Power Flex Power VentedGas Water Heater User Manual

Flammable Vapor Ignition Resistant Compliant
Power Vented
Gas Water Heater
Installation
Instructions and
Use & Care Guide
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any telephone in your building.
• Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
To obtain technical, warranty, or service assistance contact place of purchase or local distributor.
When calling for assistance, please have the following information ready:
1. Model number
2. 7 digit product number
3. Serial number
4. Date of installation
5. Place of purchase
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
6510331
September 2004
1
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.” These words mean:
You can be killed or seriously injured if you don’t imme­diately follow instructions.
You can be killed or seriously injured if you don’t follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
Important Instructions
• Do not use this appliance if any part has been under water. Immediately call a qualified service technician. Water heaters subjected to flood conditions or anytime the gas controls, main burner or pilot have been submerged in water require replacement of the entire water heater.
• Hydrogen gas can be produced in a hot water system that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable and can ignite when exposed to a spark or flame. To prevent the possibility of injury under these conditions, we recommend the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system. If hydrogen is present, there will probably be an unusual sound such as air escaping through the faucet as water begins to flow. Do not smoke or have any open flame near the faucet at the time it is open.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances.
Warning: This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
This appliance can cause low-level exposure to some of the substances listed, including formaldehyde, carbon monoxide, and soot.
Table Of Contents
Water Heater Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installing Your Gas Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Unpacking the Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Combustion Air Supply/Vent Pipe System . . . . . . . . . . . . . . . . . 7-12
Outlet Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Water System Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Operating Your Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-19
Lighting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operational Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Maintenance of Your Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . 20-22
Troubleshooting Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Repair Parts Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-25
PAGE
2
INSTALLING YOUR GAS WATER HEATER
Consumer Information
This water heater is design-certified by CSA International as a Category IV, non-direct vented water heater which takes its combustion air either from the installation area or from air ducted to the unit from the outside.
This water heater must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-latest edition. Canadian installations must be performed in accordance with CAN/CGA-B149. This is available from the following:
CSA America, Inc. 8501 East Pleasnat Valley Road
Cleveland, OH 44131 National Fire Protection Agency
1 Batterymarch Park Quincy, MA 02169-7471
Canadian Standards Association 178 Rexdale Boulevard Toronto, ON M9W 1R3
Check your phone listings for the local authorities having jurisdiction over your installation.
Unpacking the Water Heater
Important: Do not remove any permanent instructions,
labels, or the data label from outside of the water heater or on the inside of panels.
• Remove exterior packaging and place installation components aside.
• Inspect all parts for damage prior to installation andstart-up.
• Completely read all instructions before attempting to assemble and install this product.
• After installation, dispose of packaging material in the proper manner.
Consumer Responsibilities
This manual has been prepared to acquaint you with the installation, operation, and maintenance of your gas water heater and provide important safety information in these areas.
Read all of the instructions thoroughly before attempting the installation or operation of this water heater.
Do not discard this manual. You or future users of this water heater will need it for future reference.
Service to the power vented system should only be performed by a qualified service technician.
Examples of qualified service technicians include: those trained in the plumbing and heating industry, local gas utility personnel, or an authorized service person.
The manufacturer and seller of this water heater will not be liable for any damages, injuries, or deaths caused by failure to comply with the installation and operating instructions outlined in this manual.
If you lack the necessary skills required to properly install this water heater, or you have difficulty following the instructions, you should not proceed but have a qualified service technician perform the installation of this water heater. Massachusetts code requires this water heater to be installed in accordance with Massachusetts Plumbing and Fuel Gas Code 248 CMR Section 2.00 and 5.00.
A data plate identifying your water heater can be found next to the gas control valve/thermostat. When referring to your water heater, always have the information listed on the data plate readily available.
Retain your original receipt as proof of purchase.
3
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance can result in serious injury or death
Location Requirements
Do not use or store flammable products such as gasoline, solvents, or adhesives in the same room or area near the water heater. If such flammables must be used, all gas burning appliances in the vicinity must be shut off and their pilot lights extinguished. Open the doors and windows for ventilation while flammable substances are in use.
If flammable liquids or vapors have spilled or leaked in the area of the water heater, leave the area immediately and call the fire department from a neighbor’s home. Do not attempt to clean the spill until all ignition sources have been extinguished.
Site Location
Select a location near the center of the water piping system. The water heater must be installed indoors and in a vertical position on a level surface.
Consider the exhaust vent system piping and com­bustion air supply requirements when selecting the water heater location. The venting system must be able to run from the water heater to the termination with a minimal length and number of elbows. The venting system must comply with the requirements set forth in the venting section of this manual.
Locate the water heater near the existing gas piping. If installing a new gas line, locate the water heater to minimize the pipe length and elbows.
Note: This water heater must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-latest edition. Canadian installations must be
performed in accordance with CAN/CGA-B149.
4
Important: The water heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the water heater or to lower floors of the structure. Due to the
normal corrosive action of the water, the tank will eventually leak after an extended period of time. Also any external plumbing leak, including those from improper installation, may cause early failure of the water tank due to corrosion if not repaired. A qualified service technician should be contacted for repairs. A suitable metal drain pan should be
installed under the water heater as shown below, to help protect the property from damage which may occur from condensate formation or leaks in the pip­ing connections or tank. The pan must limit the water level to a maximum depth of 1-3/4” and be two inches wider than the heater and piped to an adequate drain. The pan must not restrict combustion air flow. Locate the water heater near a suitable indoor drain. Outside drains are subject to freezing temperatures which can obstruct the drain line. The piping should be at least 3/4” ID and pitched for proper drainage.
Under no circumstances will the manufacturer or seller of this water heater be held liable for any water damage which is caused by your failure to follow these instructions.
Pipe to an adequate drain
1-3/4”
max.
At least 2” greater than the
the water heater and the inlet
air pipe.
• The water heater should be located in an area not subject to freezing temperatures. Water heaters located in unconditioned spaces (i.e., attics, basements, etc.) may require insulation of the water piping and drain piping to protect against freezing. The drain and controls must be easily accessible for operation and service. Maintain proper clearances as specified on the data plate.
