Powerex SBS0507, SBS0307, SBS1307, SBS1517 User Manual

Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or prop­erty damage! Retain instructions for future reference.
Powerex • 150 Production Drive • Harrison, OH 45030 • USA
Descriptions
GENERAL
The Powerex Oilless Rotary Scroll Air Compressor has advanced scroll com­pressor technology through the devel­opment of a completely oilless unit. The Powerex Scroll Compressor offers a dynamically balanced air end which insures vibration-free operation. The rotary design permits a continuous 100% duty cycle. No oil separation, oil filtration, or inlet valves are required on the Powerex Scroll unit.
COMPRESSION CYCLE
The Powerex oilless rotary scroll air compressor is based on the theory of scroll compression. A scroll is a free standing, intricate spiral bounded on one side by a solid, flat plane or base. A scroll set, the basic compression ele­ment of a scroll compressor, is made up of two identical spirals which form right and left hand parts. One of these scroll components is indexed or phased 180
o
with respect to the other so the scrolls can mesh. Crescent-shaped gas pockets are formed and bounded by the spirals and the base plate of both scrolls. As the moving scroll is orbited around the fixed scroll, the pockets formed by the meshed scrolls follow the spiral toward the center and dimin­ish in size. The moving scroll is prevent­ed from rotating during this process so the 180
o
phase relationship of the scrolls is maintained. The compressor’s inlet is at the outer boundary of the scrolls. The compressed gas is dis­charged through the outlet at the cen­ter of the fixed scroll so no valves are needed.
Scroll Tankmount/Basemount Air Compressors
TIP SEAL
The tip seal on the scroll compressor is self-lubricated and allows the unit to operate efficiently without oil and expensive filtration. The tip seal should be replaced every 10,000 hours of operation.
BEARINGS
The bearings on the scroll compressor are regreaseable to allow extended compressor life. Service should be per­formed every 10,000 hours of opera­tion.
DRY TYPE INLET FILTER (P/N 91348550)
Order P/N 91348550 for both the 3 HP and 5HP units. Change every 2,500 hours or more often in dirty locations.
HOURMETER
The hourmeter on the scroll compres­sor indicates the actual number of hours the unit has been in operation. The hourmeter is also used to deter­mine maintenance and service timing.
An hourmeter must be installed with every Scroll compressor.
CONDENSATE DRAIN VALVE
A condensate drain valve must be installed on any tank used to allow removal of the liquid which will collect during compressor operation.
Drain liquid from tank daily.
!
NOTICE
IN258902AV 9/06
PURE AIR TECHNOLOGY
Breathable Air Warning
This compressor/pump is NOT equipped and should NOT be used “as is” to supply breathing quality air. For any application of air for human consumption, you must fit the air compressor/pump with suitable in-line safety and alarm equipment. This additional equip­ment is necessary to properly filter and purify the air to meet minimal specifications for Grade D breath­ing as described in Compressed Gas Association Commodity Specification G 7.1 - 1966, OSHA 29 CFR 1910. 134, and/or Canadian Standards Associations (CSA).
DISCLAIMER OF WARRANTIES IN THE EVENT THE COMPRESSOR IS USED FOR THE PURPOSE OF BREATHING AIR APPLICATION AND PROPER IN-LINE SAFETY AND ALARM EQUIPMENT IS NOT SIMULTANEOUSLY USED, EXIST­ING WARRANTIES ARE VOIDED, AND POWEREX DISCLAIMS ANY LIABILITY WHATSOEVER FOR ANY LOSS, PERSONAL INJURY OR DAMAGE.
!
DANGER
2
Scroll Air Compressors Tankmount/Basemount
Installation
RECEIVING THE UNIT
Immediately upon receipt of the scroll compressor, the unit should be inspect­ed for any damage which may have occurred in shipment. Any shipping damage must be immediately filed with the freight carrier.
The compressor nameplate should be checked to see if the unit is the correct model and voltage as ordered.
APPLICATION
When the scroll compressor is to be used in applications other than the compressing of atmospheric air, please contact a Powerex representative for engineering and warranty information at 1-888-769-7979.
