• Accurate (± 5%), auto-recovering, hysteretic thermal shutdown function
maintains safe PCB temperatures under all conditions
• Auto-restart protects against output short circuits and open feedback loops
• Meets EN55022 and CISPR-22 Class B conducted EMI with >15 dBµV margin
• Meets IEC61000-4-5 Class 4 AC line surge
The products and applications illustrated herein (including circuits external to the products and transformer
construction) may be covered by one or more U.S. and foreign patents or potentially by pending U.S. and foreign
patent applications assigned to Power Integrations. A complete list of Power Integrations’ patents may be found at
www.powerint.com.
®
– meets all existing and proposed harmonized energy efficiency
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
14 Revision History ....................................................................................................32
Important Note:
Although this board is designed to satisfy safety isolation requirements, the engineering prototype
has not been agency approved. Therefore, all testing should be performed using an isolation
transformer to provide the AC input to the prototype board.
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
1 Introduction
This reference design report describes a switched-mode power supply that was designed
to replace line frequency transformer based solutions. The supply uses a member of the
LinkSwitch-LP family of devices, and is capable of withstanding common-mode line
surges of up to 10 kV. That is often a requirement for applications that connect to a
telephone line, such as modems, cordless phones and answering machines.
The report includes the power supply specification, a circuit diagram, a bill of materials,
transformer documentation, a printed circuit layout board, and performance data.
Figure 1 – Populated Circuit Board Photograph.
Page 3 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
2 Power Supply Specification
Description Symbol Min Typ Max Units Comment
Input
Voltage
Frequency
No-load Input Power (230 VAC) 0.3 W
Output
Output Voltage 1
Output Ripple Voltage 1
Output Current 1
Total Output Power
Continuous Output Power
No Load Output Voltage
Efficiency
Full Load
Required average efficiency at
25, 50, 75 and 100 % of P
OUT
Environmental
Conducted EMI
Safety
Surge
Differential Mode
Common Mode
Surge 2 KV
Ambient Temperature
V
f
LINE
IN
85 265 VAC
47 50/60 64 Hz
2 Wire – no P.E.
6.7 7.7 8.7 V
V
OUT1
V
RIPPLE1
I
OUT1
400 mV
0.21 0.21 A
20 MHz bandwidth
1.4 1.6 W
P
OUT
11 V
η
η
CEC
60 %
53
%
Measured at P
Per ENERGY STAR / CEC
requirements
Meets CISPR22B / EN55022B
T
AMB
Designed to meet IEC950, UL1950
2
6
0 50
10
Class II
1.2/50 µs surge, IEC 1000-4-5,
kV
kV
o
C
Series Impedance:
Differential Mode: 2 Ω
Common Mode: 12 Ω
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
4 Circuit Description
4.1 Input Stage
Components C1, C6, L1 and L3 comprise a balanced π filter. Resistor R5 dampens low
frequency conducted EMI. The supply needs no Y1-type capacitor (that normally bridges
the primary to secondary isolation barrier) due to U1’s frequency jitter function and the
E-Shield™ techniques used in the design of transformer T1. This minimizes audible
noise in applications connected to a phone line, by eliminating a path for line frequency
leakage currents to pass onto the output of the supply. The supply easily meets
EN55022B conducted EMI limits, with more than 15 dBµV of margin.
A metal oxide varistor (RV1) and a wire wound resistor (RF1) attenuate differential line
surges. The varistor is required to meet the 2 kV differential surge requirement. In
applications where only 1 kV of surge immunity is required, RV1 can be eliminated. The
wire wound resistor (RF1) must be able to withstand high transient dissipation from initial
inrush current (when AC power is applied) and during line surges.
4.2 LinkSwitch-LP
The LinkSwitch-LP family of ICs were designed to replace linear transformer solutions in
low-power charger and adapter applications. Feedback to the LNK562P IC (U1) is
derived from a resistor divider (R1 and R2) across the bias supply (D3 and C3), which
lowers cost by eliminating the need for an optocoupler.
Linear transformers typically use thermal fuses (over temperature cut-outs) for overload
protection. However, once a thermal fuse trips, the entire charger or adapter must be
thrown away, since thermal fuses cannot be reset or repaired. Latching thermal
shutdown functions are typically used in ringing choke converter (RCC) based supplies.
