Power Generation DFHA, DFHB, DFHD, DFHC Operator's Manual

Operator Manual
Generator Set
with PowerCommandR 3100 Controller
DFHA (Spec A−J)
DFHB (Spec AJ) DFHC (Spec AJ) DFHD (Spec AJ)
Table of Contents
SECTION TITLE PAGE
IMPORTANT SAFETY INSTRUCTIONS iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INTRODUCTION 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Obtain Service 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 SPECIFICATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 OPERATION 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prestart Checks 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCC Power On / Standby Mode 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Front Panel 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stopping 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Customer Inputs 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Menu Display and Switches 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main Menu 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ENGINE Menu 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GEN Menu 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADJUST Menu 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VERSION Menu 3-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 TROUBLESHOOTING 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Considerations 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status Indicators 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting The Control 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warning and Shutdown Codes Table 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting Tables 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
California
Proposition 65 Warning
Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm.
i
SECTION TITLE PAGE
5 MAINTENANCE
General 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance Schedule 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Inspection 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Maintenance (Battery Disconnected) 5-4. . . . . . . . . . . . . . . . . .
Lubrication System 5-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling System 5-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Cleaner 5-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charge-Air Piping 5-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System 5-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Batteries 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P7 Generator Bearing Re-Lubrication 5-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 OPTIONAL ENCLOSURE FEATURES
General 6-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External Receptacle 6-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External/Internal Alarm Panels 6-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
External Emergency Stop Switch 6-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Distribution Panel 6-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel Transfer Pump 6-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 OPERATING RECOMMENDATION
No-Load Operation 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exercise Period 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low Operating Temperature 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Operating Temperature 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the generator and batter­ies.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and the equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the oper­ator, service personnel, or the equipment.
DANGER
This symbol warns of immediate hazards which will result in severe personal in­jury or death.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe per­sonal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal in­jury or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result from improper practices.
DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source near the generator set or fuel tank.
Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arc­ing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly expel discharged gases away from enclosed or sheltered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that exhaust manifolds are se­cured and not warped. Do not use exhaust gases to heat a compartment.
Be sure the unit is well ventilated.Engine exhaust and some of its constituents are
known to the state of California to cause cancer, birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Keep your hands, clothing, and jewelry away from
moving parts.
Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis­connect starting batteries, negative (−) cable first. This will prevent accidental starting.
Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc.
Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equip­ment. Loose clothing and jewelry can become caught in moving parts.
If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds, moving parts, etc.
DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire, explo­sion, severe personal injury and death. Do not operate a genset where a flammable vapor environment can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating the gen­set safely. Contact your authorized Onan/Cummins deal­er or distributor for more information.
LS-13M
iii
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing protective shields or touching electrical equipment. Use rub­ber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical con­tacts and cause shock or burning.
Use extreme caution when working on electrical
components. High voltages can cause injury or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations performed by a qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This creates a potential for elec­trocution or property damage. Connect only through an approved isolation switch or an ap­proved paralleling device.
MEDIUM VOLTAGE GENERATOR SETS
(601V to 15kV)
Medium voltage acts differently than low voltage.
Special equipment and training is required to work on or around medium voltage equipment. Operation and maintenance must be done only by persons trained and qualified to work on such devices. Im­proper use or procedures will result in severe per­sonal injury or death.
Do not work on energized equipment. Unauthorized
personnel must not be permitted near energized equipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even after the equipment is disconnected from the power source. Plan the time for maintenance with autho­rized personnel so that the equipment can be de-en­ergized and safely grounded.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex­changer pressure cap while the engine is running. Allow the generator set to cool and bleed the system pressure first.
Used engine oils have been identified by some state
or federal agencies as causing cancer or reproduc­tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or con­tact used oil.
Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFPA No. 10).
Make sure that rags are not left on or near the en-
gine.
Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating under the unit.
Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over­heating and engine damage which present a poten­tial fire hazard.
Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de­bris from the set and keep the floor clean and dry.
Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment un­safe.
Substances in exhaust gases have been identified
by some state or federal agencies as causing can­cer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
Do not store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire or explosion could result.
Wear hearing protection when going near an oper-
ating generator set.
