Thank you for purchasing our UPS, it is safe and liable, needs few maintenance.
This manual includes instructions of safety installation and operation, they help your UPS to have the
longest service life. This manual also accounts the UPS work principle and relative functions.
Please obey the instructions and notes stated in this manual. Keep this manual in a safe place, consult
it before operation.
Safety rules
Even if not connected to main power, high voltage may still presents at UPS outlets.
If the external battery cord or power cord needs to be replaced, please contact our service station or
franchiser for replacing to avoid fire disaster caused by insufficient capacity of such items. Don't dispose of battery or batteries group in a fire, otherwise, it can cause explosion and harm to people. Don't open the battery or do the battery damage, for the liquid spilled from battery is strongly poisonous and do harmful to body.
Please avoid short-circuit between battery anode and cathode; otherwise, this will cause electric shock or fire.
Don't dismantle the UPS cover, there is danger of electric shock.
Don’t touch batteries. Batteries are not isolated with the input circuit, there is high voltage between the
battery terminals and ground.
Dont connect with the electric equipment such as blower, heater, drilling machine etc. They may damage the UPS.
Note: POCASA reserves the right to make changes to product described in this manual at any time and
without notice for reasons of improvement.
Notice:
There presents high voltage in UPS. If there is any abnormal problem present, please consult the service center and do not attempt to repair the equipment under any circumstances. The
address of service center has been detailed on the warranty card.
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
2
Contents
1. Brief introduction-------------------------------------------------------------------------------------------------------------------3
1.1. Technology introduction----------------------------------------------------------------------------------------------------3
1.2. System and model description--------------------------------------------------------------------------------------------4
1.3. Description of commonly used symbols--------------------------------------------------------------------------------4
1.4. Appearance--------------------------------------------------------------------------------------------------------------------5
1.5. Product specification and performance---------------------------------------------------------------------------------6
2. Installation---------------------------------------------------------------------------------------------------------------------------8
2.1. Unpacking and inspection--------------------------------------------------------------------------------------------------8
2.2. Safety notes--------------------------------------------------------------------------------------------------------------------9
2.3. The description of front panel and display lamp--------------------------------------------------------------------10
2.4. Input and output power chords and protective earth ground installation--------------------------------------11
2.5. Operating procedure for connecting the long backup time model UPS with the external battery----------------------------------------------------------------------------------------------------------------------------------12
2.6. Parallel operation-----------------------------------------------------------------------------------------------------------13
3. Operation and operating mode-----------------------------------------------------------------------------------------------14
3.1. Operation---------------------------------------------------------------------------------------------------------------------14
3.2. Operating mode-------------------------------------------------------------------------------------------------------------15
4. Notes for battery disposal and battery replacement---------------------------------------------------------------------19
5. Troubles shooting----------------------------------------------------------------------------------------------------------------20 Appendix: The corresponding form of the LED display--------------------------------------------------------------------22 Appendix 2: EMC grade standards----------------------------------------------------------------------------------------------24
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
3
1. Brief introduction
1.1. Technology introduction
This UPS is a sophisticated piece of equipment with 16 bit Microprocessor and advanced software programming technology, high frequency SPWM is created to control the inverter of UPS. This simplifies the control circuit, enhances the stability of UPS, also enables the UPS to have enhanced real-time performance that makes UPS respond the variety of external environment rapidly and insure that the control circuit is compact and reliable.
Digital control technology to avoid the temperature excursion of hardware specification
Self-diagnoses before startup help UPS to find potential failure to avoid any losses
Double conversion on-line topology, which makes the UPS a pure sine wave machine with constant
frequency, constant voltage, low noise and no interruption with mains power fluctuation, it protect the user's equipments ideally all the time.
No transfer time when main power fail or main power restore, meets the requirements of precision instruments.
Standard bypass function When UPS meets a fault, it can transfer to bypass seamlessly and provide alarm.
Advanced voltage compensation technology, makes the wide input voltage range, reducing the battery
usage, enhancing the adaptive ability against the bad mains power variation.
Advanced wide frequency input technology Wide input frequency range of UPS gives UPS a good compatibility with generator under field
circumstances.
The advanced PFC technology on the input of UPS, improves the input power factor close to unity, raises
the power efficiency, removes the harmonic noise from UPS to utility, lowers UPS operational costs, it's really an environmental friendly protection power supply.
Smart management function Under mains power blackout, UPS would transfer to battery mode to supply power to loads, when battery
voltage is low, UPS would protect itself and shuts down automatically. When main power restores, UPS would be turned on automatically to supply power to loads.
Cold start function When there is no input, UPS can be turned on with battery pack, to meet the user's emergency needs.
The cold start function is quite strong. UPS can be cold started on full load situation.
Fault operation prevention function Every button has delay function, only when you press and hold the button for a certain time, required
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
4
operation can be activated.
Smart management function Under mains power blackout, UPS would transfer to battery mode to supply power to loads, when battery
voltage is low, UPS would protect itself and shuts down automatically. When main power restores, UPS would be turned on automatically.
