PolyGard MGC2-20 User Manual

Page 1
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard Controller MGC2-20
Multi-Point Controller
Serial Number – S00
User Manual
September 29, 2011
November 19, 2013 – Revision
Printed in USA 131119
Page 2
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Page 02
1 Description ............................................................................................................................................. 4
2 Operating Instruction ............................................................................................................................ 5
2.1 Description Keypad User Interface ................................................................................................... 5
2.2 Setting / Change Parameters ........................................................................................................... 5
2.3 Password Level ................................................................................................................................ 6
3 Menu Overview ...................................................................................................................................... 7
3.1 Malfunction management ................................................................................................................. 8
3.1.1 Acknowledge a malfunction ....................................................................................................... 8
3.1.2 History error summary ............................................................................................................... 8
3.1.3 System Errors ............................................................................................................................ 9
3.2 Stage Status ..................................................................................................................................... 9
3.3 Relay Status ..................................................................................................................................... 9
3.3.1 Manual operation of the relays ................................................................................................ 10
3.4 Menu Sensor Readings .................................................................................................................. 10
3.5 Menu Relay Setup .......................................................................................................................... 11
3.5.1 Relay Mode ............................................................................................................................. 11
3.5.2 Relay Action Steady / Flash ..................................................................................................... 11
3.5.3 Latching Mode ......................................................................................................................... 12
3.5.4 Horn Function .......................................................................................................................... 12
3.5.5 External operation of Relay. .................................................................................................... 13
3.5.6 Delay operation of Relay. ........................................................................................................ 13
3.6 Menu SP Setup .............................................................................................................................. 14
3.6.1 Activate – Deactivate SP ......................................................................................................... 15
3.6.2 Selection Type ......................................................................................................................... 16
3.6.3 Measuring range...................................................................................................................... 16
3.6.4 SP Signal ................................................................................................................................. 16
3.6.5 Stage/Setpoint / Hysteresis ..................................................................................................... 17
3.6.6 Delay time ON or OFF ............................................................................................................. 17
3.6.7 Control Mode ........................................................................................................................... 17
3.6.8 Assigned SP Fault to Relay ..................................................................................................... 17
3.6.9 Assign Relay to a Stage .......................................................................................................... 18
3.6.10 Assigned SP Signal to analog Output ...................................................................................... 18
3.7 Menu System Setup ....................................................................................................................... 19
3.7.1 Service Mode .......................................................................................................................... 20
3.7.2 Software Version ..................................................................................................................... 21
3.7.3 Maintenance Concept .............................................................................................................. 21
3.7.4 Average Value Function .......................................................................................................... 21
3.7.5 Time, Date ............................................................................................................................... 21
3.7.6 Customer Password (Code 1) ................................................................................................. 22
3.7.7 Analog Output ......................................................................................................................... 22
3.7.8 Define the Failure Relay .......................................................................................................... 22
3.7.9 Power On Time ....................................................................................................................... 22
3.7.10 Activation of expansions modules............................................................................................ 23
4 Mounting / Electrical Connection ....................................................................................................... 24
4.1 Electrical Connection ...................................................................................................................... 24
4.2 Unit position – Connection diagram ................................................................................................ 25
Printed in USA 131119
Page 3
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
5 Start-up Operation ............................................................................................................................... 29
5.1 Start-up ........................................................................................................................................... 29
5.2 Checklist Start-up operation ........................................................................................................... 30
6 Configuration- and Parameter card .................................................................................................... 31
6.1 Configurations System Setup ......................................................................................................... 31
6.2 Relay Setup .................................................................................................................................... 32
6.3 Sensor Setup .................................................................................................................................. 33
7 Specifications MGC2-20 ...................................................................................................................... 34
8 Notes and General Information ........................................................................................................... 36
8.1 Intended product application ........................................................................................................... 36
8.2 Installers` responsibilities ................................................................................................................ 36
8.3 Maintenance ................................................................................................................................... 36
8.4 Limited warranty ............................................................................................................................. 36
Page 03
Printed in USA 131119
Page 4
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Multi Point Controller MGC2
1 Description
The PolyGard® Multi Point Controller MGC2 is used for the monitoring and warning of sensor points exceeding their stage setpoints. External Transmitters can monitor and warn of toxic, combustible and refrigerant gases as well as temperature and humidity. The Controller MGC2 can measure up to twenty analog 4 to 20 mA (Gas) Transmitters.. Each Sensor Point (SP) can have five stage thresholds. Each stage threshold can be assigned to anyone of the relays (R1…R20). The Controller can interface via ten 4 to 20 mA outputs to any compatible electronic analog control, DDC/PLC control or automation system.
The adjustable parameters and staged thresholds make this system very flexible for sensor measuring and control.
The configuration of parameter settings and operation is easy to do without any programming knowledge.
PolyGard
®
Multi Point Controller MGC2 must not be used in areas requiring explosion proof equipment.
Page 04
Printed in USA 131119
Page 5
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
A
User Manual - MGC2-20
2 Operating Instruction
The complete configuration, parameterization and service are made via the keypad user interface in combination with the display screen. Security is provided via two password levels.
Page 05
Fault
larm
INTEC Controls
01.22.05 10:28 am
2.1
Description Keypad User Interface
Exits programming and saves settings, returns to the previous menu level.
Enter sub menus, stores changed values.
Scrolls down & up in Main menu and Sub menus, increases or decreases a value.
Moves cursor left or right.
LED yellow Flashes when one or more stages have been exceeded or steady if the operator has manually
overridden any relays.
LED red: Flashes when a System or Sensor Failure is detected or when the Maintenance Date is needed.
2.2 Setting / Change Parameters
Desi
red menu window open.
Opens menu window, if the password is approved the cursor jumps to the first segment position
Moves the cursor right or left to a segment position
Changes the parameter or value
Saving the changed parameter or value.
Finish
Printed in USA 131119
Page 6
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
2.3 Password Level
All changes of parameters and staged setpoint values are protected by four digit numeric Code (= password).
The code level 1 permits the operation of the MGC2. This code level is intended for the customer. It can be changed in the System Setup Menu “Change Customer Password”
With the code level 2 all parameters and set points can be changed, this code level is reserved for the service technician.
