U1
C1
CN1
1 6
MEMORY C.121
TCT101
1 2 3
Dima di foratura
28.5 x 70.5 mm
Frontal panel cut-out
Spessore suggerito
2 mm
Suggested thickness
÷8
77 mm
35 mm
53 mm
7
42mm
Enter
Memory Card
CN1
1 6
PI XSY S
Memory Card (optional)
with battery
Cod. MEMORY C243
Memory Card (optional)
Cod. MEMORY C121
Guarnizione per 32x74
Cod. 1600.00.082 (optional)
Gasket for 32x74
USER MANUAL TCT101-1ABC
PIXSYS www.pixsys.net
e-mail: sales@pixsys.net - support@pixsys.net
Software V 2.00
2300.10.120-RevB 091109
*2300.10.120-B*
Operating
conditions
Sealing
Material
Digital inputs
Outputs
Back-UP
Programming
software
Power supply
TECHNICAL DATA
0-40°C, humidity 35..95uR%
Front panel IP65 (with optional gasket) ,
Box IP30, Terminal blocks IP20
Polycarbonate UL94V0 self-exstinguishing
3PNP/NPN selectable, also analogic for
potentiometers
2 relays 5A resistive
Rechargeable battery, approx 7days autonomy
Labsoftview 2.0
24...230Vac/Vdc +/-15% 50/60Hz / 2W
DIMENSION and INSTALLATION
INTRODUCTION
Thanks for choosing a Pixsys device.
Timer TCT101 can be set in 5 different modes: Timer-ON, Timer-OFF,
Pause-Work, Oscillator, PWM (time-proportioned output), all options
with independent setting of ON-OFF time.
3 digital inputs are available (NPN/PNP) for external commands like
Start, Stop, Reset; one input is also analogic in order to allow the
modification of working times by external potentiometer.
5 different time bases (hundredths, tenths, seconds, minutes, hours).
Counting can be incremental or decremental.
MEMORY CARD (optional)
Parameters and setpoint values can be copied from one device to
another using the Memory car
There are two methods:
With the device connected to the power supply
insert the memory card when the controller is off.
On activation display 1 shows and display 2 shows
The device loads the new data and starts again
With the controller disconnected from the power supply:
The memory card is equipped with an internal battery with a life of about 1000
uses.
Insert the memory card and press the programming button.
When writing the parameters, the LED turns red and on completing the procedure
it changes to green. It is possible to repeat the procedure.
To update the memory card values, follow the procedure described in the first
method, setting display 2 to so as not to load the parameters on controller.
Enter configuration and change at least one parameter.
Exit configuration. Changes are saved automatically.
LOADING DEFAULT VALUES
This procedure restores the factory settings of the instrument.
.
>
(Only if the values stored on Mmeory Card are correct).
By pressing the key display 2 shows
Confirm using the key .
.
>
UPDATING MEMORY CARD.
PRESS
for 3 seconds
Display 1 shows
and 1st digit flashes,
display 2 shows
EFFECT OPERATION
Or
Modify flashing digit,
press to reach the following digit
Enter password
to confirm
Display shows first parameter
of configuration table
1
2
3
WIRING DIAGRAM
GND
POSITIVO
OUTPUT
POTENZIOMETER 5..10 Kohm
Accuracy 1000 points
Proximity
sensor PNP 3
3wires
Proximity
sensor PNP 2
2wires
Proximity
sensor PNP 1
2wires
PNP
NPN
P-01 Timer Function
Timer On
Timer Off
Pause/Work
Oscillator
PWM
FUNCTION CONFIGURATION
P-02 Power-off Memory
Disable
Only Timer
Timer / State
BACKUP MEMORY CONFIGURATION
P-03 Hardware Input 1
INPUT CONFIGURATION
LIST of PARAMETERS
PNP
NPN
To modify Set1 or Set2 by external potentiometer follow the steps below:
1- use potentiometers 5kOhm to 10kohm
2- connect cursor to pin I3; a wrong connection may damage the
potentiometer and lead to lock of the device.
3- accuracy on input is max 1000 points, therefore set the parameters "Upper
limit" and "Lower limit" with a max difference of 1000 units.
(Ex.: LoS1 to 50,0 and uPS1 to 150,0 to modify time value related to Set1 between
50 and 150 seconds with steps of one tenth). Greater differences would make
unstable the less significant digit.
4- To calibrate the scale of potentiometer enter the configuration mode and
select:
Hin.3 as Pot
Fin.3 as Set1 or Set2
P.tAr as Enable
Exit configuration mode and place potentiometer at minimum level and press key,
then place potentiometer at max level and press premere key: the device
automatically exit the calibration procedure.
N.B.: A switch-off of the device would interrupt the calibration.