Via internal or external SNMP card, UPS can go on internet, you can monitor and manage the UPS status
through all kinds of network management system.
1.2. System and model description
H online series is an uninterruptible power supply incorporating double-conversion technology. It provides perfect protection specifically for computer equipment communication systems to computerized instruments.
Its true online double-conversion design eliminates all mains power disturbances. A rectifier converts the alternating current from the utility power to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a pure sinusoidal AC voltage, which is constantly powering the loads.
Computers and peripherals are thus powered entirely by the UPS. In the event of power failure, the maintenance-free batteries power the inverter.
This manual is applicable to the following models:
1) The H6KS is model with inbuilt battery, hereinafter called 6KS;
2) The H6KL is a long backup time model, which is able to connect with the external battery bank,
hereinafter-called 6KL;
3) The H10KS is a standard model with inbuilt battery, hereinafter-called 10KS;
4) The H10KL a is a long backup time model, which is able to connect with the external battery bank,
hereinafter-called 10KL;
5) The H10KL3/1 is a three-phase input and single-phase output long backup time model, which is able to
connect with the external battery bank. Hereinafter called three-phase 10KL.
6) The H15KL3/1 is a three-phase input and single-phase output long backup time model, which is able to
connect with the external battery bank. Hereinafter called three-phase 15KL.
7) The H20KL3/1 is a three-phase input and single-phase output long backup time model, which is able to
connect with the external battery bank. Hereinafter called three-phase 20KL.
1.3. Description of commonly used symbols
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
5
The following symbols will be used in this manual and may appear during the course of your practical applications. Therefore, all users should be familiar with them and understand their meanings.
Notation and Explanation
Notation Explanation
Alert you to pay special attention
Caution of high voltage
Turn on the UPS
Turn off the UPS
Idle or shut down the UPS
Alternating current source (AC)
Direct current source (DC)
Protective ground
Alarm silence
Overload indication
Battery check
Recyclable
Do not dispose with ordinary trash
1.4. Appearance
Front display panel
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
6
Back view of 6KL Back view of 10KL/three phase 10KL
Back view of three phase 15KL/three phase 20KL
1.5. Product specification and performance
1.5.1. General specification (standard models)
Model H6KS H6KL H10KS H10KL
Power rating 6KVA/4.2KW 6KVA/4.2KW 10KVA/7KW 10KVA/7KW
Frequency(Hz) 50/60 50/60 50/60 50/60
Voltage (176-276)VAC (176-276)VAC (176-276)VAC (176-276)VAC
Input
Current 31A Max 31A Max 50A Max 50A Max Voltage 192/240VDC 192/240VDC 192/240VDC 192/240VDC
Battery
Current 24A Max 24A Max 40A Max 40A Max
Output Voltage 220VAC/230VAC 220VAC/230VAC 220VAC/230VAC 220VAC/230VAC
PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn
7
Dimension(W×D×H)mm 260×570×717 260×570×717 260×570×717 260×570×717
Net weight(Kg) 75 35 80 38
Model Three-phase 10KL Three-phase 15KL Three-phase 20KL
Power rating 10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Frequency(Hz) 50/60 50/60 50/60
Voltage (304-478)VAC (304-478)VAC (304-478)VAC Input Current 50A Max 75A Max 100A Max Voltage 192/240VDC 192/240VDC 192/240VDC Battery Current 40A Max 60A Max 80A Max
Output Voltage 220VAC/230VAC 220VAC/230VAC 220VAC/230VAC
Dimension(W×D×H)mm 260×570×717 260×570×717 260×570×717
Net weight(Kg) 39 52 52
1.5.2. Dimension & weight for UPS with galvanic isolation
Model H6KS H6KL H10KS H10KL
Power rating 6KVA/4.2KW 6KVA/4.2KW 10KVA/7KW 10KVA/7KW
Dimension(W×D×H)mm 700×430x845 700×430x845 700×430x845 700×430x845
Gross weight (Kg) 85 44 95 46
Model Three-phase 10KL Three-phase 15KL Three-phase 20KL
Power rating 10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Dimension(W×D×H)mm 700×430x845 700×430x845 700×430x845
Gross weight(Kg) 48 60 60
1.5.3. Electrical performance
Input
Frequency
Model Voltage
50Hz 60Hz
Power factor
6K(S)/10K(S) Single-phase ±4Hz
0.98(full load)
Three-phase
10KS/15KS/20KS
Three-phase ±4Hz
0.95(full load)
Output
Voltage
regulation
Power
factor
Frequency
tolerance
Distortion
Overload capacity
Current crest
rating
±1% 0.7 lag
Synchronized
±4Hz in Line
mode (AC mode)
±0.1% of normal
frequency in
battery mode
THD2%
full load
(linear
load)
105%-130% load transfers to
bypass mode after 10 minutes
130% load transfers to
bypass mode after 1 second
and shutdown the output after
1 minute
3:1 maximum
1.5.4. Operating environment
Temperature Humidity Altitude Storage temperature
0-40
20%-90%
1000M -15-40
Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following: