Plasmatronics Dingo Pup User Manual

Page 1
DINGO PUP
Negative Ground 20A Max. Charge 20A Max. Load
Dingo Series Expansion Unit
User Guide
Read this before installing
Page 2
Dingo Pup User Guide
2
Install your controller:
• Vertically, where air can circulate around it;
• In a dry environment out of direct sunlight;
• Away from flammable gases or liquids;
• Away from spiders, wasps or other insects
which might make nests in it.
Pup configuration:
Each Pup must have its own address.
Configure the Pup address and system voltage before connecting the Dingo accessory bus.
Page 3
3
Dingo Pup User Guide
Wiring Instructions 6
Connecting Pup to the Dingo 14
Using the Menus 8
Choosing your Settings 10
What is a Dingo Pup?
The Dingo Pup is used to expand the capacity of the Dingo solar charge controller. Up to 9 pups can be added to a system. Each Pup is controlled by the Dingo. The Dingo manages the whole charge control process and displays the total charge and Ah figures for the system.
Page 4
Dingo Pup User Guide
4
Screw wires into the high current terminals
tightly in the order listed on page 6.
Fig. 1
Warning: This controller is for DC current ONLY
638
BOOST
Di sp la y
Alarm LED
Terminals for G and sensor wires (plug in termi nal block)
Accessory port
Mounting holes
Cable tie
posts
T
Test terminal
Ah
Button
See page 8
Page 5
5
Dingo Pup User Guide
Basic Connection Order
1. Connect Battery
2. Test Solar Polarity
3. Connect Solar
4. Connect Load (if required)
5. Set Address and System Voltage
6. Connect the Pup to the Dingo Bus
T
BATTERY-
SOLAR+
BATTERY+
LOAD+
‘G’ Terminals
Sensor T+
Temperature T-
B+ Sense
LOAD-
SOLAR-
‘G’ Terminals
Accessory Port
Test terminal
Fig. 2
Page 6
Dingo Pup User Guide
6
Wiring instructions
For safety and to avoid damage, connection of wires must be done in the following order.
All connections must be tight!
a. Connect the battery first. Positive to Battery+, Negative to
Battery -. If the display comes on, then connection is correct. (see figure 4)
b. Connect the negative (-) wire from the solar panel(s) to the
solar panel negative (-) terminal.
!"#$
27%8
BO OST
V
T
Battery
+
–
Display comes on
Connect Battery
1
* *
*For safety, most installation standards require fuses or circuit breakers on both sides of the battery. For other connections, see the reference manual.
WARNINGS:
•
The controller can be damaged quickly by reverse connection of the solar array in 32, 36 and 48V systems. Test first to avoid damage.
•NEVER connect batter­ies or inverters to the load terminals
Fig. 3
Page 7
7
Dingo Pup User Guide
c. Test the solar panel connection
by touching the positive (+) wire from the solar panel onto the Test terminal (T).
•If the alarm led does not flash then it is OK.
•If the alarm led flashes quickly then it is not OK. Check the polarity and test again. (There
must be some light on the solar panels for this test to work).
If OK connect to the Solar positive (+) terminal.
d. If the load connection is being
used, connect the negative (-) wire from the DC load circuit to the load negative (-) terminal and the positive load wire to the load positive (+) terminal.
Test the load circuit.
Check the
load polarity
e: Set the system voltage and Pup
Address.
(see page 10)
f: Connect the Pup to the Dingo
accessory port.
(Multiple Pups
can be connected in a daisy chain manner by using a 3 way female adaptor and a short cable as shown in figure 6 on page 15)
.
Fig. 4
!"#$
27 %8
BOO ST
V
T
Battery
+
–
flashes if wrong
Test Solar
2
Solar
–
test here
+
!"#$
27 %8
BOO ST
V
T
Battery
+
–
Connect Load
3
Solar
–
+
Load
+
–
Page 8
Dingo Pup User Guide
8
You can move around the menus system (see figure
5) and change settings using the button on the front of the controller..
