Pixsys ATR243 User Manual

Page 1
ATR243
Controller / Regolatore
User manual / Manuale d’uso
Page 2
Page 3
ATR243 - User manual - 3
Table of contents
1 Safety guide lines ......................................................................................................................................5
3.1 General data .....................................................................................................................................5
3.2 Hardware data .................................................................................................................................6
3.3 Software data ................................................................................................................................... 6
4.1 Panel Assembly ................................................................................................................................8
4.2 Electronics Removal ........................................................................................................................8
5.1 Wiring diagram ................................................................................................................................9
6 Display and Key Functions .................................................................................................................... 15
6.1 Numeric Indicators (Display) ......................................................................................................15
6.2 Meaning of Status Lights (Led)...................................................................................................15
6.3 Keys ....................................................................................................................................................16
7 Controller Functions ...............................................................................................................................16
7.1 Modifying Main Setpoint and Alarm Setpoint Values ......................................................... 16
7.2 Auto-Tuning ....................................................................................................................................16
7.3 Manual Tuning ...............................................................................................................................16
7.4 Automatic Tuning ..........................................................................................................................17
7.5 Soft-Start ..........................................................................................................................................17
7.6 Automatic / Manual Regulation for % Output Control ....................................................... 17
7.7 Pre-Programmed Cycle ................................................................................................................18
7.8 Memory Card (optional) .............................................................................................................. 19
7.9 Latch-on function......................................................................................................................... 20
7.10 Loop Break Alarm On Current Trasformer ..............................................................................21
7.11 Digital Input Functions ............................................................................................................... 22
7.12 Dual Action Heating-Cooling ................................................................................................... 23
8 Serial Communication ...........................................................................................................................24
9 Enter configuration ................................................................................................................................ 29
9.1 Loading default values................................................................................................................ 29
10 Table of Configuration Parameters ................................................................................................... 30
11 Alarm Intervention Modes ....................................................................................................................42
12 Table of Anomaly Signals ......................................................................................................................45
13 Configuration EASY-UP ........................................................................................................................ 46
Page 4
4 - ATR243 - Manuale d’uso
Sommario
1 Norme di sicurezza .................................................................................................................................50
2 Identificazione del modello ..................................................................................................................50
3 Dati tecnici ................................................................................................................................................51
3.1 Caratteristiche generali ...............................................................................................................51
3.2 Caratteristiche Hardware ............................................................................................................51
3.3 Caratteristiche Software..............................................................................................................52
4 Dimensioni ed installazione .................................................................................................................52
4.1 Montaggio a pannello .................................................................................................................53
4.2 Estrazione dell’elettronica ..........................................................................................................53
5 Collegamenti elettrici............................................................................................................................ 54
5.1 Schema di collegamento ............................................................................................................ 54
6 Funzione dei visualizzatori e tasti ...................................................................................................... 60
6.1 Indicatori numerici (Display) .................................................................................................... 60
6.2 Significato delle spie di stato (Led) .......................................................................................... 60
6.3 Tasti ...................................................................................................................................................61
7 Funzioni del regolatore..........................................................................................................................61
7.1 Modifica valore setpoint principale e setpoint di allarme ..................................................61
7.2 Auto-Tuning ....................................................................................................................................61
7.3 Lancio del Tuning Manuale ........................................................................................................61
7.4 Lancio del Tuning Automatico .................................................................................................. 62
7.5 Soft-Start ......................................................................................................................................... 62
7.6 Regolazione automatico / manuale per controllo % uscita ............................................. 62
7.7 Ciclo pre-programmato ...............................................................................................................63
7.8 Memory Card (opzionale) .......................................................................................................... 64
7.9 Funzione Latch on .........................................................................................................................65
7.10 Loop Break Alarm da ingresso T.A. (Trasformatore Amp.) ................................................ 66
7.11 Funzioni da Ingresso digitale .................................................................................................... 66
7.12 Funzionamento in doppia azione (caldo / freddo) ..............................................................67
8 Comunicazione Seriale ..........................................................................................................................69
9 Accesso alla configurazione ................................................................................................................ 73
9.1 Caricamento valori di default ................................................................................................... 73
10 Tabella parametri di configurazione .................................................................................................74
11 Modi d’intervento allarme ....................................................................................................................87
12 Tabella segnalazioni anomalie .......................................................................................................... 90
13 Configurazione EASY-UP ...................................................................................................................... 90
Page 5
ATR243 - User manual - 5
Introduction
Thank you for choosing a Pixsys controller. With ATR243 model Pixsys integrates in a single device all options for sensor reading and actuators command, beside extended supply range 24…230 Vac/Vdc. With 18 selectable sensors and outputs configurable as relay, SSR command, 4…20 mA and 0…10 Volt the user or retailer can reduce stock needs. The series includes also a model with serial communication RS485 Modbus RTU and with a loading control function via current transformer. The possibility to repeat parametriza­tion is simplified by the Memory Cards with internal battery that do not require power supply for the controller.
1 Safety guide lines
Read carefully the safety guidelines and programming instructions contained in this manual before using/connecting the device. Disconnect power supply before proceeding to hardware settings or electrical wirings. Only qualified personnel should be allowed to use the device and/or service it and in accordance to technical data and environmental conditions listed in this manual. Do not dispose electric tools together with household waste material. In observance European Directive 2002/96/EC on waste electrical and electronic equipment and its implementation in accordance with national law, electric tools that have reached the end of their life must be collected separately and returned to an environmentally compatible recycling facility.
2 Model identification
ATR243 series includes three versions. Looking at the table here below it is possible to find the required model.
Power supply 24…230 Vac/Vdc +/-15% 50/60 Hz – 5,5 VA ATR243-20ABC 2 relays 5 A or 1 relay + 1 Ssr/V/mA
ATR243-21ABC-T 2 relays 5 A + 1 Ssr/V/mA + RS485 + current transformer* ATR243-31ABC 3 relays 5 A + 1 Ssr/V/mA + current transformer*
* Models with current transformer input for “Loop Break Alarm” function.
3 Technical Data
3.1 General data
Indicators
4x0.40 inch displays
4x0.30 inch displays Operating temperature
Temperature 0-45 °C
Humidity 35..95 uR%
Sealing
IP65 front panel (with gasket)
IP20 box and terminals Material PC ABS UL94VO self-extinguishing Weight 165 g (-20ABC) / 185 g (-21/31ABC)
Page 6
6 - ATR243 - User manual
3.2 Hardware data
Power supply
Extended range 24..230 Vac/Vdc ±15% 50/60 Hz
Consumption: 5.5 VA.
Analogue imput
1: AN1 configurable via software. Input: Thermocouple type K, S, R,
J. Automatic compensation of cold junction from 0°C to 50°C. Thermoresistance: PT100, PT500, PT1000, Ni100, PTC1K, NTC10K (β 3435K). Linear: 0-10 V, 0-20 or 4-20 mA, 0-40 mV. Current transformer: 50 mA, 1024 points on version ATR243-21/31. Potentiometers: 6 KΩ, 150 KΩ.
Tolerance (25 °C) +/-0.2% ±1 digit for thermocouple input, thermo resistance and V / mA. Cold junction accuracy 0.1 °C/°C.
Impedance: 0-10 V: Ri>110 KΩ 0-20 mA: Ri<5 Ω 4-20 mA: Ri<5 Ω 0-40 mV: Ri>1 MΩ
Relay output
2 Relays (ATR243-20..21...). 3 Relays (ATR243-31..). Configurable as command and / or alarm output.
Contacts 5 A - 250 V~. Resistive load.
SSR/V/mA output
1 SSR Linear 0/4…20mA or
0..10 Volt. Deselecting OUT2 relay on ATR243-20... Configurable as command output or retransmission of setpoint or process.
12V / 30mA (min. 10.5 V DC).
Configurable: 0-10 V with 9500 points +/-0.2% (F.s.) 0-20 mA with 7500 points +/-0.2% (F.s.) 4-20 mA with 6000 points +/-0.2% (F.s.)
3.3 Software data
Regulation algorithms
ON - OFF with hysteresis. P, P.I., P.I.D., P.D. with proportional time.
Proportional band
0...9999 °C or °F
Integral time 0,0...999,9 sec. (0 excludes integral function)
Derivative time 0,0...999,9 sec. (0 excludes derivative function)
Controller functions
Manual or automatic Tuning, configurable alarms, protection of command and alarm setpoints, activation of functions via digital input, preset cycle with Start / Stop.
