Pizzato Safety rope switch without reset Data Sheet

8
Safety rope switch without reset for simple stop
Selection diagram
FP 874-M2 FD 874-M2 FL 874-M2 FR 874-M2 FM 874-M2 FX 874-M2 FZ 874-M2
ACTUATORS ACTUATORS
CONDUIT ENTRIES
79
FP FD FL FC
79 80
CONTACT
BLOCKS
18 9 20 21
1NO+1NC
slow action
22
2NO+1NC
slow action
2NC
slow action
1NO+1NC
slow action
1NO+2NC
slow action
2NC
slow action
3NC
slow action
177
Threaded conduit entry
(standard)
product option
With cable gland
With M12 plastic
connector
With M12 metal con-
nector
General Catalogue Safety 2017-2018
Code structure Attention! The feasibility of a code number does not mean the effective availability of a product. Please contact our sales office.
article options
options
FD 1879-E7GM2K50T6
8
Housing
FD
metal, one conduit entry
FL
metal, three conduit entries
FP
technopolymer, one conduit entry
Contact block
18
1NO+1NC, slow action
9
2NC, slow action
20
1NO+2NC, slow action
21
3NC, slow action
22
2NO+1NC, slow action
33
1NO+1NC, slow action
34
2NC, slow action
Actuating head
79
longitudinal head
80
transversal head
Actuating force
standard
E7
initial 20 N...final 40 N
E9
initial 13 N...final 75 N
Threaded conduit entry
M2
(FD-FL housing only)
Contact type
silver contacts (standard)
G
(only head 79)
(only head 80)
article options
silver contacts with 1 µm gold coating
Silver contacts, 2.5 µm gold coating
G1
(not for contact blocks 20, 21, 22, 33, 34)
FC 3379-E7GM2K50T6
Ambient temperature
-25°C … +80°C (standard)
T6
-40°C … +80°C
Pre-installed cable glands or connectors
no cable gland or connector (standard)
K23
cable gland for cables Ø 6 … 12 mm
……………………
K50
M12 metal connector, 5-pole
……………………
For the complete list of possible combinations please contact our tech­nical department.
M20x1.5 (standard)
PG 13.5
options
Housing
FC
metal, one conduit entry
Contact block
33
1NO+1NC, slow action
34
2NC, slow action
Actuating head
79
longitudinal head
80
transversal head
Actuating force
standard
E7
initial 20 N...final 40 N
E9
initial 13 N...final 75 N
Housing
FD
metal, one conduit entry
FL
metal, three conduit entries
FP
technopolymer, one conduit entry
FR
technopolymer, one conduit entry
FM
metal, one conduit entry
FX
technopolymer, two conduit entries
FZ
metal, two conduit entries
Actuating force
standard
E7
initial 20 N...final 40 N
Contact type
silver contacts (standard)
G
silver contacts with 1 µm gold coating
G1
silver contacts with 2.5 µm gold coating
Pre-installed cable glands
no cable gland (standard)
K23
cable gland for cables Ø 6 … 12 mm
K50
M12 metal connector, 5-pole
Threaded conduit entry
M2
M20x1.5 (standard)
PG 11
Contact type
silver contacts (standard)
G
(only head 79)
(only head 80)
article options
silver contacts with 1 µm gold coating
options
FD 874-E7GM2K50T6
Pre-installed cable glands or connectors
no cable gland or connector (standard)
K23
cable gland for cables Ø 6 … 12 mm
……………………
K50
M12 metal connector, 5-pole
……………………
For the complete list of possible combinations please contact our tech­nical department.
Threaded conduit entry
M2
M20x1.5 (standard)
M1
A
M16x1.5
PG 13.5
PG 11
(FR-FX housing only)
(FR-FX housing only)
Ambient temperature
-25°C … +80°C (standard)
T6
-40°C … +80°C
Ambient temperature
-25°C … +80°C (standard)
T6
-40°C … +80°C
General Catalogue Safety 2017-2018
178
8
Safety rope switch without reset for simple stop
Main features
•Metal or plastic housing, from one to three conduit entries
•Protection degree IP67
•7 contact blocks available
•Versions with vertical or horizontal actuation
•Versions with assembled M12 connector
•Versions with gold-plated silver contacts
Quality marks:
IMQ approval: EG605 (FD-FL-FP-FC series)
UL approval: E131787
EG610 (FR-FX series) EG609 (FM-FZ series)
CCC approval: 2007010305230000 (FD-FL-FC series) 2007010305230014 (FP series)
(FR-FX series)
(FM-FZ series)
2007010305230013
2007010305229998
EAC approval: RUC-IT.AД35.В.00454
Technical data
Housing
FP, FR, FX series housing made of glass fibre reinforced technopolymer, self-extingui­shing, shock-proof and with double insulation: FD, FL, FC, FM, FZ series: metal housing, baked powder coating.