Do not locate the water heater near an air-moving device. The operation of air-moving devices such as exhaust fans, ventilation systems, clothes dryers, fire-places, etc., can affect the proper operation of the water heater. Special attention must be given to conditions these devices may create. Flow rever­sal of flue gases may cause an increase of carbon
monoxide inside of the dwelling.
FIGURE 1 Minimum Clearance Locations
Back
Top View
Top to ceiling
Sides
Sides
Front 24” min. for service
Vent
Clearances and Accessibility
Notice: Minimum clearances from combustible
materials are stated on the data plate located on the front of the water heater.
• The water heater is certified for installation on a combustible floor.
Important: If installing over carpeting, the carpeting must be protected by a metal or wood panel beneath the water heater. The protective panel must extend beyond the full width and depth of the water heater by at least 3 inches (76.2mm) in any direction or if in a alcove or closet installation, the entire floor must be covered by the panel.
Figure 1 may be used as a reference guide to locate the specific clearance locations. A minimum of 24 inches of front clearance and 4 inches on each side should be provided for inspection and service.
State of California Note: The water heater must be braced, anchored, or
strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area or call 1-800-456-9805 and request instructions.
5
GAS SUPPLY
Gas Requirements
Read the data plate to be sure the water heater is made for the type of gas you will be using in your home. This information will be found on the data plate
located near the gas control valve. If the information does not agree with the type of gas available, do not install or light. Call your dealer.
Note: An odorant is added by the gas supplier to the gas used by this water heater. This odorant may fade over an extended period of time. Do not depend upon this odorant as an indication of leaking gas.
Gas Piping
This gas piping must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-lat-
est edition. Canadian installations must be performed in accordance with CAN/CGA-B149.
Tables 1 and 2 on page 7 are provided as a sizing refer­ence for commonly used gas pipe materials. Consult the “National Fuel Gas Code” for the recommended gas pipe size of other materials.
Refer to Figure 2 Note: When installing gas piping, apply approved pipe
joint compound.
1. Install a readily accessible manual shut-off valve in the gas supply line as recommended by the local utility. Know the location of this valve and how to turn off the gas to this unit.
2. Install a drip leg (if not already incorporated as part of the water heater) as shown. The drip leg must be no less than three inches long for the accumulation of dirt, foreign material, and water droplets.
3. Install a ground joint union between the gas valve/ thermostat and the manual shut-off valve. This is to allow easy removal of the gas valve/thermostat.
4. Turn the gas supply on and check for leaks. Use a chloride-free soap and water solution (bubbles forming indicate a leak) or other approved method.
6
FIGURE 2 Gas Piping
Manual gas shut-off valve
Install a readily acces­sible manual shut-off valve in the gas supply line as recommended by the local utility.
Gas Pressure
Important: The gas supply pressure must not exceed the
maximum supply pressure as stated on the water heater’s data plate. The minimum supply pressure is for the pur­pose of input adjustment.
Gas Pressure Testing Important: This water heater and its gas connection must
be leak tested before placing the appliance in operation.
• If the code requires the gas lines to be tested at a pressure exceeding 14” W.C., the water heater and its manual shut-off valve must be disconnected from the gas supply piping system and the line capped.
• If the gas lines are to be tested at a pressure less than 14” W.C., the water heater must be isolated from the gas supply piping system by closing its manual shut-off valve.
U.L. recognized fuel gas and carbon monoxide (CO) detec­tors are recommended in all applications and should be installed using the manufacturer’s instructions and local codes, rules, or regulations.
Note: Air may be present in the gas lines and could prevent the pilot from lighting on initial start-up. The gas lines should be purged of air by a qualified service technician after installation of the gas piping system.
L.P. Gas
COMBUSTION AIR SUPPLY/VENT PIPE SYSTEM
buildings with indoor pools
water heaters installed in laundry, hobby, or craft rooms
water heaters installed near chemical storage areas Combustion air must be free of acid-forming chemicals
such as sulfur, fluorine, and chlorine. These elements are found in aerosol sprays, detergents, bleaches, clean­ing solvents, air fresheners, paint, and varnish removers, refrigerants, and many other commercial and household products. When burned, vapors from these products form highly corrosive acid compounds. These products should
Combustion Air Supply
This water heater takes its combustion air either from the installation area or from air ducted to the unit from the outside and all combustion products are discharged to the outdoors.
Important: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage.
The following types of installation (not limited to the fol­lowing) will require outdoor air for combustion due to chemical exposure and may reduce but not eliminate the presence of corrosive chemicals in the air:
• beauty shops
photo processing labs
not be stored or used near the water heater or air inlet. Combustion and ventilation air requirements are deter-
mined by the location of the water heater. The water heater may be located in either an open (unconfined) area or in a confined area or small enclosure such as a closet or small room. Confined spaces are areas with less than 50 cubic feet for each 1,000 BTUH of the total input for all gas-using appliances.
7
Unconfined Space
A water heater in an unconfined space uses indoor air for combustion and requires at least 50 cubic feet for each 1,000 BTUH of the total input for all gas appliances. The table below shows a few examples of the minimum square footage (area) required for various BTUH inputs.
Table 3
BTUH
Input
Min. Sq. Feet
with 8’ Ceiling
Typical Room
with 8’ Ceiling 30,000 188 9 x 21 45,000 281 14 x 20 60,000 375 15 x 25 75,000 469 15 x 31 90,000 563 20 x 28
105,000 657 20 x 33 120,000 750 25 x 30 135,000 844 28 x 30
Important: The area must be open and be able to provide the proper air requirements to the water heater. Areas that are being used for storage or contain large objects may not be suitable for water heater installation.
Water heaters installed in open spaces in buildings with unusually tight construction may still require outdoor air to function properly. In this situation, outside air openings should be sized the same as for a confined space.
Modern home construction usually requires supplying out­side air into the water heater area.
Confined Space
For the correct and proper operation of this water heater, ample air must be supplied for the combustion, ventilation, and dilution of flue gases. Small enclosures and confined areas must have two permanent openings so that suffi­cient fresh air can be drawn from outside of the enclosure. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure as shown in Figure 3.
