3 Menu Overview ...................................................................................................................................... 7
3.1.1 Acknowledge a malfunction ....................................................................................................... 8
3.1.2 History error summary ............................................................................................................... 8
3.1.3 System Errors ............................................................................................................................ 9
3.2 Stage Status ..................................................................................................................................... 9
3.3 Relay Status ..................................................................................................................................... 9
3.3.1 Manual operation of the relays ................................................................................................ 10
3.4 Menu Sensor Readings .................................................................................................................. 10
3.5 Menu Relay Setup .......................................................................................................................... 11
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
Multi Point Controller MGC2
1 Description
The PolyGard® Multi Point Controller MGC2 is used for the monitoring and warning of sensor points exceeding
their stage setpoints. External Transmitters can monitor and warn of toxic, combustible and refrigerant gases as
well as temperature and humidity. The Controller MGC2 can measure up to twenty analog 4 to 20 mA (Gas)
Transmitters.. Each Sensor Point (SP) can have five stage thresholds. Each stage threshold can be assigned to
anyone of the relays (R1…R20). The Controller can interface via ten 4 to 20 mA outputs to any compatible
electronic analog control, DDC/PLC control or automation system.
The adjustable parameters and staged thresholds make this system very flexible for sensor measuring and
control.
The configuration of parameter settings and operation is easy to do without any programming knowledge.
PolyGard
®
Multi Point Controller MGC2 must not be used in areas requiring explosion proof equipment.
Page 04
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 5
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
A
User Manual - MGC2-20
2 Operating Instruction
The complete configuration, parameterization and service are made via the keypad user interface in combination
with the display screen. Security is provided via two password levels.
Page 05
Fault
larm
INTEC Controls
01.22.05 10:28 am
2.1
Description Keypad User Interface
Exits programming and saves settings, returns to the previous menu level.
Enter sub menus, stores changed values.
Scrolls down & up in Main menu and Sub menus, increases or decreases a value.
Moves cursor left or right.
LED yellow Flashes when one or more stages have been exceeded or steady if the operator has manually
overridden any relays.
LED red: Flashes when a System or Sensor Failure is detected or when the Maintenance Date is needed.
2.2 Setting / Change Parameters
Desi
red menu window open.
Opens menu window, if the password is approved the cursor jumps to the first segment
position
Moves the cursor right or left to a segment position
Changes the parameter or value
Saving the changed parameter or value.
Finish
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 6
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
2.3 Password Level
All changes of parameters and staged setpoint values are protected by four digit numeric Code (= password).
The code level 1 permits the operation of the MGC2. This code level is intended for the customer. It can be
changed in the System Setup Menu “Change Customer Password”
With the code level 2 all parameters and set points can be changed, this code level is reserved for the service
technician.
A password must be re-entered if there is 15 minutes of inactivity.
All menu windows are visible without a password.
Factory preprogrammed system password "9001".
Page 06
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 7
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
or
Page 07
Gas concentration
User Manual - MGC2-20
3 Menu Overview
The Multi-Point Controller MGC2 is operated via a simple and logical menu structure which is easy to learn. The
operating menu contains the following levels:
of all registered transmitters in 5-second intervals
● Mainmenu
● Submenu1and2
Starting menuSub menuMain menu
Power On TimeDisplay of
After 30 sec.
INTEC
10.23.13 12:53
System Errors
Stage Status
Relay Status
Sensor Readings
Relay Setup
SP Setup
Reading and reset of errors
See Section 3.1
Display of the status of actual alarms
See Section 3.2
Display of the relay status
Manual operation of the relays
Reset function of the relays
See Section 3.3
Display of the sensor values
See Section 3.4
Reading and change of the relay parameters
See Section 3.5
Reading and change of sensor point parameters
Activate or Deactivate SP
Assignment of the alarms to the alarm relay
See Section 3.6
Data Logger
System Setup
Polygard® is a registered trademark of MSRMGC2-20
Not applicable to standard MGC2 controllers;
available as a special order option
Reading and change of the system parameters
See Section 3.7
Printed in USA 131119
Page 8
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.1 Malfunction management
Malfunction management records the last 15 malfunctions with date and time stamps. In addition, “System Errors”
are recorded in “Error Memory” when the malfunction occurs. This history can be selected and cleared only by the
service technician level 2 password.
A malfunction will display a text message in the Starting Menu. When a failure occurs the relay defined in the
system setup as “Failure relay” is activated. The red LED in the front of the Controller flashes.
During the malfunction of a sensor point (SP) stages that are assigned for sensor failure are activated. Relays that
are assigned to these stages perform as if the stage has been exceeded. These assignments are programmed in
the menu “SP Setup”.
3.1.1 Acknowledge a malfunction
Note:
Resetting a malfunction is only possible if the problem is corrected.
System Errors
Select Menu “System Errors”
Page 08
SP 01 < 3mA
Example: Failure SP 01 < 3 mA
05.02 10.38
SP 01 < 3mA
Malfunction Reset?
Reset ??