A short push tells the controller to advance to the next menu item or setting value. To do a short push, press on the button on the front of the controller, and release it immediately.
A long push “selects”, moving into a sub-menu or allowing you to change settings. To do a long push,
press the button, holding it down until the menu changes (about one second).
Getting back
Wherever you are in the menu system, a series of short-pushes will bring you back to the top-level menus without changing any settings. There are two exceptions: when a number is flashing during setting adjustment (see page 12) and when you see the word “EXIT” in the “HISTORY” sub menu - see page 22.
Using the Menu System
REVERSE & FAST FORWARD
If you overshoot the setting you want and need to go back, you can use reverse. Do a long push. The number stops flashing. Do another long push. The number starts flashing again but this time goes down. More than 5 quick pushes will start the fast forward mode. To return to normal mode, stop pushing for 1 second.
Page 9
9
Dingo Pup User Guide
Thick arrow = long push
Thin arrow = short push
SET
ADDR TIME VOLT PROG BCAP
Set Set Set Set Set
DATA
VMAX VMIN FTIM SOC TEMP SOLV HIST
History Data
OUT
INT
Clear
IN
INT
Clear
LOAD
LINT
Low Battery Disconnect
CHRG
CINT
Generator Control
BATV
Regulator State
Fig. 5
Page 10
Dingo Pup User Guide
10
Choosing your settings
Set the Pup address and configure the Pup for independent-mode operation before joining it to the Dingo system.
Each Pup must have its own address. After setting the address (ADDR), set the system voltage (VOLT) and the correct program (PROG) for your battery, and configure any advanced settings.
1. Set the Address
Short-push until the display shows “SET”. a. Long-push once and the display will show “ADDR”. b. Long-push again, and the address will start flashing. c. Short-push until the address shown is correct. If you reach 9,
it will cycle back to 0 (unset). Choose the next address after any other Pups already in use.
d: When the address is correct, long-push to set it.
2. Set the Time
Short-push to move from “ADDR” to “TIME”. a. Long-push at TIME, and the time will start flashing.
(The time is displayed in hours and tenths of hours. For example, “6.5” means 6:30am, and “13.1” means 1:06pm)
b. Short push until the time is correct. I c. When the time shown is correct, long-push to set it.
Note: The time setting is used for the system history, and, in program 4, by the event controller. The time setting does not affect battery
charging.
Page 11
11
Dingo Pup User Guide
Programs
0: Liquid Electrolyte Battery with Low Battery Disconnect option (p.12) 1: Sealed batteries (AGM or Gel) with Low Battery Disconnect option 2: Liquid Electrolyte Battery with Light Controller option
(see p.12)
3: Sealed batteries (AGM or Gel) with Light Controller option. 4: Customised setup. Choosing this program will require you to set a
number of additional parameters.
(see Reference Manual)
3. Set the System Voltage
Short-push to move from “TIME” to “VOLT”. a. Long-push and the voltage will start flashing. b. Short-push until the voltage is correct for your battery. If
you pass 48V, it will cycle back to 12V.
c. When the voltage shown is correct, long-push to set it.
4. Set the System Program
Short-push to move from “VOLT” to “PROG”.
The program number determines battery regulation settings if the Pup becomes separated from the Dingo System. See page 22 for details.
a. Long-push and the program number will start flashing.
b. Short-push to select the best program for your batteries: c.
When the program shown is correct, long-push to set it.
4. Set any advanced (program 4) settings
Information about the “REG”, “MODE” and “EVNT” settings is in the Pup reference manual. Contact Plasmatronics support or download the reference manual from the Plasmatronics web site..