A password must be re-entered if there is 15 minutes of inactivity.
All menu windows are visible without a password.
Factory preprogrammed system password "9001".
Page 06
Printed in USA 131119
Page 7
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
or
Page 07
Gas concentration
User Manual - MGC2-20
3 Menu Overview
The Multi-Point Controller MGC2 is operated via a simple and logical menu structure which is easy to learn. The operating menu contains the following levels:
● StartingmenuwithdateandtimeifnoSPisregistered,otherwisescrollingdisplayofthegasconcentrations
of all registered transmitters in 5-second intervals
● Mainmenu
● Submenu1and2
Starting menu Sub menuMain menu
Power On Time Display of
After 30 sec.
INTEC
10.23.13 12:53
System Errors
Stage Status
Relay Status
Sensor Readings
Relay Setup
SP Setup
Reading and reset of errors
See Section 3.1
Display of the status of actual alarms
See Section 3.2
Display of the relay status Manual operation of the relays Reset function of the relays
See Section 3.3
Display of the sensor values
See Section 3.4
Reading and change of the relay parameters
See Section 3.5
Reading and change of sensor point parameters Activate or Deactivate SP Assignment of the alarms to the alarm relay
See Section 3.6
Data Logger
System Setup
Not applicable to standard MGC2 controllers; available as a special order option
Reading and change of the system parameters
See Section 3.7
Printed in USA 131119
Page 8
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.1 Malfunction management
Malfunction management records the last 15 malfunctions with date and time stamps. In addition, “System Errors” are recorded in “Error Memory” when the malfunction occurs. This history can be selected and cleared only by the service technician level 2 password.
A malfunction will display a text message in the Starting Menu. When a failure occurs the relay defined in the system setup as “Failure relay” is activated. The red LED in the front of the Controller flashes.
During the malfunction of a sensor point (SP) stages that are assigned for sensor failure are activated. Relays that are assigned to these stages perform as if the stage has been exceeded. These assignments are programmed in the menu “SP Setup”.
3.1.1 Acknowledge a malfunction
Note:
Resetting a malfunction is only possible if the problem is corrected.
System Errors
Select MenuSystem Errors
Page 08
SP 01 < 3mA
Example: Failure SP 01 < 3 mA
05.02 10.38
SP 01 < 3mA
Malfunction Reset?
Reset ??
Malfunction Reset
SP 01 < 3mA Error Cleared
Malfunction Cleared Problem not corrected
or
Error still exists
Reset not possible
3.1.2 History error summary
The code level 2 password can open the menu “Hist Error Sum” in the main menu “System Errors”.
The last 15 error messages are listed for the service technician even if they have already been reset. These error messages can be deleted individually
Printed in USA 131119
Page 9
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
(SP)
User Manual - MGC2-20
3.1.3 System Errors
System Error Messages:
SP XX > 22 mA Current signal at analog Input XX > 22 mA.
Cause: Short-circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Solution: Check cable to Transmitter, Perform Calibration, Change the Transmitter.
SP XX < 3 mA Current signal to analog Input XX < 3 mA.
Cause: Open circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Solution: Check cable to Transmitter, Perform Calibration, Change the Transmitter.
GC Error: Internal Communication Error I/O Board to LCD Board.
Cause: Internal Error.
Solution: Change the Controller.
EP 0X Com Error: Communication error to expansion module (EP 0X).
(Only active, if EP module announced).
Cause: EP module address not correct. (See Start up Operation 5.0) Bus cable to EP 0X module disconnected. No power supply at the EP 0X module. EP module defective.
Solution: Check the EP module address.
Check the bus cable and the power supply.
Change the EP 0X module.
Maintenance: System maintenance is necessary.
Cause: Maintenance date exceeded.
Solution: Perform maintenance.
Page 09
3.2 Stage Status
Displays the actual stages exceeded in the sequence that they happen. The sensor point displays with the stages that have been exceeded. Changes can not be made in this menu.
SP 01 S1 S2
Symbol Description Function
SP 01
SX Stage Status
Sensor Point
No.
S1 = Stage 1 ON S2 = Stage 2 ON S3 = Stage 3 ON S4 = Stage 4 ON S5 = Stage 5 ON
3.3 Relay Status
Display the actual status of each relay and changes can be made for manual operation of the relays.
R 01 OFF
Symbol Description
R 01 Relay No. 01
OFF Status Relay OFF
Setting Status
Function
Select Relay No. OFF
ON Manual OFF Manual ON
= Relay Off (Not Activated by Stage Setpoint) = Relay On (Activated by Stage Setpoint) = Relay manual Off = Relay manual On
Printed in USA 131119
Page 10
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.3.1 Manual operation of the relays
The manual operation of the relays can be accomplished in the menu “Relay Status”. If a relay is in the Manual ON or Manual OFF status, the yellow LED at the Controller is on continuously.
The external operation of a relay by an assigned digital input has priority before the manual operation or the Stage set point of a sensor point being exceeded.
Manually operated relays can be reset by selecting the “Automatic” mode.
The reset of Latching relays also is a function in this menu.
R 01
Select Relay
OFF
Page 10
Manual ON
Manual OFF
Select Function Manual OFF = Relay OFF
Man
ual OFF
Select Function Manual operation
Manual ON = Relay ON
Automatic = Automatic operation restored Reset ? = Reset of latched relay
Relay forced to OFF Condition
3.4 Menu Sensor Readings
In this menu it displays the current value (CV) and average value (AV) with sensor unit and type for each active sensor point (SP) as well as the defined mode of control (CV or AV mode) with “*” .
SP 01 NH3 ppm 50 *AV 33 CV
Symbol Description
SP 01
NH3 Type NH3 See 3.6.2
ppm Unit See 3.6.2
CV Current value CV Current value of Gas Concentration
AV Average value Average value (10 measured values within the time unit)
* Control mode Display for the Control mode selected. (CV or AV)
Not active SP Status Not active SP disabled
Error SP Malfunction Current signal < 3 mA or > 22 mA
Sensor Point No.
Setting Status
Function
Select SP No.
Printed in USA 131119
Page 11
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.5 Menu Relay Setup
Display and change the parameters for each relay.
