Reproduction of this manual, or any portion of this manual, is prohibited without the express permission of
Plasmon Laser Magnetic Storage (LMS). Plasmon LMS reserves the right to make changes in this
document and the product referred to herein without prior notice.
Always observe the following when installing, operating or maintaining
this product:
• This unit must be connected to a power distribution system that has a
direct connection to earth ground (Terminated Terra [TT] network/
ground connected). This unit is not suitable for use on a floating
ground (Interrupted Terra [IT]) network.
• The AC input power cord must be shielded and must have a minimum
current rating of 10 A with a nominal cross-section area of 0.75 sq mm
(reference: AWG #18) per conductor, 2 wires plus ground and product
safety approvals as required for use in the country in which the unit is
installed.
• When the unit is mounted in an equipment rack or cabinet, be certain
that the internal temperature within the rack or cabinet does not
exceed the limits defined in the Product Specification or this
document.
• To ensure the integrity of safety features of this unit, maintenance must
be performed only by qualified service personnel using designated
Plasmon LMS parts.
• In case of fire or other emergency, isolate the units from the main
power by disconnecting the power plugs from their site power
receptacles. In situations where disconnecting the plugs is not
possible or practical, use the system main power disconnect to isolate
the units from the main power.
• To prevent fire or shock hazard, do not expose this unit to rain or
moisture. Refer servicing to qualified technicians.
(German Translation)
Bei der Installation, Bedienung und Wartung dieses Produkts, bitte
immer die folgenden Vorsichtsmaßnahmen treffen:
• Dieses Gerät muß an ein Stromversorgungssystem angeschlossen
werden, das direkt mit einem Erdungsanschluß verbunden ist
(Terminated- Terra-Netz [TT]/mit Erdanschluß). Dieses Gerät kann
nicht an ein ungeerdetes Netz (Interrupted Terra [IT]) angeschlossen
werden.
• Die Verbindungsschnur des Wechselstromeingangs muß entstört sein
und ihr Minimalstrom unter folgenden Bedingungen bei 10 A liegen:
Der Nennquerschnitt beträgt 0,75 mm je Leiter (Referenz: American
Wire Gauge Nr. 18), es bestehen 2 Drähte plus ein Erdanschluß und
das Produkt entspricht den im Land, in dem es aufgestellt wird,
geltenden Sicherheitsvorschriften.
• Wird das Gerät in ein Gerätegestell oder einen Geräteschrank
eingebaut, ist darauf zu achten, daß die interne Temperatur im Gestell
oder Schrank nicht über die in den Produktspezifikationen oder
diesem Dokument angegebenen Grenzwerte hinausgeht.
WARNUNG
• Um ein ordnungsgemäßes Funktionieren der Sicherheitsmerkmale
dieses Gerätes zu gewährleisten, dürfen Wartungsarbeiten nur von
qualifiziertem Fachpersonal ausgeführt werden. Es sind darüber
hinaus nur Ersatzteile zu verwenden, die von der Firma Plasmon LMS
angegeben werden.
• Im Falle eines Feuers oder in einem anderen Notfall sind die Geräte
vom Hauptnetz zu trennen, indem die Netzstecker aus den
Steckdosen am Einbauort gezogen werden. Ist ein Herausziehen der
Stecker nicht möglich oder zu umständlich, trennen Sie die Geräte mit
Hilfe des System- Hauptnetzabschalters vom Hauptnetz.
• Um Feuer- oder Stromschlaggefahr zu vermeiden, ist dieses Gerät
niemals Regen oder Feuchtigkeit auszusetzen. Wartungsarbeiten
sind qualifiziertem technischen Personal zu überlassen.