Page 12
Dingo Pup User Guide
12
Light Controller Option (Program 2-3)
The built in light controller can switch lights on at night. When the voltage from the solar ar­ray drops, the Light Controller function will switch on power to the load terminals. (The solar panel voltage is used to sense the light level.) If the battery voltage drops too low, the low battery disconnect function turns the lights off re­gardless. The light controller option will only work on the Pup if a so­lar array is connected to the charge terminals because it uses the voltage accross the ar­ray to sense light level. To use the Light Controller op­tion, choose program 2 or 3. If you have connected lights to the load terminals, they will switch on at dusk and switch off at dawn
Low Battery Disconnect (Program 0-1)
To prevent battery damage due to overdischarge, the Pup has a Low Battery Disconnect (LBD) function which can be set to turn off the load terminal if the battery falls below a pre­set voltage for a period of time. Short-term battery voltage fluctuations caused by motors starting etc. will not activate LBD. Once the battery has recharged to a safe level, the load will automatically switch on again. This may take some time. You do not have to use this fea­ture and the Pup will operate without it. To use Low Battery Disconnect, you need to con­nect your load to the regula­tor as described on page 7, and ensure that you have chosen a program 0 or program 1
Page 13
13
Dingo Pup User Guide
Load Control Menu
Long push on LINT to enter the Load Control Menu: LSET: long push to turn the Load terminal ON or OFF.
In Program 4, more Load Terminal control op­tions are available (LOFF, LON,LDEL), and more Load Function options are avail­able in the MODE menu. See the Dingo or Dingo Pup reference manual for more information.
Generator Control
The G terminal on the Pup is controlled by the Pup battery voltage in Program 0-3. Long push on CINT to enter the Generator Control Menu: GSET: long push to turn the G terminal ON or OFF. Short push to advance to GRUN: long push to adjust the generator exercise period (default 1.0 hour). Short push to advance to GDAY: long push to adjust the days between generator exercise events (default 0, not enabled). In Program 4, more Generator Terminal and Generator Function options are available. See the Dingo or Dingo Pup reference manual for more information.
Note - NEVER connect batteries or inverters to the load terminals of the controller. They will cause heavy current flow which may damage the controller.
Page 14
Dingo Pup User Guide
14
the Pup. If it is not present, check the cable connections from the Dingo to the Pup and wait for 2 minutes. There will also be entries for SWH5 under LOAD, IN and OUT.
If the Dingo is using PROG=4, then the Dingo ESET must be set correctly.
In Dingo program 4, the preloaded default setting for each pup is ESET/SW=0. This is correct for using the Pup’s charge terminal for charge control (or the Pups load terminal for shunt regulation). If using the Pups only for charge control, it should not be necessary to change the ESET/SW setting.
Connecting the Pup to the Dingo
If the program selection (PROG) on the Dingo is set in the range 0 through to 3, then the Dingo is automatically configured for using the Pups as charge controllers. The Dingo may take a short time to discover a new Pup. When the Pup is discovered, there will be an entry on the Dingo for the charge and load current and external amp hours.
For example, if the Pup address is set to 5, then in the Dingo CHRG sub menu, there will be an entry called SWH5. This is the charge current in the Pup at address 5, as seen by the Dingo.
If the CHRG/SWH5 entry is present, it confirms that the Dingo has recognised
Page 15
15
Dingo Pup User Guide
Battery
+
–
* *
!"#
42 $1
BOO ST
A
T
-
+
SOLAR
ARRAY 1
DINGO
!"#
15 $8
A
T
-
+
SOLAR
ARRAY 2
PUP 1
!"#
17 $8
A
T
-
+
SOLAR
ARRAY 3
PUP 2
Additional Pups >
*
Battery Fuses are required for safety
3 way adaptor
Dingo with Dingo Pup expansion units
Fig. 6
Page 16
Dingo Pup User Guide
16
When more charge current is required than can be con­trolled by one Dingo, then the array can be split. Dingo Pups can carry the current from these extra sub arrays. The way this is set up is shown in fig.6 on page 15. The Dingo controls the Pups. It tells them when to turn on or off. When the battery voltage is below the regulation point, all Pups will be on. When the battery voltage gets to the regulation point, the Dingo will turn off the Pups progressivly to reduce the charge current so as to maintain the regulation volt­age. If the load increases or the insolation reduces, then Pups will be turned back on until a balance is restored.
