PolyGard SPC-1110 User Manual

PolyGard SPC-1110
Carbon monoxide (CO) gas detection and control system
serial no. SPC-1110-0 00 0
User Manual
April 01, 2004
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Carbon monoxide (CO) gas detection and control system
Page 2
1 General Overview
2 Description
3 Installation
3.1 Mounting locations.................................................................................................................. 5
3.2 Enclosure ............................................................................................................................... 5
............................................................................................................................... 3
................................................................................................................................5
4 Electrical Connection
4.1 Instructions............................................................................................................................. 6
4.2 Wiring connection................................................................................................................... 7
5 Start-up Operation
5.1 Set trip/setpoints..................................................................................................................... 8
5.1.1 Set low and high trip/setpoints without optional digital display ............................................. 8
5.1.2 Control trip/setpoint voltage calculation............................................................................... 9
5.1.3 Set low and high trip/setpoints with optional digital display .................................................. 9
5.2 Select switching differential of the trip/setpoints...................................................................... 9
5.3 Calibration.............................................................................................................................. 9
5.3.1 Control span voltage calculation ....................................................................................... 10
5.4 Calibration of digital display range (optional display)............................................................. 10
5.5 Motherboard jumper selection table ...................................................................................... 11
5.6 Displayboard jumper selection table ..................................................................................... 11
.................................................................................................................. 3
.......................................................................................................... 6
................................................................................................................ 8
6 Inspection and Service
6.1 Inspection............................................................................................................................. 12
6.2 Calibration sensor................................................................................................................. 12
6.3 Replacing sensor element .................................................................................................... 12
7 Troubleshooting
7.1 Diagnostics........................................................................................................................... 13
................................................................................................................... 13
..................................................................................................... 12
8 Cross-sensitivity Data...................................................................................
9 Specifications
10 Wiring Configuration and Enclosure Dimensions
11 Notes and General Information
11.1 Intended product application ............................................................................................. 22
11.2 Installers’ responsibilities................................................................................................... 22
11.3 Maintenance ..................................................................................................................... 22
11.4 Limited warranty ............................................................................................................... 22
11.5 Return instructions ............................................................................................................ 22
........................................................................................................................ 15
............................................ 17
.................................................................................. 22
14
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Page 3
Carbon monoxide (CO) gas detection and control system
1 General Overview
The PolyGard
CO analog single point controller is used for detection of carbon monoxide in the ambient air to
warn of the presence of carbon monoxide gas and to control ventilation systems.
2 Description
Gas sensing
The sensor portion of the PolyGard CO analog single point controller is a micro-fuel cell, which is completely sealed. The measurement is a gas-in-liquid chemical reaction rather than a surface area measurement. With no surface area to coat, this sensor retains its sensitivity to carbon monoxide even after prolonged exposure to clean air.
The cell consists of a diffusion barrier, O-ring seal, electrolyte reservoir and three electrodes: sensing, counter and reference. The target gas, carbon monoxide, enters the cell through a diffusion barrier. The chemical process of the measurement is one of oxidation where one molecule of the target gas is exchanged for one molecule of oxygen. The reaction drives the oxygen molecule to the counter electrode, generating a DC microampere signal between the sensing and counter electrodes. This signal is linear to the volume concentration of the sensed gas rather than the partial pressure.
The integrated two-wire transformer converts this DC microampere signal to a standard 4-20 mA signal. In some cases, biasing is required to maintain a voltage differential between the reference and sensing electrode in order to facilitate the necessary reaction in the cell.
The transmitter electronics will provide the necessary bias voltage when configured for one of these sensor types. Most sensors produce a small amount of baseline current in clean air. This is adjusted out with the zero potentiometer on the transmitter.
This oxidation at the electrodes causes wear of the sensor. Typical life for this sensor is approximately five years in normal operation. This will vary somewhat from sensor to sensor, with some working lifetimes less than five years and some greater than 5 years. This wear also changes the characteristics of the sensor, requiring periodic re­calibration. It is recommended that the sensor accuracy be verified every six months and recalibrated as necessary
.
Relay output
The controller output provides two (2) adjustable trip/setpoints within the sensing range. If the CO concentration exceeds any trip/setpoint value the respective alarms will be activated. The low or high alarm trip/setpoint level correspond to the relay outputs 1K1 (R1) and 1K2 (R2). The output relay R3 can be assigned to either low alarm or high alarm.