Page 7
ATR243 - User manual - 7
4 Dimensions and Installation
CN1
1 6
MEMORY C.241
15
1116
234
12131415
1 6
Memory Card
12
3
4
5
11 13 14 15 1612
6 7 8 9 10
CN1
1 6
PIXSYS
DIMA DI
FORATURA
FRONTAL PANEL
CUT-OUT
46 X 46 mm
48 mm
48 mm 125 mm10
Suggested thickness / Spessore suggerito 2 ÷ 6 mm
Memory Card (option)
with battery / con batteria
2100.30.003
Memory Card (option)
2100.30.002
Insert / Inserimento Memory Card 42 mm
Page 8
8 - ATR243 - User manual
4.1 Panel Assembly
1
1
2
2
Method of panel assembly and fi xing of anchorage hooks.
1
2
To dismantle, use a screwdriver and slightly force the fi xing hooks to remove them from the fi xing guide.
4.2 Electronics Removal
To remove the electronics, grip the front part using the two specifi c side ridges.
1
1
2
Disconnect the device from the mains before starting to confi gurate or service it.
Page 9
ATR243 - User manual - 9
5 Electrical wirings
Although this controller has been designed to resist noises in an industrial environment, please notice the following safety guidelines:
• Separate control lines from the power wires.
• Avoid the proximity of remote control switches, electromagnetic meters, powerful engines.
• Avoid the proximity of power groups, especially those with phase control.
5.1 Wiring diagram
ATR243-20ABC
ATR243-21ABC-T ATR243-31ABC
V/I
5.1.a Power
10
24...230V AC/DC
SUPPLY
9
Switching power supply with extended range 24…230 Vac/ dc ±15% 50/60 Hz – 5,5 VA (with galvanic isolation).
Page 10
10 - ATR243 - User manual
5.1.b AN1 Analogue Input
For thermocouples K, S, R, J.
• Comply with polarity.
• For possible extensions, use a compensated wire and terminals suitable for the thermocouples used (compensated).
• When shielded cable is used, it should be grounded at one side only.
Rosso Red
Bianco White
Rosso Red
For thermoresistances PT100, NI100.
• For the three-wire connection use wires with the same section.
• For the two-wire connection short-circuit terminals 1 and 3.
• When shielded cable is used, it should be grounded at one side only.
• Select internal jumper JP3 as in the fi gure.
For thermoresistances NTC, PTC, PT500, PT1000 e poten­tiometers.
When shielded cable is used, it should be grounded at one side only to avoid ground loop currents.
For linear signals V / mA.
• Comply with polarity.
• When shielded cable is used, it should be grounded at one side only.
• Select internal jumper JP3 as in the fi gure.
If jumpers are not properly selected, 12 Vdc / 30 mA are not available on terminal 3 to power the sensor.
Page 11
ATR243 - User manual - 11
5.1.c Example of Connection for linear input Volt and mA
+12 V
30 mA
For signals 0….10 V.
Comply with polarity.
+12 V
30 mA
For signals 0/4….20 mA with three-wire sensor.
Comply with polarity: A= Sensor output B= Sensor ground C= Sensor power (+12Vdc / 30mA)
For signals 0/4….20 mA with external power of sensor.
Comply with polarity: A= Sensor output B= Sensor ground
+12 V
30 mA
For signals 0/4….20 mA with two-wire sensor.
Comply with polarity: A= Sensor output C= Sensor power supply (+12Vdc / 30mA)
5.1.d Serial Input
RS485 Modbus RTU communication.
5.1.e Relay Q1 Output
Capacity 5 A / 250 V~ for resistive loads.
NB: see graphic next page.
Page 12
12 - ATR243 - User manual
5.1.f Relay Q2 output for ATR243-20ABC
Capacity 5 A / 250 V~ for resistive loads. To select Q2 as relay output, verify that jumpers JP5 and JP7 are not inserted.
NB: see graphic next page.
Connecting a load without removing the jumpers will permanently damage the controller.
5.1.g Relay Q2 output for ATR243-21ABC and 31ABC
Capacity 5 A / 250 V~ for resistive loads.
NB: see graphic.
5.1.h Relay Q3 output for ATR243-31ABC
Q3 Relay Output on ATR243-31ABC.
NB: see graphic.
Electrical endurance Q1 / Q2 / Q3:
5 A, 250 Vac, resistive loads, 10
5
operations.
20/2 A, 250 Vac, cosφ = 0.3, 10
5
operations.
Page 13
ATR243 - User manual - 13
5.1.i SSR output
SSR/ V/mA
5
+
4
-
SSR command output 12 V / 30 mA (min. 10.5 V DC).
Insert JP5 and JP7 and select JP9 as in the fi gure to use the SSR output.
5.1.j mA / Volt output
SSR/V/mA
5
+
4
-
Linear output in mA confi gurable using parameters as command (parameter
c.out
) or retransmission of
process-setpoint (parameter
rE t r.
).
Insert JP5 and JP7 and select JP9 as in fi gure to use the output in mA.
SSR/V/mA
5
+
4
-
Linear output in Volt confi gurable using parameters as command (parameter
c.out
) or retransmission of
process-setpoint (parameter
rE t r.
).
Insert JP5 and JP7 and select JP9 as in fi gure to use the linear output in Volt.
Page 14
14 - ATR243 - User manual
5.1.k Current Transformer Input on ATR243-21ABC-T and ATR243-31ABC
TA
16
15
• Input 50 mA for current transformer.
• Sampling time 80 ms.
• Confi gurable by parameters.
Insert JP4 and JP6 as in fi gure to select the amperometric transformer input.
5.1.l Digital Input on ATR243-20ABC
3
2ID
+12V
Digital input using parameter
d G ti
. The use of digital input in this version is possible only with TC sensors, 0…10 V, 0/4…20 mA and 0…40 mV.
Select internal jumper JP3 as in fi gure.
5.1.m Digital Input on ATR243-21ABC-T and ATR243-31ABC
16
15ID
+12V
Digital input using parameter
d G ti
.
Insert JP4 as in fi gure to select the digital input.
Page 15
ATR243 - User manual - 15
6 Display and Key Functions
A1
C2
C1
ATR243
PIXSYS
A2
1
3
4
8 9
10
5
6
7
2
6.1 Numeric Indicators (Display)
1
1234
Normally displays the process. During the configuration phase, it displays the parameter being inserted.
2
1234
Normally displays the setpoint. During the configuration phase, it displays the parameter value being inserted.
6.2 Meaning of Status Lights (Led)
3 C1 C2
ON when the output command is on. C1 with relay/SSR/mA/Volt command or C1 (open) and C2 (close) for a motorised valve command.
4 A1 A2 A3 ON when the corresponding alarm is on.
5 MAN
ON when the “Manual” function is on.
6 TUN
ON when the controller is running an “Autotune” cycle.
7 REM ON when the controller communicates via serial port.
Page 16
16 - ATR243 - User manual
6.3 Keys
8
• Allows to increase the main setpoint.
• During the configuration phase, allows to slide through parameters. Together with the
SET
key it modifies them.
• Pressed after the
SET
key it allows to increase the alarm setpoint.
9
• Allows to decrease the main setpoint.
• During the configuration phase, allows to slide through parameters. Together with the
SET
key it modifies them.
• Pressed after the
SET
key it allows to decrease the alarm setpoint.
10
SET
• Allows to display the alarm setpoint and runs the autotuning function.
• Allows to vary the configuration parameters.
7 Controller Functions
7.1 Modifying Main Setpoint and Alarm Setpoint Values
The setpoint value can be changed by keyboard as follows:
Press Display Do
1
or
Value on display 2 changes.
Increases or decreases the main setpoint.
2
SET
Visualize alarm setpoint on display 1 value being inserted.
3
or
Value on display 2 changes.
Increases or decreases the alarm setpoint value.
7. 2 Auto-Tuning
Tuning procedure calculates the controller parameters and can be manual or automatic according to selection on parameter 57 (
tunE
).
7. 3 Manual Tuning
Manual procedure allows the user greater flexibility to decide when to update P.I.D. algorithm work parameters. The procedure can be activated in two ways.
• Running Tuning by keyboard: Press
SET
key until display 1 shows the writing
tunE
with display 2 showing
off
, press
, display 2 shows on.
TUN led switches on and the procedure begins.
• Running Tuning by digital input: Select
tune
on parameter 61
d Gt .i .
At first activation of digital input (commutation on
front panel) TUN led switches on and at second activation switches off.
Page 17
ATR243 - User manual - 17
7.4 Automatic Tuning
Automatic tuning activates when the controller is switched on or when the setpoint is modified to a value over 35%. To avoid an overshoot, the treshold where the controller calculates new P.I.D. parameters is determined by the setpoint value minus the “Set Deviation Tune” (see parameter 58
S.D. t u .
).
To exit Tuning and keep P.I.D. values unchanged, press
SET
key until display 1 shows the
writing
tune
and display 2 shows on. Press , display 2 shows
off
.
TUN
led switches off
and procedure finishes.
