TABLE 7.3: ALARM PANEL LOSES ALL DISPLAYS EXCEPT SYSTEM ALARM
Possible cause
Remarks/rectification action
1. Mains electrical
power supply failure
Check mains electrical power supply into
the panel
2. Power supply fuses
blown
Check condion of fuses on power
supply PCB. Replace as necessary
3. Main ribbon
connector faulty
Check main ribbon connector on power
supply PCB. Replace power supply PCB
as necessary.
4. Main ribbon
damaged
Check main ribbon cable. If damaged
replace light display PCB.
5. Power supply PCB
faulty
Replace power supply PCB.
6. Light display PCB
faulty
If all other checks have failed to recfy
the fault, replace the light display PCB.
TABLE 7.4: SYSTEM ALARM/FAULT INDICATION WITH
A SERVICEABLE GAS
Possible cause
Remarks/rectification action
1. Electrical power
failure
Check POWER ON indicaon is
illuminated and other indicaons are
normal.
2. Gas service pressure
incorrect
Independently check gas service pressure
in area being monitored
3. Pressure switch
stuck in fail
Check resistance of interconnecng
wiring, line monitor module and
posion pressure switch.
(180Ω ± 5% with contacts closed), (690Ω
± 5% with contacts open). If value is
incorrect check connuity exists through
plant alarm relays/pressure switch. Check
pressure switch adjustment and replace
switch as necessary, complete with line
connuity module
4. Wiring defect
between panel and
pressure switch / plant
With a serviceable pressure switch ed,
check resistance of interconnecng
wiring and line monitor module (<10
ohms indicates a short circuit or >5K
ohms indicates an open circuit). Locate
wiring defect, repair as necessary or
replace line monitor module.
5. Main ribbon
connector faulty
Check main ribbon connector on power
supply PCB. Replace power supply PCB as
necessary.
6. Main ribbon
damaged
Check main ribbon cable. If damaged
replace light display PCB.
7. Power supply PCB
faulty
Replace power supply PCB.
8. Light display PCB
faulty
If all other checks have failed to recfy
the fault, replace the light display PCB.
TABLE 7.5: REMOTE ALARM/RECORDING SYSTEM
NOT OPERATING CORRECTLY
Possible cause
Remarks/rectification action
1. JP1 set
incorrectly
Check that the jumper on JP1 is set to
the correct posion.
2. Faulty interface relay With all gas services indicang
NORMAL, check that connuity exists
between both relay terminals (N/O
and C) on power supply PCB. With a
gas service failure indicaon, check
that relay contacts open and break the
circuit between the relay terminals.
Replace power supply PCB if relay
proves to be faulty.
3. Interconnecng
wiring faulty
With a serviceable relay ed and the
fault sll evident, the interconnecng
wiring to the remote system may be
faulty. Carry out connuity checks,
locate and recfy the defecve wiring
or replace.
4. Remote alarm system
faulty
Invesgate fault, repair or replace re-
mote system as necessary
TABLE 7.6: GAS SERVICE INDICATES NORMAL WITH
A GAS SERVICE FAILURE CONDITION
Possible cause Remarks/rectification action
1. Gas service
failure set incorrectly
Check that the gas service sensor is
operang at the correct pressure
2. Faulty wiring Carry out resistance checks between
input and alarm panel (Table 9). Repair/
replace defecve wiring as necessary
3. Power supply PCB
faulty
Replace power supply PCB
4. Light display PCB
faulty
If all other checks have failed to recfy
the fault, replace the light display PCB
TABLE 7.7: SYSTEM ALARM AND AUDIBLE FAIL TO
OPERATE ON POWER FAILURE
Possible cause
Remarks/rectification action
1. Back up baery
faulty
Replace back up baery.
2. Main ribbon
connector faulty
Check main ribbon connector on power
supply PCB. Replace power supply PCB
as necessary.
3. Main ribbon
damaged
Check main ribbon cable. If
damaged replace light display PCB.
4. Power supply PCB
faulty
Replace power supply PCB.
5. Light display PCB
faulty
If all other checks have failed to recfy
the fault, replace the light display PCB.
TABLE 7.8: A GAS SERVICE DISPLAY FLASHING (INCLUDING NORMAL) WITH SYSTEM ALARM
Notes…