The controller has a self-diagnostic to detect any power supply voltage or sensor failures. When a failure occurs it triggers relay output R4. The fail-safe relay R4 will close in case of loss of supply voltage or sensor failure.
Analog output
The 1-5 VDC output is linear and represents the range of 0-250 ppm actual sensor proportional value. This signal can be used with any external DDC/PLC control or automation system.
Test button
With this button pushed, it simulates the maximum gas concentration. Low and high alarms will be activated and the display will show the maximum value.
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Page 4
Manual override of low alarm relay
Manual switch for “Auto” or “On” function of the relay 1K1 (R1)
Switch position:
Auto = alarm relay 1K1 normal operation
On = alarm relay 1K1 manually on
Caution!
Replacement sensor elements, which are not bias types, are shipped with a tiny spring of wire shorting the sensor and reference electrodes.
This spring MUST BE REMOVED prior to installing the element into the sensor assembly.
Optional Display
3.5 digits display of concentration
LED power: green Power on, and normal operation red Failure operation
LED alarm: orange Low alarm level active red Low and high alarm level active
nd
Button “Reset 2
Alarm” Reset high alarm, when relay is set to latched
Button “Reset Audible” Reset internal horn and relay R3 for remote alarm
Optional time delay relay for low alarm
Time delay relay for delayed activation of relay 1K1
RTE-P11 analog timer = on-delay, adjustable from 0.1 min to 10 min
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
3 Installation
Note:
Avoid any force (e.g. by thumb) during operation or installation on the sensor element. This could destroy
the element.
Electronics can be destroyed through static electricity. Therefore, do not work on the equipment without a
wrist strap connected to earth ground or standing on conductive floor.
3.1 Mounting locations
The specific weight of carbon monoxide is almost the same as that of air (factor 0.967).
Location of the SPC 1110 must conform to the layout of the area being monitored.
Disregard the ventilation ratio! Do not mount SPC 1110 in the center of the airflow. In larger rooms, it
might be necessary to install two or more SPC 1110 where there is not adequate air movement. Do not mount in corners or directly in front of air inlets (e.g. doors, windows, open ramps, dampers, etc.). In areas with undefined air movement, it might be necessary to distribute several SPC 1110 in a vertical and horizontal direction over the whole area to be monitored. Avoid locations where water, oil etc. may influence proper operation and where mechanical damage
might be possible. Mounting height is 5 feet to max. 6 feet (1.5 to 1.8 m) above floor.
Provide adequate space around SPC 1110 for maintenance and calibration work.
Page 5
3.2 Enclosure
The door of the enclosure is lockable with supplied key (5/16 in. (8 mm) triangle key).
Use the provided template for locating position of wall mounting holes.
Screw the enclosure vertically on wall. (see Fig. 2, page 18).
When wiring is completed, put back the wire track cover and close the door of the enclosure. (see Fig. 1,
page 17).
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Page 6
4 Electrical Connection
4.1 Instructions
Note:
Electrostatic discharge (ESD) may damage electronic components. During wiring, open the cover only when completely grounded via grounding strap or standing on conductive floor.
Connections should be made without any power applied to conductors.
Installation of the electrical wiring should be according to the connection diagram and only performed by a
trained specialist. For the 1-5 VDC analog output signal use shielded cable to avoid any influence from external interference.
Recommended cable: 18 AWG shielded, maximum resistance 20.8 /1000 ft (73 /1000 m)
Cable for power and relay outputs do not need to be shielded.
Power terminal block X1
Connector H 120 VAC 50/60Hz (24V AC/DC without transformer) Connector N 0 VAC/DC Connector G Earth ground
Motherboard terminal strip X2
Connector 1 1-5 VDC sensor output signal (common)* Connector 2 1-5 VDC sensor output signal (positive) Connector 3 Power supply 24 VAC Connector 4 0 VAC/DC Connector 5 Power supply 24 VDC (19 - 28 VDC) Connector
* Note:
When the SPC analog output signal is conntected to an external controller, the controller’s analog input must provide isolation for the 1-5 VDC signal. If the 1-5 VDC signal is used, then remove Jumper JP1 located on the motherboard.