However, AC input power must be removed and reapplied to reset most thermal latches.
Since customers typically don’t know this, they often return good units they thought were
defective, simply because the thermal latch tripped and shut the unit off. The LinkSwitch-LP family’s hysteretic thermal shutdown function has a very tight tolerance (142 °C,
±5%), and automatically restarts the power supply once the IC temperature drops below
the lower temperature threshold. This maintains the average PCB temperature at a safe
level under all conditions, and reduces the return rate of good units from the field. The
auto-recovery feature also eliminates the noise sensitivity and component aging
problems associated with discrete latching circuits.
Pin 6 is eliminated from the IC package to extend the creepage distance between the
DRAIN pin and all other low voltage pins; both at the package and on the PCB. This
reduces the likelihood that tracking or arcing will occur due to moisture or board surface
contamination (from dust and dirt), which improves reliability in high humidity and high
pollution environments. During an output short circuit or an open loop condition, the
LinkSwitch-LP’s auto-restart function limits output power to about 12% of the maximum.
This protects both the load and the supply during prolonged overload conditions.
Page 7 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
The LinkSwitch-LP family of ICs are self-biased, via a high-voltage current source that is
internally connected to the DRAIN pin of the package. A capacitor (C2) connected to the
BYPASS (BP) pin of the IC provides energy storage and local decoupling of the internal
chip power. To further reduce no-load power consumption, a resistor can be used to
provide operating current to the IC from the bias winding (once the power supply is
operating). In this design, the bias winding voltage is about 14 V and the BP pin voltage
is 5.8 V. Therefore, R6 (100 kΩ) provides about 80 µA of current to the BP pin. If the
value of R6 were reduced, it could provide the entire 220 µA of IC supply current, which
would further reduce the no-load power consumption of the supply.
The worst-case, no-load power consumption of this supply is approximately 200 mW at
an input voltage of 265 VAC, which is well below the maximum limit of most energy
efficiency standards. Heat generation is also kept to a minimum in this design, given the
high operating efficiency at all line and load conditions.
4.3 Feedback
The output voltage of the supply is regulated based on feedback from the primary-side
bias supply. The bias winding voltage is rectified and filtered by D3 and C3. The leakage
inductance between the output winding and the bias winding induces error in the bias
winding voltage. Using a standard rectifier diode for D3 makes the bias winding voltage
more accurately track the output voltage. Resistor R7 preloads (3 mA) the output of the
bias supply, which further reduces the error and also limits the no-load output voltage.
A resistor divider (R1 and R2) provides the feedback voltage to the FB pin of U1. The
values of R1 and R2 are selected so that when the output voltage is at the desired
nominal value, the voltage on the FB pin is 1.69 V, and about 70 µA flows into the FB pin.
The LinkSwitch-LP family of devices use ON/OFF control to regulate the output of the
supply. During constant voltage (CV) operation, switching cycles are skipped when the
current into the FB pin exceeds 70 µA. As the load on the output of the supply reduces,
more switching cycles are skipped. As the load increases, fewer cycles are skipped.
The result is that the average or effective switching frequency varies with the load. This
makes the efficiency fairly consistent over the entire load range, since the switching
losses scale with the load on the output of the supply.
When the load on the output of the supply reaches its maximum power capability, no
switching cycles are skipped. If the load is increased beyond that point, the output
voltage of the supply will start to drop. As the output voltage drops, the voltage on the FB
pin also drops, and the IC linearly reduces its switching frequency. This keeps the output
current from increasing significantly. Once the FB pin voltage falls below 0.8 V for more
than 100 ms, all LinkSwitch-LP devices enter an auto-restart mode. While in auto-restart,
the controller enables MOSFET switching for 100 ms. If the FB pin voltage does not
exceed 0.8 V during the 100 ms, the controller disables MOSFET switching. MOSFET
switching is alternately enabled and disables at a duty cycle of about 12% until the fault
condition clears. This protects both the supply and the load.
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
4.4 Output Rectification
The transformer secondary winding is rectified by D4 and filtered by C4. A small preload
resistor (R8) limits the no-load output voltage. Decreasing the value of the preload
resistor will further reduce the no-load output voltage, at the expense of increasing the
no-load input power consumption. In this design, a fast diode (rather than an ultra-fast)
was used for D4 to lower cost and EMI emissions.