RADIO/TV INTERFERENCE (USA)
The information in this section applies only to units in use within the United States:
This equipment generates and uses radio frequency energy and, if not installed and used properly, that is,
in strict accordance with the manufacturer's instruction, may cause interference to radio and television
reception. It has been type tested and found to comply with the limits for a Class A computing device in
accordance with the specifications of Part 15 of FCC Rules, which are designed to provide reasonable
protection against such interference in a residential installation. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
• reorient the receiving antenna
• relocate the equipment away from the receiver
• plug the equipment into a different outlet so that equipment and receiver are on different branch
circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional
suggestions. A pamphlet by the FCC ‘How to Identify and Resolve Radio-TV Interference Problems' is
available from the US Government Printing Office, Washington, D.C., 20402, Stock No. 044-000-00345-4.
CDRH COMPLIANCE
LD 8100 contains a Class 1 Laser Product. This product complies with 21CFR Chapter 1, Subchapter J,
applicable at date of manufacture.
CANADIAN EMI COMPLIANCE
Canadian Department of Communications standards require that the following statement appear in
operating manuals for any digital apparatus imported into Canada:
This digital apparatus does not exceed the Class A limits for radio noise for digital apparatus set out in the
Radio Interference Regulations of the Canadian Department of Communications.
FRENCH TRANSLATION
Cet équipement digital ne dépasse pas les limites de la Classe A pour les interférences radioélectriques
des systémes digitaux fixées par les Réglements concernant les Interférences Radioélectriques établis par
le Ministére des Communications du Canada.
All Plasmon LMS products comply with the requirements of this standard.
Agency Compliance and Approval
For details on Agency Compliance and Approval refer to the LD 8100/LF 8120/LF 8600LF 8602 Product
Specification Manual (P/N 97663035).
TABLE OF CONTENTS
SCOPE 9
RELATED PUBLICATIONS 9
NOTICES 9
GENERAL DESCRIPTION 11
DRIVE CHARACTERISTICS 13
RACK MOUNT AND DESKTOP CONFIGURATIONS 13
TOWER CONFIGURATION 15
FILENET LIBRARY CONFIGURATION 17
PLASMON 1800 LIBRARY CONFIGURATION 19
DIMENSIONS AND WEIGHTS 21
TEMPERATURE, HUMIDITY AND ALTITUDE 22
MEDIA ENVIRONMENTAL CHARACTERISTICS 23
SHOCK AND VIBRATION 23
AC POWER REQUIREMENTS 24
AC GROUND 24
AC POWER CORD 24
POWER SUPPLY OUT-OF-RANGE PROTECTION FEATURES 24
HEAT DISSIPATION 24
TILT RANGE 24
PARTICULATE LIMITS 25
WARNING LABELS 25
UNPACKING AND REPACKING INSTRUCTIONS 27
UNPACKING THE LD 8100 27
DESKTOP, RACK MOUNT AND LIBRARY CONFIGURATIONS 27
TOWER CONFIGURATION 29
INSPECTING THE LD 8100 31
REPACKING THE LD 8100 31
DESKTOP, RACK MOUNT AND LIBRARY CONFIGURATIONS 32
TOWER CONFIGURATION 34
INSTALLATION AND DE-INSTALLATION 35
INSTALLATION REQUIREMENTS 35
QUICK RELEASE RACK MOUNT KIT INSTALLATION 36
QUICK RELEASE RACK MOUNT DE-INSTALLATION 47
SCSI BUS CONSIDERATIONS 48
CONNECTING POWER AND SCSI CABLES 50
CONNECTING THE POWER CORD 50
CONNECTING MULTIPLE DEVICES 50
CONNECTING A SINGLE DEVICE 51
CONNECTOR VERIFICATION 52
OPERATING INSTRUCTIONS 53
CONTROLS AND INDICATORS 53
POWER-ON PROCEDURE 54
MODES OF OPERATION 55
OPERATING MODE 55
CONFIGURATION MODE 58
VIEWING THE CONFIGURATION ("VIEW CONFIG") 61
SETTING THE CONFIGURATION ("SET CONFIG") 63
SET DEFAULTS 66
SETTING THE SCSI ID 66
SETTING THE BUS PARITY CHECKING 67
SETTING THE LANGUAGE 67
SETTING THE WRITE PROTECT OPTION 68
SETTING THE MEDIA AUTOSPIN OPTION 68
SETTING THE LOAD SWITCH OPTION 69