To prevent serious burns, avoid contact with hot
metal parts such as radiator, turbo charger and ex­haust system.
iv
CONTAINERIZED RENTAL UNITS
POTENTIAL TIPPING PROBLEM
On all containerized rental equipment, there is a potential problem of having the container tip forward over the land­ing legs, pulling the axles off the ground when the con-
tainer is fully fueled without a semi-tractor under the king pin. Jack stands for the front of the container are required to mitigate this potential problem.
Note: The figure below shows the jack stands and their placement at the nose of the container.
Jack Stands at Nose of Container
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iii
LS-13M
THIS PAGE LEFT INTENTIONALLY BLANK
iv
1. Introduction
GENERAL
Each operator should read this manual before oper­ating the set for the first time. A generator set (gen­set) must be operated and maintained properly if you are to expect safe, reliable and quiet operation. The manual includes a troubleshooting guide and a maintenance schedule.
The engine manual is included with the set. Where there is conflicting information, this manual takes precedence over the engine manual.
WARNING
nance can lead to severe personal injury or loss of life and property by fire, electrocution, me­chanical breakdown or exhaust gas asphyxi­ation. Read and follow the safety precautions on page iii and carefully observe all instructions and precautions in this manual.
Improper operation and mainte-
HOW TO OBTAIN SERVICE
When the generator set requires servicing, contact your nearest Cummins Power Generation distribu-
tor. Factory-trained Parts and Service representa­tives are ready to handle all your service needs.
To contact your local Cummins Power Generation distributor in the United States or Canada, call 1-800-888-6626 (this automated service utilizes touch-tone phones only). By selecting Option 1 (press 1), you will be automatically connected to the distributor nearest you.
If you are unable to contact a distributor using the automated service, consult the Yellow Pages. Typi­cally, our distributors are listed under:
GENERATORS-ELECTRIC or ELECTRICAL PRODUCTS
For outside North America, call Cummins Power Generation, 1-763-574-5000, 7:30 AM to 4:00 PM, Central Standard Time, Monday through Friday. Or, send a fax to Cummins Power Generation using the fax number 1-763-528-7229.
When contacting your distributor, always supply the complete Model, Specification, and Serial Number as shown on the generator set nameplate.
WARNING
INCORRECT SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL IN­JURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND/OR MECHANICAL SERVICE.
1-1
THIS PAGE LEFT INTENTIONALLY BLANK
1-2
2. Specifications
MODEL DFHA, DFHB, DFHC, DFHD
Engine
Cummins Diesel Series
Generator (Standby Rating) See Genset Nameplate for rating information.
Electrical System
Starting Voltage Battery
Group Number CCA (minimum)
Cold Soak @ 0F (-18 C)
Cooling System
Engine and Radiator
104 F (40 C) 122 F (50 C)
Lubricating System
Oil Capacity with Filters Oil Type*
* Refer to Cummins engine Operation and Maintenance Manual for lubricating oil recommendations/specifications.
QST30
24 Volts DC
Two, 12 Volt
8D
1400
53 Gal (201 L) 57 Gal (216 L)
35 Gal (132 L)
FUEL CONSUMPTION (STANDBY/FULL LOAD/60HZ)
MODEL
US gph (L/hr) 54.7 (207.3) 57.8 (219.1) 60.2 (228.2) 69.3 (262.6)
Normal Oil Pressure
Idle Oil Pressure
DFHA DFHB DFHC DFHD
OIL PRESSURE WARNING AND
SHUTDOWN LIMITS (PCC ONLY)
45-65 psi (310-448 kPa)
Warning Limit Shutdown Limit
Warning Limit Shutdown Limit
40 psi (276 kPa) 35 psi (241 kPa)
20 psi (138 kPa)
15 psi (103 kPa) 10 psi (69 kPa)
2-1
THIS PAGE LEFT INTENTIONALLY BLANK
2-2
3. Operation
GENERAL
The following describes the function and operation of the PowerCommand dicators, displays, meters and control switches are located on the face of the control panel as illustrated in Figure 3-1.
This section covers prestart checks, starting and stopping and operating the generator set. Each op­erator should read through this entire section before attempting to start the set. It is essential that the op­erator be completely familiar with the set and the PCC control. Refer to Section 7 for operating rec- ommendations.
Control 3100 (PCC). All in-
PRESTART CHECKS
Before starting, be sure the following checks have been made and the unit is ready for operation.
Lubrication
Check the engine oil level. Keep the oil level near as possible to the dipstick high mark without overfilling.