Malfunction Reset
SP 01 < 3mA
Error Cleared
Malfunction Cleared Problem not corrected
or
Error still
exists
Reset not possible
3.1.2 History error summary
The code level 2 password can open the menu “Hist Error Sum” in the main menu “System Errors”.
The last 15 error messages are listed for the service technician even if they have already been reset. These error
messages can be deleted individually
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 9
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
(SP)
User Manual - MGC2-20
3.1.3 System Errors
System Error Messages:
SP XX > 22 mA Current signal at analog Input XX > 22 mA.
Cause: Short-circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Solution: Check cable to Transmitter, Perform Calibration, Change the Transmitter.
SP XX < 3 mA Current signal to analog Input XX < 3 mA.
Cause: Open circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Solution: Check cable to Transmitter, Perform Calibration, Change the Transmitter.
GC Error: Internal Communication Error I/O Board to LCD Board.
Cause: Internal Error.
Solution: Change the Controller.
EP 0X Com Error:Communication error to expansion module (EP 0X).
(Only active, if EP module announced).
Cause: EP module address not correct. (See Start up Operation 5.0)
Bus cable to EP 0X module disconnected.
No power supply at the EP 0X module.
EP module defective.
Solution: Check the EP module address.
Check the bus cable and the power supply.
Change the EP 0X module.
Maintenance: System maintenance is necessary.
Cause: Maintenance date exceeded.
Solution: Perform maintenance.
Page 09
3.2 Stage Status
Displays the actual stages exceeded in the sequence that they happen. The sensor point displays with the stages
that have been exceeded. Changes can not be made in this menu.
SP 01
S1 S2
Symbol Description Function
SP 01
SX Stage Status
Sensor Point
No.
S1 = Stage 1 ON
S2 = Stage 2 ON
S3 = Stage 3 ON
S4 = Stage 4 ON
S5 = Stage 5 ON
3.3 Relay Status
Display the actual status of each relay and changes can be made for manual operation of the relays.
R 01
OFF
Symbol Description
R 01 Relay No. 01
OFF Status Relay OFF
Setting
Status
Function
Select Relay No.
OFF
ON
Manual OFF
Manual ON
= Relay Off (Not Activated by Stage Setpoint)
= Relay On (Activated by Stage Setpoint)
= Relay manual Off
= Relay manual On
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 10
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.3.1 Manual operation of the relays
The manual operation of the relays can be accomplished in the menu “Relay Status”. If a relay is in the Manual ON
or Manual OFF status, the yellow LED at the Controller is on continuously.
The external operation of a relay by an assigned digital input has priority before the manual operation or the Stage
set point of a sensor point being exceeded.
Manually operated relays can be reset by selecting the “Automatic” mode.
The reset of Latching relays also is a function in this menu.
In this menu it displays the current value (CV) and average value (AV) with sensor unit and type for each active
sensor point (SP) as well as the defined mode of control (CV or AV mode) with “*” .
SP 01 NH3 ppm
50 *AV 33 CV
Symbol Description
SP 01
NH3 Type NH3 See 3.6.2
ppm Unit See 3.6.2
CV Current value CV Current value of Gas Concentration
AV Average value Average value (10 measured values within the time unit)
* Control mode Display for the Control mode selected. (CV or AV)
Not active SP Status Not active SP disabled
Error SP Malfunction Current signal < 3 mA or > 22 mA
Sensor Point
No.
Setting
Status
Function
Select SP No.
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 11
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.5 Menu Relay Setup
Display and change the parameters for each relay.
Page 11
Relay Setup
R 01
(Main menu)
(Selection Relay No.)
Relay Mode
Relay Mode
De- energized
Steady / Flash
Relay Function
0 s
See 3.5.2
Latching mode
Activate Latching Mode
No
Time Reset DI
Definition of Horn Functions
0s 0 0
External mode
Definition of external Relay Operation
DI: ON = 0: OFF = 0
See 3.5.1
See 3.5.3
See 3.5.4
See 3.5.5
Delay ON time
Set Delay ON time
0 s
Delay OFF time
Set Delay OFF time
0 s
See 3.5.6
See 3.5.6
3.5.1 Relay Mode
Symbol Description
Setting
Status
Function
R 01 Relay No. Selection Relay
Deenergized
3.5.2
Relay Action Steady / Flash
Symbol Description
R 01 Relay No.
Relay Mode
Deenergized
Setting
Status
De-energized
Energized
Function
Selection Relay
= Stage ON = Relay ON
= Stage ON = Relay OFF
0 = Relay Function steady
0 Function 0
> 0 = Relay Function flashing (= Periods time sec.)
Impulse / Break = 1:1
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 12
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.5.3 Latching Mode
Definition of Latching Function
Page 12
Symbol Description
R 01 Relay No.
No Latching Mode No
Acknow
ledging of a latching relay in the menu “Relay Status” is possible only if the sensor value is smaller than
Setting
Status
Function
Selection Relay
No
Yes
= Latching Mode non active
= Latching Mode active
the Staged set point including hysteresis. With this condition then latching is activated.
