HPH Series J-Hook Installation Instructions
1
Mounting to a vertical surface: HPH16, HPH32, HPH48 and HPH64
1” Standard HPH J-Hook, size 16
2” Standard HPH J-Hook, size 32
3” Standard HPH J-Hook, size 48
4” Standard HPH J-Hook, size 64
Use a nail*, bolt* or screw* with a minimum head diameter of 0.329” (Fig.1-A) and an
appropriate length for the substrate (Fig.1-B) to fasten the HPH J-Hook (Fig.2) to the vertical
surface (Fig.3). Insert the cables and close the latch as shown in Fig.3. The latch must be in the
closed position as shown in Fig.4 to secure the cables and complete the installation.
Fig.1 Fig.2
Fig.3 Fig.4
No.
Size
No.
2 & 4
LBS. | N
2
Mounting to a rod or ceiling wire with a Multi-Function Clip-Batwing: HPH16W,
HPH32W, HPH48W and HPH64W
HPHXXW J-Hooks (Fig.1) are pre-assembled to Multi-Function Clip-Batwings at the factory using
a fastener such as a rivet or a zinc plated ¼-20 x 3/8” pan head Phillips machine bolt and a
grade A ¼-20 hex Nylon locknut (Fig.2). A plain HPH J-Hook may be assembled to a UL listed
batwing clip in the field with the use of a similar fastener. Depress the batwing between your
fingers (Fig. 3). Attach the HPHXXW to 12 gauge ceiling wire or 1/4" threaded rod (Fig.4 and
Fig.6).
position as shown in Fig.8 to secure the cables and complete the installation.
Insert the cables and close the latch (Fig.5 and Fig.7). The latch must be in the closed
Fig. 1 Fig. 2 Fig. 3
Fig. 4 Fig. 5
3
1” Batwing HPH J-Hook, size 16
2” Batwing HPH J-Hook, size 32
3” Batwing HPH J-Hook, size 48
4” Batwing HPH J-Hook, size 64
Fig. 6 Fig. 7
Fig. 8
Size
No.
1
&
8
LBS. | N
4
Mounting to a rod or a horizontal surface with an Angle Clip 90°: HPH16AC, HPH16AC6
HPH32AC, HPH32AC6, HPH48AC, HPH48AC6, HPH64AC & HPH64AC6
HPHXXAC and HPHXXAC6 J-Hooks (Fig.1 and Fig.2) are pre-assembled to Angle Clips 90° at the
factory using a fastener such as a rivet or a zinc plated ¼-20 x 3/8” pan head Phillips machine
bolt and a grade A ¼-20 hex Nylon locknut (Fig.3). A plain HPH J-Hook may be assembled to a
Platinum Tools Angle Clip 90° in the field using a similar fastener. Fasten the HPHXXAC or
HPHXXAC6 to 1/4" or 3/8” threaded rod using two standard hex nuts (Fig.4). Thread a single nut
up to the desired location of the threaded rod. Guide the HPHXXAC or HPHXXAC6 onto the
threaded rod. Thread a second nut onto the threaded rod and tighten to the first nut, thereby
sandwiching the Angle Clip 90° between the two nuts (Fig.5). An HPHXXAC or an HPHXXAC6
may be fastened directly to the underside of a horizontal surface using an appropriate fastener*
(Fig.6). Use a fastener with an appropriate head diameter (Fig.7-A) and an appropriate length
for the substrate (Fig.7-B). Place the cables in the hook and close the latch as shown in Fig.5
and Fig.6. The latch must be in the closed position as shown in Fig.8 and Fig.9 to secure the
cables and complete the installation.
Fig.1 Fig.2 Fig. 3
Fig. 4 Fig. 5
5