Plasmon LD 8100 User Manual

THE PLASMON 8000 SERIES
OPTICAL DISK DRIVE
LD 8100
USER MANUAL
P/N 9662915 B
© 2000 Plasmon Laser Magnetic Storage
WARNING
Always observe the following when installing, operating or maintaining this product:
This unit must be connected to a power distribution system that has a
direct connection to earth ground (Terminated Terra [TT] network/ ground connected). This unit is not suitable for use on a floating ground (Interrupted Terra [IT]) network.
The AC input power cord must be shielded and must have a minimum
current rating of 10 A with a nominal cross-section area of 0.75 sq mm (reference: AWG #18) per conductor, 2 wires plus ground and product safety approvals as required for use in the country in which the unit is installed.
When the unit is mounted in an equipment rack or cabinet, be certain
that the internal temperature within the rack or cabinet does not exceed the limits defined in the Product Specification or this document.
To ensure the integrity of safety features of this unit, maintenance must
be performed only by qualified service personnel using designated Plasmon LMS parts.
In case of fire or other emergency, isolate the units from the main
power by disconnecting the power plugs from their site power receptacles. In situations where disconnecting the plugs is not possible or practical, use the system main power disconnect to isolate the units from the main power.
To prevent fire or shock hazard, do not expose this unit to rain or
moisture. Refer servicing to qualified technicians.
(German Translation)
Bei der Installation, Bedienung und Wartung dieses Produkts, bitte immer die folgenden Vorsichtsmaßnahmen treffen:
Dieses Gerät muß an ein Stromversorgungssystem angeschlossen
werden, das direkt mit einem Erdungsanschluß verbunden ist (Terminated- Terra-Netz [TT]/mit Erdanschluß). Dieses Gerät kann nicht an ein ungeerdetes Netz (Interrupted Terra [IT]) angeschlossen werden.
Die Verbindungsschnur des Wechselstromeingangs muß entstört sein
und ihr Minimalstrom unter folgenden Bedingungen bei 10 A liegen: Der Nennquerschnitt beträgt 0,75 mm je Leiter (Referenz: American Wire Gauge Nr. 18), es bestehen 2 Drähte plus ein Erdanschluß und das Produkt entspricht den im Land, in dem es aufgestellt wird, geltenden Sicherheitsvorschriften.
Wird das Gerät in ein Gerätegestell oder einen Geräteschrank
eingebaut, ist darauf zu achten, daß die interne Temperatur im Gestell oder Schrank nicht über die in den Produktspezifikationen oder diesem Dokument angegebenen Grenzwerte hinausgeht.
WARNUNG
Um ein ordnungsgemäßes Funktionieren der Sicherheitsmerkmale
dieses Gerätes zu gewährleisten, dürfen Wartungsarbeiten nur von qualifiziertem Fachpersonal ausgeführt werden. Es sind darüber hinaus nur Ersatzteile zu verwenden, die von der Firma Plasmon LMS angegeben werden.
Im Falle eines Feuers oder in einem anderen Notfall sind die Geräte
vom Hauptnetz zu trennen, indem die Netzstecker aus den Steckdosen am Einbauort gezogen werden. Ist ein Herausziehen der Stecker nicht möglich oder zu umständlich, trennen Sie die Geräte mit Hilfe des System- Hauptnetzabschalters vom Hauptnetz.
Um Feuer- oder Stromschlaggefahr zu vermeiden, ist dieses Gerät
niemals Regen oder Feuchtigkeit auszusetzen. Wartungsarbeiten sind qualifiziertem technischen Personal zu überlassen.
RADIO/TV INTERFERENCE (USA)
The information in this section applies only to units in use within the United States: This equipment generates and uses radio frequency energy and, if not installed and used properly, that is,
in strict accordance with the manufacturer's instruction, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class A computing device in accordance with the specifications of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
reorient the receiving antenna
relocate the equipment away from the receiver
plug the equipment into a different outlet so that equipment and receiver are on different branch
circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. A pamphlet by the FCC ‘How to Identify and Resolve Radio-TV Interference Problems' is available from the US Government Printing Office, Washington, D.C., 20402, Stock No. 044-000-00345-4.