Example: Relay R2 assigned to Latching mode
Alarm 2
Display in the Menu
Status Relay
Relay 2
Reset in the Menu
Status Relay
3.5.4
Horn Function
On
Off
R2
OffR2On
On
Off
On
Off
Gas Concentration greater smaller as Threshold
R2
On
R2
OnR2Latching
R2
Off
With this parameter the relay is defined as a horn relay and can be acknowledged with the following possibilities.
By pressing one of the arbitrary 6 pushbuttons. (Only possible in the starting menu)
Automatic acknowledging when the time runs out.
.
By an external pushbutton. (Assigned to an appropriate digital input).
The horn function is activated only if at least one of the two parameters (time or digital input) is set.
Special function Response
After acknowledging the relay via Pushbutton or external DI the time starts. If this time runs out and if the stage is
still exceeded, the relay is energized again.
Symbol Description
R 20 Relay No.
Reset Mode 0
Time 120
DI 0 Assignment of the digital input used for remote reset of the horn.
Polygard® is a registered trademark of MSRMGC2-20
Setting
Status
Function
Selection Relay
0 = Acknowledge the relay at time run out, or via Pushbutton
1 = Acknowledge the relay via a Pushbutton, after time runs out
and the alarm is still active, then the relay is reactivated.
Time in seconds for Automatic acknowledging or before
reactivating alarms defined by Reset function
Printed in USA 131119
Page 13
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
Acknowledge the horn relay
Page 13
Alarm 4
Relay 4
Acknowledging
signal
On
On
Off
On
Off
Of
Time
Gas Concentration greater smaller as Threshold
Special function “Response”. (Return of the horn relay)
Alarm 4
Relay 4
Acknowledging-
signal
On
Off
On
Off
On
Off
Gas Concentration greater smaller as Threshold
TimeTime
3.5.5 External operation of Relay.
Assign one digital input (DI) for external setting of the relay ON and/or OFF.
This function has priority before a
stage threshold is exceeded and/or manual switching in the menu “Relay Status”.
tting
Symbol Description
Se
Status
R 01 Relay No. DI
Function
Selection Relay
DI-ON External On 0 If digital input closed, relay switch ON
DI-OFF External Off 0 If digital input closed, relay switch OFF
3.5.6 Delay operation of Relay.
Delay ON time begins when the Stage is exceeded and/or Delay OFF time when the Stage returns to normal
condition.
Symbol Description
R 01 Relay No.
0 s Delay Time ON 0
0 s Delay Time OFF 0
Polygard® is a registered trademark of MSRMGC2-20
tting
Se
Status
Function
Selection Relay
Stage ON: Relay is only activated at expiration of the defined
time (sec.) 0 sec. = No Delay
Stage OFF: Relay is only deactivated at expiration of the defined
time (sec.) 0 sec. = No Delay
Printed in USA 131119
Page 14
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.6 Menu SP Setup
Display and Change Parameters, Assign Stage value, Assign relays to stages and activate each Sensor Point
(SP).
Page 14
SP Setup
SP 01
(Selection of a sensor point)
active
SP Mode
Activate or deactivate SP
active
See 3.6.1
SP Type
Define Type
NH3
See 3.6.2
Measuring range
Define Measuring range
300 ppm
SP-Signal
Define signal type of transmitter
linear
See 3.6.4
Stage 1
Define Stage/Setpoint 1
100 ppm
(Main Menu)
See 3.6.3
See 3.6.5
Stage 2
Define Stage/Setpoint 2
100 ppm
Stage 3
Define Stage/Setpoint 3
200 ppm
Stage 4
Define Stage/Setpoint 4
200 ppm
See 3.6.5 Stage/Setpoint
Stage 5
Define Stage/Setpoint 5
300 ppm
See 3.6.5
Hysteresis
Hysteresis
15 ppm
See 3.6.5
Delay ON time
Set Delay ON time
0 s
Polygard® is a registered trademark of MSRMGC2-20
See 3.6.5
See 3.6.5
See 3.6.6
Printed in USA 131119
Page 15
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
Delay OFF time
Set Delay OFF time
0 s
AV Mode
Define Control Mode
CV
See 3.6.7
Stage - 1 2 3 4 5
Assign a SP Fault to a Stage
Fault - 1 1 0 0 0
See 3.6.8
S1; S2; S3; S4; S5;
Assign a relay to a Stage
01; 02; 03, 04; 05;
See 3.6.9
Analog Output
Assign SP signal to a Analog Output
0
See 3.6.10
3.6.1 Activate – Deactivate SP
Page 15
See 3.6.6
Symbol Description
SP 01 Sensor point
Active SP Status
Setting
Status
not
active
Function
Selection SP No. (SP01 is the internal Transmitter)
active = Sensor point enabled for reporting
not active = Sensor point disabled for reporting
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 16
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
Carbon monoxide
Combusible gas
Nitrogen oxide
Nitrogen dioxide
Ammonia
Oxygen
2
Carbon dioxide
Sulphur dioxide
Hydrogen sulphide
Chlorine
Ethylene oxide
Air quality
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Temperature
Humidity
The measuring range can be defined from 10 to 10000. The measuring ranges in the above table are typical and
only recommendations. For actual ranges see the sensor manufacturing specifications.