Motherboard terminal strip X3 (relay output without optional time delay relay 1K1):
Connector 1-2 R1, low alarm relay activates the 1K1 relay via internal wiring Connector 3
Connector 4 Connector 5
Connector 6-7 R3, potential free contact for remote alarming Connector 8-9 R4, potential free contact for remote fail-safe alarming
Low alarm relay socket 1K1 (DPDT)
Contact set 1 of DPDT Contact set 2 of DPDT Connector 5
Connector 1 Connector 9
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
NO NC
R2, high alarm relay activates the 1K2 relay via internal wiring
COM
Connector 8 Connector 4 Connector 12
NO NC COM
User Manual - PolyGard® CO SPC-1110
High alarm relay socket 1K2 (DPDT)
Contact set 1 of DPDT Contact set 2 of DPDT Connector 5
Connector 1 Connector 9
Optional low alarm time delay relay socket 1K1 (DPDT)
Contact set 1 of DPDT Contact set 2 of DPDT Connector 6
Connector 5 Connector 8
4.2 Wiring connection
Static electricity (see section 4.1).
Open the door of the enclosure.
Pull cables via the conduit openings into the enclosure, and connect cable leads to the appropriate
terminal connectors.
Connector 8 Connector 4 Connector 12
Connector 3 Connector 4 Connector 1
NO NC COM
NO NC COM
Page 7
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
5 Start-up Operation
Only trained technicians should perform the following:
Check mounting location.
Check power voltage.
Check for correct sensor element (7 MSR) at sensorboard terminal X3 PCB EC-C.
Check and/or select the appropriate jumpers for remote alarm function, relay R3 (see section 5.5,
motherboard jumper selection table). Check and/or select the appropriate jumper for failure function, relay R2 (see section 5.5, motherboard
jumper selection table). Check and/or select the appropriate jumper for latched function, relay R2 (see section 5.5, motherboard
jumper selection table). Check and/or adjust trip/setpoints for low and high alarm levels (see section 5.1, motherboard
potentiometers R31and R32). Check and/or put switch into “Auto” position, manual override of low alarm.
Verify sensor/transmitter operation by mearsuring approximately 200 mV (about 0 ppm CO) on
sensorboard terminal -X6 and +X6.
Required instruments to start-up and calibrate the SPC:
Test gas bottle with synthetic air.
Test gas bottle with 200 ppm CO.
Gas pressure regulator with flow meter to control the gas flow at 300 ml/min.
Sensor head calibration adapter with tubing.
Digital voltmeter with a range of 0-2 VAC and 0-10 VDC, accuracy 1%
Small screwdriver.
Page 8
Note:
Please observe proper handling procedures for test gas bottles!
5.1 Set trip/setpoints
5.1.1 Set low and high trip/setpoints without optional digital display
Set low trip/setpoint
Connect a digital voltmeter to test jacks J1 (red) and JM (black) on the motherboard with a range selected
that will display 10 VDC maximum. Adjust the low trip/setpoint voltage, with potentiometer ”R31” at the motherboard, until the signal reads the
appropriate mVDC ± 2 mV (see section 5.1.2, calculation for trip/setpoint control voltage).
Set high trip/setpoint
Connect a digital voltmeter to test jacks J2 (red) and JM (black) on the motherboard with a range selected
that will display 10 VDC maximum. Adjust the high trip/setpoint with potentiometer ”R32” at the motherboard until the signal reads the
appropriate mVDC ± 2 mV (see section 5.1.2, calculation for trip/setpoint control voltage).
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
5.1.2 Control trip/setpoint voltage calculation
= 0.016 V x trip/setpoint (ppm) + 1.20 VDC
(ppm)
Example
Trip/setpoint value 50 ppm
5.1.3 Set low and high trip/setpoints with optional digital display
Control voltage 2.0 V
0.016 (V) x 50 (ppm) + 1.20 (V) = 2.0 V (ppm)
Set display jumper on displayboard into position “JP1” to “JP 1.2”. This will provide a display value with +/­sign.
Set low trip/setpoint
Set mode-operating switch “S1” on displayboard into position 1 (far left position). The digital display
indicates the low trip/setpoint value. Adjust the low trip/setpoint with potentiometer “R31” on the motherboard. The trip/setpoint value can be
read on the digital display.