CDRH COMPLIANCE
LD 8100 contains a Class 1 Laser Product. This product complies with 21CFR Chapter 1, Subchapter J, applicable at date of manufacture.
CANADIAN EMI COMPLIANCE
Canadian Department of Communications standards require that the following statement appear in operating manuals for any digital apparatus imported into Canada:
This digital apparatus does not exceed the Class A limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
FRENCH TRANSLATION
Cet équipement digital ne dépasse pas les limites de la Classe A pour les interférences radioélectriques des systémes digitaux fixées par les Réglements concernant les Interférences Radioélectriques établis par le Ministére des Communications du Canada.
All Plasmon LMS products comply with the requirements of this standard.
Agency Compliance and Approval
For details on Agency Compliance and Approval refer to the LD 8100/LF 8120/LF 8600LF 8602 Product Specification Manual (P/N 97663035).
TABLE OF CONTENTS
SCOPE 9
RELATED PUBLICATIONS 9 NOTICES 9
GENERAL DESCRIPTION 11 DRIVE CHARACTERISTICS 13
RACK MOUNT AND DESKTOP CONFIGURATIONS 13 TOWER CONFIGURATION 15 FILENET LIBRARY CONFIGURATION 17 PLASMON 1800 LIBRARY CONFIGURATION 19 DIMENSIONS AND WEIGHTS 21 TEMPERATURE, HUMIDITY AND ALTITUDE 22
MEDIA ENVIRONMENTAL CHARACTERISTICS 23 SHOCK AND VIBRATION 23 AC POWER REQUIREMENTS 24 AC GROUND 24
AC POWER CORD 24
POWER SUPPLY OUT-OF-RANGE PROTECTION FEATURES 24 HEAT DISSIPATION 24 TILT RANGE 24 PARTICULATE LIMITS 25 WARNING LABELS 25
UNPACKING AND REPACKING INSTRUCTIONS 27
UNPACKING THE LD 8100 27
DESKTOP, RACK MOUNT AND LIBRARY CONFIGURATIONS 27
TOWER CONFIGURATION 29 INSPECTING THE LD 8100 31 REPACKING THE LD 8100 31
DESKTOP, RACK MOUNT AND LIBRARY CONFIGURATIONS 32
TOWER CONFIGURATION 34
INSTALLATION AND DE-INSTALLATION 35
INSTALLATION REQUIREMENTS 35 QUICK RELEASE RACK MOUNT KIT INSTALLATION 36 QUICK RELEASE RACK MOUNT DE-INSTALLATION 47 SCSI BUS CONSIDERATIONS 48 CONNECTING POWER AND SCSI CABLES 50
CONNECTING THE POWER CORD 50
CONNECTING MULTIPLE DEVICES 50
CONNECTING A SINGLE DEVICE 51
CONNECTOR VERIFICATION 52
OPERATING INSTRUCTIONS 53
CONTROLS AND INDICATORS 53 POWER-ON PROCEDURE 54 MODES OF OPERATION 55
OPERATING MODE 55
CONFIGURATION MODE 58
VIEWING THE CONFIGURATION ("VIEW CONFIG") 61 SETTING THE CONFIGURATION ("SET CONFIG") 63 SET DEFAULTS 66 SETTING THE SCSI ID 66 SETTING THE BUS PARITY CHECKING 67 SETTING THE LANGUAGE 67 SETTING THE WRITE PROTECT OPTION 68 SETTING THE MEDIA AUTOSPIN OPTION 68 SETTING THE LOAD SWITCH OPTION 69 SETTING THE READ AHEAD OPTION 69 SETTING THE CDE CURS OPTION 70 SETTING THE BUSY OPTION 70 SETTING THE MODSEL RA OPTION 71 SETTING THE MM SPINUP OPTION 71 SELECT TARGET NEGOTIATION 72
VIEWING DIAGNOSTIC RESULTS OR PERFORMING
DIAGNOSTICOPERATIONS ("DIAGNOSTICS") 73
SET THE INTERNAL DRIVE SERIAL NUMBER ("SET SERIAL #") 78
TEST MODE 80
MEDIA CARTRIDGE HANDLING 81
SETTING THE WRITE PROTECTION SWITCH 83 AFFIXING LABELS TO THE MEDIA CARTRIDGE 84 MANUAL RELEASE MECHANISM 85
OPERATOR MAINTENANCE 87
INSPECTING AND CLEANING FAN AND BLOWER FILTERS 87 REPLACING FUSES 88 MEDIA CLEANING 90
MEDIA CLEANING USING CLEANING KIT P/N 97662550 90
APPENDIX A 91
GERMAN TRANSLATIONS/ÜBERSETZUNGEN INS DEUTSCHE 91
SCOPE
This User Manual describes unpacking, installing, operating, and maintaining the LaserDrive LD 8100 High-Performance Optical Disk Drive.