The measuring range must agree with the signal (4 to 20 mA) for active transmitters.
(4 mA = Display=0, 20 mA = Display Measuring range = max. point)
3.6.4 SP Signal
Gas transmitter with electro-chemical or catalytic bead sensors are linear for gas concentration proportional to the
4 to 20 mA signal.
Semiconductor gas sensors that are not linear and have a (exponential) signal. This signal is non-linear 4 to 20
mA signal from the gas transmitter.
The Controller MGC2 has the capability to monitor both types of gas transmitters, and other linear 4-20 mA
sensors. The type of signal is defined in this menu.
Symbol Description
SP 01 Sensor Point Selection SP No.
Linear SP Signal linear
Polygard® is a registered trademark of MSRMGC2-20
tting
Se
Status
Function
linear = Transmitter with linear Output signal
not linear = Transmitter with non linear Output signal (future).
Printed in USA 131119
Page 17
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.6.5 Stage/Setpoint / Hysteresis
Each sensor point can have five stages with set point values. If the measured level is greater than the defined
stage/set point, the associated stage is set. If the level falls below the stage/setpoint plus the hysteresis then the
stage returns to original condition.
It is recommended that the unused stages be set to max of sensor range to avoid the alarm light from false
reporting.
For O2 measurement on depletion consider when defining stage setpoints that stages will be set on a falling
measuring signal!
Page 17
Sy
mbol Description
SP 01 Sensor Point Selection SP No.
100
ppm
3.6.6
Delay ON time begins when the Stage is exceeded and/or Delay OFF time when the Stage returns to normal
condition.
3.6.7
Definition of the alarm evaluation by Current value (CV) or Average value (AV).
Concentration > Stage Threshold: Relay is only activated at
expiration of the defined time (sec.). 0 sec. = No Delay
Concentration < Stage Threshold: Relay is only deactivated at
expiration of the defined time (sec.). 0 sec. = No Delay
Function
Sensor Value > Stage/Set point1 = Stage 1
Sensor Value > Stage/Set point1 = Stage 2
Sensor Value > Stage/Set point1 = Stage 3
Sensor Value > Stage/Set point1 = Stage 4
Sensor Value > Stage/Set point1 = Stage 5
Sensor Value < (Stage/Set pointX –Hysteresis)
= Stage X OFF
Symbol Description
SP 01 Sensor Point Selection SP No.
CV Evaluation CV
t / Average Value Function See: 3.7.4
Curren
3.6.8 Assigned SP Fault to Relay
Define which stages are activated with a failure of the sensor point.
Symbol Description
SP 01 Sensor Point Selection SP No.
Stage - 1 2 3 4 5
Fault - 1 1 0 0 0
Polygard® is a registered trademark of MSRMGC2-20
Failure SP 1 1 0 0 0
Default
Status t
Function
CV = Control the Current value
AV = Control the Average value
Default
Status
Function
0 = Stage not ON at SP Failure
1 = Stage ON at SP Failure
Printed in USA 131119
Page 18
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.6.9 Assign Relay to a Stage
Any of the 5 Relays can be assigned freely to any Stage. Stages that do not activate relays receive an
assignment of 00.
Defaul
Symbol Description
SP 01 Sensor Point Selection SP No.
S1
S2
1
S3
S4
S5
Status
01
02
03
00
05
t
Function
01 = Stage 1 activate relay R 01
02 = Stage 2 activate relay R 02
03 = Stage 3 activate relay R 03
00 = Stage 4 does not activate a relay
05 = Stage 5 activate relay R 20 (internal horn)
Page 18
3.6.10
Assigned SP Signal to analog Output
The sensor point signal can be assigned to one of the ten analog Outputs. The signal defined in the control
mode (Current Value or Average Value) is transmitted.
Analog output see also: 3.7.2
Symbol Description
Default
Status
Function
SP 01 Sensor Point Selection SP No.
0 = SP Signal not assigned to any analog output
0 A 0
1 = SP Signal assigned to analog output 1
X = SP Signal assigned to analog output X
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 19
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.7 Menu System Setup
Display and change the System Parameters for the Controller
Page 19
System Setup
Service Mode
OFF
Software Version
GC02- XX
Next maint. Date
MM.DD.YY
Service Phone
858 578-7887
AV Overlay
See 3.7.4
0 s. 120 ppm
AV Time
1800 s
(Main Menu)
See 3.7.1
See 3.7.2
See 3.7.3
See 3.7.3
See 3.7.4
Time system
See 3.7.5
US
Time
See 3.7.5
hh:mm:ss
Date
See 3.7.5
MM.DD.YY
Customer Pass
Change ****
Failure Relay
See 3.7.8
19
Power On Time
See 3.7.9
30 s
Polygard® is a registered trademark of MSRMGC2-20
See 3.7.6
Printed in USA 131119
Page 20
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
EP Module 1
See 3.7.10
active
EP Module 2
See 3.7.10
active
EP Module 3
See 3.7.10
active
EP Module 4
See 3.7.10
active
EP Module 5
See 3.7.10
Not active
Page 20
GC- Address
Controller address
1
(Reserved for future expansion; value should be left at “1”)
Analog Output
See 3.7.7
Analog Output 1
See 3.7.7
Max.