Page 11
Relay Setup
R 01
(Main menu)
(Selection Relay No.)
Relay Mode
Relay Mode
De- energized
Steady / Flash
Relay Function
0 s
See 3.5.2
Latching mode Activate Latching Mode
No
Time Reset DI Definition of Horn Functions
0s 0 0
External mode Definition of external Relay Operation
DI: ON = 0: OFF = 0
See 3.5.1
See 3.5.3
See 3.5.4
See 3.5.5
Delay ON time Set Delay ON time
0 s
Delay OFF time
Set Delay OFF time
0 s
See 3.5.6
See 3.5.6
3.5.1 Relay Mode
Symbol Description
Setting Status
Function
R 01 Relay No. Selection Relay
De­energized
3.5.2
Relay Action Steady / Flash
Symbol Description
R 01 Relay No.
Relay Mode
De­energized
Setting Status
De-energized Energized
Function
Selection Relay
= Stage ON = Relay ON = Stage ON = Relay OFF
0 = Relay Function steady
0 Function 0
> 0 = Relay Function flashing (= Periods time sec.)
Impulse / Break = 1:1
Printed in USA 131119
Page 12
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.5.3 Latching Mode
Definition of Latching Function
Page 12
Symbol Description
R 01 Relay No.
No Latching Mode No
Acknow
ledging of a latching relay in the menu “Relay Status” is possible only if the sensor value is smaller than
Setting Status
Function
Selection Relay
No Yes
= Latching Mode non active = Latching Mode active
the Staged set point including hysteresis. With this condition then latching is activated.
Example: Relay R2 assigned to Latching mode
Alarm 2
Display in the Menu
Status Relay
Relay 2
Reset in the Menu
Status Relay
3.5.4
Horn Function
On
Off
R2 OffR2On
On
Off
On
Off
Gas Concentration greater smaller as Threshold
R2 On
R2 OnR2Latching
R2 Off
With this parameter the relay is defined as a horn relay and can be acknowledged with the following possibilities.
By pressing one of the arbitrary 6 pushbuttons. (Only possible in the starting menu)
Automatic acknowledging when the time runs out.
.
By an external pushbutton. (Assigned to an appropriate digital input).
The horn function is activated only if at least one of the two parameters (time or digital input) is set.
Special function Response
After acknowledging the relay via Pushbutton or external DI the time starts. If this time runs out and if the stage is still exceeded, the relay is energized again.
Symbol Description
R 20 Relay No.
Reset Mode 0
Time 120
DI 0 Assignment of the digital input used for remote reset of the horn.
Setting Status
Function
Selection Relay
0 = Acknowledge the relay at time run out, or via Pushbutton
1 = Acknowledge the relay via a Pushbutton, after time runs out and the alarm is still active, then the relay is reactivated.
Time in seconds for Automatic acknowledging or before reactivating alarms defined by Reset function
Printed in USA 131119
Page 13
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Acknowledge the horn relay
Page 13
Alarm 4
Relay 4
Acknowledging
signal
On
On
Off
On
Off
Of
Time
Gas Concentration greater smaller as Threshold
Special function “Response”. (Return of the horn relay)
Alarm 4
Relay 4
Acknowledging-
signal
On
Off
On
Off
On
Off
Gas Concentration greater smaller as Threshold
Time Time
3.5.5 External operation of Relay.
Assign one digital input (DI) for external setting of the relay ON and/or OFF.
This function has priority before a
stage threshold is exceeded and/or manual switching in the menu “Relay Status”.
tting
Symbol Description
Se Status
R 01 Relay No. DI
Function
Selection Relay
DI-ON External On 0 If digital input closed, relay switch ON
DI-OFF External Off 0 If digital input closed, relay switch OFF
3.5.6 Delay operation of Relay.
Delay ON time begins when the Stage is exceeded and/or Delay OFF time when the Stage returns to normal condition.
Symbol Description
R 01 Relay No.
0 s Delay Time ON 0
0 s Delay Time OFF 0
tting
Se Status
Function
Selection Relay
Stage ON: Relay is only activated at expiration of the defined time (sec.) 0 sec. = No Delay
Stage OFF: Relay is only deactivated at expiration of the defined time (sec.) 0 sec. = No Delay
Printed in USA 131119
Page 14
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.6 Menu SP Setup
Display and Change Parameters, Assign Stage value, Assign relays to stages and activate each Sensor Point (SP).
Page 14
SP Setup
SP 01
(Selection of a sensor point)
active
SP Mode
Activate or deactivate SP
active
See 3.6.1
SP Type
Define Type
NH3
See 3.6.2
Measuring range
Define Measuring range
300 ppm
SP-Signal
Define signal type of transmitter
linear
See 3.6.4
Stage 1
Define Stage/Setpoint 1
100 ppm
(Main Menu)
See 3.6.3
See 3.6.5
Stage 2
Define Stage/Setpoint 2
100 ppm
Stage 3
Define Stage/Setpoint 3
200 ppm
Stage 4
Define Stage/Setpoint 4
200 ppm
See 3.6.5 Stage/Setpoint
Stage 5
Define Stage/Setpoint 5
300 ppm
See 3.6.5
Hysteresis
Hysteresis
15 ppm
See 3.6.5
Delay ON time
Set Delay ON time
0 s
See 3.6.5
See 3.6.5
See 3.6.6
Printed in USA 131119
Page 15
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Delay OFF time
Set Delay OFF time
0 s
AV Mode
Define Control Mode
CV
See 3.6.7
Stage - 1 2 3 4 5
Assign a SP Fault to a Stage
Fault - 1 1 0 0 0
See 3.6.8
S1; S2; S3; S4; S5;
Assign a relay to a Stage
01; 02; 03, 04; 05;
See 3.6.9
Analog Output
Assign SP signal to a Analog Output
0
See 3.6.10
3.6.1 Activate – Deactivate SP
Page 15
See 3.6.6
Symbol Description
SP 01 Sensor point
Active SP Status
Setting Status
not active
Function
Selection SP No. (SP01 is the internal Transmitter) active = Sensor point enabled for reporting
not active = Sensor point disabled for reporting
Printed in USA 131119
Page 16
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.6.2 Selection Type
Assign sensor Type to active transmitters.