Page 9 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
5 PCB Layout
During a common mode surge, the specified surge voltage appears across the isolation
barrier. Elimination of the optocoupler and Y1-type capacitor in the design allowed the
necessary PCB clearance and creepage distance to be obtained, so that the supply can
withstand a 10 kV surge without resorting to expensive, special components.
To increase the creepage and clearance, the standard triple insulated wire used for the
secondary winding was terminated as flying leads that were soldered directly into the
PCB, instead of being terminated to transformer bobbin pins.
A 0.185 inch long, 4.7 mm wide slot was placed along the isolation barrier. Additionally,
the primary and secondary traces are separated by 0.4 inches (10 mm). A spark gap
was added across the isolation barrier (marked as points (B) in Figure 4), so that any
arcing that might occur would take place at a designated point with a well defined path.
On the primary side of the isolation barrier, the spark gap trace returns directly to C6,
which keeps surge currents away from the low-voltage pins of U1. Two additional spark
gaps were placed across L1 and L3, to prevent the breakdown of insulation on those
parts. Note: During 10 kV common mode surge testing, no arcing occurred across any
of the spark gaps.
(A)
(B)
(B)
Figure 4 – RD83 Printed Circuit Layout (2.175” x 1.475” / 55.25 mm x 37.47 mm).
YES CVCC Volts Choose "YES" from the 'CV/CC output' drop
Winding
LNK562
Volts Output Voltage (main) measured at the end of
output cable (For CV/CC designs enter typical
CV tolerance limit)
designs enter typical CC tolerance limit)
down box at the top of this spreadsheet for
approximate CV/CC output. Choose "NO" for CV
only output
cable)
Choose 'BIAS' for Bias winding feedback and
'OPTO' for Optocoupler feedback from the
'Feedback Type' drop down box at the top of this
spreadsheet
box at the top of this spreadsheet to add a Bias
winding. Choose 'NO' to continue design without
a Bias winding. Addition of Bias winding can
lower no load consumption
Choose 'YES' from the 'clampless Design' drop
ss
Amps Minimum Current Limit
0.124
Amps Maximum Current Limit
0.146
Hertz Minimum Device Switching Frequency
61000
down box at the top of this spreadsheet for a
clampless design. Choose 'NO' to add an
external clamp circuit. Clampless design lowers
the total cost of the power supply
only designs enter 0.7 if no better data available
Total losses)
Wave Rectification from the 'Rectification' drop
down box at the top of this spreadsheet
1490 Gauss Maximum Operating Flux Density, BM<1500 is
recommended
Peak to Peak)
0.20 Mm Gap Length (Lg > 0.1 mm)
insulation
thickness)
standard AWG value)
150 Cmils/Amp Primary Winding Current Capacity (150 < CMA <
500)
mils
larger standard AWG value)
Insulated Wire
Transformer capacitance and leakage
inductance. Please verify this on the bench and
ensure that it is below 650 V to allow 50 V
margin for transformer variation.
7.7 Volts Main Output Voltage (if unused, defaults to
single output design)
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
9 Performance Data
All measurements performed at room temperature, 60 Hz input frequency.
9.1 Efficiency
90
80
70
60
Efficiency (%)
50
40
30
5075100125150175200225250275300
AC Input Voltage (V)
Figure 7
– Efficiency vs. Input Voltage, Room Temperature, 60 Hz.
Page 19 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
9.1.1 Active Mode ENERGY STAR / CEC Efficiency Measurement Data
All single output cordless phone adapters manufactured for sale in California after
July 1st, 2007 must meet the CEC requirement for minimum active mode efficiency and
no-load input power. Cordless phone adapters must also meet this specification on a
voluntary basis to be able to display the ENERGY STAR logo. Minimum active mode
efficiency is defined as the average efficiency of 25, 50, 75 and 100% of rated output
power, based on the nameplate output power:
ENERGY STAR / CEC Active Mode Efficiency Specification
Nameplate
Output (P
< 1 W
≥ 1 W to ≤ 49 W 0.09 × ln (PO) + 0.49 [ln = natural log]
> 49 W 0.84 x PO
)
O
Minimum Efficiency in Active Mode
of Operation
0.49 × P
O
For adapters that are single input voltage only, the measurement is made at the rated,
single nominal input voltage (115 VAC or 230 VAC). For universal input adapters, the
measurement for ENERGY STAR qualification is made at both nominal input voltages
(115 VAC and 230 VAC); for CEC qualification, measurements are made at 115 VAC
only. To meet the standard, the measured average efficiency (or efficiencies for
universal input supplies) must be greater than or equal to the efficiency specified by the
CEC / ENERGY STAR standard.