FD, FP, FC, FR, FM series: one threaded conduit entry: M20x1.5 (standard) FX series: two knock-out threaded conduit entries: M20x1.5 (standard) FZ series: two threaded conduit entries: M20x1.5 (standard) FL series: three threaded conduit entries: M20x1.5 (standard) Protection degree: IP67 acc. to EN 60529 with
General data
For safety applications up to: SIL 3 acc. to EN 62061
Safety parameters:
: 2,000,000 for NC contacts
B
10D
Service life: 20 years Ambient temperature: -25°C … +80°C Max. actuation frequency: 1 cycle / 6 s Mechanical endurance: 1 million operating cycles Max. actuation speed: 0.5 m/s Min. actuation speed: 1 mm/s Tightening torques for installation: see page 313-324
Cable cross section (flexible copper strands)
Contact blocks
20, 21, 22, 33, 34: min. 1 x 0.34 mm2 (1 x AWG 22)
Contact blocks 18, 8, 9: min. 1 x 0.5 mm2 (1 x AWG 20)
In compliance with standards:
IEC 60947-5-1, EN 60947-5-1, EN 60947-1, IEC 60204-1, EN 60204-1, EN ISO 14119, EN ISO 12100, IEC 60529, EN 60529, UL 508, CSA 22.2 No.14 .
Approvals:
IEC 60947-5-1, UL 508, CSA 22.2 No.14, GB14048.5-2001.
Compliance with the requirements of:
Low Voltage Directive 2014/35/EU, EMC Directive 2014/30/EU.
Positive contact opening in conformity with standards:
IEC 60947-5-1, EN 60947-5-1.
cable gland of equal or higher protection degree
PL e acc. to EN ISO 13849-1
max. 2 x 1.5 mm
max. 2 x 2.5 mm
2
(2 x AWG 16)
2
(2 x AWG 14)
If not expressly indicated in this chapter, for correct installation and utilization of all articles see chapter utilization requirements
from page 313 to page 324.
Electrical data Utilization category
Thermal current (I Rated insulation voltage (U
Rated impulse withstand voltage (U
without
connector
Conditional short circuit current: 1000 A acc. to EN 60947-5-1 Protection against short circuits: type aM fuse 10 A 500 V Pollution degree: 3
): 10 A
th
): 500 Vac 600 Vdc
i
): 6 kV
imp
400 Vac 500 Vdc
(contact blocks 20, 21, 22, 33, 34)
4 kV
(contact blocks 20, 21, 22, 33, 34)
Alternating current: AC15 (50÷60 Hz)
(V) 250 400 500
U
e
Ie (A) 6 4 1 Direct current: DC13 Ue (V) 24 125 250 Ie (A) 6 1.1 0.4
Alternating current: AC15 (50÷60 Hz)
(V) 24 120 250
Thermal current (I Rated insulation voltage (U Protection against short circuits: type gG fuse 4 A 500 V
4 and 5-pole
Pollution degree: 3
with M12 connector
): 4 A
th
): 250 Vac 300 Vdc
i
U
e
Ie (A) 4 4 4 Direct current: DC13 Ue (V) 24 125 250 Ie (A) 4 1.1 0.4
Alternating current: AC15 (50÷60 Hz) Ue (V) 24 Ie (A) 2 Direct current: DC13 Ue (V) 24 Ie (A) 2
General Catalogue Safety 2017-2018
179
Thermal current (Ith): 2 A Rated insulation voltage (U
8-pole
Protection against short circuits: type gG fuse 2 A 500 V Pollution degree: 3
with M12 connector
): 30 Vac 36 Vdc
i
Description
These rope-operated safety switches are installed on machines or conveyor belts and facilitate the simple shut-down of the machine from any point and with any pull on the rope.