Page 16
Symbol Description
Se
tting
Status
Ty
pe Unit
Measuring
1
range
SP 01 Sensor point
0 – 300 0 – 100 0 – 50 0 – 25 0 – 300 0 – 25 0 – 2000 0 – 100 0 – 200 0 – 100 0 – 20 0 – 100 0 – 2000 0 – 2000 0 – 2000 0 – 2000 0 – 300 0 – 300 0 – 300 0 – 300 0 - 300 0 – 300 0 – 300 0 – 300 0 – 300 0 – 150 0 – 100
NH3 Type NH3
1
Range Recommendations for PolyGard sensors
2
During oxygen measurement falling signal!
CO Ex NO NO
2
NH
3
O2 CO
2
SO2 H
S
2
CL
2
ETC VOC R401 R402 R408 R409 R404 R416 R502 R410 R411 R11 R123 R134 R22 TEM RH
Carbon monoxide Combusible gas Nitrogen oxide Nitrogen dioxide Ammonia Oxygen
2
Carbon dioxide Sulphur dioxide Hydrogen sulphide Chlorine Ethylene oxide Air quality Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Refrigerant gas Temperature Humidity
ppm %LEL ppm ppm ppm %V/V ppm ppm ppm ppm ppm % ppm ppm ppm ppm ppm ppm ppm ppm ppm ppm ppm ppm ppm °C % RH
3.6.3 Measuring range
The measuring range can be defined from 10 to 10000. The measuring ranges in the above table are typical and only recommendations. For actual ranges see the sensor manufacturing specifications.
The measuring range must agree with the signal (4 to 20 mA) for active transmitters. (4 mA = Display=0, 20 mA = Display Measuring range = max. point)
3.6.4 SP Signal
Gas transmitter with electro-chemical or catalytic bead sensors are linear for gas concentration proportional to the 4 to 20 mA signal.
Semiconductor gas sensors that are not linear and have a (exponential) signal. This signal is non-linear 4 to 20 mA signal from the gas transmitter.
The Controller MGC2 has the capability to monitor both types of gas transmitters, and other linear 4-20 mA sensors. The type of signal is defined in this menu.
Symbol Description
SP 01 Sensor Point Selection SP No.
Linear SP Signal linear
tting
Se Status
Function
linear = Transmitter with linear Output signal not linear = Transmitter with non linear Output signal (future).
Printed in USA 131119
Page 17
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.6.5 Stage/Setpoint / Hysteresis
Each sensor point can have five stages with set point values. If the measured level is greater than the defined stage/set point, the associated stage is set. If the level falls below the stage/setpoint plus the hysteresis then the stage returns to original condition.
It is recommended that the unused stages be set to max of sensor range to avoid the alarm light from false reporting.
For O2 measurement on depletion consider when defining stage setpoints that stages will be set on a falling measuring signal!
Page 17
Sy
mbol Description
SP 01 Sensor Point Selection SP No.
100 ppm
3.6.6
Delay ON time begins when the Stage is exceeded and/or Delay OFF time when the Stage returns to normal condition.
3.6.7
Definition of the alarm evaluation by Current value (CV) or Average value (AV).
Delay time ON or OFF
Symbol Description
SP 01 Sensor point Selection SP No.
0 s Delay Time ON 0
0 s Delay Time OFF 0
Control Mode
Threshold
Default Status
100 100 200 200 300 15
Default Status
Stage/setpoint1 Stage/setpoint2 Stage/setpoint3 Stage/setpoint4 Stage/setpoint5 Hysteresis
Function
Concentration > Stage Threshold: Relay is only activated at expiration of the defined time (sec.). 0 sec. = No Delay
Concentration < Stage Threshold: Relay is only deactivated at expiration of the defined time (sec.). 0 sec. = No Delay
Function
Sensor Value > Stage/Set point1 = Stage 1 Sensor Value > Stage/Set point1 = Stage 2 Sensor Value > Stage/Set point1 = Stage 3 Sensor Value > Stage/Set point1 = Stage 4 Sensor Value > Stage/Set point1 = Stage 5 Sensor Value < (Stage/Set pointX –Hysteresis)
= Stage X OFF
Symbol Description
SP 01 Sensor Point Selection SP No.
CV Evaluation CV
t / Average Value Function See: 3.7.4
Curren
3.6.8 Assigned SP Fault to Relay
Define which stages are activated with a failure of the sensor point.
Symbol Description
SP 01 Sensor Point Selection SP No.
Stage - 1 2 3 4 5 Fault - 1 1 0 0 0
Failure SP 1 1 0 0 0
Default Status t
Function
CV = Control the Current value AV = Control the Average value
Default Status
Function
0 = Stage not ON at SP Failure 1 = Stage ON at SP Failure
Printed in USA 131119
Page 18
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.6.9 Assign Relay to a Stage
Any of the 5 Relays can be assigned freely to any Stage. Stages that do not activate relays receive an
assignment of 00.
Defaul
Symbol Description
SP 01 Sensor Point Selection SP No.
S1 S2
1
S3 S4 S5
Status
01 02 03 00 05
t
Function
01 = Stage 1 activate relay R 01 02 = Stage 2 activate relay R 02 03 = Stage 3 activate relay R 03 00 = Stage 4 does not activate a relay 05 = Stage 5 activate relay R 20 (internal horn)
Page 18
3.6.10
Assigned SP Signal to analog Output
The sensor point signal can be assigned to one of the ten analog Outputs. The signal defined in the control mode (Current Value or Average Value) is transmitted.
Analog output see also: 3.7.2
Symbol Description
Default Status
Function
SP 01 Sensor Point Selection SP No.