7. 5 Soft-Start
To reach the setpoint the controller can follow a gradient expressed in units (example: Degree/Hours). Enter the gradient on parameter 62
GrA d .
with chosen Units/Hours; only on subsequent activation the controller uses Soft-Start function. If parameter 59
op.mo.
is set on
co n t.
and parameter 63
m a . ti .
is different from 0, after switch-on and elapsing of the time set on parameter 63, setpoint does not follow the gradient anymore, but it reaches final setpoint with maximum power. Autotuning does not work when only the par.
GrA d .
is different from 0. If parameter 63
m a . ti .
is different from 0 and parameter 57
tune
is set on
Auto
the autotuning starts
when Soft-Start time is finished, while if parameter 57
tune
is set on
Man.
the autotuning
can be started only when Soft-Start finishes.
7.6 Automatic / Manual Regulation for % Output Control
This function allows to select automatic functioning or manual command of the output percentage. With parameter 60
Au.ma.
the operator can select two methods:
1 First selection (
en.
)
Pressing
SET
key display 1 shows
p.---
, while display 2 shows
Auto
.
Pressing
key display shows
Man.
; it is now possible to change the output percentage
using
and . To return to automatic mode, using the same procedure, select
Auto
on display 2: led MAN switches off and functioning returns to automatic mode.
2 Second selection (
EN.ST,
)
enables the same functioning, but with two important variants:
• If there is a temporary power failure or after switch-off, the manual functioning as well
as the previous output percentage value will be maintained at restarting.
• If the sensor breaks during automatic functioning, the controller moves to manual
mode while maintaining the output percentage command unchanged as generated by the P.I.D. immediately before breakage.
Page 18
18 - ATR243 - User manual
7.7 Pre-Programmed Cycle
The pre-programmed cycle function activates by setting
Pr. c y
or
Pc.SS.
on parameter 59
oP.Mo
.
Setpoint
Setpoint 2
Max. power
Setpoint 1
Hold
Natural cooling
Time
Gradient
First selection (
Pr. c y
): the controller reaches setpoint1 basing on the gradient set on parameter 62
Grad .
, then it reaches maximum power up to setpoint 2. When the process reaches maximum power, this setpoint is maintained for the time set on parameter 63
m a . ti .
On expiry, the command output is disabled and controller displays
stop
. Cycle starts at each activation of the controller, or via digital input if it is enabled for this type of functioning (see parameter 61
d Gt .i .
).
Setpoint
Setpoint 1
Hold
Natural cooling
Time
Gradient
Second selection (
Pr. c y
): start-up is decided only on activation of the digital input, according to the setting of parameter 61
d Gt .i .
On start-up, controller reaches setpoint 1 following gradient set in parameter 62
Grad .
When the process reaches this gradient, it is maintained for the time set on parameter 63
m a . ti .
On expiry, command output is
disabled and the controller displays
stop
.
Variation (
S.S. cY.
):
Selecting
S.S. cY.
(Soft Start Cycle) the controller will operate as per the fi rst selection (
Pr.
cy
) but with two important variations. If at starting the process is lower than SET1, the device regulates the output power according to the percentage selected on parameter 62
GrA d
.
When the process is greater than SET1 or the time selected on parameter 63
M A . ti .
is elapsed, it reaches maximum power up to SET2. When the process reaches SET2 the controller keeps it to infi nity. If parameter 59
oP.Mo.
is confi gured as
S.S. cY.
it is possible to select
Hi d E
on parameter 17
c. S.P.
: SET1 is no longer displayed and SET2 label becomes SET. Starting the manual tune during the regulation on SET1, TUN led switches ON only when the regulation switches to SET2. The autotuning (manual or automatic) works only if SET2 is being regulated. If the autotuning is launched during regulation on SET1 it doesn’t start until the regulation switches to SET2.
Page 19
ATR243 - User manual - 19
7.8 Memory Card (optional)
Parameters and setpoint values can be duplicated from one controller to another using the Memory card. 2 modes are available:
• With the controller connected to the power supply. Insert memory card when the controller is off. On activation display 1 shows
memo
and display 2 shows
---
(only if the correct
values are saved in the memory card). By pressing
key display 2 shows
Lo a d
, then
confirm using
SET
key.
Controller loads the new value and restarts.
U1
CN1
C1
MEMORY C241
LED ROSSO: acceso in programmazione
Red Light: waiting for programming
LED VERDE: programmazione eseguita
Green Light: done
With the controller not connected to power supply. The memory card is equipped with an internal battery with an autonomy of about
1000 uses (2032 button battery, replaceable). Insert the memory card and press the programming buttons. When writing the parameters, led turns red and on completing the procedure it changes to green. It is possible to repeat the procedure without any particular attention.
NB: it is not possible to transfer parameters to a device with different code: red LED is ON.
Page 20
20 - ATR243 - User manual
Updating Memory Card
To update the memory card values, follow the procedure described on first mode, setting display 2 to
----
so as not to load the parameters on controller1. Enter configuration and change at least one parameter. Exit configuration. Changes are stored automatically.
7.9 Latch-on function
For use with input
P o t .1
(potentiometer 6 KΩ) and
Po t.2
(potentiometer 150 KΩ) and with linear input (0…10 V, 0...40 mV, 0/4…20 mA), it is possible to associate start value of the scale (parameter 6
Lo L.i
) to the minimum position of the sensor and value of end scale
(parameter 7
u P.L.i
) to the maximum position of the sensor (parameter 8
La t c.
configured
as
Std .
). It is also possible to fix the point in which the controller will display 0 (however keeping the scale range between
Lo L.i
and
u P.L.i
) using the “virtual zero” option by setting
u .OSt.
or
u.Oin.
in parameter 8
La t c
.
If you set
u.Oin.
the virtual zero will reset after each activation of the tool; if you set
u .OSt.
the virtual zero remains fixed once tuned. Selecting “
dYn.L
” (dynamic limits) it is possible to surpass lower and upper limits if on input there are values out of 0/4…20mA or 0…10V . To enable the LATCH ON function select chosen configuration for parameter
LA t c
2
.
For the calibration procedure refer to the following table:
Press Display Do
1
+
simultaneously
Exit parameters configura­tion. Display 2 shows the writing
LA t c
.
Place the sensor on minimum operating value (associated with
Lo L.i .
).
2
Set the value on minimum. Display shows
Lo w
.
Place the sensor on maximum operating value (associated with
u p L.i .
).
3
Set the value to maximum. The display shows
Hi G H
.
To exit standard procedure press
SET
. For “virtual zero” settings place the sensor on the zero point.
4
SET
Set the virtual zero value. Display shows
ui r t
.
NB: For selection of
u.0in.
the procedure in point 4 should be followed on each re-activation.
To exit procedure press
SET
.
1
If on activation the controller does not display memo it means no data have been saved on the memory card, but it is possible to update values.
2
The tuning procedure starts by exiting the configuration after changing the parameter.
Page 21
ATR243 - User manual - 21
Max
Min Zero
7.10 Loop Break Alarm On Current Trasformer
This function allows to measure load current and to manage an alarm during malfunctio­ning (with power in short circuit or always off ). The current transformer connected to terminals 15 and 16 must be 50 mA (sampling time 80 ms).
• Set end scale value of the current transformer in Amperes on parameter 47
t.a .
• Set the intervention threshold of the Loop Break Alarm in Amperes on parameter 48
L.b.a.t.
• Set the intervention delay time of the Loop Break Alarm on parameter 49
L.b.a.d.
• It is possible to associate the alarm with a relay by setting the parameter
AL. 1, AL. 2
or
AL. 3
as
AL. 4.
If a remote control switch or SSR remains closed, controller signals the fault by showing
L.b.a.c.
on display 2 (alternatively with a command setpoint).
If the power stage remains open, or the load current is lower than the value set on
L.b.a.t.
,
controller shows
L.b.a.o.
on display. It is possible to display the current absorbed during
the closure phase of the power stage.
Press Display Do
1
SET
This key enables to scroll on display 2 the output percentage, auto / man selection, setpoint and alarms.
Press
SET
until the writing
am.t.a.
appears on display 1 and display 2 shows the current in amperes (
t. a .
>0). The value is also maintained when no current circulates on the load.
Setting on parameter 48
L.b.A.t.
the value 0 it is possible to visualize the current absorbed
without generating the Loop Break Alarm.
Page 22
22 - ATR243 - User manual
7.11 Digital Input Functions
On ATR243 model digital input can be enabled by using parameters 59
op.mo.
and 61
d Gt .i .
• Parameter 59
op.mo.
NB: When using this settings, parameter 61
d Gt .i .
is ignored.
2t.s.
: Switch two thresholds setpoint: with open contact ATR243 regulates on SET1;
with closed contact regulates on SET2;
2 t . s .i .
: Switch two thresholds setpoint: setpoint selection is done by an impulse on
digital input;
3 t. s .i .