SETTING THE READ AHEAD OPTION 69
SETTING THE CDE CURS OPTION 70
SETTING THE BUSY OPTION 70
SETTING THE MODSEL RA OPTION 71
SETTING THE MM SPINUP OPTION 71
SELECT TARGET NEGOTIATION 72
VIEWING DIAGNOSTIC RESULTS OR PERFORMING
DIAGNOSTICOPERATIONS ("DIAGNOSTICS") 73
SET THE INTERNAL DRIVE SERIAL NUMBER ("SET SERIAL #") 78
TEST MODE 80
MEDIA CARTRIDGE HANDLING 81
SETTING THE WRITE PROTECTION SWITCH 83
AFFIXING LABELS TO THE MEDIA CARTRIDGE 84
MANUAL RELEASE MECHANISM 85
OPERATOR MAINTENANCE 87
INSPECTING AND CLEANING FAN AND BLOWER FILTERS 87
REPLACING FUSES 88
MEDIA CLEANING 90
MEDIA CLEANING USING CLEANING KIT P/N 97662550 90
APPENDIX A 91
GERMAN TRANSLATIONS/ÜBERSETZUNGEN INS DEUTSCHE 91
SCOPE
This User Manual describes unpacking, installing, operating, and maintaining the LaserDrive LD 8100
High-Performance Optical Disk Drive.
Three levels of notices are used throughout this document.
WARNING
A WARNING is used to alert the reader of situations or conditions that
could potentially result in personal injury, fire hazard or equipment
damage.
CAUTION
A CAUTION is used to warn of undesirable procedures or of
situations in which equipment damage could potentially result.
NOTE
A NOTE is used to emphasize an area of text or to provide additional
information.
97662915 B
Page 9
WARRANTY STATEMENT
The LD 8100 is warranted as stated in the purchase agreement between Plasmon and it’s customer,
or the Plasmon sales order acknowledgment, whichever is applicable.
The Plasmon LMS quality system is in compliance and registered to ISO 9001. The LD 8100 is
manufactured from new parts, or remanufactured parts.
LD 8100 warranty does not cover defects or damage caused by the use of unauthorized parts or
repairs or improper use or maintenance. Repairs or replacements not covered by the warranty will
be invoiced at Plasmon’ then current prices.
The warranty is void when installation, service or repairs are performed by un-certified personnel;
when the product is affected by unauthorized alterations, modifications or other tampering or
misuse; when the product is incorporated into a system which causes or involves any changes in
the physical, mechanical or electrical arrangement of the product; or when the product is not used
in accordance with its applicable specifications.
The term, authorized personnel, is defined as those persons who have been trained by Plasmon
LMS Technical Services.
PLASMON LMS - LD 8100 USER MANUAL
Page 10
GENERAL DESCRIPTION
The Plasmon Infinity LaserDrive LD 8100 is a write once read many (WORM), high-capacity optical disk
drive which uses a removable 300-mm (12-in.), LM 8000 optical media cartridge with storage capacity of
30 GBytes. The LD 8100 can also read LM 6000 and LM 4000 media. Contact Plasmon LMS for
availability and ordering information for the LM 4000 media option.
The LD 8100 is available in a Rack Mount, Desktop, Tower, FileNet® Library and Plasmon Library
configurations, offering support for varied operating orientations and installation environments (see figure
below).
RACK MOUNT
CONFIGURATION
PLASMON LIBRARY
CONFIGURATION
DESKTOP
CONFIGURATION
TOWER
CONFIGURATION
FILENET LIBRARY
CONFIGURATION
Figure 1. LD 8100 Configurations
97662915 B
Page 11
The LD 8100 supports a maximum sustained read and write transfer rate of 6.0 MBytes/sec without data
verification. The drive will also support a 2.9 MBytes/sec write transfer rate with error correction and defect
management to maintain data integrity and manage media flaws.
A Drive Operator Console (DOC) located on the front panel of the drive provides user control of drive
operation, configuration and test as explained in the Operating Instruction section of this manual.