RELATED PUBLICATIONS
PUBLICATION PART NUMBER
LD 8100/LF 8120/LF 8600/LF 8602 Product Specification 97663035 LD 8100/LF 8120/LF 8600/LF 8602 SCSI Interface Specification 97662164 LD 8100 Hardware Maintenance Manual 97663081
NOTICES
Three levels of notices are used throughout this document.
WARNING
A WARNING is used to alert the reader of situations or conditions that could potentially result in personal injury, fire hazard or equipment damage.
CAUTION
A CAUTION is used to warn of undesirable procedures or of situations in which equipment damage could potentially result.
NOTE
A NOTE is used to emphasize an area of text or to provide additional information.
97662915 B
Page 9
WARRANTY STATEMENT
The LD 8100 is warranted as stated in the purchase agreement between Plasmon and it’s customer, or the Plasmon sales order acknowledgment, whichever is applicable.
The Plasmon LMS quality system is in compliance and registered to ISO 9001. The LD 8100 is manufactured from new parts, or remanufactured parts.
LD 8100 warranty does not cover defects or damage caused by the use of unauthorized parts or repairs or improper use or maintenance. Repairs or replacements not covered by the warranty will be invoiced at Plasmon’ then current prices.
The warranty is void when installation, service or repairs are performed by un-certified personnel; when the product is affected by unauthorized alterations, modifications or other tampering or misuse; when the product is incorporated into a system which causes or involves any changes in the physical, mechanical or electrical arrangement of the product; or when the product is not used in accordance with its applicable specifications.
The term, authorized personnel, is defined as those persons who have been trained by Plasmon LMS Technical Services.
PLASMON LMS - LD 8100 USER MANUAL Page 10
GENERAL DESCRIPTION
The Plasmon Infinity LaserDrive LD 8100 is a write once read many (WORM), high-capacity optical disk drive which uses a removable 300-mm (12-in.), LM 8000 optical media cartridge with storage capacity of 30 GBytes. The LD 8100 can also read LM 6000 and LM 4000 media. Contact Plasmon LMS for availability and ordering information for the LM 4000 media option.
The LD 8100 is available in a Rack Mount, Desktop, Tower, FileNet® Library and Plasmon Library configurations, offering support for varied operating orientations and installation environments (see figure below).
RACK MOUNT CONFIGURATION
PLASMON LIBRARY CONFIGURATION
DESKTOP CONFIGURATION
TOWER CONFIGURATION
FILENET LIBRARY CONFIGURATION
Figure 1. LD 8100 Configurations
97662915 B
Page 11
The LD 8100 supports a maximum sustained read and write transfer rate of 6.0 MBytes/sec without data verification. The drive will also support a 2.9 MBytes/sec write transfer rate with error correction and defect management to maintain data integrity and manage media flaws.
A Drive Operator Console (DOC) located on the front panel of the drive provides user control of drive operation, configuration and test as explained in the Operating Instruction section of this manual.
Operating messages are presented on the alphanumeric display in English, French or German. The language used is selectable.
The Auxiliary Diagnostic Port (ADP) can be used to download updates to the drive firmware in the field. Refer to the LD 8100/ LF 8120/ LF 8600/ LF 8602 Product Specification (P/N 97663035) for more information. The ADP is located on the front panel of the Rack Mount, the Desk Top and the Tower configurations. The ADP may be located on the rear panel of the Plasmon Library and the Filenet configurations. The ADP may also be used as a standard serial port for setting the SCSI ID.
The LD 8100 drive implements the Small Computer System Interface (SCSI) via standard SCSI-2 micro connectors (68 pin) located on the rear panel. Single-ended and differential, High Voltage interface options are available, and the interface can be changed in the field. Both the single-ended and differential controllers support asynchronous or synchronous data transfer operations.
