405 ➁Maximum Current, Phase CAmps/Scale Factor A0 to 32,767
1406 ➁Maximum Current Neutral, CalculatedAmps/Scale Factor A0 to 32,767
1407 ➁Reserved
1408 ➁Reserved
1409 ➁Reserved
1410 ➁Maximum Current Unbalance, Ph. APercent in 10ths0 to ±1000
1411 ➁Maximum Current Unbalance, Ph. BPercent in 10ths0 to ±1000
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
88 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix F—Register List
Reg. No. ➀Register NameUnitsRange
1412 ➁Maximum Current Unbalance, Ph. CPercent in 10ths0 to ±1000
1413 ➁Maximum Current Unbalance, WorstPercent in 10ths0 to ±1000
1414 ➁Maximum Voltage, Phase A-BVolts/Scale Factor D0 to 32,767
1415 ➁Maximum Voltage, Phase B-CVolts/Scale Factor D0 to 32,767
1416 ➁Maximum Voltage, Phase C-AVolts/Scale Factor D0 to 32,767
1417 ➁Reserved
1418 ➁Maximum Voltage, Phase AVolts/Scale Factor D0 to 32,767
1419 ➁Maximum Voltage, Phase BVolts/Scale Factor D0 to 32,767
1420 ➁Maximum Voltage, Phase CVolts/Scale Factor D0 to 32,767
1421 ➁Reserved
1422 ➁Maximum Volt. Unbalance, Ph. A-BPercent in 10ths0 to ±1000
1423 ➁Maximum Volt. Unbalance, Ph. B-CPercent in 10ths0 to ±1000
1424 ➁Maximum Volt. Unbalance, Ph. C-APercent in 10ths0 to ±1000
1425 ➁Maximum Volt. Unbalance, Worst L-LPercent in 10ths0 to ±1000
1426 ➁Maximum Volt. Unbalance, Ph. APercent in 10ths0 to ±1000
1427 ➁Maximum Volt. Unbalance, Phase BPercent in 10ths0 to ±1000
1428 ➁Maximum Volt. Unbalance, Phase CPercent in 10ths0 to ±1000
1429 ➁Maximum Volt. Unbalance, Worst L-NPercent in 10ths0 to ±1000
1430 ➁Reserved
1431 ➁Maximum True Power Factor, Ph. AIn 1000ths-100 to +1000 to +100
1432 ➁Maximum True Power Factor, Ph. BIn 1000ths-100 to +1000 to +100
1433 ➁Maximum True Power Factor, Ph. CIn 1000ths-100 to +1000 to +100
1434 ➁Maximum True Power Factor, TotalIn 1000ths-100 to +1000 to +100
1435 ➁Reserved
1436 ➁Reserved
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
1998 Square D All Rights Reserved89
Power MeterBulletin No. 3020IM9503R6/98
Appendix F—Register ListDecember 1998
Reg. No. ➀Register NameUnitsRange
1437 ➁Reserved
1438 ➁Reserved
1439 ➁Maximum Real Power, Phase AkW/Scale Factor E0 to ±32,767
1440 ➁Maximum Real Power, Phase BkW/Scale Factor E0 to ±32,767
1441 ➁Maximum Real Power, Phase CkW/Scale Factor E0 to ±32,767
1442 ➁Maximum Real Power, TotalkW/Scale Factor E0 to ±32,767
1443 ➁Maximum Reactive Power, Phase AkVAr/Scale Factor E0 to ±32,767
1444 ➁Maximum Reactive Power, Phase BkVAr/Scale Factor E0 to ±32,767
1445 ➁Maximum Reactive Power, Phase CkVAr/Scale Factor E0 to ±32,767
1446 ➁Maximum Reactive Power, TotalkVAr/Scale Factor E0 to ±32,767
1447 ➁Maximum Apparent Power, Phase AkVA/Scale Factor E0 to ±32,767
1448 ➁Maximum Apparent Power, Phase BkVA/Scale Factor E0 to ±32,767
1449 ➁Maximum Apparent Power, Phase CkVA/Scale Factor E0 to ±32,767
1450 ➁Maximum Apparent Power, TotalkVA/Scale Factor E0 to ±32,767
1451 ➁Maximum THD/thd Current, Phase APercent in 10ths0 to 10,000
1452 ➁Maximum THD/thd Current, Phase BPercent in 10ths0 to 10,000
1453 ➁Maximum THD/thd Current, Phase CPercent in 10ths0 to 10,000
1454 ➁Reserved
