PKP PUM04, PUM06 Instruction Manual

Instruction Manual
PUM04, PUM06
Pressure transmitter of stainless steel
PKP Prozessmesstechnik GmbH
Borsigstraße 24
D-65205 Wiesbaden-Nordenstadt
Tel.: ++49-(0)6122-7055-0
Email: info@pkp.de
Safety Information
General Instructions
The device should only be operated according to the specifications in the instruction manual. The requisite Health & Safety regulations for a given application must also be observed. This also aplies to the use of accessories.
Proper Usage
The pressure transmitter PUM04 and PUM06 are designed to measure the relative and absolute pressure of gaseous and liquid media which do not attack the device materials. All other usage is re­garded as being improper and outside the scope of the device.
The series PUM04 and PUM06 devices should not be deployed as the sole agents to prevent danger­ous conditions occurring in plant or machinery. Machinery and plant need to be designed so that faulty conditions do not arise that could pose a safety risk for operators.
Dangerous substances
For dangerous media such as e.g. Oxygen, Acetylene, flammable or toxic substances as well as refrigeration systems, compressors, etc. must comply with the relevant regulations beyond the general rules.
Qualified Personnel
PUM04 and PUM06 devices may only be installed by trained, qualified personnel who are able to mount the devices correctly. Qualified personnel are persons, who are familiar with assembling, in­stallation, placing in service and operating these devices and who are suitably trained and qualified.
PUM04, PUM06 Instruction manual 12/2017 page 2
Installation and Commissioning
The pressure tapping points should be prepared in accordance with the indications given for the sockets. For more details, see e.g. rule VDE/VDI 3512, sheet3.
Suitable for sealing are sealing washers to DIN 16258.
The correct tightening torque is depending on material and shape of the used seal. It should
not exeed 80 Nm.
The mounting position should not be subject to strong vibration and radiation heat.
The mounting position which the transmitter is adjusted for, is indicated on the rating plate.
If the device is installed in a different position, the zero point may be offset. In this case, the
zero point should be readjusted as described here under.
The transmitters are immediatly ready for service after the pressure and electrical connecti­ons have been made.
Pressure-connection variants
Connection G ½ B male Connection G ¼ female
Socket DIN 16288 Connector
PUM04, PUM06 Instruction manual 12/2017 page 3
***
* 101 mm at thin-film technic (from range R79: 0...40 bar) ** 65 mm at thin-film technic (from range R79: 0...40 bar)
*
*
*
*
Connecton for front flush membrane Connecton for front flush membrane up to measuring range R78, 0...25 bar from measuring range R79, 0...40 bar and for all ranges of PUM04
Socket Connector
PUM04, PUM06 Instruction manual 12/2017 page 4
Electrical Connection
Attention: Prior to the electrical connection of the device, it must be ensured that the supply voltage matches that required and the supply voltage is switched off.
Electrical connection is made by means of plug or shieldes cable with cappillary tube.
Precise wiring schemes can be seen in the drawings.
In addition, wiring details and required power supply are given on the rating plate.
Significance of applied terminal designations: supply voltage: Ub+ / Ub-
output signal: S+ / S­ cable shield/case, earth: shield / PE
Current output Voltage output
Output signal: 4...20 mA/2 wire-system Output signal: 0...10 V / 3 wire-sys-
tem
Power supply: Ub = 7,5...30 VDC Power supply: Ub = 12...30 VDC
Admissible load: Ra = (Ub-7,5 V) / 20 mA Admissible load: Ra ≥ 10 kΩ
Wiring
Attention:
The connecting cable with capillary must not be pinched or bended to avoid interruption of pressure compensation to ambient pressure.
Minimum bending radius: fixed = 20mm / flexible application = 100mm
PUM04, PUM06 Instruction manual 12/2017 page 5
Service and Maintenance
The transmitter described here under is maintenance free. If incorporates no components which have to be repaired or replaced on the site. Repairs can only be carried out at the factory. Depending on working conditions, the pressure transmitters should be checked about once a year to ensure that they are within their specifications and be adjusted if necessary.
