OWNER’S MANUAL
Wet Rotor Circulator Pumps
For Indoor Use Only
Maintenance Free
“Power-Flo Pumps & Systems,
Your Power-Ful partner
for all your pumping needs”
Power-Flo Pumps & Systems • 877-24PUMPS • www.poweropumps.com
ISP No: Circulator - 10/13/15
Wet Rotor Circulator Pumps
General Safety Information
Before installation, read the following
instructions carefully. Failure to follow
instruction and Safety information could cause
serious bodily injury, death and/or property
damage. Each Power-Flo pump is individually
factory tested to insure proper performance.
Closely following these instructions will
eliminate potential operating problems,
assuring years of trouble-free service.
Installation, wiring,
and junction
connections must be in accordance with
the National Electric Code and all applicable
state and local codes. Requirements may vary
depending on usage and location.
Installation and
servicing is to be
conducted by qualied personnel only.
This pump is not
intended for use in
swimming pools, spa areas or water
installations where human contact
with pumped uid.
Features:
Power-Flo circulator pumps are low noise,
low leakage, reliable operation and easy
installation. Single and three speed compact,
ecient wet rotor circulators for closed
loop (cast iron volute) hydronic heating and
cooling circulation and open loop (bronze and
stainless steel) domestic water recirculation
applications.
MOTOR: 2-pole, 3600rpm, single phase,
PSC with Thermal protection
LIQUID TEMPERATURE: 32°F - 230°F
MAX. SYSTEM PRESSURE: 145 PSI
INSULATION: Class H
Risk of electric shock.
To reduce risk of
electric shock, always disconnect
pump from power source before
handling. Lock out power & tag.
In the event the
retaining screws have
been pulled out of the housing,
DO NOT replace them. Use of any
other screw may short out the stator
windings, creating a risk of electrical shock.
The addition of
petroleum based uids
or certain chemical additives to the system
voids the warranty.
Pumps build up heat
and pressure during
operation. Allow time
for pumps to cool
before handling or
servicing.
Receiving Inspection
Upon receiving the pump, it should be
inspected for damage or shortages. If
damage has occurred, le a claim
immediately with the company that delivered
the pump. Care should be taken to ensure
the pump is NOT dropped or mishandled,
dropping will damage the pump. If the
manual is removed from the packaging, do
not lose or misplace.
® Power-Flo is a registered trademark of Power-Flo
Technologies Inc. Alteration Rights Reserved. 3/15, 10/15
Power-Flo Pumps & Systems • 877-24PUMPS • www.poweropumps.com
2
Wet Rotor Circulator Pumps
Dimensions
A
C
B
E
D
F
SINGLE SPEED
VOLUTE
MODEL NUMBER
PFWRC3737C1F Cast Iron 115/1 3.0 335 Closed 6-1/2 6-3/8 5-1/16 5-3/8 3-1/4 3-5/32 12.5
PFWRC3737C2F Cast Iron 230/1 1.5 335 Closed 6-1/2 6-3/8 5-1/16 5-3/8 3-1/4 3-5/32 12.5
PFWRC3737B1F Bronze 115/1 3.0 335 Open 6-1/2 6-3/8 5-1/16 5-3/8 3-1/4 3-5/32 12.5
Material
VOLTS/
PHASE
AMPS WAT TS
SYSTEM
TYPEAFace/Face
B C D E F
THREE SPEED
VOLUTE
MODEL NO
PFWRC2017C1F Cast Iron 115/1 0.9/0.7/0.5 100/70/55 Closed 6-1/2 5-7/16 4 5-1/8 3 3-5/32 7.25
PFWRC2727C1F Cast Iron 115/1 1.6/1.5/1.3 185/170/135 Closed 6-1/2 6 4-3/4 5-5/16 3-1/4 3-5/32 11.25
PFWRC2727C2F Cast Iron 230/1 .8/.75/.65 185/170/135 Closed 6-1/2 6 4-3/4 5-5/16 3-1/4 3-5/32 11.25
PFWRC2727B1F Bronze 115/1 1.6/1.5/1.3 185/170/135 Open 6-1/2 6 4-3/4 5-5/16 3-1/4 3-5/32 11.25
PFWRC3032C1F Cast Iron 115/1 1.8/1.7/1.2 200/190/135 Closed 6-1/2 6 4-3/4 5-5/16 3-1/4 3-5/32 11.25
PFWRC3032C2F Cast Iron 230/1 .9/.85/.6 200/190/135 Closed 6-1/2 6 4-3/4 5-5/16 3-1/4 3-5/32 11.25
PFWRC3032S1F Stainless 115/1 1.8/1.7/1.2 200/190/135 Open 6-1/2 6 4-3/4 5-5/16 3-1/4 3-5/32 11.25
PFWRC2644C1F Cast Iron 115/1 2.0/1.7/1.2 230/190/135 Closed 8-1/2 6-11/16 5-1/8 5-5/8 3-1/4 3-7/16 13.5
PFWRC2644C2F Cast Iron 230/1 1.0/.85/0.6 230/190/135 Closed 8-1/2 6-11/16 5-1/8 5-5/8 3-1/4 3-7/16 13.5
PFWRC2644B1F Bronze 115/1 2.0/1.7/1.2 230/190/135 Open 8-1/2 6-11/16 5-1/8 5-5/8 3-1/4 3-7/16 13.5
Material
VOLTS/
PHASE
AMPS WATT S
SYSTEM
TYPEAF/F
B C D E F
WT.
lbs
WT.
lbs
PF WRC 21 20
Shut O
Power-Flo Wet Rotor Ciculator
EXAMPLE: PFWRC2120C1F - Power-Flo Pumps - Wet Rotor Circulator - 21” Shut O Head - 20GPM Max Flow - Cast Iron Volute - 115 Volt, Flanged Connection.
Power-Flo Pumps & Systems • 877-24PUMPS • www.poweropumps.com
Head (ft)
Max Flow
(Gal)
Volute Material
C, B, S
C = Cast Iron
B = Lead Free Bronze
S = Stainless Steel
Motor Voltage
1 or 2
1 = 115 V
2 = 230V/1P
Connection Type
F, S, U
F = Flanged
S = Copper Sweat
U = Union
3