Operating messages are presented on the alphanumeric display in English, French or German. The
language used is selectable.
The Auxiliary Diagnostic Port (ADP) can be used to download updates to the drive firmware in the field.
Refer to the LD 8100/ LF 8120/ LF 8600/ LF 8602 Product Specification (P/N 97663035) for more
information. The ADP is located on the front panel of the Rack Mount, the Desk Top and the Tower
configurations. The ADP may be located on the rear panel of the Plasmon Library and the Filenet
configurations. The ADP may also be used as a standard serial port for setting the SCSI ID.
The LD 8100 drive implements the Small Computer System Interface (SCSI) via standard SCSI-2 micro
connectors (68 pin) located on the rear panel. Single-ended and differential, High Voltage interface options
are available, and the interface can be changed in the field. Both the single-ended and differential
controllers support asynchronous or synchronous data transfer operations.
Preventive maintenance for the LD 8100 is minimal. Corrective maintenance is simplified by internal
diagnostic firmware which detects, isolates and reports malfunctions to the operator and identifies the Field
Replaceable Unit (FRU).
LM 8000 media is interchangeable between the LD 8100, LF 8120, LF 8600, and the LF 8602. The
LD 8100 can also read LM 6000 and LM 4000 media. Contact Plasmon LMS for availability and ordering
information for the LM 4000 media option.The
PLASMON LMS - LD 8100 USER MANUAL
Page 12
DRIVE CHARACTERISTICS
This section describes the LD 8100 Rack Mount, Desktop, Tower, FileNet Library and Plasmon Library
configurations. All LD 8100 configurations have the same major internal subassemblies.
RACK MOUNT AND DESKTOP CONFIGURATIONS
The LD 8100 Rack Mount
configuration is designed for
horizontal operation and slide
mounting in an EIA standard
19-in. rack. The Rack Mount
configuration is installed in a
rack using the Quick Release
Rack Mount Kit (refer to the
Installation section of this
manual).
Figure 2. LD 8100 Rack Mount
Drive
The LD 8100 Desktop
configuration is designed for
horizontal operation as a standalone device on a table top. The
Desktop configuration includes an
enclosure and rubber feet.
Figure 3. LD 8100 Desktop Drive
97662915 B
Page 13
The figure below illustrates the front panel layout. The ADP connector is located beside the DOC but is
concealed by the Bezel.
BEZEL
DOC
MEDIA CARTRIDGE LOADING DOORS
ADP
Figure 4. LD 8100 Rack Mount and Desktop Front Panel Layout (Rack Mount Version Shown)
The LD 8100 Rack Mount and Desktop rear panel layout includes a DOC/ADP Blank Panel, MCLI Blank
Panel, AC Power Switch, Receptacle, SCSI-2 I/O Panel Assembly and a ground connector. The figure
below illustrates the rear panel layout. A Fan Grill and filter element are installed over the fan vent to filter
out contaminants from cooling air entering through the rear panel.
AC POWER
SWITCH
DOC/ADP
BLANK PANEL
AC POWER
RECEPTACLE
GROUND
CONNECTOR
PLASMON LMS - LD 8100 USER MANUAL
Page 14
MCLI
BLANK PANEL
SCSI-2 I/O
CONNECTORS
Figure 5. LD 8100 Rack Mount Rear Panel
TOWER CONFIGURATION
The Tower configuration (see figure below) is designed for vertical operation as a stand-alone device on
an open floor or beside a desk. The Tower configuration includes an enclosure for both the LD 8100 and
the pedestal. The pedestal is supported by four casters which can be locked to prevent unintentional
movement.
18.9 cm
(7.4 in)
67.3 cm
(26.5 in)
48.6cm
(19.1 in)
30.5 cm
(12.0 in)
66.7cm
(26.2 in)
Figure 6. LD 8100 Tower Configuration
97662915 B
Page 15
DOC
ADP
MEDIA CARTRIDGE
LOADING DOOR
The figure to the right illustrates the rear
panel of the LD 8100 Tower configuration
and identifies the location of the AC
power switch, Receptacle, ground
connector, SCSI-2 I/O Panel Assembly,
DOC/ADP Blank Panel and MCLI Blank
Panel. A Fan Grill and filter element are
installed over the fan vent to filter
contaminants from cooling air entering
through the rear panel.