0 = SP Signal not assigned to any analog output
0 A 0
1 = SP Signal assigned to analog output 1 X = SP Signal assigned to analog output X
Printed in USA 131119
Page 19
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.7 Menu System Setup
Display and change the System Parameters for the Controller
Page 19
System Setup
Service Mode OFF
Software Version GC02- XX
Next maint. Date MM.DD.YY
Service Phone 858 578-7887
AV Overlay
See 3.7.4
0 s. 120 ppm
AV Time 1800 s
(Main Menu)
See 3.7.1
See 3.7.2
See 3.7.3
See 3.7.3
See 3.7.4
Time system
See 3.7.5
US
Time
See 3.7.5
hh:mm:ss
Date
See 3.7.5
MM.DD.YY
Customer Pass Change ****
Failure Relay
See 3.7.8
19
Power On Time
See 3.7.9
30 s
See 3.7.6
Printed in USA 131119
Page 20
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
EP Module 1
See 3.7.10
active
EP Module 2
See 3.7.10
active
EP Module 3
See 3.7.10
active
EP Module 4
See 3.7.10
active
EP Module 5
See 3.7.10
Not active
Page 20
GC- Address
Controller address
1
(Reserved for future expansion; value should be left at “1”)
Analog Output
See 3.7.7
Analog Output 1
See 3.7.7
Max.
Calibration AO 1
Siehe See 3.7.7
4.0=4 mA 20 = 20.0
Analog Output XX
See 3.7.7
Max.
Calibration AO XX
See 3.7.7
4.0=4 mA 20 = 20.0
3.7.1 Service Mode
the Service mode is set to (ON) then the stage/setpoints are disabled so relays are not activated during
If calibration or service work. The service mode is Reset automatically after 60 minutes or when the service mode is set to Off.
Symbol Description
Off Service Mode Off
Default Status
Function
Off = Stages exceeded will activate the assigned relays On = Stages exceeded will not activate the assigned relays
Printed in USA 131119
Page 21
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.7.2 Software Version
Page 21
Symbol Description
GC02­XX
3.7.3
Maintenance Concept
Software Version
Default Status
Function
XX = Software Version
The MGC2 system monitors the maintenance intervals as required, by local Regulations or Customer requirements.
During startup and/or after maintenance the date for next maintenance is entered. When this date is reached at 9 o'clock the next morning a failure signal is activated and Start Menu displays the phone No. of the service company. The failure signal (maintenance) can be acknowledged by the operator. The maintenance message (Service Phone No.) is reset after maintenance is accomplished and a new maintenance date is entered.
The service phone number can be individually entered in the next menu.
Symbol Description
MM.DD.YY
Maintenance
Defaul Status
Function
MM.DD.YY = Input date for next maintenance.
t
8585.... Phone No. Input the individual service phone No.
3.7.4
Average Value Function
The Controller calculates for each active sensing point the arithmetic average value from 10 measurements within the time unit defined in this menu “AV-time”. This average value is indicated in the menu “Sensor Readings” near the Current Value. During each Sensor Point Setup the control mode of Current Value or Average Value for the Stage/Setpoint evaluation is defined.
The evaluation of the control mode Average Value is overlaid by the Current Value, if this exceeds Stage/Setpoint defined in the menu “AV-Overlay”. The overlay is delayed by the time factor set in this menu.
Defa
Symbol Description
120 s 120pm
AV- Overlay
ult
Status
120 s 120 ppm
Function
sec. = Delay time average value Overlay. 0 = No overlay Function ppm = Threshold average Overlay
1800 s AV-Time 1800 s sec. = Time to calculate average value
3
.7.5 Time, Date
Input and correction of the system time and date. Selection of the time and date format.
t
Symbol Description
US Time format US
hh.mm.ss Time
MM.DD.YY Date
Defaul Status
Function
EU = Display time and date in EU format US = Display time and date in US format
hh.mm.ss = Input the correct time (EU format) hh.mm.ss am = Input the correct time (US format)
TT.MM.JJ = Input the correct date (EU format) MM.DD.YY = Input the correct date (US format)
Printed in USA 131119
Page 22
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.7.6 Customer Password (Code 1)
Change the System Password for level 1
Symbol Description
1234
Factory preprogrammed system password "9001".
Customer­password
3.7.7 Analog Output
The Controller has two analog outputs (AO) with 4 to 20 mA signal per control module. Each of the ten analog outputs can be assigned the signal of one or more sensor points. The assignment occurs in the menu “SP Setup” for each SP. The sensor point sends the signal that is defined in the menu “C/A Mode”.
The Controller determines from the signal of all assigned sensor points the minimum, the maximum or the average value and sends this value to the analog output. The determination of which value is sent is defined in this menu “Analog Output X”. The analog output can be calibrated for 4 and 20 mA using an ampere meter attached (with measuring range 25 mA) then respective AO factor can be changed to adjust the analog output 4 and/or 20 mA During AO calibration no evaluation is made of the sensor point signals. This calibration is factory-set. The factors should only be changed if you have an accurate amp meter.
Symbol Description
Max.
4.0
20.0
Select Output mode
Calibration
Default Status
1234 1234 = Define the Customer Password with 4 characters
Default Status
Max.
4.0
20.0
Function
Function
Min. = Spends the minimum value of all assigned SP Max. = Spends the maximum value of all assigned SP Average = Spends the average value of all assigned SP
4.0 = Calibration factor at 4 mA
20.0 = Calibration factor at 20 mA
Page 22
3.7.8 Define the Failure Relay
Define the Failure Relay. See also malfunction management (3.1)
Symbol Description
19 Failure Relay R19 R19 = Define the failure relay
3.7.9 Power On Time
Sensors need a warm up period until the chemical process of the sensor reaches a stable condition. During this warm up period the current signal can cause unwanted false alarms. Therefore, the Controller starts reporting alarms after the Power ON Time delay once power is applied. While this time runs off, the Controller does not report alarms. The Power On status is displayed.
Symbol Description
30 s Power On Time 30 s XX = Define the Power On Time (sec.)
Default Status
Default Status
Function
Function
Printed in USA 131119
Page 23
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
3.7.10 Activation of expansions modules
The Gas Controller can manage, up to five expansions modules (EP-02). Each EP-02 has four analog inputs and five alarm relays and two analog outputs. Each attached EP-02 is announced in this menu. The Controller checks the communication to the registered EP-02 modules and shows a fault signal in case of a communication error. To recognize the position of the EP-02 modules a module address is assigned to each module by the address selector. See table.
The table shows the assignment of the MP and relay numbers to the individual modules.
