HP21A
SL 3.0
1,2 or 3-level thermostat / proportional controller
- Press SET to activate Relay 1, or :
- Press SET to activate 0 - 10v out
modify sets 2 & 3
Default settings
Set.1 (25˚C) Lamp OFF IN2. = OPEN
Set.2 (35˚C) Lamp FLASH IN2. = 100Ω
Set.3 (80˚C) Lamp ON IN2. = CLOSED
![](/html/7f/7fdf/7fdf1783514073c180b927b64c38d9b9402d36e52a669de1839d72555f572988/bg2.png)
Mess. Value Meaning Note
diFF
3˚ Relay out Diff, 0˚ - 25˚
*1)
R.dIF
3˚ Relative relay out adjustment, -25˚- 25˚
*1)
ProP
5˚ 0-10v out proportional band, 0˚ - 25˚
R.Pro
0˚ Relative 0-10v band adjustment, -25˚- 25˚
bArG
6˚ Bargraph band, 0˚ - 25˚
Ad.t1
0˚
Adjustment for set 1, -25˚ - 25˚ *2)
Ad.t2
0˚
Adjustment for set 2, -25˚ - 25˚ *2)
Ad.t3
0˚
Adjustment for set 3, -25˚ - 25˚ *2)
Set.‾
85˚
Maximum Set.1/2/3 value 0˚ - 150˚
n.SEt =3 Number of sets, =1, =2, =3
24v AC Line
0 - 10v Output
O.C. = 1, 100Ω = 2
S.C. = 3
External set
point select
(Using
SXA probe)
Range 0-150˚C
Temperature
Temperature
- | +