INSTALLATION SITE
1. The scroll compressor must be locat­ed in a clean, well lit and well venti­lated area.
2. The area should be free of excessive dust, toxic or flammable gases, mois­ture, water and direct sunlight.
3. Never install the compressor where the ambient temperature is higher than 104
o
F or where humidity is high.
4. Clearance must allow for safe, effec­tive inspection and maintenance.
5. If necessary, use metal shims or leveling pads to level the compressor. Never use wood to shim the compressor.
VENTILATION
1. If the scroll compressor is located in a totally enclosed room, an exhaust fan with access to outside air must be installed.
2. Never restrict the cooling fan exhaust air.
3. Never locate the compressor where hot exhaust air from other heat gen­erating units may be pulled into the unit.
WIRING
Refer to the general product manual. All electrical hook-ups must be per­formed by a qualified electrician. Installations must be in accordance with local and national electrical codes.
Use solderless terminals to connect the electric power source.
PIPING
Refer to the general product manual.
1. Make sure the piping is lined up without being strained or twisted when assembling the piping for the scroll compressor.
2. Appropriate expansion loops or bends should be installed at the com­pressor to avoid stresses caused by changes in hot and cold conditions.
3. Piping supports should be anchored separately from the compressor to reduce noise and vibration.
4. Never use any piping smaller than the compressor connection.
5. Use flexible hose to connect the out­let of the compressor to the piping so that the vibration of the compressor does not transfer to the piping.
SAFETY VALVES
Tank mounted compressors are shipped from the factory with safety valves installed in the tank. The flow capacity of the safety valve is equal to or greater than the capacity of the compressor.
1. The pressure setting of the safety valve must be no higher than the maximum working pressure of the tank.
2. Safety valves should be placed ahead of any possible blockage point in the system, i.e. shutoff valve.
3. Avoid connecting the safety valve with any tubing or piping.
4. Manually operate the safety valve every six months to avoid sticking or freezing.
Operation
BEFORE START UP
1. Make sure all safety warnings, labels and instructions have been read and understood before continuing.
2. Remove any shipping materials, brackets, etc.
3. Confirm that the electric power source and ground have been firmly connected.
4. Be sure all pressure connections are tight.
5. Check to be certain all safety relief valves, etc., are correctly installed.
6. Check that all fuses, circuit breakers, etc., are the proper size.
7. Make sure the inlet filter is properly installed.
8. Confirm that the drain valve is closed.
9. Visually check the rotation of the compressor pump. If the rotation is incorrect, have a qualified electrician correct the motor wiring.
START-UP AND OPERATION
1. Follow all the procedures under “Before start-up” before attempting operation of the compressor.
2. Switch the electric source breaker on.
3. Open the tank discharge valve com­pletely.
4. Check that the compressor operates without excessive vibration, unusual noises or leaks.
5. Close the discharge valve completely.
6. If the pressure does not rise on a three phase unit, turn the unit off. Have a qualified electrician switch the breaker OFF and exchange the L1 and L2 connections (two out of three phases of electric source) inside the magnetic starter enclosure.
7. Check the discharge pressure. Also make sure the air pressure rises to the designated pressure setting by check­ing the discharge pressure gauge.
8. Check the operation of the pressure switch by opening the tank outlet valve and confirming the compressor starts as pressure drops.
Minimum Clearances
Above 24”
Drive belt side 12”
Other sides 20”
3
Scroll Air Compressors Tankmount/Basemount
RESET
RESET
Figure 1 - SBS Scroll Basemount Simplex
Figure 2 - STS Scroll Tankmount
Figure 3 - STD Scroll Tankmount Duplex
Aftercooler
Scroll Air End
Pressure Switch
Starter
ASME Receiver 30/60 Gallon
Auto Drain (optional)
ASME Receiver 30/60 Gallon
Beltguard
Pulley
Belt
3/4” NPT Outlet
Aftercooler
Scroll Air End
Aftercooler
Scroll Air End
ASME Receiver Tank
Lag Pressure Switch
Starter
Lead Pressure Switch
Motor 3 or 5 HP
Beltguard
Pulley
Belt
3/4” NPT Outlet
4
Scroll Air Compressors Tankmount/Basemount
SCFM Full Load Gallon Dimension Ship
Model HP Phase @100 PSIG Voltage Amperage Tank LxWxH Weight (Lbs.)