Calibration AO 1
SieheSee 3.7.7
4.0=4 mA 20 = 20.0
Analog Output XX
See 3.7.7
Max.
Calibration AO XX
See 3.7.7
4.0=4 mA 20 = 20.0
3.7.1 Service Mode
the Service mode is set to (ON) then the stage/setpoints are disabled so relays are not activated during
If
calibration or service work. The service mode is Reset automatically after 60 minutes or when the service mode is
set to Off.
Symbol Description
Off Service Mode Off
Polygard® is a registered trademark of MSRMGC2-20
Default
Status
Function
Off = Stages exceeded will activate the assigned relays
On = Stages exceeded will not activate the assigned relays
Printed in USA 131119
Page 21
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.7.2 Software Version
Page 21
Symbol Description
GC02XX
3.7.3
Maintenance Concept
Software
Version
Default
Status
Function
XX = Software Version
The MGC2 system monitors the maintenance intervals as required, by local Regulations or Customer
requirements.
During startup and/or after maintenance the date for next maintenance is entered. When this date is reached at 9
o'clock the next morning a failure signal is activated and Start Menu displays the phone No. of the service
company. The failure signal (maintenance) can be acknowledged by the operator. The maintenance message
(Service Phone No.) is reset after maintenance is accomplished and a new maintenance date is entered.
The service phone number can be individually entered in the next menu.
Symbol Description
MM.DD.YY
Maintenance
Defaul
Status
Function
MM.DD.YY = Input date for next maintenance.
t
8585.... Phone No. Input the individual service phone No.
3.7.4
Average Value Function
The Controller calculates for each active sensing point the arithmetic average value from 10 measurements within
the time unit defined in this menu “AV-time”. This average value is indicated in the menu “Sensor Readings” near
the Current Value. During each Sensor Point Setup the control mode of Current Value or Average Value for the
Stage/Setpoint evaluation is defined.
The evaluation of the control mode Average Value is overlaid by the Current Value, if this exceeds Stage/Setpoint
defined in the menu “AV-Overlay”. The overlay is delayed by the time factor set in this menu.
Defa
Symbol Description
120 s
120pm
AV- Overlay
ult
Status
120 s
120 ppm
Function
sec. = Delay time average value Overlay. 0 = No overlay Function
ppm = Threshold average Overlay
1800 s AV-Time 1800 s sec. = Time to calculate average value
3
.7.5 Time, Date
Input and correction of the system time and date. Selection of the time and date format.
t
Symbol Description
US Time format US
hh.mm.ss Time
MM.DD.YY Date
Polygard® is a registered trademark of MSRMGC2-20
Defaul
Status
Function
EU = Display time and date in EU format
US = Display time and date in US format
hh.mm.ss = Input the correct time (EU format)
hh.mm.ss am = Input the correct time (US format)
TT.MM.JJ = Input the correct date (EU format)
MM.DD.YY = Input the correct date (US format)
Printed in USA 131119
Page 22
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.7.6 Customer Password (Code 1)
Change the System Password for level 1
Symbol Description
1234
Factory preprogrammed system password "9001".
Customerpassword
3.7.7 Analog Output
The Controller has two analog outputs (AO) with 4 to 20 mA signal per control module. Each of the ten analog
outputs can be assigned the signal of one or more sensor points. The assignment occurs in the menu “SP
Setup” for each SP. The sensor point sends the signal that is defined in the menu “C/A Mode”.
The Controller determines from the signal of all assigned sensor points the minimum, the maximum or the average
value and sends this value to the analog output. The determination of which value is sent is defined in this menu
“Analog Output X”. The analog output can be calibrated for 4 and 20 mA using an ampere meter attached (with
measuring range 25 mA) then respective AO factor can be changed to adjust the analog output 4 and/or 20 mA
During AO calibration no evaluation is made of the sensor point signals. This calibration is factory-set. The factors
should only be changed if you have an accurate amp meter.
Symbol Description
Max.
4.0
20.0
Select
Output mode
Calibration
Default
Status
1234 1234 = Define the Customer Password with 4 characters
Default
Status
Max.
4.0
20.0
Function
Function
Min. = Spends the minimum value of all assigned SP
Max. = Spends the maximum value of all assigned SP
Average = Spends the average value of all assigned SP
4.0 = Calibration factor at 4 mA
20.0 = Calibration factor at 20 mA
Page 22
3.7.8 Define the Failure Relay
Define the Failure Relay. See also malfunction management (3.1)
Symbol Description
19 Failure Relay R19 R19 = Define the failure relay
3.7.9 Power On Time
Sensors need a warm up period until the chemical process of the sensor reaches a stable condition. During this
warm up period the current signal can cause unwanted false alarms. Therefore, the Controller starts reporting
alarms after the Power ON Time delay once power is applied. While this time runs off, the Controller does not
report alarms. The Power On status is displayed.