Page 9
Set high trip/setpoint
Set mode-operating switch “S1” on displayboard into position 2 (second position from the left). The digital
display indicates the high trip/setpoint value. Adjust the high trip/setpont with potentiometer “R32” on the motherboard. The trip/setpoint value can be
read on the digital display. Set mode-operating switch “S1” on displayboard into position 4 (far right position). This is the normal
operating mode (see Fig. 5, page 18). Set display jumper on displayboard back into position “JP1” to “JP1.1”. This provides a display value
without any +/- sign.
5.2 Select switching differential of the trip/setpoints
Individual switching differentials can be selected per trip/setpoint via jumpers “JP6” and “JP8” on the motherboard, either 4% or 10% differential of full transmitter range (see section 5.5, motherboard jumper selection table). For example, with factory standard range 0-250 ppm CO, 4% differential =10 ppm, and 10% differential = 25 ppm.
5.3 Calibration
Note:
If calibration is necessary, the sensor element must be powered and be fully stabilized for at least 1 hour.
Zero adjustment (After sensor warm-up)
Zero-point calibration (4mA):
Connect digital voltmeter to test pins – and + at sensorboard (with a range selected that will display 2 VDC
max.). Connect the calibration adapter to sensor element.
Apply sensor element zero calibration gas, (300 ml/min; 14.5 psi ± 10%), or other clean air source.
Wait two minutes until the signal is stable; adjust signal with zero potentiometer ”Zero” until the signal is
200 mV ± 2 mV and stable (sensorboard). Remove calibration adapter carefully by turning lightly.
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Span adjustment
Note:
CO calibration gas is toxic; never inhale the gas! Symptoms: Dizziness, headache and nausea. Procedure if exposed: Bring into fresh air at once, consult doctor.
Connect calibration adapter to the sensor element.
Apply sensor element span calibration gas (200 ppm CO), (300 ml/min; 14.5 psi ± 10%).
Wait two minutes until the signal is stable, adjust signal with span potentiometer ”Span” until the signal
reads the appropriate mVDC (± 3 mV, see calculation for control voltage 5.3.1) and is stable (sensorboard). Remove calibration adapter with a careful light turn. Inspect the seating of the sensor element!
5.3.1 Control span voltage calculation
800 (mV) x test gas concentration (ppm) + 200 (mV) Sensing range CO (ppm)
Example
Sensing range CO concentration 250 ppm Test gas concentration 200 ppm Control voltage 840 mV
800 (mV) x 200 (ppm) + 200 (mV) = 840 mV 250 (ppm)
Page 10
5.4 Calibration of digital display range (optional display)
Note:
The display range is factory set and normally does not require any field adjustment. Adjustment can only be made when the sensorboard test pins “X6+” and “X6-“ read 200 mV. This represents a 0 ppm CO value.
Calibrate maximum display range of 250 ppm CO
Connect digital voltmeter to test pins “J3+” and “J4-“ on the displayboard with a range selected that will
display 300 mVDC maximum. Adjust the maximum display range voltage with potentiometer “R31” on the displayboard until the signal
reads 120 mVDC ± 1 mVDC.
Calibrate zero point display of 0 ppm CO
Adjust the zero point with potentiometer “R32” on the displayboard until the digital display reads 0 ppm.
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
5.5 Motherboard jumper selection table
Function
1-5 VDC signal for external use X 1-5 VDC not used X Relay R3 will be active with low alarm X*1 Jumper JP3
Relay R3 will be active with high alarm X*1 Jumper JP4 Relay R3 will be not active X*1 Jumper JP5 System failure also activates high alarm X System failure does not activate high alarm X High alarm without latch function 1-2 High alarm with latch function 2-3 With optional digital display X Without optional digital display X Switching differential of low trip/setpoint, 4% 1-2 Switching differential of low trip/setpoint, 10% 2-3 Switching differential of high trip/setpoint, 4% 1-2 Switching differential of high trip/setpoint, 10% 2-3 Internal function X Jumper JP7*2 Internal function 2-3 Jumper JP10*2 Internal function 1-2 Jumper JP11*2
Note: *1 Only one of the three jumpers can be installed. *2 Do not change the factory jumper position setting.