: Switch three thresholds setpoint by an impulse on digital input;
4 t. s .i
: Switch four thresholds setpoint by an impulse on digital input;
t. res .
: Customized function;
p.c.s.s.
: Pre-programmed cycle (see paragraph 7.7).
Setpoints values can be modified any time pressing
SET
key.
• Parameter 61
d Gt .i .
NB: Settings on this parameter are available only if
co n t.
or
p r. cY.
are selected on
parameter 59
op.mo.
st.s t.
: Start / Stop; operating on digital input the controller switches alternatively from
start to stop;
rn.n.o.
: Run N.O. Controller is in start only with closed input;
rn.n.c.
: Run N.C. Controller is in start only with open input;
L.c.n.o.
: With closed input allows to lock the reading of sensors;
Lc.n . c.
: With open input allows to lock the reading of sensors;
tune
: Enables / disables Tuning function if parameter 57
tune
is selected as
man.
;
a.ma.i.
: If parameter 60
au.ma.
is selected as
en.
or
en.st.
controller switch from
automatic to manual functioning;
a.ma.c.
: If parameter 60
au.ma.
is selected as
en.
or
en.st.
ATR243 works in automatic
mode if input is open or in manual mode if input is closed.
NB: The digital input functions are not available with sensors PT100 and NI100 on model ATR243-20ABC.
Page 23
ATR243 - User manual - 23
7.12 Dual Action Heating-Cooling
ATR243 is suitable also for systems requiring a combined heating-cooling action. Command output must be configured as Heating P.I.D. (
Act.t.
=
HEAT
and with a
P. b .
greater than 0), and one of the alarms (
A L .1, AL. 2
or
AL. 3
) must be configured as
co o L.
Command output must be connected to the actuator responsible for heat, while the alarm will control cooling action. Parameters to configure for the Heating P.I.D. are:
Act.t.
=
HEAT
Command output type (Heating);
P. b .
: Heating proportional band;
t.i
: Integral time heating and cooling;
t.d .
: Derivative time heating and cooling;
t. c.
: Heating time cycle. Parameters to configure for the Cooling P.I.D. are the following (ex: action associated to alarm 1):
A L .1
=
cooL
Alarm 1 selection (Cooling);
P. b . M.
: Proportional band multiplier;
ou.d.b.
: Overlapping / Dead band;
co.t.c.
: Cooling time cycle.
Parameter
p.b.m.
(that ranges from 1.00 to 5.00) determines the proportional band of cooling basing on the formula: Cooling proportional band =
P. b .
x
P. b . M.
This gives a proportional band for cooling which will be the same as heating band if
P. b . M.
= 1.00, or 5 times greater if
P. b . M.
= 5.00. Integral and derivative time are the same for both actions. Parameter
ou.d.b.
determines the percentage overlapping between the two actions. For systems in which the heating and cooling output must never be simultaneously active a dead band (
ou.d.b.
≤ 0) can be configured, and vice versa an overlapping (
ou.d.b.
> 0).
The following figure shows an example of dual action P.I.D. (heating-cooling) with
t.i .
=
0 and
t.d .
= 0.
1
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 < 0
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
Page 24
24 - ATR243 - User manual
2
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 x  = COOL
 < 0
 = 0
 (HEAT)
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
3
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 x  = COOL
 x  = COOL
 < 0
 = 0
 > 0
 (HEAT)
 (HEAT)
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
Parameter
co.t.c.
has the same meaning as the heating time cycle
t. c.
Parameter
co o . f.
(cooling fluid) pre-selects the proportional band multiplier
P. b . M.
and
the cooling P.I.D. time cycle
co.t.c.
basing on the type of cooling fluid:
c o o . F.
Cooling fluid type
P. b . M. co.t.c
Ai r
Air 1.00 10
oi L
Oil 1.25 4
H2o
Water 2.50 2
Once selected, parameter
co o . f.
, parameters
P. b . M., oud.b.
and
co.t.c.
can however be
changed.
8 Serial Communication
ATR243-21ABC-T, equipped with RS485, can receive and broadcast data via serial communication using MODBUS RTU protocol. The device can only be configured as a Slave. This function enables the control of multiple controllers connected to a supervisory system (SCADA). Each controller responds to a master query only if the query contains the same address as that in the parameter
SL. A d .
The permitted addresses range from 1 to 254 and there must not be controllers with the same address on the same line. Address 255 can be used by the master to communicate with all the connected equipment (broadcast mode), while with 0 all the devices receive the command, but no response is expected. ATR243 can introduce a delay (in milliseconds) in the response to the master request. This delay must be set on parameter 72
se. d e.
Each parameter change is saved by the controller on EEPROM memory (100000 writing cycles), while the setpoints are saved with a delay of ten seconds after the last change. NB: changes made to Words that are different from those reported in the following table can lead to malfunction.
Page 25
ATR243 - User manual - 25
Modbus RTU protocol features
Baud-rate
Selection on parameter 70
bd. rt.
:
4.8 k
4.800 bit/Sec.
9.6 k
9.600 bit/Sec.
19.2k
19.200 bit/Sec.
28.8 k
28.800 bit/Sec.
38 .4 k
38.400 bit/Sec.
57.6 k
57.600 bit/Sec.
Format 8, N, 1 (8 bit, no parity, 1 stop)
Supported functions
WORD READING (max 20 word) (0x03, 0x04) SINGLE WORD WRITING (0x06) MULTIPLE WORDS WRITING (max 20 word) (0x10)
Looking at the table here below it is possible to find all available addresses and functions:
RO Read Only R/W Read / Write WO Write Only
Modbus Address
Description Read Only
Reset value
0 Device type RO EEPROM 1 Software version RO EEPROM 5 Slave address R/W EEPROM
6 Boot version RO EEPROM 50 Automatic addressing WO ­51 System code comparison WO -
500 Loading default values (write 9999) R/W 0 510 Setpoints storing time in eeprom (0-60 s) R/W 10
999 Process subjected to the visualization filter RO -
1000
Process (degrees.tenths for temperature sensors; digits for linear sensors)
RO -
1001 Setpoint 1 R/W EEPROM 1002 Setpoint 2 R/W EEPROM 1003 Setpoint 3 R/W EEPROM 1004 Setpoint 4 R/W EEPROM 1005 Alarm 1 R/W EEPROM 1006 Alarm 2 R/W EEPROM 1007 Alarm 3 R/W EEPROM 1008 Setpoint gradient RO EEPROM
1009
Relay status (0 = Off, 1 = On): Bit 0 = Relay Q1 Bit 1 = Relay Q2 Bit 2 = Reserved Bit 3 = SSR
RO 0
1010 Heating output percentage (0-10000) RO 0
Page 26
26 - ATR243 - User manual
Modbus Address
Description Read Only
Reset value
1011 Cooling output percentage (0-10000) RO 0
1012
Alarms status (0 = None, 1 = Active) Bit 0 = Alarm 1 Bit 1 = Alarm 2 Bit 2 = Alarm 3
RO 0
1013
Manual reset: write 0 to reset all alarms. In reading (0 = Not resettable, 1 = Resettable) Bit 0 = Alarm 1 Bit 1 = Alarm 2 Bit 2 = Alarm 3
WO 0
1014
Error flags Bit 0 = Eeprom writing error Bit 1 = Eeprom reading error Bit 2 = Cold junction error Bit 3 = Process error (sensor) Bit 4 = Generic error Bit 5 = Hardware error Bit 6 = L.B.A.O. error Bit 7 = L.B.A.C. error Bit 8 = Missing calibration data error
RO 0
1015 Cold junction temperature (degrees.tenths) RO -
1016
Start / Stop 0 = Controller in STOP 1 = Controller in START
R/W 0
1017
Lock conversion ON / OFF 0 = Lock conversion off 1 = Lock conversion on
R/W 0
1018
Tuning ON / OFF 0 = Tuning off 1 = Tuning on
R/W 0
1019
Automatic / manual selection 0 = Automatic 1 = Manual
R/W 0