Provided with self-control function, they allow the constant monitoring of correct functioning, signalling with the opening of the contacts an eventual loosening or breaking of the rope.
Head with variable orientation
8
For all switches, the head can be adjusted in 90° steps after removing the four fastening screws.
Protection degree IP67
These devices are designed to be used in the toughest environmental conditions and they pass
the IP67 immersion test acc. to EN 60529. They can therefore be used in all environments where maximum protec­tion degree of the housing is required.
Indicator for rope adjustment
Tension
indicator
Area of correct rope tightening
electrical safety contacts will open.
The switches (head 79 and
80) are provided with a green ring that shows the area of the correct tightening of the rope. The installer has only to tighten the rope until the black indicator will be in the middle of the green area. If the ten­sion (or loosening) on the rope is so high that the black indi­cator exits the green area, the
Extended temperature range
These devices are also available in a special version suitable for an ambient operating tem­perature range from -40ºC up to +80°C.
They can therefore be used for applications in cold stores, sterilisers and other equipment with low temperature environments. The spe­cial materials used to produce these versions retain their characteri­stics even under these conditions, thereby expanding the installation possibilities.
Actuating forces
These switches can be supplied with reduced hardness internal springs on request. The force required to actuate the switch can thereby be reduced without changing the actuating path of the electrical contacts. This is particularly advantageous for smaller spans, but must, howe­ver, always make use of rope pulleys.
Features approved by IMQ
Rated insulation voltage (U
Conventional free air thermal current (I Protection against short circuits: type aM fuse 10 A 500 V Rated impulse withstand voltage (U
Protection degree of the housing: IP67 MV terminals (screw terminals) Pollution degree: 3 Utilization category: AC15 Operating voltage (U Operating current (I
Forms of the contact element: Zb, Y+Y, Y+Y+X, Y+Y+Y, Y+X+X Positive opening contacts on contact blocks 18, 8, 9, 20, 21, 22, 33, 34 In compliance with standards: EN 60947-1, EN 60947-5-1+ A1:2009, fundamental requirements of the Low Voltage Directive 2014/35/EU.
Please contact our technical department for the list of approved products.
General Catalogue Safety 2017-2018
): 500 Vac
i
): 400 Vac (50 Hz)
e
): 3 A
e
400 Vac
): 10 A
th
imp
): 6 kV
(for contact blocks 20, 21, 22, 33, 34)
4 kV
(for contact blocks 20, 21, 22, 33, 34)
Features approved by UL
Utilization categories Q300 (69 VA, 125-250 Vdc)
A600 (720 VA, 120-600 Vac) Housing features type 1, 4X “indoor use only”, 12, 13 For all contact blocks use 60 or 75 °C copper (Cu) conductor, rigid or flexible, wire size 12, 14 AWG. Tightening torque for terminal screws of 7.1 lb in (0.8 Nm).
In compliance with standard: UL 508, CSA 22.2 No.14
Please contact our technical department for the list of approved products.