Preventive maintenance for the LD 8100 is minimal. Corrective maintenance is simplified by internal diagnostic firmware which detects, isolates and reports malfunctions to the operator and identifies the Field Replaceable Unit (FRU).
LM 8000 media is interchangeable between the LD 8100, LF 8120, LF 8600, and the LF 8602. The LD 8100 can also read LM 6000 and LM 4000 media. Contact Plasmon LMS for availability and ordering information for the LM 4000 media option.The
PLASMON LMS - LD 8100 USER MANUAL Page 12
DRIVE CHARACTERISTICS
This section describes the LD 8100 Rack Mount, Desktop, Tower, FileNet Library and Plasmon Library configurations. All LD 8100 configurations have the same major internal subassemblies.
RACK MOUNT AND DESKTOP CONFIGURATIONS
The LD 8100 Rack Mount configuration is designed for horizontal operation and slide mounting in an EIA standard 19-in. rack. The Rack Mount configuration is installed in a rack using the Quick Release Rack Mount Kit (refer to the Installation section of this manual).
Figure 2. LD 8100 Rack Mount
Drive
The LD 8100 Desktop configuration is designed for horizontal operation as a stand­alone device on a table top. The Desktop configuration includes an enclosure and rubber feet.
Figure 3. LD 8100 Desktop Drive
97662915 B
Page 13
The figure below illustrates the front panel layout. The ADP connector is located beside the DOC but is concealed by the Bezel.
BEZEL
DOC
MEDIA CARTRIDGE LOADING DOORS
ADP
Figure 4. LD 8100 Rack Mount and Desktop Front Panel Layout (Rack Mount Version Shown)
The LD 8100 Rack Mount and Desktop rear panel layout includes a DOC/ADP Blank Panel, MCLI Blank Panel, AC Power Switch, Receptacle, SCSI-2 I/O Panel Assembly and a ground connector. The figure below illustrates the rear panel layout. A Fan Grill and filter element are installed over the fan vent to filter out contaminants from cooling air entering through the rear panel.
AC POWER SWITCH
DOC/ADP
BLANK PANEL
AC POWER RECEPTACLE
GROUND CONNECTOR
PLASMON LMS - LD 8100 USER MANUAL Page 14
MCLI
BLANK PANEL
SCSI-2 I/O CONNECTORS
Figure 5. LD 8100 Rack Mount Rear Panel
TOWER CONFIGURATION
The Tower configuration (see figure below) is designed for vertical operation as a stand-alone device on an open floor or beside a desk. The Tower configuration includes an enclosure for both the LD 8100 and the pedestal. The pedestal is supported by four casters which can be locked to prevent unintentional movement.
18.9 cm (7.4 in)
67.3 cm
(26.5 in)
48.6cm (19.1 in)
30.5 cm
(12.0 in)
66.7cm (26.2 in)
Figure 6. LD 8100 Tower Configuration
97662915 B
Page 15
DOC
ADP
MEDIA CARTRIDGE LOADING DOOR
The figure to the right illustrates the rear panel of the LD 8100 Tower configuration and identifies the location of the AC power switch, Receptacle, ground connector, SCSI-2 I/O Panel Assembly, DOC/ADP Blank Panel and MCLI Blank Panel. A Fan Grill and filter element are installed over the fan vent to filter contaminants from cooling air entering through the rear panel.
AC POWER RECEPTACLE
AC POWER SWITCH
The illustration to the left shows the front panel of the LD 8100 Tower configuration and identifies the location of the DOC and ADP connector. The ADP connector is located below the DOC but is concealed by the bezel.
Figure 7. LD 8100 Tower Front Panel Layout
SCSI-2 I/O PANEL ASSEMBLY
MCLI BLANK PANEL
FAN/GRILL AND FILTER ASSEMBY
Figure 8. Rear View of LD 8100 Tower
PLASMON LMS - LD 8100 USER MANUAL Page 16
DOC BLANK PANEL
GROUND CONNECTOR
FILENET LIBRARY CONFIGURATION
The FileNet Library configuration (see figure below), does not have a Bezel and is designed for vertical or horizontal mounting and for operation in a FileNet Library. The FileNet Library configuration has the same major assemblies as the other LD 8100 configurations but is configured for use in a FileNet Library by adding the MCLI connector and Registration Panel.