Page 11
Element
Jumper JP1
Jumper JP9
Jumper JP12
Jumper JP2
Jumper JP6
Jumper JP8
Factory Set
5.6 Displayboard jumper selection table
Function
Display value without sign +/- X Display value with sign +/- X Jumper JP1.2 Button “Reset 2 (high) alarm” enabled X
Button “Reset 2 (high) alarm” disabled X Internal function X Jumper JP71
1 Do not change the factory jumper position setting
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
Element
Jumper JP1.1
Jumper JP12
Factory Set
User Manual - PolyGard® CO SPC-1110
Page 12
6 Inspection and Service
6.1 Inspection
Inspection and service of the single point controller should be done by a trained technician and executed on a periodic interval. It is recommended that the sensor operation be verified at least every six months.
6.2 Calibration sensor
(See part 5.3)
Service at periodic intervals is to be decided by the person responsible for the gas detection system.
If span calibration voltage of 840 mV (see note below) is no longer attainable when applying 200 ppm
carbon monoxide in air, then the sensor element has to be replaced. After the sensor element has been replaced, a calibration is required.
Note:
If using a different level of span test gas ppm, or different sensor range, then the mV needs to be calculated.
6.3 Replacing sensor element
Static electricity ( see section 4.1).
Sensor should always be installed without power applied, remove fuse “1F1”.
Unplug old sensor element out from the sensorboard.
Take new sensor element out of original packing and remove the shorting wire on the sensor element
contacts. Plug sensor element in the connector X3 at the sensorboard.
After sensor warm-up, turn potentiometer “Span”, located on sensorboard, to its center position.
(Turn the pot 25 rotations counter-clockwise, then 11 rotations clockwise to be centered.)
Calibrate (see section 5.3).
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
7 Troubleshooting
7.1 Diagnostics
Trouble Reason Solution
Page 13
No indication of power (opional with display),
and/or
test button does not function
No indication value at digital display
Cannot calibrate sensorboard
Power not applied Measure power on terminal block X1
terminal H / N for 120 VAC (24
Fuse failure Check miniature fuses 1F1, 1F2 or F1 on
motherboard
Interruption in the cable
Check cable connections for tight fit connection between motherboard and displayboard
Failure on displayboard Replace displayboard
Mode operating switch S1 on displayboard, position 3 = OFF
Set switch in position:
1 = low trip/setpoint
2 = high trip/setpoint
4 = sensed value Interruption in the cable
Check cable connections for tight fit connection between motherboard and displayboard
Failure on displayboard Replace displayboard
Interruption in the cable
Check cable connections for tight fit connection between motherboard and displayboard
Sensor sensitivity too low Replace sensor
Failure on sensorboard Replace sensorboard
Cannot set trip/setpoints
Trip/setpoint values are set too high
Adjust trip/setpoint values again
(see section 5.1 to 5.3) Failure on motherboard Replace motherboard
Fail-safe alarm
Interruption of sensor cable or sensor sensitivity too low
Control span voltage lower then 200mV
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
Check cable connection, or if necessary
replace and calibrate sensor
Recalibrate the sensor, or if necessary
replace sensor element
User Manual - PolyGard® CO SPC-1110
Page 14
8 Cross-sensitivity Data
This table shows the typical response to be expected from the sensor when exposed to the following gases.
Gas
Acetone (CH3)CO(CH3) 200 ppm < 0.46 ppm
Ammonia NH3 100 ppm 0 pmm
Chlorine CL2 1 ppm 0 ppm
Ethanol C2H5OH 200 ppm 0 ppm
Chemical mark Gas concentration Tolerance ppm CO
Ethylene C2H4 100 ppm
Hydrogen H2 100 ppm
Hydrogen chloride HCI 5 ppm 0 ppm
Hydrogen cyanide HCN 10 ppm < 2 ppm
Hydrogen sulphide H2S 15 ppm
Nitric oxide NO 35 ppm
Nitrogen dioxide NO2 5 ppm
Sulphur dioxide SO2 5 ppm 0 ppm
Toluene C6H5CH3 200 ppm 0 ppm
Trichloraethane C2HCL2 200 ppm < 10 ppm
100 ppm
< 60 ppm
< 0.3 ppm
7 ppm
- 1 ppm
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
9 Specifications
Page 15
Electrical
120 VAC, -10%/ +20%, 50/60 Hz, or
Power supply:
24 VAC/DC, –10%/ +20%, without built-in transformer resettable 1.6 A fuse
Power consumption: 0.6 A (15 VA), max.