The size of each opening (free area) is determined by the total BTUH input of all gas utilization equipment (i.e., water heaters, furnaces, clothes dryers, etc.) and the method by which the air is provided. The BTUH input can be found on the water heater data plate. Additional air can be provided by two methods:
1. All air from inside the building.
2. All air from outdoors.
FIGURE 3 Opening Locations Confined Spaces
All Air from Inside the Building
When additional air is to be provided to the confined area from additional room(s) within the building, the total volume of the room(s) must be of sufficient size to properly pro­vide the necessary amount of fresh air to the water heater and other gas utilization equipment in the area. If you are unsure that the structure meets this requirement, contact your local gas utility company or other qualified agency for a safety inspection.
Each of the two openings shall have a minimum free area of 1 square inch per 1,000 BTUH of the total input rating of all gas utilization equipment in the confined area, but not less than 100 square inches (Figure 4).
FIGURE 4 All Air From Inside Building Confined Space Installation
8
All Air from Outdoors
Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be prop­erly ventilated to the outside.
Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum dimension of rectangular air ducts cannot be less than three inches.
The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 4 to calculate the minimum free area for each opening. Figures 5, 6, and 7 are typical examples of each method.
Louvers and Grilles
In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 1/4” mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.
Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.
Keep louvers and grilles clean and free of debris or other obstructions.
Table 4
Minimum Free Area of Permanent Openings for
Ventilation and Combustion Air Supply -
All Air from Outdoors Only
Based on the total BTUH input rating for all gas utilizing equipment within the confined space.
Minimum
Free Area Per
Opening Source
Directed to Outdoors* 1 sq. in. per 4000 BTUH Figure 5
Vertical Ducts 1 sq. in. per 4000 BTUH Figure 6
Horizontal Ducts 1 sq. in. per 2000 BTUH Figure 7
Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq. in.
Opening (Sq. In.)
*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside wall.
Consult the local codes of your area for specific ventilation and combustion air requirements.
Reference
Drawing
FIGURE 5 All Air From Outdoors: Inlet Air From Ventilated Crawl Space/ Outlet Air To Vented Attic
FIGURE 6 All AIr From Outdoors Through Ventilated Attic
FIGURE 7 All Air From Outdoors Using Horizontal Ducts
9
Vent Pipe System
This water heater must be properly vented for removal of exhaust gases to the outside atmosphere. Correct instal-
lation of the vent pipe system is mandatory for the safe and efficient operation of this water heater and is an important factor in the life of the unit.
Vent pipe installation must be performed in accordance with state and local codes, or in the absence of such, the National Fuel Gas Code, NFPA 54, ANSI Z223.1-latest edi­tion. Canadian installations must be performed in accordance with CAN/CGA-B149. Important: Check to make sure the vent pipe is not blocked in any way. NOTE: Do not common vent this water heater with any other appliance. Do not install in the same chase or chimney with a metal or high-temperature plastic from another gas or fuel burning appliance.
Vent Pipe Material
The following plastic materials may be used for both the combustion air inlet and exhaust outlet piping subject to state and local codes:
• 2 or 3 inch Schedule 40 PVC or ABS
• 2 or 3 inch Schedule 40 or 80 CPVC
• DWV Pipe is acceptable NOTE: Use only solid (not foam core) piping. Plastic pipe and fittings are available through most plumb­ing suppliers. Always check the marking on the pipe to make sure you are using the correct material.
Vent Pipe Connection to Blower
A 3x2” reducer is supplied with the water heater to connect either 2” or 3” venting to the blower. Important: These connections must be properly sealed to prevent the leak­age of the products of combustion into the living area.
Vent Pipe Installation
The following guidelines should be followed when installing the exhaust outlet piping:
Venting should be as direct as possible with a minimum number of pipe fittings.
Vent diameter must not be reduced unless specifically noted in the installation instructions.
Support all horizontal pipe runs every four feet and all vertical pipe runs every six feet or according to local codes.
Vents run through unconditioned spaces where below freezing temperatures are expected should be prop­erly insulated to prevent freezing. For horizontal runs, wrap the vent pipe with self-regulating 3 or 5 watt heat tape. The heat tape must be U.L. listed and installed per the manufacturer’s instructions.
Do not connect this venting system with an existing vent or chimney.
Do not common vent with the vent pipe of any other water heater or appliance.
The exhaust outlet piping and termination may be installed in one of the following type terminations:
1. Standard Horizontal
2. Vertical
All pipe, fittings, pipe cement, primers and procedures must conform to American National Standard Institute and
10
American Society for Testing and Materials (ANSI/ASTM) standards in the United States. This water heater has been design certified by CSA International for use with the speci­fied (CSA) listed plastic vent pipe. Important: Do not use vent elbows in this vent pipe installation (see figure 8).
All joints in the outlet piping must be properly cemented.
Figure 8 Correct and Incorrect Pipe Fittings
Size and cut all piping before cementing.
1. Cut the pipe end square and remove all ragged edges and burrs. Make sure the inside of the pipe is clean and free of cuttings and loose dirt. Chamfer the end and apply primer to the fitting and pipe.
2. Using a suitable grade of pipe cement, apply a moder­ate, even coat inside the fitting. Apply a liberal amount of cement to the outside of the pipe to socket depth. NOTE: It is important to select the proper pipe cement for the type plastic pipe being used.
3. Assemble the parts quickly while the cement is still wet. Twist the pipe 1/4 turn during insertion and hold for 30 seconds.
Vent Pipe Length
Size the exhaust outlet as specified in Tables 5 & 6 below. These tables list the maximum allowable length in feet of the exhaust outlet pipe as related to the number of required elbows and the termination. The specified maximum lengths are for exhaust pipe systems. Minimum pipe length is 3 feet with one elbow.
1. Determine termination type and pipe size.
2. Determine number of elbows in exhaust pipe (Do not include elbows in the termination.) Corresponding number indicates the maximum length of exhaust pipe.