Coolant
Check the engine coolant level. The coolant should be about 3/4 inch (18 mm) below the radiator cap lower sealing surface. Do not check while the en­gine is hot.
WARNING
gine cool down before removing coolant pres­sure cap. Turn cap slowly, and do not open it ful­ly until the pressure has been relieved.
To prevent severe scalding, let en-
Fuel
Make sure the fuel tanks have sufficient fuel and that fuel system is primed. Check to make sure there are no leaks and that all fittings are tight.
Exhaust
Check to make sure entire exhaust system is tight, that no combustible materials are near system, and gases are discharged away from building openings.
3-1
PCC POWER ON / STANDBY MODE
The control panel can be set to function in one of the following modes; Power On or Standby.
To select the alternate mode, refer to the Installation manual.
Power On Mode: In this mode, power is continu-
ously supplied to the control panel. The control’s operating software and control panel LED’s/display will remain active.
Standby Mode: In this mode, the control’s operat­ing software is inactive and the LED’s and displays on the front panel are all off. The operating software is initialized and the front panel is turned on in re­sponse to one of the following:
moving the Run/Off/Auto switch to the Run
position,
pressing the Self Test button,a remote start input signal (generator set in
Auto mode), or
any one of several “wake-up” signals from ex-
ternal switches.
The wake up signals are:
Low Engine Coolant Level Low Engine Coolant Temperature Low Fuel Customer Fault Inputs 2 and 3 Run Selected on Run/Off Auto Switch Remote Start Signal in Auto Mode Emergency Stop
With the switch set to Standby mode, pressing the Self Test button will allow you to activate and view the menu displays without starting the generator set. If no menu selections are made, a software tim­er will shut down the power after 30 seconds.
When left in the Standby mode, and a “Warning” signal is sensed by the PCC (for example, low cool­ant temp), the control will wake up and display the warning message. The control will remain active until the warning condition is corrected and the Re­set button is pressed to clear the warning message.
3-2
KILOWATT
METER
(PERCENT LOAD)
FREQUENCY
METER
AC
VOLTMETER
AC AMMETER
MENU
SELECTION
SWITCH
(1 of 4)
ACTIVE SWITCH
INDICATOR
(1 of 6)
ALPHANUMERIC
DISPLAY
UPPER AND LOWER
SCALE INDICATOR
PCC 3100
LABEL
RUN/OFF/AUTO
SWITCH
SELF TEST
SWITCH
NON-AUTOMATIC
WARNING
SHUTDOWN
STATUS INDICATORS
RESET
SWITCH
MENU
SWITCH
FIGURE 3-1. FRONT PANEL (PCC 3100)
3-3
PANEL LAMP
SWITCH
PHASE SELECTOR
SWITCH AND
INDICATORS
EMERGENCY
STOP PUSH
BUTTON
FRONT PANEL
Figure 3-1 shows the features of the front panel.
Self Test Switch: Press and hold this switch to light all front panel LEDs and cycle through all shutdown and warning messages.
AC Voltmeter: Dual scale instrument indicates AC voltage. Measurement scale in use is shown on scale indicator lamp.
AC Ammeter: Indicates current output in percent of maximum rated current.
Kilowatt Meter: Indicates 3-phase AC power out­put as percent of rated load.
Frequency Meter: Indicates generator output fre­quency in hertz.
Upper and Lower Scale Indicator Lamps: Indi­cate AC voltmeter scale.
Digital Display: This two-line, 16-character per line alphanumeric display is used in the menu-driven operating system, in conjunction with the display menu selection switches and the Menu switch. Re­fer to the menu trees later in this section. The dis­play is also used to show warning and shutdown messages.
Display Menu Selection Switches: Four momen­tary switches—two on each side of the digital dis­play window—are used to step through the various menu options and to adjust generator set parame­ters. The green arrow adjacent to the switch is lit when the switch can be used (switch is “active”).
Menu Switch: Press this switch to return the digital display to the MAIN MENU. Refer to the menu trees later in this section.
Reset Switch: Press this switch to reset warning and shutdown messages after the condition has been corrected. To reset a shutdown message with the Reset switch, the Run/Off/Auto switch must be in the Off position.
In Auto mode, shutdown faults can be reset by re­moving the remote start input and then cycling the remote reset input.