The Expanded Dingo System
The Pups report back their current to the Dingo which displays the total current in the system. It also shows the individual contibutions from each device. The Dingo and the Pups are connected together with a cable. If a Pup becomes dis­connected from the cable, then it will regulate like an independant Dingo. A system based on a Dingo 2020N is negative ground. This means that the battery negative terminals are all connected together. Switch­ing is done on the positive side. A Pup may also be operated as an external switch, con­trolled by the event, alarm or load disconnect outputs of the parent Dingo.
Page 17
17
Dingo Pup User Guide
Dingo Bus Accessories
It is not possible to use any Dingo Bus accessories with the Pup in independant mode.
Accessories such as shunt adaptors and computer interfaces can be connected to the Dingo connection bus, but they communicate with the Dingo, not the Pups. However, the Pup information can be accessed via the Dingo.
External Battery Temperature Sensor (DT or DTB).
Pup temperature input has no effect on battery charging when the Pup is part of a Dingo System.
The DT is a plastic-cased unit for direct attachment to the battery wall. The DTB has a bolt-on lug for attaching to the battery terminal (either terminal) It connects to the T+ and T- inputs on the green plug-in terminal block under the wiring cover. See Section
7.4.3 of the reference manual for details. Independent mode
only.
Page 18
Dingo Pup User Guide
18
Monitoring your system
The Pups monitoring functions provide you with information about what that Pup has done. The overall system information is kept by the Dingo.
How much energy has this Pup collected today?
The IN screen shows how many Amp hours have been collected by the Pup today.
How much energy has this Pup used today?
The OUT screen shows how many Amp hours the Pup load has used today.
What voltage did the battery reach?
VMAX shows today’s maxi­mum voltage since midnight;
VMIN
shows today’s minimum voltage. Both are in the DATA sub-menu. The actual battery voltage is shown on the BATV screen.
What is the Pup’s charge current?
The CHRG screen displays the charge current.
What is the Pup’s load current?
The LOAD screen displays the load (or discharge) current.
Are components working correctly?
A battery temperature sensor can be connected to
the Pup to improve regulation if it is oper­ating on its own. If this sensor is installed, the
battery tempera­ture is shown on the TEMP screen in the DATA sub-menu. (If it is blank, no temperature
Page 19
19
Dingo Pup User Guide
sensor is attached). To test your solar array, the SOLV screen in the DATA menu shows the open-circuit voltage of the solar array.
(Note: charg­ing is interupted while the SOLV screen is displayed - this will eventually time out to prevent the controller being left in a non charging state)
The Data Menu
This is a quick summary of the screens in the data submenu which are reached by a long push on the DATA screen and the values stored each day by the history function.
VMAX Maximum battery voltage since midnight.
VMIN Minimum battery voltage since midnight.
FTIM Time of day the controller entered the Float state if it didn’t begin in float.
SOC This is not relevant to the Pup as part of a system.
TEMP Temperature being sensed by the battery tempera­ture sensor (if attached).
SOLV Solar panel open cir- cuit voltage. NB: charging stops while displaying this screen.
HIST Entry point for his- tory data display. At midnight, IN (Amp hours), OUT (Amp hours), VMAX, VMIN, FTIM (Float TIMe) and SOC (State Of Charge) are stored in the his­tory data and reset. VMAX and VMIN respond very slowly to changes in battery voltage. This allows them to ignore short term voltage fluctuations.
Page 20
Dingo Pup User Guide
20
Retrieving historical
data
In addition to storing today’s performance data, the controller can display information about the last 99 days of operation. Historical performance information can be accessed from the DATA sub menu. After a
long-push on DATA, short­push until you see HIST. A long-push on HIST will put you in “history mode”, where you can cycle through each day’s data. In the history display, DAY 1 is yesterday and DAY 99 is 99 days ago.
