Powerex SBS0307, BSB1307, SBS0507, SBS1517, STS030 User Manual

...
Scroll Tankmount/Basemount Air Compressors
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Description
GENERAL
The Powerex Oilless Rotary Scroll Air Compressor has advanced scroll compressor technology through the development of a completely oilless unit. The Powerex Scroll Compressor offers a dynamically balanced air end which insures vibration-free operation. The rotary design permits a continuous 100% duty cycle. No oil separation, oil fi ltration, or inlet valves are required on the Powerex Scroll unit.
COMPRESSION CYCLE
The Powerex oilless rotary scroll air compressor is based on the theory of scroll compression. A scroll is a free standing, intricate spiral bounded on one side by a solid, fl at plane or base. A scroll set, the basic compression element of a scroll compressor, is made up of two identical spirals which form right and left hand parts. One of these scroll components is indexed or phased 180° with respect to the other so the scrolls can mesh. Crescent-shaped gas pockets are formed and bounded by the spirals and the base plate of both scrolls. As the moving scroll is orbited around the fi xed scroll, the pockets formed by the meshed scrolls follow the spiral toward the center and diminish in size. The moving scroll is prevented from rotating during this process so the 180° phase relationship of the scrolls is maintained. The compressor’s inlet is at the outer boundary of the scrolls. The compressed gas is discharged through the outlet at the center of the fi xed scroll so no valves are needed.
TIP SEAL
The tip seal on the scroll compressor is self-lubricated and allows the unit to operate effi ciently without oil and expensive fi ltration. On standard pressure units, the tip seal should be replaced every 10,000 hours of operation. On high pressure units, the tip seal should be replaced every 5,000 hours of operation.
BEARINGS
The bearings on the scroll compressor are regreaseable to allow extended compressor life. For standard pressure units, service should be performed every 10,000 hours of operation. For high pressure units, service should be performed every 5,000 hours of operation.
DRY TYPE INLET FILTER (P/N ST073925AV)
Order element P/N ST073921AV for both the 3 HP and 5HP units. Change every 2,500 hours or more often in dirty locations.
Figure 1 - SBS Scroll Basemount Simplex
Specifi cations
Product
Performance Specifi cations
California Ordinance 462 (L) (2)
Compression Cycle Scroll
Control Panel UL508A Listed (panels are optional)
Drive 2 - 3V Belts
Lubrication Grease fi lled bearings
Motor Overload Protection IEC Motor overload relay (optional)
Operating Temperature 34° F - 104° F (1° C thru 40° C) at inlet
Operating Voltages
Outlet Air Connections
Overpressure Protection
Standard Pressure Settings
High Pressure Settings
Tank Isolation Standard tank mount units
Tank Size (Tankmount Units)
STS, STD, SBS Scroll or STSH, STDH, SBSH High Pressure Scroll Tankmount / Basemount Air Compressors
See Page 2
Tankmount units meet the requirements of this ordinance
280-230 Volts, 60 Hz 3Ø 208-320/460 Volts, 60 Hz
1/2 inch Basemount 3/4 inch NPT Tankmount
ASME safety valve factory set and sealed
Simplex: 95-115 psi Duplex: 90-110 psi; 95-115 psi
Simplex: 115-145 psi Duplex: 110-140 psi; 115-145 psi
Simplex Units: 30 and 60 gallon ASME Rated 200 psig Duplex Units: 80 and 120 gallon ASME Rated 200 psig
Powerex • 150 Production Drive • Harrison, OH 45030 • USA 1-888-769-7979 • www.powerexinc.com
IN258910AV 1/14
Scroll Air Compressors Tankmount/Basemount
Performance Specifi cations
Model HP Phase SCFM @ 100 psig SCFM @ 145 psig Voltage Gallon Tank
Scroll
Basemount
Simplex -
Model SBS
Scroll
Tankmount
Simplex -
Model STS
Scroll
Tankmount
Duplex -
Model STD
SBS0307 3 3 8.8 7.1
SBS1307 3 1 8.8 7.1 Basemount
SBS0507 5 3 15.2 12.5
SBS1517 5 1 15.2 12.5 Basemount
STS030 3 3 8.8 7.1
STS130 3 1 8.8 7.1 30 / 60
STS050 5 3 15.2 12.5
STS151 5 1 15.2 12.5 30 / 60
STD030 3 (2) 3 17.6 14.2
STD130 3 (2) 1 17.6 14.2 80
STD050 5 (2) 3 30.4 25.0
STD151 5 (2) 1 30.4 25.0 80 / 120
208-230 / 460
115 / 230
208-230 / 460
208-230
208-230 / 460
115 / 230
208-230 / 460
208-230
208-230 / 460
115 / 230
208-230 / 460
208-230
NOTE: All high pressure models have an “H” at the end of the model identifi cation. These units are measured at 145 psig.