Potentiometer:
Timer operating modes
Activate output at elapsing of counting
Deactivate output at elapsing of counting
T1 and T2 start in sequence
T1 and T2 start in sequence and cycling
Activate a percentage of output on a fixed time base
Memory after switch-off
Disabled
Memory stores only value of Timer
Memory stores value of Timer and START/STOP status
NPN
PNP
TTL
NPN
PNP
TTL
P-04 Hardware Input 2
Configuration Input 1
NPN
PNP
TTL
NPN
PNP
TTL
Configuration Input 2
Default
Default
Default
Default
SETPOINT CONFIGURATION
OUTPUT CONFIGURATION
DISPLAY CONFIGURATION
P-05 Hardware Input 3
P-06 Active State Input 1
P-07 Active State Input 2
P-08 Active State Input 3
PNP
TTL
Potent.
High Level
Low Level
Rising edge
High Level
Low Level
Rising edge
High Level
Low Level
Rising edge
Configuration input 3
Activate Input 1
Activate Input 2
Activate Input 3
PNP
TTL
Potentiometer
High level
Low level
Rising edge
High level
Low level
Rising edge
High level
Low level
Rising edge
P-09 Function Input 1
P-12 Function Key UP
P-10 Function Input 2
P-11 Function Input 3
P-16 Format Set 1
P-18 Display Set 1
P-17 Format Set 2
P-19 Display Set 2
P-13 Output Q1 Setup
P-14 Output Q2 Setup
P-15 Type of Timer
Disable
Start / Stop
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
Second.Cent
Second.Decimal
Second
Minute.Second
Hour.Minute
Second.Cent
Second.Decimal
Second
Minute.Second
Hour.Minute
Disable
Start / Stop
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
Reset
Wait
Hold
Disable
Out Timer 1 n.o.
Out Timer 1 n.c.
Out Timer 2 n.o.
Out Timer 2 n.c.
Start
Stop
Disable
Out Timer 1 n.o.
Out Timer 1 n.c.
Out Timer 2 n.o.
Out Timer 2 n.c.
Start
Stop
Incremental
Decremental
Disable
Visualized
Modifiable
Disable
Visualized
Modifiable
Disable
Enable
P-24 Potent. tarature
P-20 Lower limit Set 1
P-21 Upper limit Set 1
P-22 Lower limit Set 2
P-23 Upper limit Set 2
Disable
Reset
Disable
Wait
Hold
Potent. To SET1
Potent. To SET2
Function of Input 1
Function of key
Function Input 2
Function Input 3
Format of counting
Visualization of Set 1
Format of counting
Visualization of Set 2
Setting of output Q1
Setting of output Q2
Counting mode
Disabled
Start / Stop
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
Seconds, Hundredths
Seconds, Tenths
Seconds
Minutes, Seconds
Hours, Minutes
Seconds, Hundredths
Seconds, Tenths
Seconds
Minutes, Seconds
Hours, Minutes
Disabled
Start / Stop
Start / Stop-Reset
Reset-Start / Stop
Reset / Start / Stop
Reset
Wait (stop the counting)
Hold (hold value on display but counting goes on)
Disabled
Output Timer 1 N.O.
Output Timer 1 N.C.
OutputTimer 2 N.O.
Output Timer 2 N.C.
Start
Stop
Disabled
Output Timer 1 N.O.
Output Timer 1 N.C.
Output Timer 2 N.O.
Output Timer 2 N.C.
Start
Stop
Incremental
Decremental
Disabled
Visualized
Visualized and modifiable
Disabled
Visualized
Visualized and modifiable
Disabledd
Enabled
Calibration of potentiometer
Low limit Set 1
Upper limit Set 1
Low limit Set 2
Upper limit Set 2
Reset
Disabledd
Wait (stop the counting)
Hold (Hold value on display but counting goes on)
Modify SET1 by potentiometer
Modify SET2 by potentiometer
Disabled
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
Default
0.0
0.0
99.9
99.9
Default
PRESS
for 3 seconds
Display 1shows
and 1st digit flashes,
Display 2 shows
EFFECT
OPERATION
O
Modify the flashing digit,
press to reach the next digit
Enter password
to confirm
The device loads default values
(factory settings)
Switch-off and restart
the device
1
2
3
Scroll the parameters
4
Or
Increade or decrease value on display
by pressing and one of the arrow keys
at same time
Enter new data
which will be stored
releasing the keys
5
+ Or
End of configuration,
the device exits programming mode.
6
MODIFY PARAMETERS
LOADING DEFAULT SETTINGS
PRESS
Display SETPOINT 1 / 2
EFFECT
OR
Modify selected SETPOINT
Select the chosen digit
1
2
2a
Modify the flashing digit of the selected setpoint
3a
O
MODIFY SETPOINT