AC POWER
RECEPTACLE
AC POWER
SWITCH
The illustration to the left shows the front
panel of the LD 8100 Tower configuration
and identifies the location of the DOC and
ADP connector. The ADP connector is
located below the DOC but is concealed by
the bezel.
Figure 7. LD 8100 Tower Front Panel Layout
SCSI-2 I/O
PANEL
ASSEMBLY
MCLI BLANK
PANEL
FAN/GRILL AND
FILTER ASSEMBY
Figure 8. Rear View of LD 8100 Tower
PLASMON LMS - LD 8100 USER MANUAL
Page 16
DOC BLANK
PANEL
GROUND
CONNECTOR
FILENET LIBRARY CONFIGURATION
The FileNet Library configuration (see figure below), does not have a Bezel and is designed for vertical or
horizontal mounting and for operation in a FileNet Library. The FileNet Library configuration has the same
major assemblies as the other LD 8100 configurations but is configured for use in a FileNet Library by
adding the MCLI connector and Registration Panel.
Figure 9. FileNet Library Configuration
97662915 B
Page 17
BLANK
PANEL
MEDIA CARTRIDGE
LOADING SLOT
REGISTRATION
PANEL
The figure on the left illustrates the
front panel of the FileNet Library
configuration and identifies the
location of the DOC/ADP Blank
Panel. The DOC and ADP connector
are located on the rear panel, so the
DOC/ADP Blank Panel is used to
cover the DOC and ADP mounting
holes. A special Registration Panel is
installed on the FileNet Library
configuration in place of the Bezel.
Figure 10. LD 8100 FileNet Library
Front Panel
The figure on the right illustrates
the rear panel of the LD 8100
FileNet Library configuration and
identifies the location of the AC
Power Switch, Receptacle, ground
connector, SCSI-2 I/O Panel
Assembly, DOC, ADP connector
and the MCLI connector. A Fan
Grill and filter element are installed
over the fan vent to filter
contaminants from cooling air
entering through the rear panel.
Figure 11. LD 8100 FileNet Library
Rear Panel
AC POWER
RECEPTACLE
AC POWER
SWITCH
DOC
SCSI-2 1/O
CONNECTORS
MCLI I/O
CONNECTOR
FAN GRILL AND
FILTER ELEMENT
GROUND
CONNECTOR
ADP
CONNECTOR
PLASMON LMS - LD 8100 USER MANUAL
Page 18
PLASMON 1800 LIBRARY CONFIGURATION
The Plasmon Library configuration (see figure below), which does not have a Bezel or Registration Panel,
is designed for horizontal mounting and operation in a Plasmon 1800 Series Library. The Plasmon Library
configuration has the same major assemblies as the other LD 8100 configurations but is adapted for use in
a Plasmon 1800 Library by adding an MCLI connector.
Figure 12. Plasmon 1800 Series Library Drive
97662915 B
Page 19
The figure below illustrates the front panel of the Plasmon Library configuration and identifies the location
of the DOC/ADP Blank Panel. The DOC and ADP connector are located on the rear panel. The DOC/ADP
Blank Panel is used to cover the DOC and ADP mounting holes.
DOC/ADP
BLANK PANEL
MEDIA CARTRIDGE
LOADING PORT
Figure 13. LD 8100 Plasmon Library Front Panel
The figure below illustrates the rear panel of the LD 8100 Plasmon Library configuration and identifies the
location of the AC Power Switch, AC Receptacle, ground connector, SCSI-2 I/O Panel Assembly, DOC,
ADP connector and the MCLI connector. A Fan Grill and filter element are installed over the fan vent to
filter contaminants from cooling air entering through the rear panel.