NOTE: For system electrical information (including motor FLA ratings), see the wiring diagram shipped with the unit.
Basemount
Basemount
30 / 60
30 / 60
80 / 120
80
MODEL STD MODEL STS MODEL SBS
Figure 2 - Standard model confi guration and optional equipment
Refrigerated Air Dryer Option
Refrigerated Air Dryer Option
MODEL STD WITH MODEL STS WITH
OPTIONAL EQUIPMENT OPTIONAL EQUIPMENT
2
Scroll Air Compressors Tankmount/Basemount
Installation
HOURMETER
The hourmeter on the scroll compressor indicates the actual number of hours the unit has been in operation. The hourmeter is also used to determine maintenance and service timing. An hourmeter must be installed with every
Scroll compressor.
CONDENSATE DRAIN VALVE
A condensate drain valve must be installed on every tank to allow removal of the liquid which will collect during compressor operation.
Drain liquid from tank daily.
Safety Guidelines
This manual contains information that is very important to know and understand. This information is provided for SAFETY and to PREVENT EQUIPMENT PROBLEMS. To help recognize this information, observe the following symbols.
Danger indicates an imminently hazardous
situation which, if not avoided, WILL result
in death or serious injury.
Notice indicates important information,
that if not followed, may cause damage to
equipment.
NOTE: Information that requires special attention.
RECEIVING THE UNIT
Immediately upon receipt of the scroll compressor, the unit should be inspected for any damage which may have occurred in shipment. Any shipping damage must be immediately fi led with the freight carrier.
The compressor nameplate should be checked to see if the unit is the correct model and voltage as ordered.
APPLICATION
When the scroll compressor is to be used in applications other than the compressing of atmospheric air, please contact a Powerex representative for engineering and warranty information at 1-888-769-7979.
INSTALLATION SITE
1. The scroll compressor must be located in a clean, well lit and well ventilated area.
2. The area should be free of excessive dust, toxic or fl ammable gases, moisture, water and direct sunlight.
3. Never install the compressor where the ambient temperature is higher than 104° F or where humidity is high.
MINIMUM CLEARANCES
Above 24 inches
Drive belt side 12 inches
Other sides 20 inches
Breathable Air Warning
This compressor/pump is not equipped and should not be used “as is” to supply breathing quality air. For any application of air for human consumption, you must fi t the air compressor/pump with suitable in-line safety and alarm equipment. This additional equipment is necessary to properly fi lter and purify the air to meet minimal specifi cations for Grade D breathing as described in Compressed Gas Association Commodity Specifi cation G 7.1 - 1966, OSHA 29 CFR
1910. 134, and/or Canadian Standards Associations (CSA).
DISCLAIMER OF WARRANTIES
IN THE EVENT THE COMPRESSOR IS USED FOR THE PURPOSE OF BREATHING AIR APPLICATION AND PROPER IN-LINE SAFETY AND ALARM EQUIPMENT IS NOT SIMULTANEOUSLY USED, EXISTING WARRANTIES SHALL BE VOIDED, AND POWEREX DISCLAIMS ANY LIABILITY WHATSOEVER FOR ANY LOSS, PERSONAL INJURY OR DAMAGE.
4. Clearance must allow for safe, effective inspection and maintenance.
5. If necessary, use metal shims or leveling pads to level the compressor tank or basemount unit. Never use wood to shim the unit.
VENTILATION
1. If the scroll compressor is located in a totally enclosed room, an exhaust fan with access to outside air must be installed.
2. Never restrict the cooling fan exhaust air.
3. Never locate the compressor where hot exhaust air from other heat generating units may be pulled into the unit.
WIRING
Refer to the general product manual. All electrical hook-ups must be performed by a qualifi ed electrician. Installations must be in accordance with local and national electrical codes.
Use solderless terminals to connect the electric power source.
3
Scroll Air Compressors Tankmount/Basemount
Installation (Continued)
PIPING
General Guidelines
Refer to the general product manual.
1. Make sure the piping is lined up without being strained or twisted when assembling the piping for the compressor.
2. Appropriate expansion loops or bends should be installed at the compressor to avoid stresses caused by changes in hot and cold conditions.
3. Piping supports should be anchored separately from the compressor to reduce noise and vibration.
4. Never use any piping smaller than the compressor outlet connection.
5. Use fl exible hose to connect the outlet of the compressor to the piping so that the vibration of the compressor does not transfer to the piping.
Remote Intake Piping
Powerex Compressor Systems with pipe thread connectors on the intake fi lters are intended for installation with remote air intake. Piping for the remote intake system must be installed at the fi nal operating site.
Under some conditions, the intake piping may facilitate the condensation of humidity in the intake air stream into liquid water.
The intake fi lters supplied by Powerex will
not stop ingestion of liquid water by the pumps. Liquid water going into the pumps will damage the pumps and void the warranty.