- w/optional heater 1.6 A (39 VA), max. RFI/EMI protection 5.0 W @ 1ft. (0.31 m) radiated Sensor Performance Gas detected Carbon monoxide (CO) Sensor element Electrochemical, diffusion Range 0 – 250 ppm factory sete 0 – 150 to 0 – 300 ppm, adjustable via calibration Stability & resolution
± 0.5 ppm of reading Repeatability ± 1% of reading Long term output drift Response time
< 0.4% signal loss/month
t90 30 sec. Sensor life expectancy 5 years, normal operating environment Sensor coverage 5,000 sq.ft. (465 m2) to 10,000 sq.ft. (930 m2) under “ideal conditions”
Installation Location
Mounting height 5 to 6 ft. (1.5 to 1.8 m) above floor
Relay outputs
Low alarm (1K1)
DPDT, 10 A (optional time delay relay, 10 A) potential free, 250 VAC High alarm (1K2) DPDT, 10 A, potential free, 250 VAC max. Remote alarm (R3) SPST, 5 A, potential free, 250 VAC max. Fail-safe (R4) SPST, 5 A, potential free, 250 VAC max.
Type of Control
General Two-stage, low and high alarm Trip/setpoints Trip/setpoints
- Low alarm 50 ppm CO (factory calibrated, user adjustable)
- High alarm 100 ppm CO (factory calibrated, user adjustable) Switching differential 4% or 10% of sensing range, selectable
Analog output signal
1-5 VDC for external controller (the controller’s analog input must
provide isolation for the 1-5 V DC signal), load > 50 kOhm Audible alarm 90 dB, enabled or disabled, selectable
Visual Indications and Reset Push Buttons, optional
Digital display 3.5 digit, ppm reading Power/operating status LED Green = power on / Red = failure Alarm status LED Orange = low alarm / Red = high alarm Reset 2nd alarm button LED on = w/high alarm on (only w/latched relay configuration) Reset audible button LED on = w/internal horn and/or relay R3 for remote alarm is on Alarm acknowledgement / reset
function
Low alarm: auto reset
High alarm: auto reset or manual reset, selectable
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Page 16
Operating Environment Working temperature 23 °F to 104 °F (-5 °C to + 40 °C) Storage temperature -4 °F to 104 °F (-25 °C to + 40 °C) Humidity 15 to 95% RH non-condensing Pressure range Atmospheric ±10%
Optional Heater, built-in
For low temperature environment Ambient temperature -22 °F to 104 °F (-30 °C to 40 °C) Thermostatic control 32 °F (0 °C) ± 5 °F (3 °C) Physical Characteristics Enclosure material Steel case Enclosure color Light beige Protection NEMA 4 (IP 55) Installation Wall (surface) mounted Dimensions, enclosure (HxWxD) 9.06 x 8.27 x 5.6 in. (230 x 210 x 142 mm) Dimensions, splash guard (HxDia.) 0.63 x 2.56 in. (16 x 65 mm) Cable entry 3 holes for ½ in. conduit, covered Wire connection Terminal blocks, screw type for lead wire Wire size Min. 24 AWG (0.25 mm2) max. 14 AWG (2.5 mm2) Weight 8.8 Ibs. (4.0 kg) Approvals/Listings
- unit City of Los Angeles Approved CE VDI 2053 (pending) EMV Compliance 89/336/EWG
- sensor UL Recognized
- relays
UL Recognized, CSA Certified, TÜV
- transformer UL Listed, CSA Certified
Warranty
Two years material and workmanship
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