Symbol Description
30 s Power On Time 30 s XX = Define the Power On Time (sec.)
Default
Status
Default
Status
Function
Function
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 23
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
3.7.10 Activation of expansions modules
The Gas Controller can manage, up to five expansions modules (EP-02). Each EP-02 has four analog inputs and
five alarm relays and two analog outputs. Each attached EP-02 is announced in this menu. The Controller checks
the communication to the registered EP-02 modules and shows a fault signal in case of a communication error. To
recognize the position of the EP-02 modules a module address is assigned to each module by the address
selector. See table.
The table shows the assignment of the MP and relay numbers to the individual modules.
Symbol Description
EP- Module No 1 active
EP- Module No 2 active 2 11 to 15 09 to 12 05 to 06
Not
active
EP- Module No 3 active 3 16 to 20 13 to 16 07 to 08
EP- Module No 4 active 4 ---- 17 to 20 09 to 10
EP- Module No 5 Not active 5 ---- ----- ------
Default
Status
Function
Active
= EP announced.
Not active
= EP not announced
Module
Addr.
Relay
No.
1 06 to 10 05 to 08 03 to 04
Page 23
SP No.
Output
No.
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 24
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
4 Mounting / Electrical Connection
The Controller is installed through the 4 marked mounting holes at the back of the housing. These mounting holes
are accessible after opening the housing. See Fig. 01
The mounting holes should be covered with the enclosed caps after installation.
Please consider the following when selecting the mounting place:
Avoid locations where water, oil etc. may influence proper operation and where mechanical damage might
be possible.
Install cables only from the Topside.
On the left side keep at least 150 mm distance to open the transparent door.
Consider any unusual condition or requirements of the Customer.
Fig. 01
8.7 in. (220 mm)
21,1in. (536mm)
Page 24
4.1 Electrical Connection
Installation must be done per local electrical codes with the consideration of the technical requirements of the
product.
The alarms are available as SPDT, potential free contacts.
For the exact position of the terminations of the relays see the following connection diagram.
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 25
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
4.2 Unit position – Connection diagram
GGreen/Ye
XGray
HGray
120 VAC
(see ill. 1)
(see ill. 4)
NBlue
Input Power
GGreen/Ye
Binary - Relay Outputs
R01R03R02R04 R05
2 345678910 11 12 1314 151
1
2
X1
FaultFaultAlarmAlarm
X2
INTEC Controls
05.07.10 10: 28am
X10X11
12345678910111 2 1 23456789101112
Sensor
Inputs
Digital
Inputs
Analog
Outputs
(see ill. 2)
DIN Rail
Optional:
Modbus Interface
(see ill. 8)
345678
12
X2
C5 Comm.
Coupler
Optional:
BACnet
(see ill. 7)
Page 25
X1
1234
X2
X2
2
Power Unit
(see ill. 5) (see ill. 6)
1
2
X1
EP-02-2EP-02-1
12345678910111 2 123456789101112
Analog
Outputs
Sensor
Inputs
(see ill. 6)(see ill. 4)
1
2
X1
EP-02-4EP-02-3
12345678910111 2 123456789101112
Analog
Outputs
24 VDC1
Output
Sensor
Inputs
LNG
V-
TopBottom
Binary - Relay Outputs
R11R13R12R14 R15
2345678910 11 12 1314 151
X10X11
2345678910 11 12 1314 151
X10X11
V+
(see ill. 2)
Binary - Relay Outputs
R06R08R07R09 R10
2345678910 11 12 1314 151
1
2
X1
X10X11
12345678910111 2 1 23456789101112
Sensor
Inputs
(see ill. 4)(see ill. 6)
1
(see ill. 2)
Binary - Relay Outputs
R16R18R17R19R20
2345678910 11 12 13 14 151
2
X1
X10X11
(see ill. 4)
12345678910111 2 123456789101112
Sensor
Inputs
(see ill. 3)
Terminal
block “X1”
Circuit breaker
1F1
Horn
(see ill. 2)
X2
X2
DIN Rail
Analog
Outputs
ill. 1
)”
2
DIN Rail
Analog
Outputs
(see ill. 6)(see ill. 6) (see ill. 4)
120 VAC Input Power Supply
120 VAC (90...230 VAC), 50/60 Hz
AC hot
AC neutral
Earth ground
G
H N
• Resettable breaker, max 10 A,
rated current approx. 2 A
• “Min wire size 16 AWG (1.5 mm
Terminal block
Green/Yellow
Blue
Gray
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 26
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
Page 26
Binary - Relay Outputs “R01 to R15”
Stage-level control & alarming
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
Stage-level control & alarming
#5
#4
#3
#2
#1
#10
#9
#8
#7
#6
“EP-02-1”
(Located at Controller module, EP-02-1
& EP-02-2 modules)
NO
NC
COM
COM
NC
NO
1 24 5 6 7 8 911 12 13 14 15
3
NO
NC
COM
COM
NO
10
NC
NO
NC
R01R02R03R04R05
Normal condition (factory default)
D1D2D3D4D5
NO
NC
COM
COM
NC
NO
1 24 5 6 7 8 911 12 13 14 15
3
NO
NC
COM
COM
NO
10
NC
NO
NC
COM
X2
COM
X2
R06R07R08R09R10
Normal condition (factory default)
D1D2D3D4D5
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
#15
#14
Stage-level control & alarming
#13
#12
#11
NO
NC
COM
10
NO
NC
“EP-02-2”
NO
NC
COM
COM
NC
NO
1 24 5 6 7 8 911 12 13 14 15
3
R11R12R13R14R15
Normal condition (factory default)
D1D2D3D4D5
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
COM
NO
NC
COM
X2
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 27
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
can be reassigned/converted for remote control,
stage-level #19 and/or #20
= Relay status LEDs D1 to D5 located below terminal connection of sensor inputs (X10)
24 VDC Output Supply
24 VDC max 0.5 A
(+)
for remote alarm
(-)
display units
1 2
(–)
(+)
***
#18
#17
#16
ill. 2 (cont...)
