POLA HP59/W Handbook

HP59/W
Handbook
SL 3.0
Air pressure controller
MAIN SETTING (Run Mode).
PRESSURE SETTING
Press SET (key lamp flashes): this message will be displayed instead of the
Set Pression (mm H2o).
Press + or - to modify, press SET to escape.
INSTALLATION
Pressure range= 0 / 3mBar (0.0 / 30.0mmH20). Maximum permissive pressure= 3mBar (30mmH20). Operating temperature= 0 - 70°C Waterproof= IP55
Example with
Set.P
=
3.0
As it company policy to continually improve the products the Manufacturers reserve the right to make any modifications thereto without prior notice. They cannot be held liable for any damage due to malfunction.
020214
LINEA 230V
456
Uscita MAX
Uscita MIN
www.pola.it
How to connect the line Connect 230V line on terminals L-N. Protect supply with adequate fuse.
3x0.5mmq section, L. m a x = 3 m t
HPAL contacts connection:
Contact relays are free voltage, max 4AMP AC1, fuses protection are 4A T H=35A.
IN= Ambient air input (pressure +). OUT= External air input (pressure -).
OUT 0.5-4.5V
0-30 mm H20
230V LINE
HP59
IN
OUT
456
230V LINE
MAX Output
MIN Output
To obtain maximum precision of pressure control, place HP59/W in vertical position.
Mess. Value Meaning Note
n.b.
1.0 N eutral band (mmH 20). *1
diF.P
0.2 P ressure differential (mmH20). *1
t.oF
2" Waiting time of actioning *2
t.on
2" Working time of actioning *2
IntE
1" Pressure reading integration time
ABLE
=1 Key SET abilitation *3
Ad.Pr
0.0 P ressure sensor correction (+ o -)
"HAND MODE"
.
In some start-up conditions may be useful to work in "hand" mode.
Power off the processor, press + key and keep it pressed giving power on:
HAnd
message will be displayed (release now + key). Push + until is displayed number required to be handed(1= relay MIN, 2=relay MAX) and push SET for activing relay. Pushing again + for increase relay number previous relay is disactivated. You can press SET for a least two seconds to escape and return to the
Run Mode.
These settings refer to the mode operation of the system and must be made on initial start-up. Press - / + together for at least one second. the message
C.O.S.t.
will be displayed. Press than repeatly SETuntil interested variable's message is displayed (see table below) : variable value and related message will be displayed. Press + or - to set a new value and then SET to confirm. The next system constant will then appear. You can press SET for a least two second to escape and return to the
Run Mode
.
COSt PROGRAMMING (System constants).
*1) For more details see
Operative Diagrams.
*3) Key SET qualification:
=0
key not able (pressing SET
no-oP
message will be displayed).
=1
Key able.
STATE INDICATION LAMPS
.
Lam p.
Actioning N° relay HPAL con tacts
MIN
MIN On actioning
RYA 3-4-5
MAX
MAX On actioning
RYB 6-7-8
If
t.Of
and
t.On
time worked (see COSt), MIN and MAX lamp flash during the request of actioning, and
lighting during the action of the relay.
Swinging Ambient / Set temperature (t.SEt) indicator
OUTPUT MAX ON
OUTPUT MIN ON
diF.P
OPERATIVE DIAGRAM.
diF.P
ON
OFF
MAXMIN
ON
OFF
MAX ON actioning conditionated by
t.Of
and
t.On
time
(see COSt).
MIN ON actioning conditionated by
t.Of
and
t.On
time (see COSt).
IN-OUT DIFFERENCE OF PRESSURE.
SEt.P
1/2 n.b. 1/2 n.b.
SEt.P
1/2 n.b. 1/2 n.b.
At delivery this processor is ready programmed with the following (variable) settings. To return to these settings at any time: Power off the processor, press SET key and keep it pressed giving power on: when
boot
full message will be displayed (release now SET key).
SEt.P=
3.0
The COSt values are shown in
COSt Programming.
PRESET PROGRAMS (Bootstrap).
*2) When actioning is required (MIN o MAX) , the request must remain for a higer
time than
t.oF
, then come execute for the time
t.On
and again wait for the time
t.oF
, and so on until remain the request of actioning. With
t.oF=0
the request of actioning come execute without delay time.