Figure 9. FileNet Library Configuration
97662915 B
Page 17
BLANK PANEL
MEDIA CARTRIDGE
LOADING SLOT
REGISTRATION PANEL
The figure on the left illustrates the front panel of the FileNet Library configuration and identifies the location of the DOC/ADP Blank Panel. The DOC and ADP connector are located on the rear panel, so the DOC/ADP Blank Panel is used to cover the DOC and ADP mounting holes. A special Registration Panel is installed on the FileNet Library configuration in place of the Bezel.
Figure 10. LD 8100 FileNet Library
Front Panel
The figure on the right illustrates the rear panel of the LD 8100 FileNet Library configuration and identifies the location of the AC Power Switch, Receptacle, ground connector, SCSI-2 I/O Panel Assembly, DOC, ADP connector and the MCLI connector. A Fan Grill and filter element are installed over the fan vent to filter contaminants from cooling air entering through the rear panel.
Figure 11. LD 8100 FileNet Library
Rear Panel
AC POWER
RECEPTACLE
AC POWER
SWITCH
DOC
SCSI-2 1/O CONNECTORS
MCLI I/O CONNECTOR
FAN GRILL AND
FILTER ELEMENT
GROUND CONNECTOR
ADP
CONNECTOR
PLASMON LMS - LD 8100 USER MANUAL Page 18
PLASMON 1800 LIBRARY CONFIGURATION
The Plasmon Library configuration (see figure below), which does not have a Bezel or Registration Panel, is designed for horizontal mounting and operation in a Plasmon 1800 Series Library. The Plasmon Library configuration has the same major assemblies as the other LD 8100 configurations but is adapted for use in a Plasmon 1800 Library by adding an MCLI connector.
Figure 12. Plasmon 1800 Series Library Drive
97662915 B
Page 19
The figure below illustrates the front panel of the Plasmon Library configuration and identifies the location of the DOC/ADP Blank Panel. The DOC and ADP connector are located on the rear panel. The DOC/ADP Blank Panel is used to cover the DOC and ADP mounting holes.
DOC/ADP BLANK PANEL
MEDIA CARTRIDGE LOADING PORT
Figure 13. LD 8100 Plasmon Library Front Panel
The figure below illustrates the rear panel of the LD 8100 Plasmon Library configuration and identifies the location of the AC Power Switch, AC Receptacle, ground connector, SCSI-2 I/O Panel Assembly, DOC, ADP connector and the MCLI connector. A Fan Grill and filter element are installed over the fan vent to filter contaminants from cooling air entering through the rear panel.
AC POWER SWITCH
DOC
FAN GRILL AND FILTER ELEMENT
AC POWER
RECEPTACLE
SCSI-2 1/O CONNECTORS
ADP
CONNECTOR
GROUND CONNECTOR
Figure 14. LD 8100 Plasmon Library Rear Panel
PLASMON LMS - LD 8100 USER MANUAL Page 20
MCLI
CONNECTOR
DIMENSIONS AND WEIGHTS
The following table lists the dimensions of the LD 8100 Rack Mount, Desktop and Tower, FileNet and Plasmon Library configurations. These dimensions do not include extending media cartridges or interface cabling. Refer to the LX 8000 Series Product Specification (P/N 97663035) for the dimensions of the FileNet and Plasmon Library configurations with a media cartridge and interface cabling.