(Located at EP-02-3 module)
NO
NC
COM
COM
NC
NO
1 24 5 6 7 8 911 12 13 14 15
3
NO
NC
COM
COM
NO
10
NC
NO
NC
R16R17R18R19R20
Normal condition (factory default)
D1D2D3D4D5
1H1
COM
X2
Terminal block X1
ill. 3
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 28
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
Page 28
Sensor Inputs “SP01 to SP20”
1 24 5 6 7 8 9 103X10
SP01
SP02
SP03
SP04
SP05
SP06
SP07
SP08
SP13
SP14
SP15
SP16
4-20 mA
24 VDC
SP01/02- (–)
4-20 mA
24 VDC
4-20 mA
24 VDC
SP03/04- (–)
4-20 mA
24 VDC
“EP-02-1”
4-20 mA
24 VDC
SP05/06- (–)
4-20 mA
24 VDC
4-20 mA
24 VDC
SP07/08- (–)
4-20 mA
24 VDC
“EP-02-3”
4-20 mA
24 VDC
SP13/14- (–)
4-20 mA
24 VDC
4-20 mA
24 VDC
SP15/16- (–)
4-20 mA
24 VDC
1 24 5 6 7 8 9 103X10
1 24 5 6 7 8 9 103X10
(Located at Controller module, EP-02-1, EP-02-2,
2-wire sensor / transmitter
“EP-02-2”
SP09
SP10
SP11
SP12
SP17
SP18
SP19
SP20
4-20 mA
24 VDC
SP09/10- (–)
4-20 mA
24 VDC
4-20 mA
24 VDC
SP11/12- (–)
4-20 mA
24 VDC
“EP-02-4”
4-20 mA
24 VDC
SP17/18- (–)
4-20 mA
24 VDC
4-20 mA
24 VDC
SP19/20- (–)
4-20 mA
24 VDC
EP-02-3 & EP-02-4 modules)
3-wire sensor / transmitter
4-20 mA
24 VDC
1 24 5 6 7 8 9 103X10
1 24 5 6 7 8 9 103X10
4-20 mA
24 VDC
(–)
Digital Inputs “DI01 to DI04”
(Located at Controller module)
1 2 3 4 5 6 7 8 9 10 11 12
Polygard® is a registered trademark of MSRMGC2-20
ill. 4
X11
ill. 5
Printed in USA 131119
Page 29
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
5 Start-up Operation
5.1 Start-up
Before beginning start-up the wiring of the Controller including all field devices must be completely terminated!
After switching the power supply “ON” and the end of the Power On Time, then the Controller is ready for use.
The electrochemical sensor needs a warm up time of 1 hour to reach its highest accuracy.
The Controller is delivered with standard parameters and stages/set points. The assignment of the relays to the
individual stages can occur at start-up unless arrangements have been made with the factory for programming. All
other parameters are to be examined and adapted to the local conditions.
Page 29
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 30
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
5.2 Checklist Start-up operation
System Setup
Parameters
Registration of existing EP-02 modules
Time and Date
Parameter Average Function
Password level 1 (Customer Password)
Function analog output
Define failure relay
Power On Time
Service Phone No.
Maintenance date
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
7 Specifications MGC2-20
Page 34
Electrical
Power supply
Power Consumption 60 VA, max.