SBS0307 3 3 8.6 208/230/460 8.7/8.0/4.0 Basemount 29x19x19 160 SBS1307 3 1 8.6 230 17 Basemount 29x19x19 175 SBS0507 5 3 14.7 208/230/460 13.7/13.2/6.6 Basemount 29x19x19 180 SBS1517 5 1 14.7 230 25 Basemount 29x19x19 190
Specifications
Scroll Basemount Simplex - Model SBS
SCFM Full Load Gallon Dimension Ship
Model HP Phase @100 PSIG Voltage Amperage Tank LxWxH Weight (Lbs.)
STS030 3 3 8.6 208/230/460 8.7/8.0/4.0 30 / 60 39x22x35 / 51x23x39 280 / 390 STS130 3 1 8.6 230 17 30 / 60 39x22x35 / 51x23x39 295 / 405 STS050 5 3 14.7 208/230/460 13.7/13.2/6.6 30 / 60 39x22x35 / 51x23x39 300 / 410 STS151 5 1 14.7 230 25 30 / 60 39x22x35 / 51x23x39 310 / 420
Scroll Tankmount Simplex - Model STS
SCFM Full Load Gallon Dimension Ship
Model HP Phase @100 PSIG Voltage Amperage Tank LxWxH Weight (Lbs.)
STD030 3 (2) 3 17.2 208/230/460 17.4/16.0/8.0 80 64x26x40 650 STD130 3 (2) 1 17.2 230 34 80 64x26x40 680 STD050 5 (2) 3 29.4 208/230/460 27.4/26.4/13.2 80 / 120 64x26x40 / 71x35x75 690 / 715 STD151 5 (2) 1 29.4 230 50 80 / 120 64x26x40 / 71x35x75 710 / 735
Scroll Tankmount Duplex - Model STD
Refrigerated or Desiccant Dryers
Magnetic Starter
Automatic Drain
Corrosion Resistant Tanks
MODEL SBS MODEL STS MODEL STD OPTIONAL EQUIPMENT
RESET
RESET
5
Maintenance Schedule
Operating Hours
Item Action needed 500 2500 5000 10,000 15,000 20,000 Remarks
Tank Drain moisture Daily
Inlet air filter Replace (Every 2,500 hrs or less) Part #91348550
Blower fan Clean 
Fan Duct Clean 
Compressor Fins Clean (Every 2,500 hrs or less)
Bearings Grease Service Center Only
Tip seal Replace 
Dust seal Replace 
V-belt Inspect, replace *Note 3 
Pressure Switch Confirm operation 
Magnetic starter Inspect Replace if contact
points deteriorated
Safety valve Confirm operation (Every 2,500 hrs or less)
Pressure gauge Inspect (Every 2,500 hrs or less)
Inspect
Replace
NOTES:
1. Inspect and perform maintenance periodically according to maintenance schedule.
2. The maintenance schedule relates to the normal operating conditions. If the circumstances and load condition are adverse,
shorten the cycle time and do maintenance accordingly.
3. * The tension of the V-belt should be adjusted during the initial stage and inspected every 2,500 hours afterwards. Proper
belt tension for 3 HP units is 7 lbs./.16” deflection; for 5 HP units, 7 lbs./.19” deflection.
4. See Compressor Pump Manuals for replacement or service procedures.
Scroll Air Compressors Tankmount/Basemount
6
Scroll Air Compressors Tankmount/Basemount
Electrical Wiring Diagram - Simplex
Figure 4 - 3-5 HP Basemount/Simplex Single-Phase 208/230 Volts
Field furnished
power supply
Disconnect
Red
Black
Motor
Red Red
Pressure
electric
switch
L1
L2
T1
T2
Open
Red
Black
Red
Red
Red
Red
Black
Red
Blank
Main disconnect and branch circuit protection to be installed by a
qualified electrician in accordance with national and local codes.
Loading...
+ 14 hidden pages