Panel Lights Switch: Press this switch to turn con­trol panel illumination on and off. The illumination will shut off after about eight minutes.
Phase Selector Switch and Indicators: Press this momentary switch to select phases of generator output to be measured by AC voltmeter and amme­ter. LEDs indicate the selected phase.
Run/Off/Auto Switch: This switch starts and stops the set locally, or enables start/stop control of the engine from a remote location. (Ground to start.)
Emergency Stop Button: Push the switch in for emergency shutdown of the engine.
To reset:
Pull the button out or turn the button clockwise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to Off. Press the front panel Reset switch. Select Run or Auto, as required.
Non-Automatic Status Indicator: This red lamp flashes continuously when the Run/Off/Auto switch is not in the Auto position.
Warning Status Indicator: This yellow lamp is lit whenever the control detects a warning condition. After the condition is corrected, warning indicators can be reset by pressing the Reset switch. (It is not necessary to stop the generator set.) In auto mode, warning indicators can also be reset by cycling the remote reset input after the condition is corrected.
Shutdown Status Indicator: This red lamp is lit whenever the control detects a shutdown condition. After the condition is corrected, shutdown indica­tors can be reset by turning the Run/Off/Auto switch to the Off position, and pressing the Reset switch. In auto mode, shutdown faults can be reset by remov­ing the remote start input and then cycling the re­mote reset input.
Emergency Stop shutdown status (Code 102) can be reset only at the PCC front panel.
3-4
STARTING
Automatic Starting from ATS
The following sections cover the three systems used to start the generator set.
Before starting the generator set, make sure that exhaust and fuel fittings are tight and properly posi­tioned and that proper maintenance has been per­formed. See Prestart Checks in this section.
Starting at Control Panel
Move the Run/Off/Auto switch to the Run position. This will activate the engine control system and the starting system. The starter will begin cranking, and after a few seconds the engine will start and the starter will disconnect.
If the engine does not start, the starter will disen­gage after a specified period of time and the control will indicate an overcrank shutdown.
Generator sets with the cycle cranking option se­lected will alternately crank and rest for 3, 4, or 5 cycles. The crank times and rest times can be indi­vidually preset for 7 to 20 seconds.
To change the cycle number, and the crank and rest times, contact an authorized service center.
Generator sets with the cycle cranking option not selected will crank continuously for up to 75 sec­onds before disengaging the starter.
To clear an overcrank shutdown, place the Run/Off/ Auto switch in the Off position and momentarily press the Reset switch. Wait two minutes for the starter motor to cool and then repeat the starting procedure. If the engine does not run after a second attempt, refer to the Troubleshooting section.
Starting from Remote Location
Place the Run/Off/Auto switch in the Auto position. This allows the generator set to be started from a re­mote switch.
The operating software is initialized and the front panel is turned on in response to a remote run sig­nal. Closing the remote switch initiates the starting sequence described in the previous section.
Starter cranking will begin after the start time delay timer (0300 seconds) has timed out. Refer to Time Delay Start in the Adjust menu.
Place the Run/Off/Auto switch in the Auto position if an automatic transfer switch (ATS) is used. The op­erating software is initialized in response to a re­mote run signal from the transfer switch. This allows the transfer switch to start the generator set if a pow­er outage occurs and stop it when the power re­turns.
Starter cranking will begin after the start time delay timer (0300 seconds) has timed out. Refer to Time Delay Start in the Adjust menu.
Cold Starting with Loads
In accordance with NFPA 110, Cummins Power Generation recommends installing diesel standby generator sets (life safety systems) equipped with engine jacket water coolant heaters in locations where the minimum ambient temperature is above 40
F (4C). NFPA also requires that the engine be
heated as necessary to maintain the water jacket temperature determined by the manufacturer for cold start and load acceptance for the type of sys­tem. Although most Cummins Power Generation generator sets will start in temperatures down to
25
F (−32C) when equipped with engine jacket
water coolant heaters, it might take more than 10 seconds to warm the engine before a load can be applied when ambient temperatures are below 40
F (4C).