!!! Attention !!! Opening the pressure transmitter will void the warranty
PUM04, PUM06 Instruction manual 12/2017 page 6
Pressure Measurements and Monitoring
PUM04
Pressure Transmitter of Stainless Steel with Ceramic Membrane
relative pressure measurement
accuracy: standard: 1 (1,5) % FS
precision: 0,3 % FS
optional front flush ceramic membrane
robust design
current or voltage output
max. temperature: 80 °C
measuring range from -1 to +400 bar
Description:
The pressure transmitter PUM04 can be used for relative pressure measurement of gaseous and liquid media. The pressure is tapped via a thin-film sensor element. In this case, the change in resistance of a strain gauge is translated with a high response speed into an output signal which is proportional to the applied pressure. The pressure sensor is a ceramic membrane. The electrical signal present at the output can be used for remote transmission or for direct display. We recommend the PKP plug-in display AZ01, which is simply placed between the transmitter and the plug and displays the measured value without additional supply voltage.
Typical applications:
The robust design of the PUM04 pressure transmitter offers the user the ability of pressure measurement of gases and liquids accurately in the process, even in harsh operating conditions. Even highly viscous and crystallizing media can be measured without hesitation. If necessary, the pressure transmitters are equipped with a front-flushed ceramic membrane, which prevents such substances from getting lodged inside the housing. In addition to the general use of the measuring instruments in almost all industrial processes, a typical application is the use in hydraulic systems. A self-powered plug-in display is optionally available for displaying the measured value.
PKP Prozessmesstechnik GmbH
Borsigstr. 24 • D-65205 Wiesbaden
S +49 (0) 6122-7055-0 •  +49 (0) 6122 7055-50
info@pkp.de • www.pkp.de
PKP Process Instruments Inc.
10 Brent Drive • Hudson, MA 01749
S +1-978-212-0006 •  +1-978-568-0060
info@pkp-usa.com • www.pkp-usa.com
180219
Technical Data:
Process connection: G ½ B male thread
G ¾ B with front-flush membrane G ¼ female thread other designs on request
Material:
Housing: stainless steel 1.4301
Pressure connec. stainless steel 1.4571
Pressure sensor: ceramic membrane = thin-film,
FKM gasket
Media temperature: −25 ... +80 °C
Ambient temperature: −20 ... +70 °C
Storage temperature: −40 ... +100 °C
Accuracy:
Standard:
Precision:
according to IEC 61298-2, linearity + hysteresis+repeatability:
+/- 1,0 % FS
(for MR R70 a. R86 +/- 1,5 % FS) <0,3 % FS, <0,2 % FSL
Temperature error: average TK zero point:
<0,2 % FS / 10 K average TK range: <0,2 % FS / 10 K
Reaction time:
< 10 ms
Weight: ca. 0,23 kg
Dimensions:
Connection G 1/2 B A, male thread: front-flush membrane:
Connection: G ¼ female thread
Order Code:
Order number: PUM04.
Universal pressure transmitter
S. 2. 1. 2. 1. R76. 0
Accuracy:
S = standard 1 (1,5) % FS P = precision 0,3 % FS
Output signal:
1 = 4...20 mA, 2-wire 2 = 0...10 V, 3-wire
Calibration:
1 = relative pressure
Electrical connection:
1 = angle plug, IP65, EN 175301-803 form A 2 = fixed connection cable IP68 (1 m standard length)
Process connection:
1 = G 1/2 B male thread, ac. to EN 837-1, inside membrane 2 = G 3/4 B male thread front flush membrane 3 = G 1/4 female thread, inside membrane 9= special connection (please specify in plain text )
Measuring range / Overrange limit:
R16 = −1...0 bar / 2,0 bar (not at PUM04.S...) R69 = 0...1 bar / 2,0 bar (not at PUM04.S...) R70 = 0...1,6 bar / 4 bar R72 = 0...2,5 bar / 4 bar R73 = 0...4 bar / 10 bar R74 = 0...6 bar / 10 bar R75 = 0...10 bar / 20 bar R76 = 0...16 bar / 40 bar R78 = 0...25 bar / 40 bar R79 = 0...40 bar / 100 bar R80 = 0...60 bar / 120 bar R81 = 0...100 bar / 200 bar R82 = 0...160 bar / 400 bar R84 = 0...250 bar / 400 bar R86 = 0...400 bar / 650 bar further measuring ranges on request
Options:
0 = without 9 = please specify in plain text
Accessory:
Self powered plug-in display AZ01
Electrical Data:
Power supply: 7,5...30 VDC at current output
12...30 VDC at voltage output
Power consumption: max. 0,75 W
Output: current output 4...20 mA, 2-wire
load = (U-7,5 V) / 0,025 A voltage output 0...10 V, 3-wire load > 10 kOhm special range are adjustable at factory
Transient emissions: according to EN 61326
Immunity: according to EN 61326
Protection class: IP65 EN 60 529 / IEC 529
IP68 with cable connection
PKP Prozessmesstechnik GmbH
Borsigstr. 24 • D-65205 Wiesbaden
S +49 (0) 6122-7055-0 •  +49 (0) 6122 7055-50
info@pkp.de • www.pkp.de
PKP Process Instruments Inc.