Table 1. Dimensions of the LD 8100 Configurations
DIMENSION RACKMOUNT DESKTOP TOWER FILENET PLASMON
Chassis Length:
With Mounting Kit:
Chassis Width:
With Mounting Kit:
Chassis Height:
With Mounting Kit:
60.9 cm (24.0 in)
65.3 cm
(25.7 in)
43.0 cm (16.9 in)
47.5 cm
(18.7 in)
16.9 cm (6.7 in)
17.8 cm
(7.0 in)
64.3 cm (25.3 in)
67.3 cm
1
(26.5 in)
2
64.3 cm (25.3 in)
67.3 cm
(26.5 in)
64.3 cm (25.3 in)
64.3 cm (25.3 in)
67.3 cm
2
(26.5 in)
3
66.5 cm
(26.2 in)
43.0 cm (16.9 in)
48.6 cm
1
(19.1 in)
2
16.9 cm (6.7 in)
18.8 cm
(7.4 in)
4
16.9 cm (6.7 in)
2
43.0 cm (16.9 in)
30.5 cm
(12.0 in)
16.9 cm (6.7 in)
18.8 cm
1
(7.4 in)
5
48.6 cm (19.1 in)
63.2 cm
(24.8 in)
4
43.0 cm (16.9 in)
16.9 cm (6.7 in)
43.8 cm
6
(17.2 in)
3
60.9 cm
Mounting Depth
1 Includes the Bezel. 2 Includes the Bezel and chassis cover. 3 Includes the Registration Panel. 4 The pedestal and pedestal skin. 5 Includes the rubber feet. 6 Includes the chassis skin, pedestal and casters. 7 Depth to which the drive extends into the mounting rack.
(24.0 in
)7
The following weight specifications do not include interface cabling or optical media:
Rack Mount 30.5 kg (67 lbs) Desktop 35.9 kg (79 lbs) Includes Enclosure Tower 41.8 kg (92 lbs) Includes Enclosure and Pedestal FileNet Library 31.4 kg (69 lbs) Includes Registration Panel Plasmon Library 30.5 kg (67 lbs)
97662915 B
Page 21
TEMPERATURE, HUMIDITY AND ALTITUDE
The following table lists the LD 8100 operating, nonoperating, storage and transit limits for temperature, humidity, and altitude.
Table 2. Temperature, Humidity and Altitude Limits
CONDITION OPERATING NONOPERATING
Temperature
Maximum Rate of
10° to 42° C
(50° to 108° F)
11° C/hr (20° F/hr) 20° C/hr (36° F/hr) 20° C/hr (36° F/hr)
2
-40° to 66° C
(-40° to 151° F)
Change Humidity
10 to 99% 5 to 95% 5 to 95%
(Noncondensing) Maximum Rate of
10%/hr 10%/hr 10%/hr
Change Maximum Wet Bulb
Temperature
3
Minimum Dew Point
28° C (82° F) 46° C (115° F) 46° C (115° F)
2° C (35.6° F) 2° C (35.6° F) 2° C (35.6° F)
Altitude
-300 to 3000 m (-984 to 9840 ft)
-300 to 3000 m
(-984 to 9840 ft)
STORAGE/TRANSIT
-40° to 66° C
(-40° to 151° F)
Storage:
-300 to 3000 m (984 to 9840 ft)
Transit:
-300 to 12,000 m (-984 to 40,000 ft)
1
1 Storage specifications are for 90 days maximum in Plasmon LMS packaging. No condensation is permitted. Transit specifications are
based on a maximum 1-week period in a factory-sealed container.
2 Maximum operating temperature is 42°C (107.6°F) for a free-standing drive at sea level unless otherwise stated. Maximum operating
temperature is derated linearly above 300 m altitude to 38°C (100.4°F) at 2,000 m altitude.
3 See the LD 8100/LF 8600/LF 8602 Product Specification (P/N 97663035) for more information concerning the temperature and humidity
operating range.
PLASMON LMS - LD 8100 USER MANUAL Page 22
MEDIA ENVIRONMENTAL CHARACTERISTICS
The following table presents the LM 8000 Media environmental characteristics.
Table 3. Media Operation, Storage and Transportation Environments
OPERATION AND
SPECIFICATION
SHORT TERM
STORAGE
(2 years maximum)
TRANSPORTATION (2 weeks maximum)
LONG TERM
STORAGE
Temperature 10°C to 47°C
50°F to 116.6°F
Relative Humidity (no condensation)
Wet Bulb Temperature 26°C max. (78.8°F) 26°C max. (78.8°F) 26°C max. (78.8°F) Temperature Gradient 10°C/hr max.
Air Pressure N/A N/A N/A Solar Radiation N/A Case to be kept closed Not to be stored in direct
5% - 80% 5% - 90% 5% - 80%
(18.0°F/hr max.)
-20°C to +55°C
-4.0°F to 131.o°F
31°C/hr max.