1020 T.A. current ON (Ampere with tenths) RO ­1021 T.A. current OFF (Ampere with tenths) RO 1022 OFF LINE* time (milliseconds) R/W 1023 Instant Current (Ampere) R/W 0 1024 Digital Input State R/W 0
1025
Synchronized Tuning for multizone system 0 = Tuning OFF (Normal operating of the regulator) 1 = Output command OFF 2 = Output command ON 3 = Start Tuning 4 = End Tuning and output command OFF (Write
0 for normal operating)
R/W 0
1099
Process subjected to the visualization filter and decimal point selection
RO
1100 Process with decimal point selection RO 1101 Setpoint 1 with decimal point selection R/W EEPROM
Page 27
ATR243 - User manual - 27
Modbus Address
Description Read Only
Reset value
1102 Setpoint 2 with decimal point selection R/W EEPROM 1103 Setpoint 3 with decimal point selection R/W EEPROM 1104 Setpoint 4 with decimal point selection R/W EEPROM 1105 Alarm 1 with decimal point selection R/W EEPROM 1106 Alarm 2 with decimal point selection R/W EEPROM 1107 Alarm 3 with decimal point selection R/W EEPROM 1108 Gradient Setpoint with decimal point selection RO EEPROM 1109 Percentage heating output (0-1000) R/W 0
1110 Percentage heating output (0-100) RO 0 1111 Percentage cooling output (0-1000) RO 0
1112 Percentage cooling output (0-100) RO 0 2001 Parameter 1 R/W EEPROM 2002 Parameter 2 R/W EEPROM 2072 Parameter 72 R/W EEPROM 3000 Disabling serial control of machine** RO 0 3001 First word display 1 (ascii) R/W 0 3002 Second word display 1 (ascii) R/W 0 3003 Third word display 1 (ascii) R/W 0 3004 Fourth word display 1 (ascii) R/W 0 3005 Fifth word display 1 (ascii) R/W 0 3006 Sixth word display 1 (ascii) R/W 0 3007 Seventh word display 1 (ascii) R/W 0 3008 Eighth word display 1 (ascii) R/W 0 3009 First word display 2 (ascii) R/W 0 3010 Second word display 2 (ascii) R/W 0
3011 Third word display 2 (ascii) R/W 0 3012 Fourth word display 2 (ascii) R/W 0 3013 Fifth word display 2 (ascii) R/W 0
3014 Sixth word display 2 (ascii) R/W 0
3015 Seventh word display 2 (ascii) R/W 0
3016 Eight word display 2 (ascii) R/W 0
3017
Word LED Bit 0 = LED C1 Bit 1 = LED C2 Bit 2 = LED A1 Bit 3 = LED A2 Bit 4 = LED A3 Bit 5 = LED MAN Bit 6 = LED TUN Bit 7 = LED REM
R/W 0
Page 28
28 - ATR243 - User manual
Modbus Address
Description Read Only
Reset value
3018
Word keys (write 1 to command keys) Bit 0 = Bit 1 = Bit 2 =
SET
R/W 0
3019
Word serial relay Bit 0 = Relay Q1 Bit 1 = Relay Q2 Bit 2 = Relay Q3
R/W 0
3020 Word SSR serial (0 = Off, 1 = On) R/W 0 3021 Word output 0...10 V serial (0…10000) R/W 0 3022 Word output 4...20 mA serial (0…10000) R/W 0
3023
Relay state in case of off-line (only if controlled by serial) Bit 0 = Relay Q1 Bit 1 = Relay Q2 Bit 2 = Relay Q3
R/W 0
3024
Output state SSR / 0…10 V / 4…20 mA in case of off-line (only if controlled by serial) (0…10000)
R/W 0
3025
Serial process. Setting parameter 54 it is possible to make averages on the remote process
R/W 0
4001 Parameter 1*** R/W EEPROM 4002 Parameter 2*** R/W EEPROM 4072 Parameter 72*** R/W EEPROM
* If value is 0, control is disabled. If different from 0, it is the max. time that can elapse between two pollings
before the controller goes off-line. If it goes off-line, the controller returns to Stop mode, control output is disabled but the alarms are active.
** By writing 1 on this word, the effects of the writing are cancelled on all the Modbus addresses from 3001 to
3022. Control therefore returns to the controller.
*** Parameters modified using serial address 4001 to 4072 will be stored on eeprom only after 10” since last
writing of one parameter.
Page 29
ATR243 - User manual - 29
9 Enter configuration
For configuration parameters see paragraph 10.
Press Display Do
1
SET
for 3 seconds
Display 1 shows
0.000
with the 1st digit flashing, while display 2 shows
PASS
.
2
or
Changes flashing digit and move to the next one using
SET
key.
Enter password:
1234
.
3
SET
to confirm
Display 1 shows the first parameter and display 2 shows the value.
4
or
Slide up / down through parameters.
5
SET
or
Increase or decrease displayed value by keep pressing
SET
and after an
arrow key.
Enter new data which will be saved on releasing the keys. To change another parameter return to point 4.
6
+
simultaneously
End of configuration parameter change. The controller exits from programming.
9.1 Loading default values
This procedure allows to restore factory settings of the instrument.
Press Display Do
1
SET
for 3 seconds
Display 1 visualizes
0.000
with 1st digit blinking, while display 2 shows
PASS
.
2
o
Change blinking digit and move to the next one with
SET
.
Enter password:
9999
.
3
SET
to confirm
Device loads default settings.
Turn off and restart the instrument.
Page 30
30 - ATR243 - User manual
10 Table of Configuration Parameters
The following table includes all parameters. Some of them will not be visible on the models which are not provided with relevant Hardware data.
1
C.out
Command Output
Command output type selection (see tables).
c. o1
Default (necessary for using process and setpoint retransmission function with Volt / mA output)
c. o2
Command on relay output Q2
3
c.SSr
Command in tension for SSR
4
c. u A L.
Servo-valve command with open loop
3
c.4 . 2 0
4...20 mA command
4
c.0.20
0...20 mA command
4
c.0.10
0...10 V command
4
ATR243-20ABC
COMMAND ALARM 1
c. o1
Q1 Q2
c. o2
Q2 Q1
c.SSr
SSR Q1
c. u A L.
Q1 (opens) / Q2 (closes) -
c.4 . 2 0
4 ... 20 mA Q1
c.0.20
0 ... 20 mA Q1
c.0.10
0 ... 10 V Q1
ATR243-21ABC-T
COMMAND ALARM 1 ALARM 2
c. o1
Q1 Q2 SSR
c. o2
Q2 Q1 SSR
c.SSr
SSR Q1 Q2
c. u A L.
Q1 (opens) / Q2 (closes) SSR -
c.4 . 2 0
4 ... 20 mA Q1 Q2
c.0.20
0 ... 20 mA Q1 Q2
c.0.10
0 ... 10 V Q1 Q2
ATR243-31ABC
COMMAND ALARM 1 ALARM 2 ALARM 3
c. o1
Q1 Q2 Q3 SSR
c. o2
Q2 Q1 SSR SSR
c.SSr
SSR Q1 Q2 Q3
c. u A L.
Q2 (opens) / Q3 (closes) Q1 SSR -
c.4 . 2 0
4 ... 20 mA Q1 Q2 Q3
c.0.20
0 ... 20 mA Q1 Q2 Q3
c.0.10
0 ... 10 V Q1 Q2 Q3
3
Only on ATR243-20ABC do not select if process retransmission function is used.
4
Do not select if process retransmission function is used.
Page 31
ATR243 - User manual - 31
2
SEN.
Sensor
Analogue input configuration/sensor selection
Tc.K
Tc-K (Default) -260 °C ... 1360 °C
Tc. s
Tc-S -40 °C ... 1760 °C
Tc. r
Tc-R -40 °C ... 1760 °C
Tc. j
Tc-J -200 °C ... 1200 °C
Pt
Pt100 -200 °C ... 600 °C
P t1
Pt100 -200 °C ... 140 °C
ni
NI100 -60 °C ... 180 °C
ntc
NTC10K -40 °C ... 125 °C
Ptc
PTC1K -50 °C ... 150 °C
Pts
Pt500 -100 °C ... 600 °C
P t1 k
Pt1000 -100 °C ... 600 °C
0 .1 0
0 ... 10 Volt
0.20
0 ... 20 mA
4.20
4 ... 20 mA
0.4 0
0 ... 40 mVolt
P o t .1
Potentiometer max 6 Kohm (See paragraph 7.09)
Po t.2
Potentiometer max 150 Kohm (See paragraph 7.09)
t.A.
50 mA secondary Current transformer (Only ATR243-21/31ABC)
3
d . P.
Decimal Point
Select type of visualized decimal point
0
Default
0.0
1 Decimal
0.00
2 Decimal
0.000
3 Decimal
4
Lo .L.S.
Lower Limit Setpoint
Lower limit selectable for setpoint
-999…+9999 [digit
5
] (degrees.tenths for temperature sensors), Default: 0.
5
u p.L.S.
Upper Limit Setpoint
Upper limit selectable for setpoint
-999…+9999 [digit
5
] (degrees.tenths for temperature sensors),
Default: 1750.
6
Lo L.i
Lower Linear Input
Range AN1 lower limit only for linear. Example: with input 4...20 mA this parameter takes value associated to 4 mA
-999 bis +9999 [digit
5
], Default: 0.
7
u p.L.i .
Upper Linear Input
Range AN1 upper limit only for linear. Example: with input 4...20 mA this parameter takes value associated to 20 mA
-999 bis +9999 [digit
5
], Default: 1000.