Symbol Description
EP- Module No 1 active EP- Module No 2 active 2 11 to 15 09 to 12 05 to 06
Not active
EP- Module No 3 active 3 16 to 20 13 to 16 07 to 08
EP- Module No 4 active 4 ---- 17 to 20 09 to 10
EP- Module No 5 Not active 5 ---- ----- ------
Default Status
Function
Active = EP announced.
Not active = EP not announced
Module Addr.
Relay No.
1 06 to 10 05 to 08 03 to 04
Page 23
SP No.
Output No.
Printed in USA 131119
Page 24
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
4 Mounting / Electrical Connection
The Controller is installed through the 4 marked mounting holes at the back of the housing. These mounting holes are accessible after opening the housing. See Fig. 01
The mounting holes should be covered with the enclosed caps after installation.
Please consider the following when selecting the mounting place:
Avoid locations where water, oil etc. may influence proper operation and where mechanical damage might
be possible.
Install cables only from the Topside.
On the left side keep at least 150 mm distance to open the transparent door.
Consider any unusual condition or requirements of the Customer.
Fig. 01
8.7 in. (220 mm)
21,1in. (536mm)
Page 24
4.1 Electrical Connection
Installation must be done per local electrical codes with the consideration of the technical requirements of the product.
The alarms are available as SPDT, potential free contacts.
For the exact position of the terminations of the relays see the following connection diagram.
Printed in USA 131119
Page 25
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
4.2 Unit position – Connection diagram
GGreen/Ye XGray HGray
120 VAC
(see ill. 1)
(see ill. 4)
NBlue
Input Power
GGreen/Ye
Binary - Relay Outputs
R01 R03R02 R04 R05
2 345678910 11 12 1314 151
1
2
X1
FaultFault AlarmAlarm
X2
INTEC Controls
05.07.10 10: 28am
X10 X11
12345678910111 2 1 23456789101112
Sensor Inputs
Digital Inputs
Analog Outputs
(see ill. 2)
DIN Rail
Optional: Modbus Interface
(see ill. 8)
345678
12
X2
C5 Comm. Coupler
Optional:
BACnet
(see ill. 7)
Page 25
X1
1234
X2
X2
2
Power Unit
(see ill. 5) (see ill. 6)
1
2
X1
EP-02-2EP-02-1
12345678910111 2 123456789101112
Analog Outputs
Sensor Inputs
(see ill. 6) (see ill. 4)
1
2
X1
EP-02-4EP-02-3
12345678910111 2 123456789101112
Analog Outputs
24 VDC1 Output
Sensor Inputs
LNG
V-
Top Bottom
Binary - Relay Outputs
R11R13R12R14 R15
2345678910 11 12 1314 151
X10 X11
2345678910 11 12 1314 151
X10 X11
V+
(see ill. 2)
Binary - Relay Outputs
R06 R08R07 R09 R10
2345678910 11 12 1314 151
1
2
X1
X10 X11
12345678910111 2 1 23456789101112
Sensor Inputs
(see ill. 4) (see ill. 6)
1
(see ill. 2)
Binary - Relay Outputs
R16R18R17 R19R20
2345678910 11 12 13 14 151
2
X1
X10 X11
(see ill. 4)
12345678910111 2 123456789101112
Sensor Inputs
(see ill. 3)
Terminal block “X1”
Circuit breaker
1F1
Horn
(see ill. 2)
X2
X2
DIN Rail
Analog Outputs
ill. 1
)”
2
DIN Rail
Analog Outputs
(see ill. 6)(see ill. 6) (see ill. 4)
120 VAC Input Power Supply
120 VAC (90...230 VAC), 50/60 Hz
AC hot
AC neutral
Earth ground
G
H N
• Resettable breaker, max 10 A,
rated current approx. 2 A
• “Min wire size 16 AWG (1.5 mm
Terminal block
Green/Yellow
Blue
Gray
Printed in USA 131119
Page 26
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Page 26
Binary - Relay Outputs “R01 to R15”
Stage-level control & alarming
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
Stage-level control & alarming
#5 #4 #3 #2 #1
#10 #9 #8 #7 #6
“EP-02-1”
(Located at Controller module, EP-02-1
& EP-02-2 modules)
NO
NC
COM
COM
NC
NO
1 2 4 5 6 7 8 9 11 12 13 14 15
3
NO
NC
COM
COM
NO
10
NC
NO
NC
R01 R02 R03 R04 R05
Normal condition (factory default)
D1 D2 D3 D4 D5
NO
NC
COM
COM
NC
NO
1 2 4 5 6 7 8 9 11 12 13 14 15
3
NO
NC
COM
COM
NO
10
NC
NO
NC
COM
X2
COM
X2
R06 R07 R08 R09 R10
Normal condition (factory default)
D1 D2 D3 D4 D5
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
#15 #14
Stage-level control & alarming
#13 #12 #11
NO
NC
COM
10
NO
NC
“EP-02-2”
NO
NC
COM
COM
NC
NO
1 2 4 5 6 7 8 9 11 12 13 14 15
3
R11 R12 R13 R14 R15
Normal condition (factory default)
D1 D2 D3 D4 D5
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
COM
NO
NC
COM
X2
Printed in USA 131119
Page 27
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Page 27
Binary - Relay Outputs “R16 to R20”
Built-in horn alarming*** factory wired, 24 VDC
Fault (fail) alarming
Stage-level control & alarming
“EP-02-3”
***Factorypre-conguredhornandfault(fail-safe),
can be reassigned/converted for remote control, stage-level #19 and/or #20
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
24 VDC Output Supply
24 VDC max 0.5 A
(+)
for remote alarm
(-)
display units
1 2
(–) (+)
*** #18
#17 #16
ill. 2 (cont...)