1455 ➁Maximum THD/thd Voltage, Phase APercent in 10ths0 to 10,000
1456 ➁Maximum THD/thd Voltage, Phase BPercent in 10ths0 to 10,000
1457 ➁Maximum THD/thd Voltage, Phase CPercent in 10ths0 to 10,000
1458 ➁Reserved
1459 ➁Reserved
1600–Unused
1616
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
90 1998 Square D All Rights Reserved
Bulletin No. 3020IM9503R6/98Power Meter
December 1998Appendix F—Register List
Reg. No. ➀Register NameUnitsRange
ENERGY VALUES ➁
Accumulated Energy
1617–Apparent EnergyVAH0 to 9,999,999,999,999,999
16203-Phase Total
1621–Real EnergyWH0 to +/-9,999,999,999,999,999
16243-Phase Total
1625–Reactive EnergyVArH0 to +/-9,999,999,999,999,999
16283-Phase Total
1629–Unused
1663
DEMAND VALUES ➂
Current Demand
1700Unused
1701Present CurrentAmps/Scale0 to 32,767
Demand Phase AFactor A
1702Present CurrentAmps/Scale0 to 32,767
Demand Phase BFactor A
1703Present CurrentAmps/Scale0 to 32,767
Demand Phase CFactor A
1704Present DemandAmps/Scale0 to 32,767
Neutral CurrentFactor A
1705–Unused
1708
1709Peak CurrentAmps/Scale0 to 32,767
Demand Phase AFactor A
1710Peak CurrentAmps/Scale0 to 32,767
Demand Phase BFactor A
1711Peak CurrentAmps/Scale0 to 32,767
Demand Phase CFactor A
1712Peak CurrentAmps/Scale0 to 32,767
Neutral CurrentFactor A
1730Unused
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ Each energy is kept in 4 registers, modulo 10,000 per register.
➂ Demand Values available in PM-620 and PM-650 only.
for the Modbus offset of one. Regard all registers as holding registers where a
1998 Square D All Rights Reserved91
Power MeterBulletin No. 3020IM9503R6/98
Appendix F—Register ListDecember 1998
Reg. No. ➀Register NameUnitsRange
Power Demand ➁
1731PresentkW/Scale0 to +/–32,767
Real PowerFactor E
Demand, 3-Phase Total
1732PresentkVAr/Scale0 to +/–32,767
Reactive PowerFactor E
Demand, 3-Phase Total
1733PresentkVA/Scale0 to 32,767
Apparent Power DemandFactor E
3-Phase Total
1734Peak RealkW/Scale0 to +/–32,767
Power Demand,Factor E
3-Phase Total
1735AveragePercent–100 to +1000
Power Factor,in 1000thsto +100
@ Peak Real
1736–Unused
1737
1738Peak ReactivekVar/Scale0 to +/–32,767
Power DemandFactor E
3-Phase Total
1739AveragePercent–100 to +1000
Power Factorin 1000thsto +100
@ Peak Reactive
1740–Unused
1741
1742PeakkVA/Scale0 to 32,767
Apparent PowerFactor E
Demand, 3-Phase Total
1743AveragePercent–100 to +1000
Power Factorin 1000thsto +100
@ Peak Apparent
1744Unused
1745Unused
➀ These registers can be used with POWERLOGIC, Modbus, or Jbus protocols. Although POWERLOGIC
and Jbus protocols use a zero-based register addressing convention and Modbus uses a one-based
register addressing convention, the power meter, when configured for Modbus communications,
automatically compensates
30,000 or 40,000 offset can be used (e.g., Current, Phase A = 31,003 or 41,003).
➁ Reactive Demand may be calculated either using the fundamental only (default) or using total harmonics,
user selectable.
for the Modbus offset of one. Regard all registers as holding registers where a
92 1998 Square D All Rights Reserved
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.