(55.8°F/hr max.)
10°C to 30°C
50°F to 86.0°F
5°C/hr max.
(9.0°F/hr max.)
sunlight
SHOCK AND VIBRATION
The following table lists the conditions and limits for shock and vibration.
Table 4. Shock and Vibration Criteria and Limits
CONDITION OPERATING
Swept Vibration (bidirectional) 1 Octave/Min
5 to 250 Hz 0.1 g peak, 250 to 500 Hz
0.20 g peak
NONOPERATING
5 to 44 Hz, 0.03 in double amplitude, 44 to 500 Hz
3.0 g peak
1
STORAGE/TRANSIT
5 to 44 Hz, 0.03 in double amplitude, 44 to 500 Hz
3.0 g peak
2
3
Shock (host retries may be required and drive performance may
10 - msec half sine pulse of 5.0 g peak with pulses applied every 3 sec
degrade during test) Unpacked (3 axis) 5 - msec half sine
Packed on Pallet 46 - cm (18 - in) drop
1 With media removed 2 In Plasmon LMS-approved packaging 3 Shock repetition rate should be limited to allow mechanical system transients to subside between pulses.
pulse of 20 g peak
test flat
97662915 B
Page 23
AC POWER REQUIREMENTS
The LD 8100 has an AC power switch with an integral grounded power connector and fuses located on the rear panel. Two spare fuses are included within the power connector. Refer to Replacing Fuses section for the fuse replacement procedure.
The required fuses are 5A slow blow, 5 x 20 mm, hot and neutral. The power supply will operate with the line voltages listed in the following table. The power supply is auto
ranging and does not require mechanical switching for input voltage or frequency selection.
Table 5. Typical RMS Line Current and Power Requirements
AC LINE
VOLTAGE
95.0V TO 128V 1.3A / 101W 10A
173.0 TO 269V 0.7 / 110W 5A 1.0A / 160W 15
1
This current measurement determines the stated power and maximum heat dissipation of the Drive (546 BTU/hr) based on RMS
current over the 10S cycle derated by the Power Factor. It also determines the 2.0 A UL plate rating.
READY
SURGE PEAK
<1s
(SPIN-UP)
READY + 1 SPIN-UP/DN
CYCLE EVERY 10 s
2.0A / 160W
(1)
MIN
SERVICE
RATING
15A
AC GROUND
The LD 8100 AC power cord connects the LaserDrive to safety ground through the site AC power system. The site AC power system must tie this safety ground connection to earth ground. All site AC power connections must be maintained on the same safety ground.The line ground connector located on the rear panel can also be used to tie chassis ground to earth ground. This ground connector is a 6-mm (0.24-in) M4 stud with a nut and lock washer.
AC POWER CORD
The type of AC power cord that is supplied with the LD 8100 is based on the configuration ordered and the destination country.
POWER SUPPLY OUT-OF-RANGE PROTECTION FEATURES
The LD 8100 power supply provides over and under voltage protection, over current protection, and over temperature protection. Should an out-of-range condition be detected, the LD 8100 will shut down the DC outputs of the power supply. Once the situation has been corrected, power can be restored by turning the AC power switch to the off position and then to the on position again.
HEAT DISSIPATION
The drive will typically present a heat load of 95 calories/hr (376 BTU/hr) during a read/write operation. When media cartridges are inserted, loaded, spun up, spun down, unloaded and removed at the rate of one per 10 seconds, the drive will typically present a heat load of 137 calories/hr (546 BTU/hr).
TILT RANGE
The LD 8100 Rack Mount, Desktop and Plasmon Library configurations will operate over a tilt range of 10° from the horizontal position. The Tower and FileNet Library configuration will operate over a tilt range of 10° from the vertical position. The LD 8100 is not designed for dynamic tilt environments.
PLASMON LMS - LD 8100 USER MANUAL Page 24
PARTICULATE LIMITS
The LD 8100 is designed for use in an office or computer room. The environment must have a low dust level. The LD 8100 filters incoming air for cooling to reduce the quantity of particles entering the drive; however, the filter is not effective against small particles (including tobacco smoke) which will become deposited on optical components and media, causing degradation in drive performance. Refer to the Operator Maintenance section for media cleaning and air filter cleaning instructions.
