INTRODUCTION
LOW MAINTENANCE
The PA660 is designed for continuous operation without requiring replace­ment parts. It is recommended that the device is mounted downstream of the filter to ensure the carbon fiber brushes remain clean.
CLEANING INTERVAL:
The PA660 was designed for low maintenance. The device should be checked semi-annually to confirm the brushes are clean for maximum output. If the carbon fiber brushes do get dirty, the instructions below outline how to clean the device:
1. Disconnect power.
2. Remove any accumulated dust on bristles of the brushes with either
compressed air or a toothbrush.
3. Reconnect power.
MECHANICAL INSTALLATION INSTRUCTIONS
GENERAL MOUNTING CRITERIA:
1. Do not connect to power before mechanical installation is complete.
2. Mount ionization unit to allow access for general maintenance.
3. Mount the unit at or near the fan inlet using the holes in the mounting
flanges, insuring that the air stream flows over the 2 brushes simultane­ously. See figures 1 & 2.
4. The unit should be mounted downstream of the filter.
5. For best results avoid locations directly after a cooling coil or humidifier.
6. Ensure that there is at least 1/2" of clearance between the brushes and
any metal or other obstructions.
IONIZATION BRUSHESMOUNTING FLANGE MOUNTING FLANGE
AIR FLOW
FIGURE 1
MONITORING
BAS
WIRES
POWER WIRES LED INDIC ATOR LIGHT