(Located at EP-02-3 module)
NO
NC
COM
COM
NC
NO
1 2 4 5 6 7 8 9 11 12 13 14 15
3
NO
NC
COM
COM
NO
10
NC
NO
NC
R16 R17 R18 R19 R20
Normal condition (factory default)
D1 D2 D3 D4 D5
1H1
COM
X2
Terminal block X1
ill. 3
Printed in USA 131119
Page 28
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Page 28
Sensor Inputs “SP01 to SP20”
1 2 4 5 6 7 8 9 103 X10
SP01
SP02
SP03
SP04
SP05
SP06
SP07
SP08
SP13
SP14
SP15
SP16
4-20 mA 24 VDC
SP01/02- (–)
4-20 mA 24 VDC
4-20 mA 24 VDC
SP03/04- (–)
4-20 mA 24 VDC
“EP-02-1”
4-20 mA 24 VDC
SP05/06- (–)
4-20 mA 24 VDC
4-20 mA 24 VDC
SP07/08- (–)
4-20 mA 24 VDC
“EP-02-3”
4-20 mA 24 VDC
SP13/14- (–)
4-20 mA 24 VDC
4-20 mA 24 VDC
SP15/16- (–)
4-20 mA 24 VDC
1 2 4 5 6 7 8 9 103 X10
1 2 4 5 6 7 8 9 103 X10
(Located at Controller module, EP-02-1, EP-02-2,
2-wire sensor / transmitter
“EP-02-2”
SP09
SP10
SP11
SP12
SP17
SP18
SP19
SP20
4-20 mA 24 VDC
SP09/10- (–)
4-20 mA 24 VDC
4-20 mA 24 VDC
SP11/12- (–)
4-20 mA 24 VDC
“EP-02-4”
4-20 mA 24 VDC
SP17/18- (–)
4-20 mA 24 VDC
4-20 mA 24 VDC
SP19/20- (–)
4-20 mA 24 VDC
EP-02-3 & EP-02-4 modules)
3-wire sensor / transmitter
4-20 mA
24 VDC
1 2 4 5 6 7 8 9 103 X10
1 2 4 5 6 7 8 9 103 X10
4-20 mA 24 VDC (–)
Digital Inputs “DI01 to DI04”
(Located at Controller module)
1 2 3 4 5 6 7 8 9 10 11 12
ill. 4
X11
ill. 5
Printed in USA 131119
Page 29
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
5 Start-up Operation
5.1 Start-up
Before beginning start-up the wiring of the Controller including all field devices must be completely terminated!
After switching the power supply “ON” and the end of the Power On Time, then the Controller is ready for use.
The electrochemical sensor needs a warm up time of 1 hour to reach its highest accuracy.
The Controller is delivered with standard parameters and stages/set points. The assignment of the relays to the individual stages can occur at start-up unless arrangements have been made with the factory for programming. All other parameters are to be examined and adapted to the local conditions.
Page 29
Printed in USA 131119
Page 30
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
5.2 Checklist Start-up operation
System Setup
Parameters Registration of existing EP-02 modules Time and Date Parameter Average Function Password level 1 (Customer Password) Function analog output Define failure relay Power On Time Service Phone No. Maintenance date
Relay Setup
Parameters
Relay R 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Relay Mode Function Steady / Flash
Latching Mode
Horn function
External Relay operation
Delay ON time
Delay OFF time
SP Setup
Parameters
SP No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
SP Mode
Type
Measuring range
SP- Signal
Stage/Setpoint 1
Stage/Setpoint 2
Stage/Setpoint 3
Stage/Setpoint 4
Stage/Setpoint 5
Hysteresis
Delay ON time
Delay OFF time
C/A Mode
Assigned Failure <> Stage
Assigned Stage<> Relay
Assig. SP <> Anal. Output
Finish
Finish
Finish
Page 30
Printed in USA 131119
Page 31
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
6 Configuration- and Parameter card
Commission: Project No. Customer: Start-up - company Start-up - date: Service Technician
6.1 Configurations System Setup
Page 31
Service Software
Version
Default 15 06.06.06 858 578-7887 120 120 1800 US 1234 30 s 19
Analog output 1 Analog output 2 Analog output 3 Analog output 4
Calibration Calibration Calibration Calibration
Mode = 4 = 20 Mode = 4 = 20 Mode = 4 = 20 Mode = 4 = 20
Max. 4.0 20.0 Max. 4.0 20.0 Max. 4.0 20.0 Max. 4.0 20.0
Mainten-
ance date
Service
Phone
AV- Overlay Time
ppm Time AV-
Time
system
Customers
pass
Analog output 5 Analog output 6 Analog output 7 Analog output 8
Calibration Calibration Calibration Calibration
Mode = 4 = 20 Mode = 4 = 20 Mode = 4 = 20 Mode = 4 = 20
Max. 4.0 20.0 Max. 4.0 20.0 Max. 4.0 20.0 Max. 4.0 20.0
Analog output 9 Analog output 10
Calibration Calibration
Mode = 4 = 20 Mode = 4 = 20
Max. 4.0 20.0 Max. 4.0 20.0
Power
On
Time
Failure
Relay
Printed in USA 131119
Page 32
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
6.2 Relay Setup
Page 32
Relay
No.
Mode Steady
Flash
Latching
mode
Horn
Function
External Delay time
ON OFF ON OFF
Ti Reset DI DI DI Time Time
Defaul Energize 0 s No 0 0 0 0 0
R01 R02 R03 R04 R05 R06 R07 R08 R09 R10 R11 R12 R13 R14 R15 R16 R17 R18 R19 R20
Printed in USA 131119
Page 33
Customer Services (858) 578-7887 & (888) GO INTEC
(
)
y
INTEC Controls, 12700 Stowe Dr., Suite 110, Poway, CA 92064
Polygard® is a registered trademark of MSR MGC2-20
17
18
19
20
13
14
15
16
09
10
11
12
05
06
07
08
01
02
03
04
6.3 Sensor Setup
Default Not active CO 250 Linear 25 50 100 250 100 15 0 0 CV 1 1 0 1 0 R1 R2 R3 0 R5 0
No.
SP
Status
SP
Type Measur
PolyGard
User Manual - MGC2-20
range
ing
Signal
SP-
S1 S2 S3 S4 S1 ON OFF S1 S2 S3 S4 S5 S1 S2 S3 S4 S5
Stage/Setpoints Hyst Delay time
®
Multi-Point Controller
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specicationsubjecttochangewithoutnotice.
Printed in USA 131119
sec.