10 Brent Drive • Hudson, MA 01749
S +1-978-212-0006 •  +1-978-568-0060
info@pkp-usa.com • www.pkp-usa.com
Druck
Pressure Measurements and Monitoring
PUM06
Universal Pressure Transmitter of Stainless Steel
relative- or absolute pressure measurement
accuracy: 0,3 % FS
optional front flush stainless steel membrane
robust design
current or voltage output
max. temperature: 80 °C
measuring range from -1 to +2500 bar
Description:
The universal pressure transmitter PUM06 can be used for relative and absolute pressure measurement in almost all pressure ranges for gaseous and liquid media. The pressure is tapped either piezoresistively or via a thin-film sensor element. In the case of the low measuring ranges, the pressure change is registered by the electrical resistance of a piezocrystal which changes under mechanical load. In contrast, at higher measurement ranges, the thin-film technique is used, where the resistance change of an extremely thin strain gauge is translated into an output signal which is proportional to the applied pressure. The combination of these two techniques covers all DIN measuring ranges from -1...0 bar to 0...2500 bar with constant accuracy.
Typical applications:
The robust design of the PUM06 pressure transmitter offers the user the ability of accurate pressure measurement of gases and liquids in the process, even in harsh operating conditions. A stainless steel membrane protects the measuring system against damage, so that a variety of media, even highly viscous and crystallizing media can be detected. If necessary, the pressure transmitter are equipped with a front-flush membrane, which prevents such substances from getting lodged inside the housing. The electrical signal present at the output can be used for remote transmission or for direct display. We recommend the PKP plug-in display AZ01, which is simply placed between the transmitter and the plug and displays the measured value without additional power supply.
Models:
PKP Prozessmesstechnik GmbH
Borsigstr. 24 • D-65205 Wiesbaden
S +49 (0) 6122-7055-0 •  +49 (0) 6122 7055-50
info@pkp.de • www.pkp.de
PKP Process Instruments Inc.
10 Brent Drive • Hudson, MA 01749
S +1-978-212-0006 •  +1-978-568-0060
info@pkp-usa.com • www.pkp-usa.com
180220
Meas. system piezoresistive: MR: -0,1...0 to 0...25 bar Meas. system thin-film: MR: 0...40 to 0...2500 bar
Technical Data:
Process connection: G ½ B male thread
G ¾ B with front flush membrane (to MR R78 0...25 bar) G ½ B with front flush membrane (at MR R79 0...40 bar) G ¼ female other designs on request
Material:
Housing: stainless steel 1.4301
Pressure port: stainless steel 1.4571
Pressure sensor: 1.4435 (piezoresistive)
1.4545 (thin-film)
Media temperature: −25 ... +80 °C
Ambient temperature: −20 ... +70 °C
Storage temperature: −40 ... +100 °C
Accuracy: according to IEC 61298-2
linearity+hysteresis+repeatability: <0,3 % FS, <0,2 % BFSL
Temperature error: average TK zero point:
<0,2 % FS / 10 K average TK range: <0,2 % FS / 10 K
Reaction time:
< 10 ms
Weight: ca. 0,24 kg
Dimensions:
G ½ B, inside membrane
* 101 mm at thin-film technology (from MR R79: 0...40 bar) ** 65 mm at thin-film technology (from MR R79: 0...40 bar)
Order Code:
Order number: PUM06.