On generator sets equipped with a graphic display, the Low Coolant Temperature (Code 210) mes- sage, in conjunction with illumination of the Warning LED, is provided to meet the requirements of NFPA
110. The engine cold sensing logic initiates a warn­ing when the engine jacket water coolant tempera­ture falls below 70 the ambient temperature falls below 40 cold engine may be indicated even though the cool­ant heaters are connected and operating correctly. Under these conditions, although the generator set may start, it may not be able to accept load within 10 seconds. When this condition occurs, check the coolant heaters for proper operation. If the coolant heaters are operating properly, other precautions may be necessary to warm the engine before apply­ing a load.
F (21C). In applications where
F (4C), a
3-5
STOPPING
Before Stopping
Run the generator set at no load for three to five minutes before stopping. This allows the lubricating oil and engine coolant to carry heat away from the combustion chamber and bearings.
Stopping at Control Panel
If the set was started at the set control panel, move the Run/Off/Auto switch to the Off position. The set will stop immediately. The control will respond to “wake up” signals from the external sensing switches when the Run/Off/Auto switch is in the Off position.
Stopping from Remote Location
Move the remote starting switch to the Off position.
The set will stop after the stop time delay timer (0600 seconds) has timed out. Refer to Time Delay Stop in the Adjust menu.
Automatic Stopping from ATS
If the set was started by an automatic transfer switch, the transfer switch control will send a remote stop signal after the normal power source returns.
To reset, pull the button out or turn the button clock­wise (button with arrow) and allow it to pop out. Move the Run/Off/Auto switch to the Off position. Then momentarily push the Reset switch.
Emergency Stop shutdown status can be reset only at the PCC front panel.
CUSTOMER INPUTS
Remote Start Input: When the Run/Off/Auto switch is in the Auto position, selecting this input ini­tiates the engine cranking and start sequence.
Remote Reset Input: When the Run/Off/Auto switch is in the Auto position and the remote start switch is open, selecting this input resets any latched shutdown fault (except Emergency Stop, which must be reset at the front panel.)
Engine Idle Input: When the set is operating in the RUN mode, selecting this input causes generator build up to be inhibited and the engine to be gov­erned at 800 RPM. When ground is removed from this input, the set returns to normal speed and volt­age.
Engine idle operation is applicable only in the RUN mode. The PCC operating program does not permit engine idle operation when the set is operating in AUTO mode.
The set will stop after the stop time delay timer (0600 seconds) has timed out. Refer to Time Delay Stop in the Adjust menu.
Emergency Stop (Code 102)
The emergency stop button is located on the lower right side of control panel (Figure 3-1). Push the but­ton in for emergency stop. The red Shutdown status LED will light, and the digital display message will be: “EMERGENCY STOP
102 SHUTDOWN”
When the engine idle function is enabled, the con­trol automatically sets lower oil pressure warning and shutdown trip points to reflect the lower operat­ing speed. When the engine idle function is re­moved and the set reverts to normal operating speed, the control automatically resets oil pressure warning and shutdown trip points to the normal set­tings.
Remote Emergency Stop Input: Grounding this input causes an immediate shutdown. Emergency stop must be reset at the front panel.
3-6
FIGURE 3-2. DIGITAL DISPLAY AND MENU SELECTION SWITCHES
MENU DISPLAY AND SWITCHES
Figure 3-2 shows the digital display and the menu selection switches.
In Standby Mode, to activate and view the menu dis­plays without starting the generator set, press and release the Self Test switch. This will initialize the PCC operating software and permit operation of the menu display panel. If no menu selections are made, a software timer will shut down the display power af­ter 30 seconds. In Power On Mode, power is continu­ously supplied to the control panel. Display will al­ways remain active.
Digital Display: This two-line, 16-character per line alphanumeric display is used in the menu-driven operating system, in conjunction with the display menu selection switches and the Menu switch.
Display Menu Selection Switches: Four momen­tary switches—two on each side of the digital dis-
play window—are used to step through the various menu options and to adjust generator set parame­ters. The green arrow adjacent to the switch is lit when the switch is available for use (is active).
Menu Switch: Press this momentary switch to re­turn the digital display to the main menu. (Refer to the main menu diagram on the next page.
Reset Switch: Press this momentary switch to re­set warning and shutdown messages after the con­dition has been corrected.
In the digital display, the “>>” symbol indicates that selecting the adjacent button causes the operating program to branch to the next menu display—as shown in the menu diagrams.
In the digital display, the “<<” symbol indicates that selecting the adjacent button causes the operating program to go back to the previous menu display.
3-7
Loading...
+ 43 hidden pages