RF/RMI proteced 4.0 W @ 3 ft. (1 m) radiated
Type of control
General
Analog Input Twenty (20), 4 - 20 mA
Analog reading Current and mean (average) value
Power supply for Analog inputs 24 VDC max. 50 mA / channel
Stage level / setpoint
- hysteresis/ switching differential Selectable for each sensor point
Digital inputs
Relay outputs (R1-R20) w/ status LEDs
- each stage level (S1-S5) Assignable to any relay
- sensor fail-safe Assignable to any stage level
Time delay switching
VDC output supply 24 VDC, 0.5 A fused
Analog output
Audible alarm
Alarm acknowledgement
User Interface
Keypad type See 2.1 “Description Keypad User Interface”
Touch buttons Six (6)
Status LED’s Yellow: Alarm; Red: Fault (fail)
Digital display
- unit display
Environmental
Permissible ambient
- working temperature 23 °F to 104 °F (-5 °C to+ 40 °C)
- storage temperature -4 °F to 104 °F (-20 °C to + 40 °C)
- humidity 15 to 95 % RH non condensing
- working pressure Atmospheric ± 10%
120 VAC (90 to 230 VAC) 50/60Hz
resettable breaker
Five-stage (S1 to S5) control, assignable up to
twenty (20) binary/relay output, i.e.
Low-med-high-fault / fail-horn*, or low1-low 2med1-med2-high, or any other combinations
(* = horn/audible alarm built-in and factory preconfigured to relay output “R20”)
Field adjustable over full range, five (5) per
analog input, assignable to current or mean
(average) value
Four (4) each can be individually assigned to
any relay (R1..R20). Digital inputs are used for
remote audio/visual alarm reset
Twenty (20) SPDT, 8 A, 24 VAC/VDC -250
VAC contact resistance 100 m, max.
Selectable for make and brake of each sensor
point (SP1 to SP20) 0-9,999 seconds
Ten (10) independent 4 - 20 mA signal, 500
max. load, selectable as low, high or averaging
of sensor inputs
90 db, enabled or disabled, selectable;
assignable to stage level S1, S2, S3, S4 or S5
Menu-driven and system reset function for
latched relays
Liquid Crystal Display (LCD), two lines, 16
characters per line, 1 digit resolution, backlit
Menu selectable, per sensor;
ppm, %v/v, %LEL; °F or % RH
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 35
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
Page 35
Physical
Enclosure (panel) Plastic housing with view cover
- material
Polycarbonate, impact resistance
EN 50102/K08, flammability rating UL 94-5V
- conformity UL Type 1, UL508/UL 50 standards
- color Light gray, smoked gray for cover
- protection NEMA 4X (IP65)
- installation Wall (surface) mounted
Dimensions (H x W x D)
- base 22.8 x 12.0 x 5.7 in. (580 x 306 x 145 mm)
- Cable entry 10 holes for ½ in. conduit, covered
Wire connection
Wire size
- input
- output
Terminal blocks, Push-on connect and screw
type for lead wire
Min. 22 AWG (0.34 mm
Max. 16 AWG (1.5 mm
Min. 24 AWG (0.25 mm
Max. 14 AWG (2.5 mm
2
)
2
)
2
)
2
)
Weight 14.5 Ibs. (6.6 kg)
Approvals / Listings
City of Los Angeles Approved (pending)
- unit
VDI 2053, C-No. 418791, CE
EMV-Compliance 89/336/EWG
- power supply unit
UL Recognized, E183223
CSA Certified, E183223
UL Recognized, E5610 & E108658
- relays (R1 – R20)
CSA, C22.2 No. 14, LR35579
VDE
- enclosure (panel) UL Listed, E75645
Polygard® is a registered trademark of MSRMGC2-20
Printed in USA 131119
Page 36
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Specication subject to change without notice.
PolyGard® Multi-Point Controller
User Manual - MGC2-20
8 Notes and General Information
It is important to read this user manual thoroughly and clearly understand the information and instructions. The
PolyGard
appropriate operating and maintenance instructions and recommendations must be followed.
Due to ongoing product development, MSR reserves the right to change specifications without notice. The
information contained herein is based upon data considered to be accurate. However, no guarantee is expressed
or implied regarding the accuracy of this data.
8.1 Intended product application
8.2 Installers’ responsibilities
®
MGC2 monitoring, control and alarm system must be used within product specification capabilities. The
The PolyGard® MGC2 are designed and manufactured for control applications for energy savings and OSHA
air quality compliance in commercial buildings and manufacturing plants (i.e., detection and automatic exhaust
fan control for automotive maintenance facilities, enclosed parking garages, engine repair shops, warehouses
with forklifts, fire stations, tunnels, etc.).
It is the installer’s responsibility to ensure that all PolyGard® MGC2 are installed in compliance with all national
and local codes and OSHA requirements. Installation should be implemented only by individuals familiar with
proper installation techniques and with codes, standards and proper safety procedures for control installations
and the latest edition of the National Electrical Code (ANSI/NFPA70). It is also essential to strictly follow all
instructions as provided in the user manual.
Page 36
8.3 Maintenance
It is recommended that the PolyGard® MGC2 performance check is done on a routine schedule. Any
performance deviations may be serviced based on needed requirements. Part replacement may be
implemented in the field by a qualified individual and with the appropriate tools.
8.4 Limited warranty
MSR-Electronic-GmbH and INTEC Controls warrants the PolyGard® MGC2 for a period of two years from the
date of shipment against defects in material or workmanship. Should any evidence of defects in material or
workmanship occur during the warranty period, INTEC Controls will repair or replace the product at their own
discretion, without charge.