180
8
Safety rope switch without reset for simple stop
Dimensional drawings
Contact type:
= slow action
L
65
28
7
60
5.9 30
Contact block
18
9 20 21 22 33 34
Actuating force
Travel diagrams
L
L
L
L
L
L
L
40
FP 1879-M2 FP 979-M2 FP 2079-M2 FP 2179-M2 FP 2279-M2 FP 3379-M2 FP 3479-M2
Initial 63 N…final 83 N (90 N )
page 182 - group 1
5.4
5.4x7.4
14.5
16.2
15.2
30.4
38.6
1NO+1NC
2NC
1NO+2NC
3NC
2NO+1NC
1NO+1NC
2NC
14.5
All values in the drawings are in mm
14.5
1NO+1NC
2NC
1NO+2NC
3NC
2NO+1NC
1NO+1NC
2NC
14.5
16
15
30.4
36.5
)
84
65
28
28
7
606.2
5.3
5.3x7.3
30 40
FD 1879-M2 FD 979-M2 FD 2079-M2 FD 2179-M2 FD 2279-M2 FD 3379-M2 FD 3479-M2
Initial 63 N…final 83 N (90 N )
28
16
15
30.4
36.5
1NO+1NC
2NC
1NO+2NC
3NC
2NO+1NC
1NO+1NC
2NC
page 182 - group 1
14.5
20
15
7
606.2
5.3
30
5.3x7.3
40
FD 1880-M2 FD 980-M2 FD 2080-M2 FD 2180-M2 FD 2280-M2 FD 3380-M2 FD 3480-M2
Initial 147 N…final 235 N (250 N
page 182 - group 2
18
1NO+1NC
2NC
1NO+2NC
3NC
2NO+1NC
1NO+1NC
2NC
14.5
14.5
14.5
1NO+1NC
2NC
14.5
14.5
14.5
33.4
84
65
6.5
31.5
28
45.5 7
5.3
30 40
FC 3379-M2 FC 3479-M2
Initial 63 N…final 83 N (90 N )
14.5
14.5
33.4
1NO+1NC
2NC
28
page 182 - group 1
20
15
5.3
30
45.5 7
40
FC 3380-M2 FC 3480-M2
Initial 147 N…final 235 N (250 N
page 182 - group 2
Contact block
18
9 20 21 22 33 34
Actuating force
Travel diagrams
65
28
757
40
56
L
FL 1879-M2
L
FL 979-M2
L
FL 2079-M2
L
FL 2179-M2
L
FL 2279-M2
L
FL 3379-M2
L
FL 3479-M2
Initial 63 N…final 83 N (90 N )
page 182 - group 1
6.5
14.5
18
14.5
1NO+1NC
2NC
1NO+2NC
3NC
2NO+1NC
1NO+1NC
2NC
31.5
84
28
20
15
757
40
56
FL 1880-M2 FL 980-M2 FL 2080-M2 FL 2180-M2 FL 2280-M2 FL 3380-M2 FL 3480-M2
Initial 147 N…final 235 N (250 N )
page 182 - group 2
How to read travel diagrams All values in the diagrams are in mm
NO opening
0
1.5
4
2
S
NC closing
Ideal rope tension point
Maximum travel
7.5
8.5
11-12
7
8
23-24
Positive opening travel
Example diagram
Closed contact
Open contact
IMPORTANT: In safety applications, actuate the switch at least up to the
positive opening travel shown in the travel diagrams with symbol . Actuate the switch at least with the positive opening force, reported in brackets below each article, next
to the actuating force value.
)
Items with code on green background are stock items
181
Accessories See page 299
The 2D and 3D files are available at www.pizzato.com
General Catalogue Safety 2017-2018
S
S
Contact type:
= slow action
L
Contact block
8
L
15.325.1
7
60
5.9
FP 874-M2
8
5.3
5.3x7.3
1NC
14.5
16
15
30.4
36.5
15.325.1
757
FL 874-M2
14.5
6.5
14.5
40
56
18
14.5
31.5
1NC
14.5
15.325.1
7
5.4
16.2
15.2
5.4x7.4
30 40
30.4
38.6
1NC
606.2
FD 874-M2
30 40
Actuating force
Travel diagrams
Initial 63 N…final 83 N (90 N )
page 182 - group 3
3
38.8 15.3
108.6
51.5
Contact block
L
8
Actuating force
Travel diagrams
FR 874-M2
Initial 63 N…final 83 N (90 N )
page 182 - group 3
Travel diagrams table
Contact block
18
1NO+1NC
8
1NC
9
2NC
20
1NO+2NC
21
3NC
22
2NO+1NC
33
1NC+1NO
34
2NC
Initial 63 N…final 83 N (90 N )
Initial 63 N…final 83 N (90 N )
page 182 - group 3
4.2x7.2
12.2
14.2
24.2
46.1
56
12.2
4.2x7.2
20 22
30.8 30.8
24.2
14.2
3
38.8 15.3
111.5
20 22
54.4
30.8 31.5
1NC
FM 874-M2
Initial 63 N…final 83 N (90 N )
page 182 - group 3
1NC
FX 874-M2
Initial 63 N…final 83 N (90 N )
Group 1 Group 2 Group 3
0 16133.5
0 8.57
1.5
4
S
1.1
7.4
0 8.5
4
S
7.21.4
0 8.571.5
0 8.5
0 8.571.5
0 8.57
1.5
1.1
0 8.5
8
4
S
7.41.1
8
4
S
71.5
8
4
S
7.41.1
4
S
7.4
8
4
71.5
S
8
8
8
8
S
4 12.6
14.5
8
0
S
133.5
0 16
3.8 12.6
8
133.5
S
0 163.5 12.6
8
0
3.8 12.6
8
8
0
3.8 12.6
S
133.5
8
0 163.8 12.6
S
14
16
14
14
14
16
14
16
14
page 182 - group 3
15.3
11
20
45
22 40
42 58
page 182 - group 3
0
4
S
6.3
12.2
15.3
4
3
24.2
18.5
14.2
31.7
1NC
3
38.8
102.1
45
FZ 874-M2
20 22 40 42
50
4.2x7.2
18.5
1NC
12.2
14.2
24.2
31.5
Initial 63 N…final 83 N (90 N )
page 182 - group 3
In the rest position (with rope cor­rectly tightened) the two contacts of con- tact block 8 are both closed and are acti-
8
8.51
vated respectively by tightening or loosening the rope. In order to use this con­tact block for safety applications it is necessary to connect the two contacts in series. For this reason, in the wiring diagrams the contact block 8 is indicated as 1NC, whe­reas in travel diagrams both con­tacts are indicated.