Table 5 - Maximum Allowable Length in Feet of
Exhaust Pipe - (42K BTU/Hr models only)
Pipe
Number of 90° Elbows (medium or long sweep only)
Size
Pipe
Size
Notes:
1. N/A - Not Applicable
2. The above maximum lengths are for outlet pipe systems.
3. Maximum of 6 elbows may be used. Use only medium or long sweep elbows. See figure 8 for details.
4. Two 45° elbows are considered equivalent to one 90° elbow.
5. Minimum length is 3 foot with 1 elbow.
6. Use schedule 40 CPVC, ABS, or PVC pipe and fittings.
0123456
(in)
2 50 45 40 35 30 25 20 Std. Horizontal 2 40 35 30 25 20 15 10 Vertical 3 125 120 115 110 105 100 95 Std. Horizontal 3 115 110 105 100 95 90 85 Vertical
Table 6 - Maximum Allowable Length in Feet of
Exhaust Pipe - (50K/60K BTU/Hr models only)
Number of 90° Elbows (medium or long sweep only)
0123456
(in)
2 N/A Std. Horizontal 2 N/A Vertical 3 65 60 55 50 45 40 35 Std. Horizontal 3 55 50 45 40 35 30 25 Vertical
Termination
Options
Termination
Options
Vent Termination Locations
The exhaust outlet must be installed with the following minimum clearances (see figure 9):
• Twelve inches above grade or maximum anticipated snow level.
• Twelve inch minimum clearance on top or four foot clearance below or to the side of door or window that may be open.
• Four feet horizontally and vertically from gas or electric meters, gas regulators, dryer vents, vent hoods, bathroom fan exhaust, attic fans and turbines.
• Two feet from an inside corner formed by two exterior walls.
• Two feet from porches, decks, overhangs and other obstructions.
Figure 9 Minimum Termination Clearance for Outlet Vent
In addition to maintaining the minimum clearances , the vent should terminate according to the following guidelines:
1. Do not expose any reducers or bushings to outdoor ambient temperatures.
2. The exhaust outlet must not terminate under a patio, deck or any covered area.
3. Do not terminate the vent near walkways or into alleys or other publicly accessible areas.
4. Do not terminate the vent in an area where children or animals could block pipes.
5. Do not locate the vent terminal too close to shrubs or bushes.
6. Caulk all cracks, seams and joints within 6 feet horizontally above and below the vent.
US Installations
A. 12 in (30 cm) min. clearance above grade,
veranda, porch, deck, balcony, or maximum anticipated snow level.
12 in. (30 cm) min. clearance on top or 4 ft.
B.
clearance below or to the side of door or window that may be open.
C. Clearance to permanently closed window.** D. 12 in (30 cm) min. vertical clearance to ventilated
soffit located above the terminal within a horizontal distance of 2 ft (61 cm) from the center line of the terminal.
E. 12 in (30 cm) min. clearance to unventilated soffit. F. Clearance to outside corner. ** G. 2 ft (61 cm) clearance to inside corner formed by
two exterior walls.
H. 4 ft (122 cm) clearance to each side of center line
extending above meter/regulator assembly.
I. 4 ft (122 cm) clearance to service regulator vent
outlet.
J. 12 in (30 cm) clearance on top or 4 ft (122 cm)
clearance below or to the side of nonmechanical air supply inlet to building or the combustion air inlet to any other appliance.
Canadian Installations
A. 12 in (30 cm) min. clearance above grade,
veranda, porch, deck, balcony, or maximum anticipated snow level.
B. 12 in (30 cm) min. clearance on top and side of
window or door that may be opened. Do not install below a window or door that may be opened.
C. Clearance to permanently closed window.** D. 12 in (30 cm) min vertical clearance to ventilated
soffit located above the terminal within a horizontal distance of 2 ft (61 cm) from the center line of the terminal.
E. 12 in (30 cm) min. clearance to unventilated soffit. F. Clearance to outside corner.** G. 2 ft (61 cm) clearance to inside corner formed by
two exterior walls.
H. 3 ft (91 cm) within a height 15 ft (4.57m) above the
meter/regulator assembly.
I. 4 ft (122 cm) clearance to service regulator vent outlet. J. 12 in (30 cm) clearance to nonmechanical air
supply inlet to building or the combustion air inlet to any other appliance.
K. 6 ft (1.83 m) clearance to mechanical air supply
inlet.
K. 3 ft (91 cm) above if within 10 ft (3 m) horizontally
of mechanical air supply inlet.
**Clearance in accordance with local installation codes and the requirements of the gas supplier.
11
OUTLET VENT TERMINATIONS
Standard Horizontal Termination
The standard horizontal exhaust outlet termination is a 2 inch or 3 inch pipe which terminates 12 inches from the outside wall (see figure 10). To prevent potential conden­sate from collecting in the venting system slope the vent at a downward pitch of 1/8” per 5ft. away from the water heater.
Install the correct size coupling at the outside wall on the exhaust to prevent the termination from being pushed inward.
FIGURE 10 Standard Horizontal Termination
Vertical Termination
The vertical exhaust outlet requires a return bend or two medium or long sweep radius 90° elbows to keep the exhaust outlet downward and prevent entry of rain. Do not include these elbows when calculating the maximum allowable vent pipe because they have already been con­sidered in the vent tables. The vertical exhaust outlet ter­mination is a 2 inch or 3 inch pipe which must be at least 12 inches above the roof line or anticipated snow levels. See figure 11.
FIGURE 11 Vertical Vent Termination
12
WATER SYSTEM PIPING
Tempered Water to fixtures
Cold
Water
Inlet
Tempering Valve (set to 120°F or lower)
Piping Installation
Piping, fittings, and valves should be installed according to the installation drawing (Figure 12). If the indoor installation area is subject to freezing temperatures, the water piping must be protected by insulation.
Water supply pressure should not exceed 80% of the work­ing pressure of the water heater. The working pressure is stated on the water heater’s data plate. If this occurs a pressure limiting valve with a bypass may need to be installed in the cold water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.
Important: Heat cannot be applied to the water fittings on the heater as they may contain nonmetallic parts. If solder connections are used, solder the pipe to the adapter before attaching the adapter to the hot and cold water fittings.
