![](/html/2e/2e0c/2e0c2db7f9eb55a79fdbd1bc3716302439a11f45fa206cf57e6ea7a4499ea946/bg1.png)
POLON 4000
INTERACTIVE FIRE DETECTION AND ALARM SYSTEM
ROP-4001M & ROP-4001MH
FIRE MANUAL CALL POINTS
Installation and Maintenance Manual
IK-E325-001GB
IIC Edition
![](/html/2e/2e0c/2e0c2db7f9eb55a79fdbd1bc3716302439a11f45fa206cf57e6ea7a4499ea946/bg2.png)
2 IK-E325-001GB
The ROP-4001M and ROP-4001MH manual call points, covered by the present manual, complies with
the requirements of the following European Union directives:
CPD 89/106/EWG on electric construction materials;
EMC 2004/108/WE on electromagnetic compatibility.
The ROP-4001M and ROP-4001MH manual call points have been attested with the EC-Certificate of
Conformity No. 1438/CPD/0090 issued by the Scientific and Research Centre for Fire Protection
(CNBOP) Józefów, Poland, a EU notified authority No. 1438, confirming its compliance with the
requirements of the PN-EN 54-11:2004 standard.
The certificate may be downloaded from
www.polon-alfa.pl web site.
The ROP-4001M and ROP-4001MH call points have been approved by the CNBOP with the Allowance
Certificate No. 0345/2008.
1438
Polon-Alfa Spółka z ograniczoną odpowiedzialnością Sp. k.
155, Glinki Street, PL 85-861 Bydgoszcz, POLAND
07
1438/CPD/0090
EN 54-11
ROP-4001M & ROP-4001MH manual call points (addressable, B type)
Application – fire safety
Technical data - IK- E325-001GB manual
Read the manual carefully before assembling and operation. Any nonconformity with the instructions
contained in the manual may be harmful or may cause a violation of the law in force.
POLON-ALFA bears no responsibility for any damage resulting from any usage inconsistent with the
manual.
The waste product, unsuitable for further use, shall be passed to
a waste electric and electronic equipment collection point.
NOTE: The manufacturer reserves a right to change specifications of the products at any time
without a prior notice.
![](/html/2e/2e0c/2e0c2db7f9eb55a79fdbd1bc3716302439a11f45fa206cf57e6ea7a4499ea946/bg3.png)
IK-E325-001GB 3
1 PURPOSE
The ROP-4001M and ROP-4001MH manual call points are designated for operation in addressable
loops of the POLON 4000 system detecting lines. They are addressable devices installed in order to
transfer information about a noticed fire by their manual actuation.
The ROP-4001M manual call point in the standard execution is intended for indoor installation.
The ROP-4001MH manual call point (with a higher ingress protection level) is intended for outdoor
installation.
Both versions are suitable for semi-flush (in wall plaster) and surface (on wall plaster) mounting
installation – the basic version is the first one, the semi-flush type. A special auxiliary RM-60-R
masking frame is applied for surface mounting; it is not a part of the standard equipment and should
be ordered separately.
2 TECHNICAL SPECIFICATIONS
Call point type B, acc. to PN-EN 54-11:2004
Operation voltage (from detection line) 16.5 V … 24.6 V
Max. current draw in quiescent mode < 140 µA
Allowable cable wire diameter 0.8…1.2 mm
Address coding range 1 ÷ 127
Ingress protection:
ROP-4001M IP 30
ROP-4001MH IP 55
Operating temperature range:
ROP-4001M from -25 °C to +55 °C
ROP-4001MH from -40 °C to +70 °C
Allowable relative humidity: up to 95 % at 40 °C
Dimensions 102.5 x 98 x 45.5 mm
Mass:
ROP-4001 < 220 g
ROP-4001H < 260 g
Case colour red
3 SAFETY CONDITIONS
3.1 Repairs and maintenance
Any maintenance works or periodic inspections shall be executed by a skilled personnel employed by
companies authorised and trained by POLON-ALFA.
Any repairs must be carried out by the manufacturer. POLON-ALFA bears no responsibility for the
operation of any apparatus being serviced and repaired by an unauthorised personnel.
3.2 Anti-dusting eye protection
It is obligatory to use protective anti-dusting glasses and masks during installation works that
produce high amount of dust, such as hole drilling in walls.
Any electric tools shall be used strictly obeying the safety rules stated in the manufacturer instruction
manuals.