Page 32
32 - ATR243 - User manual
8
La tc.
Latch On Function
Automatic setting of limits for linear inputs and potentiometers (see paragraph 7.9)
di s .
Disabled (Default)
std.
Standard
u.0s t.
Virtual zero stored
u . 0i n
Virtual zero initialized
dYn.L
Allows to surpass lower and upper limits if on input there are values out of
0/4…20mA or 0…10V.
9
o . cAL.
Offset Calibration
Value added / subtracted to process visualization (usually correcting the value of environment temperature)
-999…+1000 [digit
5
] for linear sensors and potentiometers.
-200.0…+100.0 (degrees.tenths for temperature sensors), Default 0.0.
10
G. cA L.
Gain Calibration
Percentage value that is multiplied for the process value (allows to calibrated the working point)
-9 9.9 %…+10 0. 0% (Default = 0.0) ex: to correct the range from 0...1000°C showing 0...1010°C, set the parameter to -1.0.
11
Act. t.
Action type
Regulation type
Heat
Heating (N.O.) (Default)
cooL
Cooling (N.C.)
H.o.o.S.
Lock command above SPV. Example: command output disabled when
reaching setpoint, also with P.I.D. value different from 0
12
c. re.
Command Reset
Type of reset for state of command contact (always automatic in P.I.D. functioning)
a re.
Automatic reset (Default)
m re.
Manual reset
m re.s.
Manual reset stored (keeps relay status also after an eventual power failure)
13
c. S.e.
Command State Error
State of contact for command output in case of error
c. o.
Open contact (Default)
c. c.
Closed contact
14
c. Ld.
Command Led
State of the OUT1 led corresponding to the relevant contact
c. o.
ON with open contact
c. c.
ON with closed contact (Default)
Page 33
ATR243 - User manual - 33
15
c. HY.
Command Hysteresis
Hysteresis in ON/OFF or dead band in P.I.D.
-999…+999 [digit
5
] (degrees.tenths for temperature sensors), Default 0.0.
16
c. d e.
Command Delay
Command delay (only in ON / OFF functioning). In case of servo valve it also works in P.I.D. and represents the delay between opening and closure of the two contacts
-180…+180 seconds (tenths of second in case of servo valve). Negative: delay in switching off phase. Positive: delay in activation phase.
Default: 0.
17
c. s. p.
Command Setpoint Protection
Allows or not to modify the command setpoint value
free
Modification allowed (Default)
Lo c k
Protected
18
p. b.
Proportional Band
Proportional band Process inertia in units (example: if temperature is in °C) 0 ON / OFF
t.i .
if equal to 0 (Default)
1-9999 [digit
5
] (degrees for temperature sensors)
19
t.i .
Integral Time
Process inertia in seconds
0.0-999.9 seconds (0 = integral disabled), Default: 0.0
20
t.d.
Derivative Time
Normally ¼ of integral time
0.0-999.9 seconds (0 = derivative disabled), Default: 0.0
21
t. c.
Cycle Time
Cycle time (for P.I.D. on remote control switch 10 / 15 sec., for P.I.D. on SSR 1 sec.) or servo time (value declared by servo-motor manufacturer) 1-300 seconds, Default: 10.
22
o .Po L.
Output Power Limit
Select max. value for command output percentage 0…100 % , Default: 100%. Es: with
c.out
selected as 0...10 V and
o . P o L.
as 90%, command output can modulate
from a min. of 0 V to a max. of 9 V.
5
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.
Page 34
34 - ATR243 - User manual
23
A L.1
Alarm 1
Alarm 1 selection. Alarm intervention is related to AL1. (See paragraph 11)
di s .
Disabled (Default)
A. AL.
Absolute alarm, referring to process
b . AL.
Band alarm
H. d .AL.
Upper deviation alarm
L. d .AL.
Lower deviation alarm
A. c.AL.
Absolute alarm, referring to command setpoint
s t. A L.
Status alarm (active in Run / Start)
cooL
Cooling action
L. b .A.
Status alarm “load control” (Loop Break Alarm). Example: status of contactors
/ SSR or heating elements
24
A.I.5.0
Alarm 1 State Output
Alarm 1 output contact and intervention type
n . o. s.
(N.O. Start) Normally open, active at start (Default)
n . c. s.
(N.C. Start) Normally closed, active at start
n . o. t.
(N.O. Threshold) Normally open, active on reaching alarm
6
n . c. t.
(N.C. Threshold) Normally closed, active on reaching alarm
6
25
a1 . r e .
Alarm 1 Reset
Alarm 1 contact reset type
a re.
Automatic reset (Default)
m re.
Manual reset
SET
m re.s.
Manual reset stored. (keeps relay status also after an eventual power
failure)
26
a .1 . s . e .
Alarm 1 State Reset
State of contact for alarm 1 output in case of error
c. o.
Open contact (Default)
c. c.
Closed contact
27
a.1.Ld.
Alarm 1 Led
Defines the state of OUT2 led corresponding to the relative contact
c. o.
ON with open contact
c. c.
ON with closed contact (Default)
28
a .1 . H y .
Alarm 1 Hysteresis
-999…+999 [digit7] (degrees.tenths for temperature sensors), Default: 0.0.
6
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm condition reappers, after that it was restored.
7
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.
Page 35
ATR243 - User manual - 35
29
a .1 . d e .
Alarm 1 Delay
-180…+180 seconds. Negative: delay in alarm output phase. Positive: delay in alarm entry phase.
Default: 0.
30
a .1 . s p .
Alarm 1 Setpoint Protection
Alarm 1 set protection. Does not allow user to modify setpoint
free
Modification allowed (Default)
Lo c k
Protected
Hi d e
Protected and not visualized
31
AL. 2
Alarm 2
Alarm 2 selection. Alarm intervention is related to AL2. (See paragraph 11)
di s .
Disabled (Default)
A. AL.
Absolute alarm, referring to process
b . AL.
Band alarm
H. d .AL.
Upper deviation alarm
L. d .AL.
Lower deviation alarm
A. c.AL.
Absolute alarm, referring to command setpoint
s t. A L.
Status alarm (active in Run / Start)
cooL
Cooling action
L. b .A.
Status alarm “load control” (Loop Break Alarm). Example: status of contactors
/ SSR or heating elements
32
a .2. s o .
Alarm 2 State Output
Alarm 2 output contact and intervention type
n . o. s.
(N.O. Start) Normally open, active at start (Default)
n . c. s.
(N.C. Start) Normally closed, active at start
n . o. t.
(N.O. Threshold) Normally open, active on reaching alarm
8
n . c. t.
(N.C. Threshold) Normally closed, active on reaching alarm
8
33
A2. r e.
Alarm 2 Reset
Alarm 2 contact reset type
Are.
Automatic reset (Default)
m re.
Manual reset (reset / manual reset by keyboard)
SET
m re.s.
Manual reset stored. (keeps relay status also after an eventual power
failure)
34
a .2. s . e .
Alarm 2 State Error
State of contact for alarm 2 output in case of error
c. o.
Open contact (Default)
c. c.
Closed contact
8
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm condition reappers, after that it was restored.
Page 36
36 - ATR243 - User manual
35
a.2.Ld.
Alarm 2 Led
State of OUT2 led corresponding to relative contact
c. o.
ON with open contact
c. c.
ON with closed contact (Default)
36
a.2.HY.
Alarm 2 Hysteresis
-999…+999 [digit9] (degrees.tenths for temperature sensors), Default: 0.0.
37
a.2.d.e.
Alarm 2 Delay
-180…+180 seconds. Negative: delay in alarm exit phase. Positive: delay in alarm entry phase.
Default: 0.
38
a .2. s . p .
Alarm 2 Setpoint Protection
Alarm 2 set protection. Does not allow operator to change value set
free
Modification allowed (Default)
Lo c k
Protected
Hi d e
Protected and not visualized
39
AL. 3
Alarm 3
Alarm 3 selection. Alarm intervention is associated with AL3. (See par. 11)
di s .
Disabled (Default)
A. AL.
Absolute alarm, referring to process
b . AL.
Band alarm
H. d .AL.
Upper deviation alarm
L. d .AL.
Lower deviation alarm
A. c.AL.
Absolute alarm, referring to command setpoint
s t. A L.
Status alarm (active in Run / Start)
cooL
Cooling action (see Par. 7.12)
L. b .A.
Status alarm “load control” (Loop Break Alarm). Example: status of contactors
/ SSR or heating elements
40
a .3.5. o .
Alarm 3 State Output
Alarm 3 output contact and intervention type
n . o. s.
(N.O. Start) Normally open, active at start (Default)
n . c. s.
(N.C. Start) Normally closed, active at start
n . o. t.
(N.O. Threshold) Normally open, active on reaching alarm
10
n . c. t.