Universal pressure transmitter
2. 1. 2. 1. R76. 0
Output signal:
1 = 4 bis 20 mA, 2-wire 2 = 0 bis 10 V, 3-wire
Calibration:
1 = relative pressure 2 = absolute pressure
Electrical connection:
1 = angle plug, IP65, EN 175301-803 form A 2 = fixed connection cable IP68 (1 m standard length)
Process connection:
1 = G ½ B male, acc. to EN 837-1, inside membrane 2 = G ¾ B male front flush membrane (up to MR R78) 3 = G ½ B male front flush membrane (from MR R79) 4 = G 1 B male front flush membrane 5 = G ¼ female, inside membrane 9 = special connection (please specify in plain text)
Measuring range / Overrange limit:
R = relative A = absolute
R11 = -0,10...0 bar / 0,6 bar R12 = -0,16...0 bar / 0,6 bar R13 = −0,25...0 bar / 0,6 bar R14 = −0,4...0 bar / 2,0 bar R15 = −0,6...0 bar / 2,0 bar R16 = −1...0 bar / 2,0 bar R43 = −1...1,5 bar / 4 bar R45 = −1...5 bar / 13 bar R63 = 0...0,1 bar / 0,6 bar R64 = 0...0,16 bar / 0,6 bar R65 = 0...0,25 bar / 0,6 bar A65 = 0...0,25 bar / 0,6 bar R66 = 0...0,4 bar / 2,0 bar A66 = 0...0,4 bar / 2,0 bar R67 = 0...0,6 bar / 2,0 bar A67 = 0...0,6 bar / 2,0 bar R69 = 0...1 bar / 2,0 bar A69 = 0...1 bar / 2,0 bar R70 = 0...1,6 bar / 4 bar A70 = 0...1,6 bar / 4 bar R72 = 0...2,5 bar / 6 bar A72 = 0...2,5 bar / 6 bar R73 = 0...4 bar / 13 bar A73 = 0...4 bar / 13 bar R74 = 0...6 bar / 13 bar A74 = 0...6 bar / 13 bar R75 = 0...10 bar / 32 bar A75 = 0...10 bar / 32 bar R76 = 0...16 bar / 32 bar A76 = 0...16 bar / 32 bar R78 = 0...25 bar / 32 bar R79 = 0...40 bar / 80 bar R80 = 0...60 bar / 108 bar R81 = 0...100 bar / 170 bar R82 = 0...160 bar / 256 bar R84 = 0...250 bar / 400 bar R86 = 0...400 bar / 600 bar R87 = 0...600 bar / 840 bar R88 = 0...1000 bar / 1400 bar R89 = 0...1600 bar / 2080 bar further measuring ranges R90 = 0...2500 bar / 3000 bar on request
Options:
0 = without 9 = please specify in plain text
Accessory: Self powered plug-in display AZ01
Electrical Data:
Power supply:
7,5...30 VDC at current output
12...30 VDC at voltage output
Power consumption:
max. 0,75 W
Output:
current output 4...20 mA, 2-wire. load = (U-7,5 V) / 0,025 A voltage output 0...10 V, 3-wire. load > 10 kOhm special range factory adjustable
Transient emissions:
according to EN 61326
Immunity:
according to EN 61326
Protection class:
IP65 EN 60 529 / IEC 529 IP68 with cable connection
PKP Prozessmesstechnik GmbH
Borsigstr. 24 • D-65205 Wiesbaden
S +49 (0) 6122-7055-0 •  +49 (0) 6122 7055-50
info@pkp.de • www.pkp.de
PKP Process Instruments Inc.
10 Brent Drive • Hudson, MA 01749
S +1-978-212-0006 •  +1-978-568-0060
info@pkp-usa.com • www.pkp-usa.com