Always install drip legs with suffi cient capacity to capture liquid water in the intake piping before the air fi lters. Drip legs must be sized with low enough air velocity to make sure they are effective at capturing liquid water in the intake air and must be maintained (drained) at frequent intervals to make sure they remain effective.
Operation
BEFORE START UP
1. Make sure all safety warnings, labels and instructions have been read and understood before continuing.
2. Remove any shipping materials, brackets, etc.
3. Confi rm that the electric power source and ground have been fi rmly connected.
4. Be sure all pressure connections are tight.
5. Check to be certain all safety relief valves, etc., are correctly installed.
6. Check that all fuses, circuit breakers, etc., are the proper size.
7. Make sure the inlet fi lter is properly installed.
8. Confi rm that the drain valve is closed.
START-UP AND OPERATION
1. Follow all the procedures under “Before start-up” before
attempting operation of the compressor.
2. Switch the electric source breaker on.
3. Open the tank discharge valve completely.
4. Check that the compressor operates without excessive vibration, unusual noises or leaks.
5. Close the discharge valve completely.
6. If the pressure does not rise on a three phase unit, turn the unit off. Have a qualifi ed electrician switch the breaker OFF and exchange the L1 and L2 connections (two out of three phases of electric source) inside the magnetic starter enclosure.
7. Check the discharge pressure. Also make sure the air pressure rises to the designated pressure setting by checking the discharge pressure gauge.
8. Check the operation of the pressure switch by opening the tank outlet valve and confi rming the compressor starts as pressure drops.
SAFETY VALVES
Tank mounted compressors are shipped from the factory with safety valves installed in the tank. The fl ow capacity of the safety valve is equal to or greater than the capacity of the compressor.
1. The pressure setting of the safety valve must be no higher than the maximum working pressure of the tank.
2. Safety valves should be placed ahead of any possible blockage point in the system, i.e. shutoff valve.
3. Avoid connecting the safety valve with any tubing or piping.
4. Manually operate the safety valve every six months to avoid sticking or freezing.
4
Figure 3 - SBS and SBSH Scroll Basemount Simplex
Scroll Air Compressors Tankmount/Basemount
NAMEPLATE
Scroll Air End
Aftercooler
Figure 4 - STS and STSH Scroll Tankmount
Scroll Air EndAftercooler Scroll Air EndAftercooler
Pressure Switch
Starter
ASME Receiver 30 / 60 Gallon
Electric Auto Drain (optional)
Motor 2, 3, or 5 HP
Lead Pressure
Switch
Alternator
Panel
Beltguard
Pulley (inside beltguard)
Belt (inside beltguard)
3/4 inch NPT Outlet (either end)
Motor 2, 3, or 5 HP
Beltguard
Pulley (inside beltguard)
Belt (inside beltguard)
1/2 inch NPT Outlet
Figure 5 - STD and STDH Scroll Tankmount Duplex
Lag Pressure
Switch
ASME
Electric Auto Drain (optional)
Receiver 80 / 120 Gallon
5
Scroll Air Compressors Tankmount/Basemount
Maintenance
Operating Hours
Item Action needed 500 2500 5000 10,000 15,000 20,000 30,000 Remarks
Pump Replace
Tank Drain moisture Daily
Inlet air fi lter Inspect,
Replace
Blower fan Clean
Fan duct Clean
Compressor fi ns Clean
Bearings Grease
Bearings Grease
Tip seal Replace
Tip seal Replace
Heat insulation pipe
Heat insulation pipe
V-belt Inspect,
Pressure switch Confi rm
Magnetic starter
Safety valve Confi rm
Pressure gauge Inspect
Inspect
Replace
Maintenance requirements for high pressure units.
Replace
Replace
Replace
operation
Inspect
operation
●▲
* Note
3
●▲▲▲▲
(Every 2,500 hrs or less) Element ST073921AV
(Every 2,500 hrs or less)
(Every 2,500 hrs or every 6 months, whichever comes fi rst)
(Every 2,500 hrs or less)
●●●●
●●●●
▲▲
▲▲▲▲
▲▲
▲▲▲▲
▲▲
▲▲▲▲▲
●●
●●
Part #
Service Center Only
Service Center Only
Every 10,000 hours
Every 5,000 hours
Every 10,000 hours
Every 5,000 hours
Replace if contact points deteriorated
Notes: 1. Inspect and perform maintenance periodically according to maintenance schedule.
2. The maintenance schedule relates to the normal operating conditions. If the circumstances and load condition are
adverse, shorten the cycle time and do maintenance accordingly.
3. * The tension of the V-belt should be adjusted during the initial stage and inspected every 2,500 hours afterwards.
Proper belt tension for 3 HP units is 7 lbs/0.19” defl ection; for 5 HP units, 7 lbs/0.19” defl ection.
4. See Compressor Pump Manuals for replacement or service procedures.
6
Loading...
+ 14 hidden pages