AC POWER
SWITCH
DOC
FAN GRILL AND
FILTER ELEMENT
AC POWER
RECEPTACLE
SCSI-2 1/O
CONNECTORS
ADP
CONNECTOR
GROUND
CONNECTOR
Figure 14. LD 8100 Plasmon Library Rear Panel
PLASMON LMS - LD 8100 USER MANUAL
Page 20
MCLI
CONNECTOR
DIMENSIONS AND WEIGHTS
The following table lists the dimensions of the LD 8100 Rack Mount, Desktop and Tower, FileNet and
Plasmon Library configurations. These dimensions do not include extending media cartridges or interface
cabling. Refer to the LX 8000 Series Product Specification (P/N 97663035) for the dimensions of the
FileNet and Plasmon Library configurations with a media cartridge and interface cabling.
Table 1. Dimensions of the LD 8100 Configurations
DIMENSIONRACKMOUNTDESKTOPTOWERFILENETPLASMON
Chassis Length:
With Mounting Kit:
Chassis Width:
With Mounting Kit:
Chassis Height:
With Mounting Kit:
60.9 cm
(24.0 in)
65.3 cm
(25.7 in)
43.0 cm
(16.9 in)
47.5 cm
(18.7 in)
16.9 cm
(6.7 in)
17.8 cm
(7.0 in)
64.3 cm
(25.3 in)
67.3 cm
1
(26.5 in)
2
64.3 cm
(25.3 in)
67.3 cm
(26.5 in)
64.3 cm
(25.3 in)
64.3 cm
(25.3 in)
67.3 cm
2
(26.5 in)
3
66.5 cm
(26.2 in)
43.0 cm
(16.9 in)
48.6 cm
1
(19.1 in)
2
16.9 cm
(6.7 in)
18.8 cm
(7.4 in)
4
16.9 cm
(6.7 in)
2
43.0 cm
(16.9 in)
30.5 cm
(12.0 in)
16.9 cm
(6.7 in)
18.8 cm
1
(7.4 in)
5
48.6 cm
(19.1 in)
63.2 cm
(24.8 in)
4
43.0 cm
(16.9 in)
16.9 cm
(6.7 in)
43.8 cm
6
(17.2 in)
3
60.9 cm
Mounting Depth
1 Includes the Bezel.
2 Includes the Bezel and chassis cover.
3 Includes the Registration Panel.
4 The pedestal and pedestal skin.
5 Includes the rubber feet.
6 Includes the chassis skin, pedestal and casters.
7 Depth to which the drive extends into the mounting rack.
(24.0 in
)7
The following weight specifications do not include interface cabling or optical media:
Rack Mount30.5 kg (67 lbs)
Desktop35.9 kg (79 lbs) Includes Enclosure
Tower41.8 kg (92 lbs) Includes Enclosure and Pedestal
FileNet Library31.4 kg (69 lbs) Includes Registration Panel
Plasmon Library30.5 kg (67 lbs)
97662915 B
Page 21
TEMPERATURE, HUMIDITY AND ALTITUDE
The following table lists the LD 8100 operating, nonoperating, storage and transit limits for temperature,
humidity, and altitude.
Table 2. Temperature, Humidity and Altitude Limits
Air PressureN/AN/AN/A
Solar RadiationN/ACase to be kept closedNot to be stored in direct
5% - 80%5% - 90%5% - 80%
(18.0°F/hr max.)
-20°C to +55°C
-4.0°F to 131.o°F
31°C/hr max.
(55.8°F/hr max.)
10°C to 30°C
50°F to 86.0°F
5°C/hr max.
(9.0°F/hr max.)
sunlight
SHOCK AND VIBRATION
The following table lists the conditions and limits for shock and vibration.