Important: Always use a good grade of joint compound and be certain that all fittings are drawn up tight.
1. Install the water piping and fittings as shown in Figure
12. Connect the cold water supply (3/4” NPT) to the fitting marked “C”. Connect the hot water supply (3/4” NPT) to the fitting marked “H”. Important: Some mod­els may contain energy saving heat traps to prevent the circulation of hot water within the pipes. Do not remove the inserts within the heat traps.
2. The installation of unions in both the hot and cold water supply lines is recommended for ease of remov­ing the water heater for service or replacement.
3. The manufacturer of this water heater recommends installing a tempering valve or an anti-scald device in the domestic hot water line as shown in Figure 13. These valves reduce the point of use temperature of the water by mixing cold and hot water and are readily available for use. Contact a licensed plumber or the local plumbing authority.
4. If installing the water heater in a closed water system, install an expansion tank in the cold water line as specified under “Closed System/Thermal Expansion”.
5. Install a shut-off valve in the cold water inlet line. It should be located close to the water heater and be easily accessible. Know the location of this valve and how to shut off the water to the heater.
6. Install a temperature and pressure relief valve in the opening marked “Temperature and Pressure (T & P) Relief Valve” on the water heater. Add a discharge line to the opening of the T & P relief valve. Follow the instructions under Temperature and Pressure Relief Valve”.
FIGURE 12 Typical Water Piping Installation
FIGURE 13 Typical Tempering Valve Installation
Please note the following: DO NOT install this water heater with iron piping. The
system should be installed only with piping that is suitable for potable (drinkable) water such as copper, CPVC, or polybutylene. DO NOT use PVC water piping.
DO NOT use any pumps, valves, or fi ttings that are not compatible with potable water.
DO NOT use valves that may cause excessive restriction to water fl ow. Use full fl ow ball or gate valves only.
DO NOT use 50/50 tin-lead solder (or any lead based solder) in potable water lines. Use 95/5 tin-antimony or other equivalent material.
DO NOT tamper with the gas valve/thermostat, igniter, thermocouple, or temperature and pressure relief valve. Tampering voids all warranties. Only qualifi ed service technicians should service these components.
DO NOT use with piping that has been treated with chromates, boiler seal, or other chemicals.
DO NOT add any chemicals to the system piping which will contaminate the potable water supply.
13
Closed System/Thermal Expansion
Periodic discharge of the temperature and pressure relief valve may be due to thermal expansion in a closed water supply system. The water utility supply meter may contain a check valve, backfl ow preventer or water pressure reducing valve. This will create a closed water system. During the heating cycle of the water heater, the water expands causing pressure inside the water heater to increase. This may cause the temperature and pressure relief valve to discharge small quantities of hot water. To prevent this, it is recommended that a diaphragm-type expansion tank (suitable for potable water) be installed on the cold water supply line. The expansion tank must have a minimum capacity of 1.5 U.S. gallons for every 50 gallons of stored water. Contact the local water supplier or plumbing inspector for information on other methods to control this situation.
Important: Do not plug or remove the temperature and pressure relief valve.
FIGURE 14 Temperature and Pressure Relief Valve Installation
Temperature and Pressure Relief Valve
For protection against excessive pressures and temperatures, a temperature and pressure relief valve must be installed in the opening marked “T & P RELIEF VALVE” (see Figure 14.) This valve must be design certifi ed by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials as meeting the requirements for Relief Valves and Automatic Shut-off Devices for Hot Water Supply Systems, ANSI Z21.22. The function of the temperature and pressure relief valve is to discharge water in large quantities in the event of excessive temperature or pressure developing in the water heater. The valve’s relief pressure must not exceed the working pressure of the water heater as stated on the data plate.
Important: Only a new temperature and pressure relief valve should be used with your water heater. Do not use an old or existing valve as it may be damaged or not adequate for the working pressure of the new water heater. Do not place any valve between the relief valve and the tank.
The Temperature and Pressure Relief Valve:
Must not be in contact with any electrical part.
Must be connected to an adequate discharge line.
Must not be rated higher than the working pressure shown on the data plate of the water heater.
The Discharge Line:
Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line.
Must not be capped, blocked, plugged or contain any valve between the relief valve and the end of the discharge line.
Must terminate a maximum of six inches above a fl oor drain or external to the building.
Must be capable of withstanding 250°F (121°C) without distortion.
Must be installed to allow complete drainage of both the valve and discharge line.
14
ELECTRICAL CONNECTIONS
Before plugging in the water heater, always make sure:
The voltage and frequency correspond to that specified
on the water heater wiring diagram.
The electrical outlet has the proper overload fuse or
breaker protection. Important: Do not use an extension cord to connect the water heater to an electrical outlet.
The water heater and the outlet are properly grounded. Installed in accordance with prevailing provisions of
local codes, or in the absence of such, National Electric Code, ANSI/NFPA 70 and/or the CSA C22.1, Electrical
Code.
Note: Always reference the wiring diagram for the correct electrical connections.
After making all electrical connections, completely fill the tank with water and check all connections for leaks. Open the nearest hot water faucet and let it run for 3 minutes to purge the water lines of air and sediment and to ensure
complete filling of the tank. The electrical power may then be turned on. Verify proper operation after servicing.
WIRING DIAGRAM
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
15
INSTALLATION CHECKLIST
Water Heater Location
Centrally located with the water piping system.
Located as close to the gas piping and vent pipe system as possible.
Located indoors and in a vertical position. Protected
from freezing temperatures.
Proper clearances from combustible surfaces
maintained and not installed directly on a carpeted fl oor.
Provisions made to protect the area from
water damage. Drain pan installed and piped to an adequate drain.
Installation area free of corrosive elements and
fl ammable materials.
• Suffi cient room to service the water heater.
Water heater not located near an air-moving device.
Gas Supply and Piping
Gas supply is the same type as listed on the water
heater data plate.
Gas line equipped with shut-off valve, union, and
drip leg.
Approved pipe joint compound used.
Adequate pipe size and of approved material.
Chloride-free soap and water solution or other
approved means used to check all connections and fi ttings for possible gas leaks.
