PM800HSA120
Powerex, Inc., 200 Hillis Street, Youngwood, Pennsylvania 15697-1800 (724) 925-7272
A
D
Q
AMP
TYP
TYP
DD
E
V SQ.(5 PLACES)
TYP
E
AA
B
P
C
C
Tm
E
BB
C
R (2 REQD)
X
12 345
W
∅K
∅L
∅M
H
J
1
VI
1.5 OHM
Rfo
FO
5
2
SR
3
CI
4
VC
C1
300 pf
S ∅
(4 HOLES)
G
T
F CC
N
TEMP
OUT1
OUT2
SENS
SINK
Rref
VCC
FO
SR
IN
GND
Outline Drawing and Circuit Diagram
Dimensions Inches Millimeters
A 3.94 100.0
B 5.20 132.0
C 1.33 +0.04/-0.02 33.7 +1.0/-0.5
D 3.23±0.010 82.0±0.25
E 4.33±0.010 110.0±0.25
F 2.84 72.0
G 1.42 36.0
H 0.53 13.5
J 0.06 1.5
K 0.17 4.4
L 0.15 3.8
M 0.06 1.5
Dimensions Inches Millimeters
Q 0.10 2.54
R M8 Metric M8
SØ 6.5 Ø 6.5
T 1.02 26.0
U 0.26 6.5
V 0.025 0.64
W 0.20 5.0
X 1.97 50.0
AA 0.71 18.0
BB 0.55 14.0
CC 0.39 10.0
DD 1.14. 29.0
N 0.35 9.0
P 0.53 13.5
Intellimod™ Module
Half Phase
IGBT Inverter Output
800 Amperes/1200 Volts
Description:
Powerex Intellimod™ Intelligent
Power Modules are isolated base
modules designed for power
switching applications operating
at frequencies to 20kHz. Built-in
control circuits provide optimum
gate drive and protection for the
IGBT and free-wheel diode
power devices.
Features:
□ Complete Output Power
Circuit
□ Gate Drive Circuit
□ Protection Logic
– Short Circuit
–Over Current
–Over Temperature
– Under Voltage
Applications:
□ Inverters
□ UPS
□ Motion/Servo Control
□ Power Supplies
Ordering Information:
Example: Select the complete
part number from the table below
-i.e. PM800HSA120 is a 1200V,
800 Ampere Intellimod™ Intelligent
Power Module.
Type Current Rating V
Amperes Volts (x 10)
PM 800 120
CES
1
Powerex, Inc., 200 Hillis Street, Youngwood, Pennsylvania 15697-1800 (724) 925-7272
PM800HSA120
Intellimod™ Module
Half Phase IGBT Inverter Output
800 Amperes/1200 Volts
Absolute Maximum Ratings, T
Characteristics Symbol PM800HSA120 Units
Power Device Junction Temperature T
Storage T emper ature T
Case Operating Temperature T
Mounting Torque, M6 Mounting Screws — 26 in-lb
Mounting Torque, M8 Main Terminal Screws — 95 in-lb
Module Weight (T ypical) — 1700 Grams
Supply Voltage Protected by OC and SC (VD = 13.5 - 16.5V, Inverter Part) V
Isolation Voltage, AC 1 minute, 60Hz Sinusoidal V
= 25°C unless otherwise specified
j
j
stg
C
CC(prot.)
RMS
-20 to 150 °C
-40 to 125 °C
-20 to 100 °C
800 Volts
2500 Volts
Control Sector
Supply Voltage Applied between (V1-VC)V
Input Voltage Applied between (C1-VC)V
Fault Output Supply Voltage (Applied between Fo-Vc)V
Fault Output Current I
D
CIN
FO
FO
20 Volts
10 Volts
20 Volts
20 mA
IGBT Inverter Sector
Collector-Emitter Voltage (VD = 15V, V
Collector Current, ± I
Peak Collector Current, ± I
Collector Dissipation P
= 5V) V
CIN
CES
C
CP
C
1200 Volts
800 Amperes
1600 Amperes
4630 Watts
2