Table 4. Shock and Vibration Criteria and Limits
CONDITIONOPERATING
Swept Vibration
(bidirectional)
1 Octave/Min
5 to 250 Hz 0.1 g
peak, 250 to 500 Hz
0.20 g peak
NONOPERATING
5 to 44 Hz, 0.03 in
double amplitude,
44 to 500 Hz
3.0 g peak
1
STORAGE/TRANSIT
5 to 44 Hz, 0.03 in
double amplitude,
44 to 500 Hz
3.0 g peak
2
3
Shock
(host retries may be
required and drive
performance may
10 - msec half sine
pulse of 5.0 g peak
with pulses applied
every 3 sec
degrade during test)
Unpacked (3 axis)5 - msec half sine
Packed on Pallet46 - cm (18 - in) drop
1 With media removed
2 In Plasmon LMS-approved packaging
3 Shock repetition rate should be limited to allow mechanical system transients to subside between pulses.
pulse of 20 g peak
test flat
97662915 B
Page 23
AC POWER REQUIREMENTS
The LD 8100 has an AC power switch with an integral grounded power connector and fuses located on the
rear panel. Two spare fuses are included within the power connector. Refer to Replacing Fuses section for
the fuse replacement procedure.
The required fuses are 5A slow blow, 5 x 20 mm, hot and neutral.
The power supply will operate with the line voltages listed in the following table. The power supply is auto
ranging and does not require mechanical switching for input voltage or frequency selection.
Table 5. Typical RMS Line Current and Power Requirements
AC LINE
VOLTAGE
95.0V TO 128V1.3A / 101W10A
173.0 TO 269V0.7 / 110W5A1.0A / 160W15
1
This current measurement determines the stated power and maximum heat dissipation of the Drive (546 BTU/hr) based on RMS
current over the 10S cycle derated by the Power Factor. It also determines the 2.0 A UL plate rating.
READY
SURGE PEAK
<1s
(SPIN-UP)
READY + 1 SPIN-UP/DN
CYCLE EVERY 10 s
2.0A / 160W
(1)
MIN
SERVICE
RATING
15A
AC GROUND
The LD 8100 AC power cord connects the LaserDrive to safety ground through the site AC power system.
The site AC power system must tie this safety ground connection to earth ground. All site AC power
connections must be maintained on the same safety ground.The line ground connector located on the rear
panel can also be used to tie chassis ground to earth ground. This ground connector is a 6-mm (0.24-in)
M4 stud with a nut and lock washer.
AC POWER CORD
The type of AC power cord that is supplied with the LD 8100 is based on the configuration ordered and the
destination country.
POWER SUPPLY OUT-OF-RANGE PROTECTION FEATURES
The LD 8100 power supply provides over and under voltage protection, over current protection, and over
temperature protection. Should an out-of-range condition be detected, the LD 8100 will shut down the DC
outputs of the power supply. Once the situation has been corrected, power can be restored by turning the
AC power switch to the off position and then to the on position again.
HEAT DISSIPATION
The drive will typically present a heat load of 95 calories/hr (376 BTU/hr) during a read/write operation.
When media cartridges are inserted, loaded, spun up, spun down, unloaded and removed at the rate of
one per 10 seconds, the drive will typically present a heat load of 137 calories/hr (546 BTU/hr).
TILT RANGE
The LD 8100 Rack Mount, Desktop and Plasmon Library configurations will operate over a tilt range of 10°
from the horizontal position. The Tower and FileNet Library configuration will operate over a tilt range of
10° from the vertical position. The LD 8100 is not designed for dynamic tilt environments.
PLASMON LMS - LD 8100 USER MANUAL
Page 24
PARTICULATE LIMITS
The LD 8100 is designed for use in an office or computer room. The environment must have a low dust
level. The LD 8100 filters incoming air for cooling to reduce the quantity of particles entering the drive;
however, the filter is not effective against small particles (including tobacco smoke) which will become
deposited on optical components and media, causing degradation in drive performance. Refer to the
Operator Maintenance section for media cleaning and air filter cleaning instructions.
WARNING LABELS
The LD 8100 is classified as a laser product. As such, it is subject to United States Federal requirements
covering laser products. The warning labels shown in the figure below are necessary to ensure compliance
with Federal regulations and must not be removed from the LD 8100.