Combustion Air Supply/Vent Pipe System
Sufficient fresh air supply for proper water heater
operation.
Fresh air not taken from areas that contain negative pressure producing devices such as exhaust fans, replaces, etc.
Fresh air supply free of corrosive elements and flammable vapors.
• Fresh air openings sized correctly with consideration
given to the blocking effect of louvers and grilles.
• Ductwork is the same cross-sectional area as the
openings.
• Vent pipe and fittings of approved material.
Acceptable size, length, and number of elbows on
exhaust outlet pipe.
Installed in accordance with prevailing provisions of
local codes, or in the absence of such, National Fuel Gas Code, NFPA 54, ANSI Z223.1-Latest Edition. Canadian Installations must be performed in accordance with CAN/CGA-B149.
Slope 2” & 3” horizontal piping at a downward pitch
of 1/8” per 5ft. away from the water heater.
Not obstructed in any way.
Vent Termination
Horizontal
12” Min. above grade/snow level.
Slope 2” & 3” horizontal piping at a downward pitch
of 1/8” per 5ft. away from the water heater.
Away from corners, other vents, windows, etc.
Vertical
Outlet - 12” Min. above roof/snow level.
Water System Piping
Temperature and pressure relief valve properly installed with a discharge line run to an open drain and protected from freezing.
All piping properly installed and free of leaks.
• Heater completely fi lled with water.
Closed system pressure build-up precautions installed.
Tempering valve installed per manufacturer’s instructions.
Electrical Connections
Unit connected to a dedicated power supply.
Unit connected to a 120V electrical supply.
• Proper polarity.
Water heater properly grounded.
Installed in accordance with prevailing provisions of local codes, or in the absence of such, the latest edition of the National Electric Code, ANSI/NFPA 70 and/or the CSA C22.1, Electrical Code.
16
OPERATING YOUR WATER HEATER
Lighting Instructions
Read and understand these directions thoroughly before attempting to operate the water heater. Make sure the tank is completely fi lled with water before operating the water heater. Check the data plate near the gas control valve/thermostat for the correct gas. Do not use this water heater with any gas other than the one listed on the data plate. If you have any questions or doubts, consult your gas supplier or gas utility company.
L.P.G. (Bottled Propane) Models
Liquefi ed petroleum gas is over 50% heavier than air and in the occurrence of a leak in the system, the gas will settle at fl oor level. Basements, crawl spaces, skirted areas under mobile homes (even when ventilated), closets and areas below ground level will serve as pockets for the accumulation of gas. Before lighting an L.P. gas water heater, smell all around the appliance at oor level. If you smell gas, follow the instructions as given in the warning on the front page.
When your L.P. tank runs out of fuel, turn off the gas at all gas appliances including pilot lights. After the tank is refi lled, all appliances must be re-lit according to their manufacturer’s instructions.
17
Water Heater Operation
Figure 15 below shows the water heater’s sequence of operation when a call for heat is initiated. The ignition con­trol module will attempt to light the burner three times. If the ignition control does not detect ignition it will enter lock­out mode, indicated by a three flash error code.
FIGURE 15 Sequence of Operation
Burner Flames
Inspect the burner flames through the viewport and compare them to the drawings in Figure
16. A properly operating burner should produce a soft blue flame. Blue tips with yellow inner cones are satisfactory. The tips of the flame may have a slight yellow tint. The flame should not be all yellow or have a sharp blue-orange color. Contaminated air may cause an orange colored flame. Contact a qualified service technician if the flame is not satisfactory.
FIGURE 16 Flame Characteristics
The thermostat is adjusted to its lowest temperature when it is shipped from the factory. Water temperature can be regulated by moving the temperature dial to the preferred setting. The preferred starting point is 120°F (49°C). Align the index bar on the thermostat with the desired water temperature as shown in Figure 17. There is a hot water scald potential if the thermostat is set too high.
Important: Adjusting the thermostat past the 120°F (49°C) bar on the temperature dial will increase the risk of scald injury. Hot water can produce fi rst degree burns within:
120°F (49°C) more than 5 minutes 130°F (54°C) at 20 seconds 140°F (60°C) at 3 seconds 150°F (66°C) at 1-1/2 seconds 160°F (71°C) at less than 1 second
Note: During low demand periods when hot water is not being used, a lower thermostat setting will reduce energy losses and may satisfy your normal hot water needs. If hot water use is expected to be more than normal, a higher thermostat setting may be required to meet the increased demand. When leaving your home for extended periods (vacations, etc.) turn the temperature dial to its lowest setting. This will maintain the water at low temperatures with minimum energy losses and prevent the tank from freezing during cold weather.
Figure 17 Robertshaw Gas Valve/Thermostat Settings
Stacking
Stacking occurs when a series of short draws of hot water (3 gallons or less) are taken from the water heater tank. This causes increased cycling of the burner and can result in increased water temperatures at the hot water outlet. An anti-scald device is recommended in the hot water supply line to reduce the risk of scald injury.
Emergency Shut Down
Important: Should overheating occur or the gas supply fails to shut off, turn off the water heater’s manual gas control valve and call a qualified service technician.
18
Operational Conditions
Condensation
Moisture from the products of combustion condenses on the tank surface and the outside jacket of the water heater and forms drops of water which may fall onto the burner or other hot surfaces. This will produce a “sizzling” or “frying” noise. This condensation is normal and should not be confused with a leaking tank. Condensation may increase or decrease at different times of the year.
High effi cient energy saver water heaters will produce larger amounts of condensation on initial start-up or when a large amount of hot water is being used. Do not confuse this with a “tank leak”. Once the water reaches a temperature of 120°F (49°C) and the tank warms up (usually 1-2 hours), the condensation will stop.
Important: It is always recommended that a suitable drain pan be installed under the water heater to protect the area from water damage resulting from normal condensation production, a leaking tank or piping connections. Refer to “Location Requirements” on page 4. Under no circumstances is the manufacturer to be held responsible for any water damage in connection with this water heater.