Percent of
Full Load
25
50
75
100
Average
CEC
specified
minimum
average
efficiency (%)
Efficiency (%)
115 VAC 230 VAC
61.0
65.4
66.5
67.4
65.1
53.2
56.1
62.6
63.6
62.9
61.3
More states within the USA and other countries are adopting this standard. For the latest
information, please visit the PI Green Room at:
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
10 Thermal Performance
10.1 LNK562 Temperature Rise
The RD-83 was installed within a sealed plastic enclosure, placed inside a sealed
cardboard box, and placed into a thermal chamber at 50 °C. The cardboard box
prevented the chamber circulation fan from blowing air across the plastic enclosure. A
thermocouple, attached to pin 2 of U1, was used to monitor its temperature.
Item
Ambient
LinkSwitch (U1)
Temperature (°C)
85 VAC 265 VAC
50 50
78 84
This result indicates acceptable thermal margin of approximately of 16 °C to the
recommended maximum SOURCE pin temperature of 100 °C
10.2 Thermal Image
An infrared thermograph of the board was taken to measure the temperature of other
components. This identified U1 and D4 as the highest temperature components. Using
the results from the previous section, this indicates that D4 would also have an
acceptable temperature rise at 50 °C ambient.
Figure 11 – Thermal Image of the RD-83 at Full Load, 85 VAC Input and Ambient Temperature of 22 °C.
Page 23 of 36
Tel: +1 408 414 9200 Fax: +1 408 414 9201
Power Integrations
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
11 Waveforms
11.1 Drain Voltage and Current, Normal Operation
Figure 12 – 85 VAC, Full Load .
Upper: I
Lower: V
, 0.1 A / div.
DRAIN
, 200 V/Div, 2 µs / div.
DRAIN
Figure 13 – 265 VAC, Full Load.
Upper: I
Lower: V
DRAIN
DRAIN
11.2 Output Voltage Start-up Profile
The output was loaded with a 39 Ω resistive load.
Figure 14 – Start-up Profile, 115VAC.
2 V, 20 ms / div.
Figure 15 – Start-up Profile, 230 VAC.
2 V, 20 ms / div.
The start-up waveforms show minimal output overshoot (<200 mV).
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
11.3 Drain Voltage and Current Start-up Profile
The output was loaded with a 39 Ω resistive load and the output profile captured. These
waveforms show no sign of core saturation and acceptable margin to the recommended
maximum drain voltage of 650 VPK.
Figure 16 – 85 VAC Input and Maximum Load.
Upper: I
Lower: V
, 0.1 A / div.
DRAIN
, 100 V & 1 ms / div.
DRAIN
Figure 17 – 265 VAC Input and Maximum Load.
Upper: I
Lower: V
, 0.1 A / div.
DRAIN
, 200 V & 1 ms / div.
DRAIN
Page 25 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
11.4 Load Transient Response (50% to 100% Load Step)
In the figures shown below, signal averaging was used to better enable viewing the load
transient response. The oscilloscope was triggered using the load current step as a
trigger source. Since the output switching and line frequency occur essentially at random
with respect to the load transient, contributions to the output ripple from these sources
will average out, leaving the contribution only from the load step response.
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
11.5 Output Ripple Measurements
11.5.1 Ripple Measurement Technique
For DC output ripple measurements, a modified oscilloscope test probe must be utilized
in order to reduce the pickup of spurious signals. Details of the probe modification are
provided in Figure 20 and Figure 21.
The 5125BA probe adapter (from probe master) is affixed with two capacitors tied in
parallel across the probe tip. The capacitors include one (1) 0.1 µF/50 V ceramic type
and one (1) 1.0 µF/50 V aluminum electrolytic. The aluminum electrolytic type capacitor
is polarized, so proper polarity across DC outputs must be maintained (see Figure 21).
Probe Ground
Probe Tip
Figure 20 – Oscilloscope Probe Prepared for Ripple Measurement (End Cap and Ground Lead Removed).
