POLA HP58 Handbook

HP58
SL 4.0
Handbook
0-10V Proportional
TEMPERATURE SETTING
Press SET (key lamp flashes): this message will be displayed instead of the ° Set temperature value . Press + or - to modify, press SET to escape.
Example with t.SEt = 25.0°
STATE INDICATIONS LAMPS
MAIN SETTING (Run Mode)
INSTALLATION
Press TEMP key for at least 2 seconds to display % insert (PErC message will be displayed instead of the infra-red lamps power % inserction).
Output Relay
HEAT ON
Output Relay
COOL ON
BAR-GRAPH % 0-10V INSERT
The lamps near set key indicates relay command status.
COOL output
contact
HEAT output
contact
230V LINE*
HP58
- +
O-10V output
(min 10 Kohm)
SX temperature
probe *
As it company policy to continually improve the products the Manufacturers reserve the right to make any modifications thereto without prior notice. They cannot be held liable for any damage due to malfunction.
11.07.14
How to connect the sensors
Connect the sensor provided as shown in the diagram. For remote connections use a standard 0.5-square millimeter two-pole wire, taking great care over the connections, by insulating and sealing the joins carefully.
-O.C.- is displayed when the temperature sensor wiring is open, -S.C.- is displayed when the temperature sensor wiring is short circuit.
How to connect the line
Connect line on terminals L-N. Protect supply with adequate fuse.
How to connect the contacts
Connect terminals on the terminal block (contacts up to 4AMP.AC1).
Press + : will be displayed followed by
°Maximum Temperature Recording.
Press - : will be displayed followed by
°Minimum Temperature Recording.
VIEWING TEMPERATURE RECORDING
Values are permanently stored in the memory: for deleting all values in the memory keep pushed + key for more than 3 seconds: CLEA message will appear on display before clearing operation.
* Other power voltage if you required.
* 4-20mA humidity probe connection (with setting tEnP=3 in COSt).
10 9
R
230V LINE
Example with our
RHR humidity probe
R=100 ohm resistor to be connected
in parallel by 9-10 terminals.
*1) For more details see 0-10V Proportional output Operative Diagrams.
*2) For more details see Relay output Operative Diagrams. *3) =1 : °C Temperature range.
*4) You can correct the readings on the various sensor (+ or -).
CYCL = 1"...999"
100%
diFF
H 1
OFF
TEMPERATURA
75%
50%
25%
0%
TEMPERATURA
diFF
H 1
ON
OFF
1/2 d.HEA 1/2 d.HEA
CYCL= 0"
*1 Relay's operating computed with 1% resolution and actioned minimum 0,5 sec.
ON ON
CYCL
CYCL
ON ON
CYCL
OFF
ON
*1 Relay's output in the time.
ON
ON
Relay output
Set.t + rELA Set.t + rELA
0-10V Proportional Output
ProP
TEMPERATURE
10V
*1
7,5V
5V
2,5V
0V
0V
*1
0-10V output computated with 0,1V resolution.
10-0V (Negative proportional)
- Prop
TEMPERATURE
10V
*1
7,5V
5V
2,5V
0V
*1
10V
*1
0-10V output computated with 0,1V resolution.
0-10V (Positive proportional)
Set.t + rEL.P Set.t + rEL.P
COSt PROGRAMMING (System constants)
These settings refer to the operation mode of the system and must be made on initial startup. Press - / + at the same time for at least one second: the message C.O.S.t. will be displayed. Press than repeatedly SET until the message regarding the chosen variable is displayed (see table below) : value of variable and message will be displayed. Press + or - to set a new value and then press SET to confirm. The next system constant will then appear. You can press SET for at least 2 seconds to exit and return to the Run Mode.
=2 : °F Temperature range. =3 : 4-20mA (0.0%...100.0%). See Installation.
OPERATIVE DIAGRAMS
PRESET PROGRAMS (Bootstrap)
This processor is already programmed with the following (variable) settings. To return to these settings at any time you may:
Power off the processor, press SET key and keep it pressed giving power on:
boot message will be displayed (release now SET key). t.SEt = 25.0 The COSt values are shown in COSt Programming.
*1
Minimum and maximun output
conditionated by P._ _ _ e P.- - - set.
*1
Minimum and maximun output
conditionated by P._ _ _ e P.- - - set.
In some start-up conditions may be useful to work in "hand" mode: Power off the processor, press + key and keep it pressed giving power on: HAnd
message will be displayed (release now + key). Press + until is displayed number required to be handed (see relays table in State indication lamps) and push SET for activing relay. Pressing again + for increase relay number previous relay is disactivated. You can press SET key for a least two seconds to escape and return to the Run Mode.
MANUAL MODE
.sseM eulaV gninaeM etoN
P.LEr
°0.0
tES.totgnirrefertfihsgnittesV01-0°
)1*
PorP
°0.2
)tuptuoV01-0(dnablnoitroporP°
)1*
___.P
%0
muminimtlovtuptuO%
)1*
---.P
%001
mumixamtlovtuptuO%
)1*
ALEr
°0.0
tES.totgnirrefertfihsgnittesyaleR°
)2*
FFid
°2.0
)tuptuoyaler(laitnereffiD°
)2*
LCYC
"0
)tuptuoyaler(sdnocesniemitelcycnoitalugeromrehT
)2*
PnEt
1=
noitatneserpererutarepmeT )Am02-4=3,F°=2,C°=1(
)3*
Et.dA
°0.0
)-ro+(noitcerrocrosneserutarepmettupnI°
)4*