Water Heater Sounds
During the normal operation of the water heater, sounds or noises may be heard. These noises are common and may result from the following:
1. Normal expansion and contraction of metal parts during periods of heat-up and cool-down.
2. Condensation causes sizzling and popping within the burner area and should be considered normal.
3. Sediment buildup in the tank bottom will create varying amounts of noise and may cause premature tank failure. Drain and fl ush the tank as directed under “Draining and Flushing”.
Smoke/Odor
The water heater may give off a small amount of smoke and odor during the initial start-up of the unit. This is due to the burning off of oil from metal parts of a new unit and will disappear after a few minutes of operation.
Anode Rod/Water Odor
Each water heater contains at least one anode rod, which will slowly deplete while protecting the glass-lined tank from corrosion and prolonging the life of the water heater. Certain water conditions will cause a reaction between this rod and the water. Once the anode is depleted, the tank will start to corrode, eventually developing a leak. The most common complaint associated with the anode rod is a “rotten egg smell” produced from the presence of hydrogen sulfi de gas dissolved in the water. Do not remove this
rod permanently as it will void any warranties, stated or implied. A special anode can be ordered if water odor or discoloration occurs. This rod may reduce but not eliminate water odor problems. The water supply system
may require special fi ltration equipment from a water conditioning company to successfully eliminate all water odor problems.
Artifi cially softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank.
The anode rod should be removed from the water heater tank every 3 years for inspection. If the rod is more than 50% depleted, the anode rod should be replaced.
In replacing the anode:
1. Turn off gas supply to the water heater.
2. Shut off the water supply and open a nearby hot water faucet to depressurize the water tank.
3. Drain approximately 5 gallons of water from tank (Refer to “Draining and Flushing” for proper procedures.) Close drain valve.
4. Remove old anode rod.
5. Use Tefl on® tape or approved pipe sealant on threads and install new anode rod.
6. Turn on water supply and open nearby hot water faucet to purge air from water system.
7. Restart the water heater as directed under “Operating Your Water Heater.” See the “Repair Parts Illustration” for anode rod location on page 24.
Safety Shut-off
This water heater is designed to automatically shut-off in the event of the following:
1. The water temperature exceeds 180°F (83°C.)
2. A blockage occurs in the combustion chamber air inlet,
the fl ue gas exhaust outlet, or both the inlet and outlet.
3. The blower fails to operate or operates improperly.
A high temperature limit switch or ECO (Energy Cut Off) in the tank is used to shut off the unit if the water temperature exceeds 180°F (83°C.) The ECO is a single use switch and requires complete replacement of the entire thermostat. If the ECO should function, the water heater cannot be used until the thermostat is replaced by a qualifi ed service technician. Contact your local dealer for service information.
19
MAINTENANCE OF YOUR WATER HEATER
Draining and Flushing
It is recommended that the tank be drained and fl ushed every 6 months to remove sediment which may build up during operation. The water heater should be drained if being shut down during freezing temperatures. To drain the tank, perform the following steps:
1. Turn off the gas to the water heater at the manual
gas shut-off valve.
2. Turn off the electrical supply to the water heater.
3. Close the cold water inlet valve.
4. Open a nearby hot water faucet.
5. Connect a hose to the drain valve and terminate it to
an adequate drain. Note: The drain hose should be rated for at least 200°F
(93°C). If the drain hose does not have this rating, open the cold water inlet valve and a nearby hot faucet until the water is no longer hot.
6. Open the water heater drain valve and allow all the
water to drain from the tank. Flush the tank with water as needed to remove sediment.
7. Close the drain valve, refi ll the tank, and restart the
heater as directed under “Operating Your Water Heater”.
If the water heater is going to be shut down for an extended period, the drain valve should be left open.
Important: Condensation may occur when refi lling the tank and should not be confused with a tank leak.
Routine Preventative Maintenance
At least annually, a visual inspection should be made of the venting and air supply system, piping systems, main burner, and pilot burner. Check the water heater for the following:
Obstructions, damage, or deterioration in the venting
system. Make sure the ventilation and combustion air supplies are not obstructed.
Build up of soot and carbon on the main burner and
pilot burner. Check for a soft blue fl ame.
Leaking or damaged water and gas piping.
• Presence of fl ammable or corrosive materials in the
installation area.
Presence of combustible materials near the water
heater.
Verify proper operation after servicing this water
heater. Important: If you lack the necessary skills required to
properly perform this visual inspection, you should not proceed, but get help from a qualifi ed service technician.
Temperature and Pressure Relief Valve
Manually operate the temperature and pressure relief valve at least once a year to make sure it is working properly (see Figure
14.) To prevent water damage, the valve must be properly connected to a discharge line which terminates at an adequate drain. Standing clear of the outlet (discharged water may be hot), slowly lift and release the lever handle on the temperature and pressure relief valve to allow the valve to operate freely and return to its closed position. If the valve fails to completely reset and continues to release water, immediately shut off the manual gas valve and the cold water inlet valve and call a qualifi ed service technician.
FIGURE 14 Temperature & Pressure Relief Valve
20
Replacement Parts
Replacement parts may be ordered through your plumber or the local distributor. Parts will be shipped at prevailing prices and billed accordingly. When ordering replacement parts, always have the following information ready:
1. model, serial, and product number
2. type of gas
3. item number
4. parts description
See pages 24 & 25 for a list of available repair parts.
Removing the Burner/Manifold Assembly
1. Turn off the gas to the water heater at the man­ual shut-off valve (See figure 2), and disconnect power to the water heater.
2. Depress the gas con­trol lever to turn it to the “OFF” position (Figure
17.)
3. Remove the outer doors.
4. Remove the 2 screws securing the manifold door assembly to the skirt.
5. Disconnect the pilot tube, the igniter wire and manifold tube at the thermostat. (Figure 19) Note: L.P. gas systems use reverse (left-hand) threads on the manifold tube.