LASER CLASS LABEL
FCC, RFI, CLASS A
LABEL
LASER DANGER
LABEL
CANADIAN CLASS A
COMPLIANCE LABEL
Figure 15. Locations of the LD 8100 Warning Labels
97662915 B
Page 25
PLASMON LMS - LD 8100 USER MANUAL
Page 26
UNPACKING AND REPACKING
INSTRUCTIONS
If the Laser Drive’s shipping carton shows evidence of rough handling or damage, return the unit in its
carton to your supplier and request a replacement.
UNPACKING THE LD 8100
Each LD 8100 is shipped on a pallet in a shipping carton with foam packing material which protects the unit
from shock and vibration.
After you receive your LD 8100, inspect the shipping carton for damage before unpacking the unit to
substantiate a claim with the carrier if the unit is damaged. Retain all original packing materials and
receipts for possible reshipment.
WARNING
The LD 8100 must be unpacked, repacked and transported by two
persons. Physical injury can result if one person attempts to transport
or lift the LD 8100. A wheeled cart is recommended for transporting
the LD 8100 within a building. Precautions should be taken to guard
against sudden bumps and jarring.
DESKTOP, RACK MOUNT AND LIBRARY CONFIGURATIONS
To unpack the LD 8100 Desktop, Rack Mount and Library configurations, refer to the next figure and
perform the following procedure:
1) Cut the bands that secure the outer carton to the lower carton.
2) Lift the outer carton away from the lower carton and pallet.
3) Remove the small options and accessories tray.
The shipping carton will also contain a Quick Release Rack Mount Kit if it is ordered with the LD 8100 Rack
Mount configuration. If you are unpacking an LD 8100 Rack Mount configuration, check for the Quick
Release Rack Mount Kit carton and remove it at this time.
4) Lift both foam cushions away from the LD 8100.
5) Remove the ESD packing material.
6) Carefully lift and remove the LD 8100 from the shipping carton and place it on a flat
surface.
97662915 B
Page 27
OPTION/
ACCESORY
TRAY
OUTER
CARTON
FOAM
CUSHION
MOUNTING/SLIDE
(RACK MOUNT
CONFIGURATION)
FRONT FOAM
CUSHION
LOWER
CARTON
KIT
ESD PACKING
MATERIAL
LD 8100
FOAM PADS
PALLET
Figure 16. Unpacking the LD 8100 Desktop, Rack Mount and Library Configurations
PLASMON LMS - LD 8100 USER MANUAL
Page 28
TOWER CONFIGURATION
To unpack the LD 8100 Tower configuration, refer to the next figure and perform the following procedure:
1) Cut the bands that secure the carton to the lower portion pallet.
2) Carefully lift the carton up and away from the pallet while supporting the wooden hinged
ramp.
3) Lower the ramp to the floor.
4) Remove the options and accessories tray.
5) Lift both foam cushions away from the LD 8100.
6) Remove the ESD packing material.
WARNING
The LD 8100 must be unpacked, repacked and transported by two
persons. Physical injury can result if one person attempts to transport
or lift the LD 8100. A wheeled cart is recommended for transporting
the LD 8100 within a building. Precautions should be taken to guard
against sudden bumps and jarring.
Ensure that all four casters are locked. Lift the front end of the LD 8100 high enough to remove the bottom
cushion.
7) Remove the foam bumper.
8) Remove the bottom cushion.
9) Lower the LD 8100 onto the pallet.
10) Unlock the casters and roll the LD 8100 down the ramp to its installation location.
11) Lock the casters once you have the LD 8100 situated at its installation location.
97662915 B
Page 29
CARTON
OPTIONS/
ACCESSORIES
TRAY
FRONT FOAM
CUSHION
REAR FOAM
CUSHION
ESD PACKING
MATERIAL
FOAM
BUMPER
HINGED
WOODEN
RAMP
PALLET
Figure 17. Unpacking and Repacking the LD 8100 Tower Configuration
PLASMON LMS - LD 8100 USER MANUAL
Page 30
LD 8100
BOTTOM
CUSHION
Loading...
+ 75 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.