Thin arrow = short push Thick arrow = long push
BATV
CHRG
LOAD
IN
OUT
DATA
SET
DAY 1 IN OUT VMAX VMIN FTIM SOC NEXT BACK EXIT
DAY 2 DAY 99 DATA
VMAX VMIN FTIM SOC TEMP SOLV HIST
DAY 2 IN OUT VMAX VMIN FTIM SOC NEXT BACK EXIT
DAY 3 DAY 1 DATA
DAY 3 IN OUT VMAX VMIN FTIM SOC NEXT BACK EXIT
DAY 4 DAY 2 DATA
DAY 99 IN OUT VMAX VMIN FTIM SOC NEXT BACK EXIT
...
...
...
...
...
...
...
DAY 1 DAY 98 DATA
Page 21
21
Dingo Pup User Guide
Further information
This controller is capable of more than what is described in this user manual. For information on how to customise your regulation setup and set up larger systems, as well as the many additional features, consult the Reference Manual. This is available from your dealer or can be downloaded from our website:
www.plasmatronics.com.au.
Independent Mode
When the Pup is not under the control of a Dingo, it operates as if it were a Dingo (but with­out the ability to have acces­sories connected to it).
The Charge, Load, and Gen­erator terminals may also be configured for independent control while the Pup is con­nected to a Dingo system.
In Program 0-3, the Low Battery Disconnect and Light Controller Option operate independently, as does the Generator control, and, if a Dingo is connected, the Dingo controls the Charge terminals.
Page 22
Dingo Pup User Guide
22
Independent Mode settings used in Programs 0-3
When programs 0-3 are selected, the controller automatically uses the values in the table on the right to control its operation.
The voltage settings are shown correct for 12V operation. For higher voltages, scale these up (eg. for a 24V system, multiply each voltage figure by 2.)
CHRG
Setting for program number
Parameter 0 1 2 3
GMOD 0
G ON (V) 11.5
GOFF (V) 13.8
GDEL (Min) 10
GEXD (Day) 30
GRUN (Hr) 1.0
LOAD
Setting for program number
Parameter 0 1 2 3
LOFF (V) 11.3
L ON (V) 12.8
LDEL (Min) 10
SET/REG
Setting for program number
Parameter 0 1 2 3
BMAX (V) 15.0 14.2 15.0 14.2
EMAX (V) 16.0 14.0 16.0 14.0
ETIM (Hr) 1.0 0 1.0 0
EFRQ (day) 45
ABSV (V) 14.0
ATIM (Hr) 2.0
FLTV (V) 13.8
HYST (V) 0.4
BRTN (V) 12.3
CHRG (A)
20 BFRQ (Day) 15
TCMP 0
Page 23
23
Dingo Pup User Guide
Nominal system voltages 12,24,32,36,48 V
Maximum voltage BAT+ to BAT- 100 V
Max short term voltage BAT+ to BAT- (2 min) 120 V
Maximum voltage SOL+ to BAT- 100 V
Max. voltage LOAD+ to BAT+ 70 V
Max. voltage between the “G” relay terminals 90 V
Max. voltage B+sense to BAT+ +/-30 V
Max. continuous charge current (SOL+) 20 A
Max. continuous load current (LOAD+) 20 A
Max. short term load current (5 minutes) 30 A
Max “G” relay current 300
mA
Battery Temp sensor range -20 to +70
°C
Max. storage temperature 70
°C
Supply Current (device only, 12V) 9 mA
Supply Current (device only, 60V) 15 mA
Supply Current max (with acces.) 26 mA
Meter Accuracy <+/-2% +/-2 digits
Max wire entry size: 16mm2 (6 AWG)
Wire size, Green Terminal Block 0.2-1.3mm2 (26-16AWG)
Specifications
Page 24
Dingo Pup User Guide
24
Plasmatronics Pty Ltd
75 Newman St. Thornbury 3071 Victoria, Australia ph (61) 3 94869902
[email protected] www.plasmatronics.com.au
Loading...