Accessories See page 299 The 2D and 3D files are available at www.pizzato.com
General Catalogue Safety 2017-2018
182
8
Safety rope switch without reset for simple stop
Application examples and max. rope length for switches with longitudinal head
Example
A
VF AF-TR5
FD 1879-M2
2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m
24 m MAX
VF AF-CA5
VF AF-MR5
FD 1879-M2
VF AF-TR5
VF AF-CA5
VF AF-MR5
VF AF-ME78
Example
B
FD 1879-M2
VF AF-TR5
2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m
18 m MAX
VF AF-CA5
VF AF-MR5
Example
C
Example
D
FD 1879-M2
FD 1879-M2
VF AF-TR5
2 ÷ 3 m 2 ÷ 3 m 2 ÷ 3 m
12 m MAX
VF AF-MR5
VF F05
6 m MAX
VF AF-CA10
VF AF-IFGR03
VF AF-MR5
Application examples and max. rope length for switches with transversal head
VF AF-TR5
VF AF-CA5
VF AF-MR5
3 m max
FD 1879-M2 FD 874-M2
Example
E
VF F05
VF AF-IFGR03VF AF-IFGR03
VF AF-IFGR03
VF AF-TR8
3 m max
Example
F
Example
G
Example
H
Example
I
FD 1880-M2
FD 1880-M2
FD 1880-M2
FD 1880-M2
VF AF-TR5
VF AF-TR5
VF AF-TR5
3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m
70 m MAX
VF AF-CA5
3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m
50 m MAX
VF AF-CA5
3 ÷ 5 m 3 ÷ 5 m 3 ÷ 5 m
35 m MAX
VF AF-MR5
VF F05
16 m MAX
VF AF-MR5
VF AF-MR5
VF AF-ME80
VF AF-CA10
VF AF-IFGR03
VF AF-MR5
3 m max
5 m max
FD 1880-M2
FD 1880-M2
Example
J
VF F05
VF AF-TR8
3 m max
5 m max
VF AF-IFGR03VF AF-IFGR03
VF AF-IFGR03
183
General Catalogue Safety 2017-2018
Maximum spans
30
25
20
15
10
Max. rope length (m)
5
0
0 10 20 30 40 50 60 70 80 90 100
Maximum spans for switches with longitudinal head
Temperature difference (°C)
example A example B example C-E example D
8
The max. recommended spans are indicated in the diagram as a function of the temperature fluctuations (temperature differences) to which the switch may be exposed at the point of use. For instance, with installa­tion of type C and a tempe­rature difference of 30°C, the max. recommended rope length is 10 metres.
Maximum spans for switches with transversal head
80
70
60
50
40
Max. rope length (m)
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100
Temperature difference (°C)
Important: The above data are guaranteed only using original rope and accessories. See page 185.
example F example G example H-J example I
Adjustment of the switching point
For switches with head 79 and 80: Tighten the rope con-
nected to the switch, until the end of the indicator (1) rea­ches about the middle of the green ring (2).
General Catalogue Safety 2017-2018
For switches with head 74: Tighten the rope connected to the switch until the thimble will be at about 4 mm from the head.
184