Installation Instructions
Conductor must have insulation acceptable for wet or damp locations
Wipe off any foreign material (dirt, water, oil, etc.) on insulation of conductor to be spliced
Mark the conductor insulation 3/4” and 2-1/4” from the end. Insulation strip length imprinted on connector
Remove the conductor insulation up to the 3/4” strip length, be sure not to “score” or “nick” conductor (bare wire). TIP - For wire sizes #1 and larger bevel edge of insulation
ISPBO
Brush all conductors before inserting into connector.
Select and cut off the step appropriate for size indicated on the sleeve. Make sure to cut sleeve straight across the end of the appropriate size step
Reinsert the conductor sleeve into wiring
Remove set-screw access plug and loosen set-screw to allow conductor insertion
For easier assembly lubricate the exterior of conductor insulation with the included dielectric silicone grease
Insert conductor into the cable outlet or conductor sleeve until the cable outlet or conductor sleeve until the 2-1/4” reference mark is even with end of cable outlet. The end of the conductor should hit back of connector
Tighten the pressure screws to the recommended torque per the Chart below
Replace set-screw access plug
Wire Range
(MCM/AWG)
ISPB
ISPBS
Max Torque
(In./Lbs.)
©2019 NSI Industries, LLC
#10 - #14 35
#8 75
2/0 - #6 120