(N.C. Threshold) Normally closed, active on reaching alarm
10
9
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.
10
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm condition reappers, after that it was restored.
Page 37
ATR243 - User manual - 37
41
a .3. re.
Alarm 3 Reset
Alarm 3 contact reset type
a re.
Automatic reset (Default)
m re.
Manual reset
m re.
Manual reset stored. (keeps relay status also after an eventual power
failure)
42
a .3.s . e.
Alarm 3 State Error
State of contact for alarm 3 output in case of error
c. o.
Open contact (Default)
c. c.
Closed contact
43
a.3.Ld.
Alarm 3 LED
State of OUT3 led corresponding to relative contact
c. o.
ON with open contact
c. c.
ON with closed contact (Default)
44
a .3.HY.
Alarm 3 Hysteresis
-999…+999 [digit11] (degrees.tenths for temperature sensors), Default: 0.0.
45
a .3. d e.
Alarm 3 Delay
-180…+180 seconds
Negative: delay in alarm exit phase. Positive: delay in alarm entry phase.
Default: 0.
46
a .3.s . p.
Alarm 3 Setpoint Protection
Alarm 3 set protection. Does not allow operator to change the setpoint value
free
Modification allowed (Default)
Lo c k
Protected
Hi d e
Protected and not visualized
47
t.a.
Current Transformer
Activation and scale range of current transformer 0 Disabled 1-200 Ampere
Default: 0
48
L.b.a.t.
Loop Break Alarm Threshold
Intervention threshold of Loop Break Alarm
0.0-200.0 Ampere Default: 50.0
11
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.
Page 38
38 - ATR243 - User manual
49
L.b.a.d.
Loop Break Alarm Delay
Delay time for Loop break alarm intervention
00.00-60.00 mm.ss
Default: 01.00
50
co o . f.
Cooling Fluid
Type of refrigerant fluid for heating / cooling P.I.D.
Ai r
Air (Default)
oi L
Oil
H2o
Water
51
p.b.m.
Proportional Band Multiplier
Proportional band multiplier. Proportional band for cooling action is given by parameter 18 multiplied for this parameter
1.00-5.00 (Default: 1.00)
52
oud.b.
Overlap / Dead Band
Dead band combination for heating / cooling action in heating / cooling P.I.D. mode (dual action)
-20.0-50.0% of proportional band value (Default: 0). Negative indicates dead band value. Positive means overlap.
53
co.t.c.
Cooling Cycle Time
Cycle time for cooling output 1-300 seconds, Default: 10.
54
c. fLt.
Conversion Filter
ADC Filter: Number of input sensor readings to calculate the mean that defines process value. NB: When means increase, control loop speed slows down
di s .
Disabled
2. s . m .
2 Samples Mean
3. s. m .
3 Samples Mean
4. s. m .
4 Samples Mean
5. s. m .
5 Samples Mean
6. s. m .
6 Samples Mean
7. s . m .
7 Samples Mean
8. s. m .
8 Samples Mean
9. s. m .
9 Samples Mean
10.s. m .
10 Samples Mean (Default)
11 . s . m .
11 Samples Mean
12. s . m .
12 Samples Mean
13.s . m .
13 Samples Mean
14.s . m .
14 Samples Mean
15.s . m .
15 Samples Mean
Page 39
ATR243 - User manual - 39
55
c. frn .
Conversion Frequency
Sampling frequency of analogue / digital converter. NB: Increasing the conversion speed will slow down reading stability (example: for fast transients, as pressure, it is advisable to increase sampling frequency)
242H.
242 Hz (Maximum speed conversion)
123H.
123 Hz
62 H.
62 Hz
50 H.
50 Hz
39 H.
39 Hz
33.2H.
33.2 Hz
19.6H.
19.6 Hz
1 6.7 H.
16.7 Hz (Default) Ideal for filtering noises 50 / 60 Hz
12.5H.
12 .5 Hz
10 H.
10 Hz
8.33H.
8.33 Hz
6.25H.
6.25 Hz
4 .1 7 H .
4.17 Hz (Minimum speed conversion)
56
u . FLt.
Visualization Filter
Slow down the refresh of display, to simplify reading
di s .
Disabled with pitchfork (max. speed of display update) Default.
fi . o r.
First order filter with pitchfork
2. s . m .
2 Samples Mean
3. s. m .
3 Samples Mean
4. s. m .
4 Samples Mean
5. s. m .
5 Samples Mean
6. s. m .
6 Samples Mean
7. s . m .
7 Samples Mean
8. s. m .
8 Samples Mean
9. s. m .
9 Samples Mean
10.s. m .
10 Samples Mean (Maximum slow down of display update)
n u LL
Disabled without pitchfork
f. o . 2
First order filter
57
tune
Tune
Tuning type selection. (See paragraph 7.2)
diS.
Disabled (Default)
Auto
Automatic (P.I.D. parameters are calculated at activation and at change of
set point)
Man.
Manual (launch by keyboard or digital IN)
sYn c.
Synchronized [see word modbus 1025 (only ATR243-21ABC-T)]
58
s. dtu.
Setpoint Deviation Tune
Select the deviation from the command setpoint for the threshold used by autotuning to calculate the P.I.D. parameters
Page 40
40 - ATR243 - User manual
0-5000 [digit12] (degrees.tenths if temperature).
Default: 10.
59
op.mo.
Operating Mode
Select operating mode. (See paragraphs 7.7 and 7.11)
co n t.
Controller (Default)
p r. cY.
Pre-programmed cycle (See paragraph 7.7)
2t.s .
Setpoint change by digital input
2t .s .i .
Setpoint change by digital input with impulse command
3 t . s .i .
3 sets change by digital input with impulse command
4 t . s .i .
4 sets change by digital input with impulse command
t. res .
Reset time (custom function)
p.c.s.s.
Pre-programmed cycle with Start / Stop only by digital input
60
au.ma.
Automatic / Manual
Enable automatic / manual selection. (See paragraph 7.6)
di s .
Disabled (Default)
En.
Enabled
En .St.
Enabled with memory
61
d G t.i .
Digital Input
Digital input functioning (P59 selection must be
co n t.
or
Pr. cY.
). (See paragraph 7.11)
di s .
Disabled (Default)
st.st.
Start / Stop
rn.n.o.
Run N.O. (enables regulation with N.O. contact)
rn.n.c.
Run N.C. (enables regulation with N.C. contact)
L.c.n.o.
Lock conversion N.O. (stop conversion and display value with N.O.)
L.c.n.c.
Lock conversion N.C. (stop conversion and display value with N.C.)
tu n e
Manual Tune (by digital input)
a.ma.i.
Automatic / Manual Impulse (if enabled on parameter 60)
a.ma.c.
Automatic / Manual Contact (if enabled on parameter 60)
62
Grad .
Gradient
Rising gradient for Soft-Start or pre-programmed cycle 0 Disabled (Default) 1-9999 [Digit/hour
13
] (degrees/hour with display of tenth for temperature sensor)
63
m a . ti .
Maintenance Time
Maintenance time for pre-programmed cycle
00.00-24.00 hh.mm. Default: 00.00
12
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.
13
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.
Page 41
ATR243 - User manual - 41
64
u.m.c.p.
User Menu Cycle Programmed
Allows to modify rising gradient and maintenance time, from user menu, when pre­programmed cycle is operating
di s .
Disabled (Default)
Grad .
Gradient
m a . ti .
Maintenance time
ALL
Both gradient and maintenance time
65
ui . tY.
Visualization Type
Select visualization for display 1 and 2
1. p . 2. s .
1 Process, 2 Setpoint (Default)
1. p.2.H.
1 Process, 2 Hide after 3 sec.
1.s.2.P.
1 Setpoint, 2 Process
1.s.2.H.
1 Setpoint, 2 Hide after 3 sec.
1.p.2.a.
1 Process, 2 Ampere (T.A. input)
66
d eG r.
Degree
Select degree type
c
Centigrade (Default)
f
Fahrenheit
67
re t r.
Retransmission
Retransmission for output 0-10 V or 4…20 mA (select Jumpers JP5, JP7 and JP9). Parameters 68 and 69 define the lower and upper limits of the scale.
di s .
Disabled
u o . p.
Retransmits process in Volt
m a . p.
Retransmits process in mA
u o . c.
Retransmits command setpoint in Volt
m a . c.
Retransmits command setpoint in mA
uo.o.p.
Volt output percentage
ma.o.p.
mA output percentage
uo.a.1
Volt alarm 1 setpoint
ma.a.1
mA alarm 1 setpoint
uo.a.2
Volt alarm 2 setpoint
ma.a.2
mA alarm 2 setpoint
uo.t.a.
Volt T. A.
ma.t.a.
mA T.A.
68
Lo . L. r.
