10A
Safety module CS AR-07
Module for emergency stops and end
position monitoring for movable guards
Main features
•For safety applications up to SIL CL 3/PL e
•Input with 1 or 2 channels
•Choice between automatic start, manual start
or monitored start
•Connection of input channels of opposite
potentials
•Reduced housing width of 22.5 mm
•Output contacts:
4 NO safety contacts,
1 NC auxiliary contact
•Supply voltage:
24 Vac/dc
Utilization categories
Alternating current: AC15 (50…60 Hz)
Ue (V) 230
Ie (A) 3
Direct current: DC13 (6 oper. cycles/min.)
Ue (V) 24
Ie (A) 4
Technical data
Housing
Polyamide housing PA 66, self-extinguishing V0 acc. to UL 94
Protection degree: IP40 (housing), IP20 (terminal strip)
Dimensions: see page 295, design B
General data
SIL CL: up to SIL CL 3 acc. to EN 62061
Performance Level (PL): up to PL e acc. to EN ISO 13849-1
Safety category: up to cat. 4 acc. to EN ISO 13849-1
Safety parameters: see page 349
Ambient temperature: -25°C…+55°C
Mechanical endurance: >10 million operating cycles
Electrical endurance: >100,000 operating cycles
Pollution degree: external 3, internal 2
Impulse withstand voltage (U
Rated insulation voltage (U
Overvoltage category: II
Weight: 0.3 kg
Supply
Rated supply voltage (U
Max. DC residual ripple in DC: 10%
Supply voltage tolerance: ±15% of U
Power consumption AC: < 5 VA
Power consumption DC: < 2 W
Control circuit
Protection against short circuits: PTC resistance, Ih=0.5 A
PTC times: Response time > 100 ms, release time > 3 s
Maximum resistance per input:
Current per input: 30 mA (typical)
Min. duration of start impulse t
Response time t
Release time t
Release time in absence of power supply t
Simultaneity time t
: < 70 ms
A
: < 40 ms
R1
: unlimited
C
In compliance with standards:
EN 60204-1, EN ISO 13855, EN 1037, EN ISO 12100, EN ISO 13850, EN 60529,
EN 61000-6-2, EN 61000-6-3, EN 61326-1, EN 60664-1, EN 60947-1, EN ISO 13849-1,
EN ISO 13849-2, EN 62061, UL 508, CSA C22.2 n° 14-95
): 4 kV
imp
): 250 V
i
): 24 Vac/dc; 50…60 Hz
n
n
50
: > 100 ms
MIN
: < 80 ms
R
Quality marks and certificates:
EC type examination certificate: IMQ CP 432 DM
UL approval: E131787
CCC approval: 2013010305640211
EAC approval: RUC-IT.AД35.В.00454
Compliance with the requirements of:
Low Voltage Directive 2014/35/EU,
Machinery Directive 2006/42/EC,
EMC Directive 2014/30/EU
Code structure
CS AR-07M024
Connection type
M
Connector with screw terminals
X Connector with spring terminals
Output circuit
Output contacts: 4 NO safety contacts
1 NC auxiliary contact
Contact type: forcibly guided
Material of the contacts: gold-plated silver alloy
Maximum switching voltage: 230/240 Vac; 220 Vdc
Max. current per contact: 6 A
Conventional free air thermal current (Ith): 6 A
Max. total current Σ Ith
2
: 72 A
2
Minimum current: 10 mA
Contact resistance:
100 m
External protection fuse: 4 A
The number and the load capacity of output contacts can be increased by using expansion modules or
contactors. See page 241-250.
Stock items
CS AR-07M024
Supply voltage
024
24 Vac/dc
Features approved by UL
Rated supply voltage (Un): 24 Vac/dc; 50…60 Hz
Power consumption AC: < 5 VA
Power consumption DC: < 2 W
Maximum switching voltage: 230 Vac
Max. current per contact: 6 A
Utilization category C300
Notes:
- Use 60 or 75 °C copper (Cu) conductors, rigid or flexible, wire size 30-12 AWG.
- Tightening torque for terminal screws of 5-7 lb in.
- Only for 24 Vac/dc versions: power supply only with class 2 sources or with
limited voltage and energy. (Supply from Remote Class 2 Source or limited
voltage limited energy).
201
General Catalogue Safety 2017-2018

K1
K2
A1
S11
S12
S34
13
23
33
51
S31
S33
43
A2
S21
S35
14
24
34
52
S22
44
LED
CH1
LED
CH2
Safety module CS AR-07
Pin assignment
13 23 33
S33 S34 S31 S35
14 24 34
Internal block diagram
L / +
43
44
LED
PWR
A1 S11 S12
ITALY
PWR
CH1
CH2
A2 S21 S22
LOGIC LOGIC
10A
Function diagrams
Configuration with automatic start
51
tCt
tR1tCt
A
t
t
R1
A
A
Configuration with monitored start
52
t
t
R1
A
tAt
t
R1
MINtA
Configuration with manual start
t
Legend:
t
: Min. duration of start impulse
MIN
tC: simultaneity time
tA: response time
tR1t
A
t
t
A
R1
MIN
t
: release time
R1
: release time in absence of
t
R
power supply
A1/A2
S11/S12
S21/S22
13/14, 23/24,
33/34, 43/44
51/52
t
R
A1/A2
S11/S12
S21/S22
S33/S34 (START)
13/14, 23/24,
33/34, 43/44
51/52
t
R
A1/A2
S11/S12
S21/S22
S33/S34 (START)
13/14, 23/24,
33/34, 43/44
51/52
t
R
Notes:
The configurations with one channel are obtained taking into consideration the S11/
S12 input only. In this case it is necessary to consider time tR1 referred to input
S11/S12, time tR referred to the supply, time tA referred to input S11/S12 and to the
start, and time t
referred to the start.
MIN
N / -
Input configuration
Emergency stop circuits
Input configuration with manual start
1 channel 2 channels
S21
S22
L / +
A1
S21 S22
S11
CS AR-07
S12
S31
S34
S33
S35
A2
N / -
Movable guard monitoring
The safety module can monitor emergency stop
circuits and control circuits for movable guards.
Replace the emergency stop contacts with the
switch contacts.
S35
L / +
S12
S11
A1
CS AR-07
S21 S22
The diagram does not show the exact position of the terminals in the product
S31
Automatic start
With regard to the
indicated diagrams, bridge
the start button between
S33 and S34 in order to
activate the automatic
start module.
S34 S34
S34
S33
S35
A2
N / -
Monitored start
With regard to the
indicated diagrams,
S21
remove the connection
between S22 and S35
in order to activate the
monitored start module.
S35
S22
Items with code on green background are stock items
General Catalogue Safety 2017-2018
Application examples See page 251