10 Wiring Configuration and Enclosure Dimensions
Wiring Configuration Fig. 1
Low alarm level option, with time delay relay (instead of standard relay)
8
5
6
1
4
3
Common
NC
NO
Common
NC
NO
Low alarm level time delay DPDT relay "1K1 (R1)"
Relay 1K1 (R1)
NO
Low Alarm
Time Delay
NCNCNO
Note: NC-NO connection is reversed on the relay socket compared to the standard relay
Page 17
RTE-P11
C
coilcoil
C
9
1
5
12
4
8
9
1
5
12
4
8
7
6
X3
9
8
X3
G
2
1
X2
Common
NC
NO
Common
NC
NO
Common
NC
NO
Common
NC
NO
NO
Common
NC
Common
Ground shield
(+)
1-5 VDC analog output signal to remote controller or BAS
(–)
Low alarm level standard DPDT relay "1K1 (R1)"
High alarm level standard DPDT relay "1K2 (R2)"
Remote strobe/horn/ display alarm actuation "R3"
Remote fail-safe "R4"
Relay contact positions 1K1 (R1), 1K2 (R2), R3 and R4: – Power off, as drawn – Power on and no alarm condition, as drawn, and R4 is open – Power on and alarm condition for 1K1 (R1), 1K2 (R2) and R3, contacts are closed between common and NO, and R4 stays open – Power loss or system failure, R4 is closed
Recommended Twisted, shielded wire for 1-5 VDC output signal Grounded housing
NONONC
NONONC
X1
Motherboard
X1 = Ribbon cable connection to transmitter and display (factory installed)
Low Alarm
Standard
Relay 1K1 (R1)
NC
High Alarm
Standard
Relay 1K2 (R2)
NC
Power
Terminal
Block X1
1F1 FUSE
1F2 FUSE
1-5
VDC24VAC24VDC
(–) (+) (+) (–) (+)
12345
X2
C
coilcoil
C
C
coilcoil
C
H N G
*
X3
Wire Track
per fuse holder
1.6 A replaceable fuse is installed
R1 R2 R3 R4
123456789
Power terminal block "X1"
Gray Blue Green/yellow
H N
G
AC hot AC neutral Earth ground
120 VAC or 24 VAC/DC power supply
* With 24 VAC/DC power supply:
– Remove factory installed transformer "1T1" and transformer wires
– Disconnect lead wire from " 1F2" fuse block terminal and connect to "1F1 *(right hand)" fuse block terminal
1F1 FUSE
1F2 FUSE
– Add wire and connect between AC neutral "N (leftside)" of power terminal block and "X2 - terminal 4" of motherboard
(–)
4
X2
Terminal Block X1
Transformer
1T1
*
Power
H N G
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Page 18
Assembly Fig. 2
8.27 in. (210 mm)
6.70 in. (170 mm)
NONONC
NONONC
Mounting hole
d = 0.2 in. (5 mm)
X1
JP1
JP2
S1
R31
Low Alarm
Standard
Relay
NC
1K1 (R1)
High Alarm
Standard
Relay
NC
1K2 (R2)
Power
Terminal
Block X1
Fuse
(1,6 A)
Fuse
(1,6 A)
1-5 VDC24VA C24VDC
F1
(+) (~) (-)
(-) (+)
800mA
X2 X3
JP7
JP5 JP4 JP3
Motherboard 23050167
C
C
COIL COIL
C
C
COIL COIL
H N G
1F1
*
1F2
R1 R2 R3 R4
12345678912345
R1 R2 R3 R4
1
JP12
JP6
1
J1
1
JP9
JP11
J2 JM
1
JP10
Wire Track
1T1 Transformer 4011MWSH
Mounting hole
d = 0.2 in. (5 mm)
Low alarm override
S1
ON
AUTO
JP8
1
R32
9.06 in. (230 mm)
5.90 in. (150 mm)
Horn
0.40 in. (10 mm)
Dimensions Fig. 3
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
8.27 in. (210 mm)
0.63 in. (16 mm)
Page 19
) m m 0
3 2
( . in 6
0
. 9
0.63 in. (16 mm)
//
MSR
0 8 0
green = Power orange= 1. Alar m
Power
red = Trouble
2. Alarm
Reset
Reset
Audible
PolyGard
ppm
Alarm
red = 2. Alarm
) m m 2
4 1
( .