WARNING LABELS
The LD 8100 is classified as a laser product. As such, it is subject to United States Federal requirements covering laser products. The warning labels shown in the figure below are necessary to ensure compliance with Federal regulations and must not be removed from the LD 8100.
LASER CLASS LABEL
FCC, RFI, CLASS A LABEL
LASER DANGER LABEL
CANADIAN CLASS A COMPLIANCE LABEL
Figure 15. Locations of the LD 8100 Warning Labels
97662915 B
Page 25
PLASMON LMS - LD 8100 USER MANUAL Page 26
UNPACKING AND REPACKING
INSTRUCTIONS
If the Laser Drive’s shipping carton shows evidence of rough handling or damage, return the unit in its carton to your supplier and request a replacement.
UNPACKING THE LD 8100
Each LD 8100 is shipped on a pallet in a shipping carton with foam packing material which protects the unit from shock and vibration.
After you receive your LD 8100, inspect the shipping carton for damage before unpacking the unit to substantiate a claim with the carrier if the unit is damaged. Retain all original packing materials and receipts for possible reshipment.
WARNING
The LD 8100 must be unpacked, repacked and transported by two persons. Physical injury can result if one person attempts to transport or lift the LD 8100. A wheeled cart is recommended for transporting the LD 8100 within a building. Precautions should be taken to guard against sudden bumps and jarring.
DESKTOP, RACK MOUNT AND LIBRARY CONFIGURATIONS
To unpack the LD 8100 Desktop, Rack Mount and Library configurations, refer to the next figure and perform the following procedure:
1) Cut the bands that secure the outer carton to the lower carton.
2) Lift the outer carton away from the lower carton and pallet.
3) Remove the small options and accessories tray.
The shipping carton will also contain a Quick Release Rack Mount Kit if it is ordered with the LD 8100 Rack Mount configuration. If you are unpacking an LD 8100 Rack Mount configuration, check for the Quick Release Rack Mount Kit carton and remove it at this time.
4) Lift both foam cushions away from the LD 8100.
5) Remove the ESD packing material.
6) Carefully lift and remove the LD 8100 from the shipping carton and place it on a flat surface.
97662915 B
Page 27
OPTION/ ACCESORY TRAY
OUTER CARTON
FOAM CUSHION
MOUNTING/SLIDE
(RACK MOUNT
CONFIGURATION)
FRONT FOAM CUSHION
LOWER CARTON
KIT
ESD PACKING MATERIAL
LD 8100
FOAM PADS
PALLET
Figure 16. Unpacking the LD 8100 Desktop, Rack Mount and Library Configurations
PLASMON LMS - LD 8100 USER MANUAL Page 28
TOWER CONFIGURATION
To unpack the LD 8100 Tower configuration, refer to the next figure and perform the following procedure:
1) Cut the bands that secure the carton to the lower portion pallet.
2) Carefully lift the carton up and away from the pallet while supporting the wooden hinged ramp.
3) Lower the ramp to the floor.
4) Remove the options and accessories tray.
5) Lift both foam cushions away from the LD 8100.
6) Remove the ESD packing material.
WARNING
The LD 8100 must be unpacked, repacked and transported by two persons. Physical injury can result if one person attempts to transport or lift the LD 8100. A wheeled cart is recommended for transporting the LD 8100 within a building. Precautions should be taken to guard against sudden bumps and jarring.
Ensure that all four casters are locked. Lift the front end of the LD 8100 high enough to remove the bottom cushion.
7) Remove the foam bumper.
8) Remove the bottom cushion.
9) Lower the LD 8100 onto the pallet.
10) Unlock the casters and roll the LD 8100 down the ramp to its installation location.
11) Lock the casters once you have the LD 8100 situated at its installation location.
97662915 B
Page 29
CARTON
OPTIONS/ ACCESSORIES TRAY
FRONT FOAM CUSHION
REAR FOAM CUSHION
ESD PACKING MATERIAL
FOAM
BUMPER
HINGED WOODEN RAMP
PALLET
Figure 17. Unpacking and Repacking the LD 8100 Tower Configuration
PLASMON LMS - LD 8100 USER MANUAL Page 30
LD 8100
BOTTOM CUSHION
Loading...
+ 75 hidden pages