6. Grasp the manifold tube and push down slightly to free themanifold, and pilot tube.
7. Carefully remove the manifold assembly from the burner compartment. Be sure not to damage internal parts.
8. Check the burner to see if it is dirty or clogged. The burner may be cleaned with soap and hot water.
FIGURE 19 Gas Valve/Manifold Assembly
FIGURE 20A Natural Gas Burner Assembly
FIGURE 20B 50K BTU/Hr L.P. Gas Burner Assembly
L.P. Gas Burner - 42K BTU Models
1. Separate the pilot bracket from the L.P. burner by removing screw.
2. Loosen set screw located on top of the L.P. burner near the manifold door. Carefully, pull the burner away from the manifold door assembly.
3. Check the burner to see if it is dirty or clogged. The burner may be cleaned with soap and hot water (Figure 21).
Removing the Burner from the Manifold Assembly
Natural Gas Burner & 50K BTU/Hr L.P. Models
1. Take off the burner by removing the two (2) screws located underneath the burner.
2. Check the burner to see if it is dirty or clogged. The burner may be cleaned with soap and hot water (See Figure 20A-Natural Gas, See Figure 20B-L.P. Gas).
FIGURE 21 L.P. Burner Assemblies
21
Replacing the Manifold Assembly
1. Check the door gasket for damage or imbedded debris prior to installation.
2. Inspect the viewport for damage and replace as required.
3. Insert the manifold assembly into the burner compartment making sure that the tab of the manifold tube engages in the slot of the bracket inside the combus­tion chamber (Figure
22). The tab is locat­ed at the bottom of the burner for L.P. Models.
4. Inspect the door gasket and make sure there is no fiber­glass insulation between the gasket and the combustion chamber.
5. Replace the two screws which secure the manifold assembly door to the combustion chamber. Tighten securely. There should be no space between the gasket part of the manifold door and combustion chamber. Do
not operate the water heater if the door gasket is not sealed
6. Reconnect the manifold tubing and pilot tubing to the thermostat. Do not cross-thread or apply any thread sealant to these fittings.
Note: L.P. gas systems use reverse (left-hand) threads on the manifold tube.
7. Reconnect the igniter wire.
8. Turn gas supply on and refer to the “Lighting Instructions” on page 17.
9. Check for leaks. Use a chloride-free soap and water solu­tion (bubbles forming indicate a leak) or other approved method. All leaks must be fixed immediately.
10. Replace the outer door.
FIGURE 22 Manifold Tab
Removing and Replacing the Gas Control Valve/Thermostat
Important: Use only factory authorized replacement parts.
1. On the gas control valve/thermostat turn the tem­perature dial counterclockwise to its lowest setting. Depress the gas control lever to turn it to the “OFF” position (Figure 17).
2. Turn off the gas at the manual shut-off valve on the gas supply pipe (Figure 2).
3. Drain the water heater. Refer to the section of “Draining and Flushing” on page 20 and follow the pro­cedure.
4. Disconnect the igniter wire from the thermostat. Disconnect the manifold and pilot tube at the thermo­stat (Figure 19). Note: L.P. gas systems use reverse (left-hand) threads on the manifold tube.
5. Refer to “Gas Piping” (Figure 2) and disconnect the ground joint union in the gas piping. Disconnect the remaining pipe from the gas valve/thermostat.
Important: When removing the gas control valve/ thermostat do not use pipe wrench or vise to grip body. Do not insert any type of blunt instr ument into the inlet or outlet connections. Using these t ype tools may result in damage to the gas control valve/ther mostat.
6. Turn the gas control valve/thermostat counter-clock­wise. Remove the gas control valve/thermostat.
To replace the gas control valve/thermostat, reassemble in reverse order. Use only factory authorized replacement parts.
Be sure to use approved Teflon tape or pipe joint com­pound on the gas piping connections and fitting on the back of the gas valve that screws into tank.
Be sure to remove the pilot ferrule nut from the new gas control valve/thermostat.
Turn gas supply on and check for leaks. Use a chloride­free soap and water solution (bubbles forming indicate a leak) or other approved method.
Be sure tank is completely filled with water before light­ing and activating the water heater. Follow the “Lighting Instructions” on page 17.
If additional information is required, contact the Service Department at: 1-800-456-9805.
22
TROUBLESHOOTING FLOWCHART
23
REPAIR PARTS ILLUSTRATION
When ordering repair parts always give the following information:
1. Model, serial and product number
2. Type of gas
3. Item number
4. Parts description
7
1
5
4
Repair Parts List
Item
No.
1 Blower 2 Outlet Pressure Switch (Not Pictured) 3 Flue Baffle 4 Heat Trap (Cold) 5 Heat Trap (Hot) 6 Cold Water Dip Tube 7 Anode Rod* 8 Temperature and Pressure Valve
9 Drain Valve 10 Gas Valve/Thermostat 11 Restrictor Plate 12 Pilot Assembly - Natural Gas/L.P. Gas** 13 Natural Gas Burner 14 L.P. Gas Burner** 15 Manifold Door Assembly - Natural Gas 16 Manifold Door Assembly - L.P. Gas** 17 Two Piece Wire Connector w/Retainer Clip** 18 Manifold Door Gasket** 19 Viewport Assembly** 20 Outer Door
* Special anode rod available, see page 19. ** Pictured on next page.
Parts Description
15
13
6
3
11
8
10
9
20
24
Listed Parts Kits and Illustrations
Item 12: Pilot Assembly. (Note: Pilot Assembly is specific to type of gas, please specifiy model for correct assembly.) Item 13: Burner (Natural Gas) Item 14: Burner (L.P. Gas) 42K BTU/Hr & 50T60 Models Item 15: Manifold door assembly which contains the manifold tube, gasket, door, pilot tube, two piece wire connector with retainer clip, and pilot assembly. (Natural Gas) Item 16: Manifold door assembly which contains the manifold tube, gasket, door, pilot tube, two piece wire connector with retainer clip, and pilot assembly. (L.P. Gas) Item 17: Contains two piece wire connector with retainer clip. Item 18: Contains manifold door gasket. Item 19: Contains viewport.
ITEM 12
ITEM 15 ITEM 16
ITEM 13
ITEM 14
ITEM 17
© 2004 American Water Heater Company, All Rights Reserved. Printed in the U.S.
ITEM 18
ITEM 19
25
Loading...