in 6
. 5
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Motherboard Fig. 4
1-5 VDC24VAC24VDC
ly
d
a
r
p
a o
is
b
d
r
r
o
o
s
t
n
c
e
e
s
n n
d
o
n
C
a
F1
800mA
1 X
JP1
Analog output
w/without display
JP2
S1
R31
(-) (+)
(+) (~) (-)
X2
7 P
J
JP5 JP4 JP3
Motherboard 23050167
R1 R2 R3 R4
12345678912345
R1 R2 R3
JP11
J1
JP6
1
1
9 P
J
J2 JM
1
JP10
1
JP8
R4
R32
X3
R3 = not active
R3 = w/High alarm active R3 = w/Low alarm active
Testpin JM (Common) Testpin J2 High trip/setpoint value Testpin J1 Low trip/setpoint value
Switching differential of High trip/setpoint value
Adjustment trip/setpoint High trip/setpoint
Page 20
Adjustment trip/setpoint Low trip/setpoint
Displayboard Fig. 5
R31
R32
JP7
JP12
ANZEXST.CDR
JP12
JP1.2
Display w/without sign
J3
J4
Testpin display range
Changing display range
Button “Reset Alarm High” activates
JP1.1
Mode operating switch 1 = set trip/setpoint Low 2 = set trip/setpoint High 3 = NC 4 = Normally operating mode
Adjusted max. value
Adjusted min. value
Displayboard 2305001
S1
1
1
System failure actives high alarm
High alarm latch
234
X1
ly
d
a
r
p
a o
is
b
d
r
r
o s
to
n
c
e
e
s
n n
d
o
n
C
a
Switching differential of Low trip/setpoint valueTest button
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Sensorboard Fig. 6
1
X2
+
X6
-
EC-C 003
VR3
VR2
230398
Span
Zero
C
Sensor
Platin310
S
RX3
X9
Page 21
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
User Manual - PolyGard® CO SPC-1110
Page 22
11 Notes and General Information
It is important to read this user manual thoroughly and clearly understand the information and instructions. The PolyGard® single point controller must be used within product specification capabilities. The appropriate operating and maintenance instructions and recommendations must be followed.
Due to ongoing product development, MSR reserves the right to change specifications without notice. The information contained herein is based upon data considered to be accurate. However, no guarantee is expressed or implied regarding the accuracy of this data.
11.1 Intended product application
The PolyGard® CO SPC-1110 single point controller is designed and manufactured for control applications for energy savings and OSHA air quality compliance in commercial buildings and manufacturing plants (i.e., detection and automatic exhaust fan control for automotive maintenance facilities, enclosed parking garages, engine repair shops, warehouses with forklifts, fire stations, tunnels, etc.).
11.2 Installers’ responsibilities
It is the installer`s responsibility to ensure that all PolyGard® single point controller is installed in compliance with all national and local codes and OSHA requirements. Installation should be implemented only by individuals familiar with proper installation techniques and with codes, standards and proper safety procedures for control installations and the latest edition of the National Electrical Code (ANSI/NFPA70). It is also essential to strictly follow all instructions as provided in the user manual.
11.3 Maintenance
It is recommended that the PolyGard® single point controller performance check be done on a routine schedule. Any performance deviations may be serviced based on needed requirements. Re-calibration and part replacement may be implemented in the field by a qualified individual and with the appropriate tools. Alternatively, the easily removable plug-in transmitter card with the sensor may be returned for service to INTEC Controls.
11.4 Limited warranty
MSR and INTEC Controls warrant the PolyGard
®
single point controller for a period of two (2) years from the date of shipment against defects in material or workmanship. Should any evidence of defects in material or workmanship occur during the warranty period, MSR or INTEC Controls will repair or replace the product at their own discretion, without charge.
This warranty does not apply to units that have been altered, had repair attempted, or been subjected to abuse, accidental or otherwise. The warranty also does not apply to units in which the sensor element has been overexposed or gas poisoned. The above warranty is in lieu of all other express warranties, obligations or liabilities.
This warranty extends only to the PolyGard® single point controller. MSR and INTEC Controls shall not be liable for any incidental or consequential damages arising out of or related to the use of the PolyGard® single point controller.
11.5 Return instructions
If the PolyGard
®
single point controller needs to be returned to INTEC Controls for service, an RMA number
must be obtained prior to sending.
PolyGard is a registered trademark of MSR SPC1110I01
Phone (858) 578-7887 & (888) GO INTEC Fax (858) 578-4633 & (888) FX INTEC Specification subject to change without notice. INTEC Controls, Inc., P.O. Box 12506, La Jolla, CA 92039 www.inteccontrols.com Printed in USA 040401
Loading...