AV
AO
CV/
Assigned SP fault < >Stage
Page 33
Assigned Stage/Setpoint<>
Rela
AO
Page 34
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
7 Specifications MGC2-20
Page 34
Electrical
Power supply
Power Consumption 60 VA, max. RF/RMI proteced 4.0 W @ 3 ft. (1 m) radiated
Type of control
General
Analog Input Twenty (20), 4 - 20 mA Analog reading Current and mean (average) value Power supply for Analog inputs 24 VDC max. 50 mA / channel
Stage level / setpoint
- hysteresis/ switching differential Selectable for each sensor point
Digital inputs
Relay outputs (R1-R20) w/ status LEDs
- each stage level (S1-S5) Assignable to any relay
- sensor fail-safe Assignable to any stage level
Time delay switching
VDC output supply 24 VDC, 0.5 A fused
Analog output
Audible alarm
Alarm acknowledgement
User Interface Keypad type See 2.1 “Description Keypad User Interface” Touch buttons Six (6) Status LED’s Yellow: Alarm; Red: Fault (fail)
Digital display
- unit display
Environmental
Permissible ambient
- working temperature 23 °F to 104 °F (-5 °C to+ 40 °C)
- storage temperature -4 °F to 104 °F (-20 °C to + 40 °C)
- humidity 15 to 95 % RH non condensing
- working pressure Atmospheric ± 10%
120 VAC (90 to 230 VAC) 50/60Hz resettable breaker
Five-stage (S1 to S5) control, assignable up to twenty (20) binary/relay output, i.e. Low-med-high-fault / fail-horn*, or low1-low 2­med1-med2-high, or any other combinations (* = horn/audible alarm built-in and factory pre­configured to relay output “R20”)
Field adjustable over full range, five (5) per analog input, assignable to current or mean (average) value
Four (4) each can be individually assigned to any relay (R1..R20). Digital inputs are used for remote audio/visual alarm reset Twenty (20) SPDT, 8 A, 24 VAC/VDC -250 VAC contact resistance 100 m, max.
Selectable for make and brake of each sensor point (SP1 to SP20) 0-9,999 seconds
Ten (10) independent 4 - 20 mA signal, 500 max. load, selectable as low, high or averaging of sensor inputs 90 db, enabled or disabled, selectable; assignable to stage level S1, S2, S3, S4 or S5 Menu-driven and system reset function for latched relays
Liquid Crystal Display (LCD), two lines, 16 characters per line, 1 digit resolution, backlit Menu selectable, per sensor; ppm, %v/v, %LEL; °F or % RH
Printed in USA 131119
Page 35
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
Page 35
Physical Enclosure (panel) Plastic housing with view cover
- material
Polycarbonate, impact resistance EN 50102/K08, flammability rating UL 94-5V
- conformity UL Type 1, UL508/UL 50 standards
- color Light gray, smoked gray for cover
- protection NEMA 4X (IP65)
- installation Wall (surface) mounted Dimensions (H x W x D)
- base 22.8 x 12.0 x 5.7 in. (580 x 306 x 145 mm)
- Cable entry 10 holes for ½ in. conduit, covered
Wire connection
Wire size
- input
- output
Terminal blocks, Push-on connect and screw type for lead wire
Min. 22 AWG (0.34 mm Max. 16 AWG (1.5 mm Min. 24 AWG (0.25 mm Max. 14 AWG (2.5 mm
2
)
2
)
2
)
2
)
Weight 14.5 Ibs. (6.6 kg) Approvals / Listings
City of Los Angeles Approved (pending)
- unit
VDI 2053, C-No. 418791, CE EMV-Compliance 89/336/EWG
- power supply unit
UL Recognized, E183223 CSA Certified, E183223 UL Recognized, E5610 & E108658
- relays (R1 – R20)
CSA, C22.2 No. 14, LR35579 VDE
- enclosure (panel) UL Listed, E75645
Printed in USA 131119
Page 36
Customer Services (858) 578-7887 & (888) GO INTEC INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller User Manual - MGC2-20
8 Notes and General Information
It is important to read this user manual thoroughly and clearly understand the information and instructions. The PolyGard appropriate operating and maintenance instructions and recommendations must be followed.
Due to ongoing product development, MSR reserves the right to change specifications without notice. The information contained herein is based upon data considered to be accurate. However, no guarantee is expressed or implied regarding the accuracy of this data.
8.1 Intended product application
8.2 Installers’ responsibilities
®
MGC2 monitoring, control and alarm system must be used within product specification capabilities. The
The PolyGard® MGC2 are designed and manufactured for control applications for energy savings and OSHA air quality compliance in commercial buildings and manufacturing plants (i.e., detection and automatic exhaust fan control for automotive maintenance facilities, enclosed parking garages, engine repair shops, warehouses with forklifts, fire stations, tunnels, etc.).
It is the installer’s responsibility to ensure that all PolyGard® MGC2 are installed in compliance with all national and local codes and OSHA requirements. Installation should be implemented only by individuals familiar with proper installation techniques and with codes, standards and proper safety procedures for control installations and the latest edition of the National Electrical Code (ANSI/NFPA70). It is also essential to strictly follow all instructions as provided in the user manual.
Page 36
8.3 Maintenance
It is recommended that the PolyGard® MGC2 performance check is done on a routine schedule. Any performance deviations may be serviced based on needed requirements. Part replacement may be implemented in the field by a qualified individual and with the appropriate tools.
8.4 Limited warranty
MSR-Electronic-GmbH and INTEC Controls warrants the PolyGard® MGC2 for a period of two years from the date of shipment against defects in material or workmanship. Should any evidence of defects in material or workmanship occur during the warranty period, INTEC Controls will repair or replace the product at their own discretion, without charge.
Thiswarrantydoesnotapplytounitsthathavebeenaltered,hadattemptedrepair,orbeensubjecttoabuse,
accidental or otherwise. The above warranty is in lieu of all other express warranties, obligations or liabilities.
This warranty applies only to the PolyGard liable for any incidental or consequential damages arising out of or related to the use of the PolyGard
If the PolyGard
®
MGC2 needs to be returned to INTEC Controls for service, an RMA number must be obtained
®
MGC2. MSR-Electronic-GmbH and/or INTEC Controls shall not be
®
MGC2.
prior to sending.
Printed in USA 131119
Loading...