Figure 21 – Oscilloscope Probe with Probe Master 5125BA BNC Adapter (Modified with wires for probe
ground for ripple measurement, and two parallel decoupling capacitors added).
Page 27 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
11.5.2 Measurement Results
Figure 22 – Ripple, 85 VAC, Full Load.
5 ms, 50 mV / div (240 mV
Figure 24 – Ripple, 230 VAC, Full Load.
5 ms, 50 mV /div (130mV
P-P
P-P
).
).
Figure 23 – Ripple, 115 VAC, Full Load.
5 ms, 50 mV / div (80 mV
P-P
).
Figure 25 – Ripple of a Linear adaptor, 115 VAC
Input, Full Load.
2 ms, 200 mV/div (800 mV
P-P
).
Figure 22 shows increased line frequency ripple. If required, this could be lowered to the
level shown in Figure 23 by increasing the value of C6 and C1 to 4.7 µF.
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
12 Line Surge
Differential and common mode 1.2/50 µs surge testing was completed on a single test
unit, to IEC61000-4-5. Input voltage was set at 230 VAC / 60 Hz. The output of the
supply was loaded to full load, and correct operation was verified following each surge
event.
Surge
Level (V)
+2000 230 L to N 90 Pass
-2000 230 L to N 90 Pass
+10000 230 L,N to RTN90 Pass
-10000 230 L,N to RTN90 Pass
Unit passed under all test conditions.
Input
Voltage
(VAC)
Injection
Location
Injection
Phase (°)
Test Result
(Pass/Fail)
Page 29 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
R
V
R
13 Conducted EMI
Measurements were made with the output RTN of the supply connected to the artificial
hand connection on the LISN (line impedance stabilization network) to represent worstcase conditions.
The results show excellent margin of >15 dBµV to both the quasi-peak and the average
limit lines.
Power Integrations
28.Aug 06 09:43
dBµVdBµV
80
70
1 QP
EN55022Q
CLRW
60
EN55022A
2 A
CLRW
50
RBW 9 kHz
MT 500 ms
PREAMP OFFAtt 10 dB AUTO
1 MHz10 MHz
LIMIT CHECK MARG
LINE EN55022A MARG
LINE EN55022Q MARG
Marker 1 [T1 ]
28.50 dBµV
182.849162999 kHz
SGL
TDF
40
1
30
20
10
0
-10
-20
150 kHz30 MHz
Figure 26 – Conducted EMI, Maximum Steady State Load, 115 VAC, 60 Hz, and EN55022 B Limits.
29-Sept-06 RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand
Notes
Page 35 of 36
Power Integrations
Tel: +1 408 414 9200 Fax: +1 408 414 9201
www.powerint.com
RDR-83 7.7 V, 210 mA Adapter with 10 kV surge withstand 29-Sept-06
For the latest updates, visit our we bsite :
www.powerint.com
Power Integrations reserves the right to make changes to its products at any time to improve reliability or manufacturability. Power
Integrations does not assume any liability arising from the use of any device or circuit described herein. POWER INTEGRATIONS
MAKES NO WARRANTY HEREIN AND SPECIFICALLY DISCLAIMS ALL WARRANTIES INCLUDING, WITHOUT
LIMITATIO N, THE IMPLIE D WARRANTI ES OF M ERCHAN TABILI TY, FITNE SS FOR A PARTICU LAR PURP OSE, AND
NON-INFRINGEMENT OF THIRD PARTY RIGHTS.
PATENT INFORMATION
The products and applications illustrated herein (including transformer construction and circuits external to the products) may be
covered by one or more U.S. and foreign patents, or potentially by pending U.S. and foreign patent applications assigned to Power
Integrations. A complete list of Power Integrations’ patents may be found at www.powerint.com. Power Integrations grants its
customers a license under certain patent rights as set forth at http://www.powerint.com/ip.htm.
5F, No. 318, Nei Hu Rd., Sec. 1
Nei Hu Dist.
Taipei, Taiwan 114 , R.O.C.
Phone: +886-2-2659-4570
Fax: +886-2-2659-4550
e-mail:
taiwansales@powerint.com
UNITED KINGDOM
1st Floor, St. James’s House
East Street, Farnham
Surrey, GU9 7TJ
United Kingdom
Phone: +44 (0) 1252-730-140
Fax: +44 (0) 1252-727-689
e-mail: euros a les@powerint. com