Lower Limit Retransmission
Output V / mA retransmission lower limit range
-999…+9999 [digit
14
] (degrees.tenths for temperature sensors), Default: 0.
69
up.L.r.
Upper Limit Retransmission
Output V / mA retransmission upper limit range
-999…+9999
[digit14] (
degrees.tenths for temperature sensors
),
Default
: 1000.
14
The display of the decimal point depends on the setting of parameter
sen.
and the parameter
d. p.
Page 42
42 - ATR243 - User manual
70
bd . rt.
Baud Rate
Select baud rate for serial communication
4.8 k
4.800 Bit/s
9.6 k
9.600 Bit/s
19.2k
19.200 Bit/s (Default)
28.8 k
28.800 Bit/s
39.4 k
39.400 Bit/s
57.6 k
57.600 Bit/s
71
sL. a d .
Slave Address
Select slave address for serial communication 1 – 254.
Default: 254
72
se. d e.
Serial Delay
Select serial delay 0 – 100 milliseconds.
Default: 20
73
L.L. o . p.
Lower Limit Output Percentage
Selects min. value for command output percentage 0 – 100%, Default: 0%. Ex: with
c.out
selected as 0...10 V and
L.L. o .P.
set at 10%, command output can change
from a min. of 1 V to a max. of 10 V.
11 Alarm Intervention Modes
11.a Absolute Alarm or Threshold Alarm (
a . AL.
selection)
1
Alarm Spv
Pv
O
On On
O
Hysteresis parameter  > 0
Time
Alarm output
Absolute alarm with controller in heating functioning (par. 11
Act.t.
selected
Heat
)
and hysteresis value greater than “0” (par. 28
A.1.HY.
> 0). *
2
Alarm Spv
O
On On
O
Hysteresis parameter  < 0
Time
Alarm output
Absolute alarm with controller in heating functioning (par. 11
Act.t.
selected
Heat
) and
hysteresis value less than “0” (par. 28
A.1.HY.
< 0). *
Page 43
ATR243 - User manual - 43
3
Alarm Spv
Pv
O
On On
O
Hysteresis parameter  > 0
Time
Alarm
output
Absolute alarm with controller in cooling functioning (par. 11
Act.t.
selected
Co o L
) and
hysteresis value than “0” (par. 28
A.1.HY.
> 0). *
4
Time
O O
On On
Alarm Spv
Pv
Hysteresis parameter  < 0
Alarm
output
Absolute alarm with controller in cooling functioning (par. 11
Act.t.
selected
Co o L
) and
hysteresis value less than “0” (par. 28
A.1.HY.
< 0). *
11.b Absolute Alarm or Threshold Alarm Referring to Setpoint Command
(
a . c. AL.
selection)
1
O
On
O
Time
Alarm Spv
Hysteresis parameter  > 0
Alarm output
Comand Spv
Absolute alarm refers to the command set, with the controller in heating functioning (par. 11
Act.t.
selected
Heat
) and hysteresis value
greater than “0” (par. 28
A.1.HY.
> 0). * The command set can be changed by pressing the arrow keys on front panel or using serial port RS485 commands. *
11.c Band Alarm (
b . AL.
selection)
1
Pv
O O
On On On
Hysteresis parameter
> 0
Time
Alarm
output
Band alarm hysteresis value greater than “0” (par. 28
A.1.HY.
> 0). *
Page 44
44 - ATR243 - User manual
2
Alarm Spv
O O O
On On On
Hysteresis parameter  < 0
Hysteresis parameter
Time
Alarm output
Alarm Spv
Comand Spv
Band alarm hysteresis value less than “0” (par. 28
A.1.HY.
< 0). *
* a) The example refers to alarm 1; the function can also be enabled for alarm 2 and 3 on models that include
it.
11.d Upper Deviation Alarm (
H. d .AL.
selection)
1
Pv
Comand Spv
Alarm Spv
O O
Hysteresis parameter  > 0
Time
Alarm output
Alarm Spv
Comand Spv
Upper deviation alarm value of alarm setpoint greater than “0” and hysteresis value greater than “0” (par. 28
A.1.HY.
> 0). **
2
Pv
Comand Spv Alarm Spv
O O
On On
Hysteresis parameter  > 0
Time
Alarm output
Comand Spv
Upper deviation alarm value of alarm setpoint less than “0” and hysteresis value greater than “0” (par. 28
A.1.HY.
> 0). **
Page 45
ATR243 - User manual - 45
11.e Lower Deviation Alarm (
L. d .AL.
selection)
1
Pv
Comand Spv
Alarm Spv
O O
On On
Hysteresis parameter  > 0
Time
Alarm output
Lower deviation alarm value of alarm setpoint greater than “0” and hysteresis value greater than “0” (par. 28
A.1.HY.
> 0). **
2
Pv
Comand Spv
Alarm Spv
O O
On On
Hysteresis parameter  > 0
Time
Alarm
output
Lower deviation alarm value of alarm setpoint less than “0” and hysteresis value greater than “0” (par. 28
A.1.HY.
> 0). **
** The example refers to alarm 1; the function can also be enabled for alarms 2 and 3 on models that include
it. b) With hysteresis value less than “0” (
A.1.HY.
< 0) the broken line moves under the alarm setpoint.
12 Table of Anomaly Signals
If installation malfunctions, controller will switch off regulation output and will report the anomaly. For example, controller will report failure of a connected thermocouple visualizing
e -05
fl ashing on display for other signals, see table below.
Cause what to do
E- 01
SYS.E
Error in EEPROM cell programming.
Call Assistance.
E-02
SYS.E
Cold junction sensor fault or room temperature outside of allowed limits.
Call Assistance.
E-04
SYS.E
Incorrect confi guration data. Possible loss of calibration values.
Check if the confi guration parameters are correct.
E-05
SYS.E
Thermocouple open or temperature outside of limits.
Check the connection with the sensors and their integrity.
E-08
SYS.E
Missing calibration data. Call Assistance.
Page 46
46 - ATR243 - User manual
13 Configuration EASY-UP
To simplify the setting of parameters and the integration of the different components involved in the control system, Pixsys introduces the EASY-UP coding which allows to set sensors and/or command outputs in one single step. By means of the code listed in the data sheet enclosed to the sensor or actuator (SSR, motorized valve, etc.) the EASY-UP coding will set the relevant main parameters on the controllers (ex. selection of PT100 on parameter “Sensor” and the corresponding measuring range on parameters “Lower and Upper limits of the setpoint”). Different codes may be entered on the controllers in sequence to configure inputs, control output or retransmission of signal.
Password 2200
P2
SEN.
Sensor
PT
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 500,
Password 2201
P2
SEN.
Sensor
PT
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 250,
Password 2202
P2
SEN.
Sensor
ptc
,
P4
Lo .L.S.
Lower Limit Setpoint -50,
P5
u p.L.S.
Upper Limit Setpoint 150,
Password 2203
P2
SEN.
Sensor
ntc
,
P4
Lo .L.S.
Lower Limit Setpoint -40,
P5
u p.L.S.
Upper Limit Setpoint 125,
Password 2301
P2
SEN.
Sensor
tc. j
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 400,
Password 2351
P2
SEN.
Sensor
tc. k
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 800,
Password 2352
P2
SEN.
Sensor
tc. k
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 600,
Page 47
ATR243 - User manual - 47
Password 2401
P2
SEN.
Sensor
4.20
,
P4
Lo .L.S.
Lower Limit Setpoint 0,
P5
u p.L.S.
Upper Limit Setpoint 100,
P6
Lo L.i
Lower Linear Input 0,
P7
u p.L.i .
Upper Linear Input 100,
Password 4400
P1
C.out
Command Output
c.SSr
,
P21
t. c.
Cycle Time 1,
P57
tune
Tune
Auto
,
Password 4600
P1
C.out
Command Output
c.vaL.
,
P21
t. c.
Cycle Time 60,
P57
tune
Tune
Auto
,
Password 6501
P1
C.out
Command Output
c. 01
,
P67
re t r.
Retransmission
m a . p
,
P68
Lo . L. r.
Lower Limit Retransmission -100,
P69
up.L.r.
Upper Limit Retransmission 250,
Password 6502
P1
C.out
Command Output
c. 01
,
P67
re t r.
Retransmission
v o . p
,
P68
Lo . L. r.
Lower Limit Retransmission -100,
P69
up.L.r.
Upper Limit Retransmission 250,
Notes / Updates
Page 48
48 - ATR243 - User manual
Table of configuration parameters
1
C.out
Command Output 30
2
SEN.
Sensor 31
3
d . P.
Decimal Point 31
4
Lo .L.S.
Lower Limit Setpoint 31
5
u p.L.S.
Upper Limit Setpoint 31
6
Lo L.i
Lower Linear Input 31
7
u p.L.i .
Upper Linear Input 31
8
La tc.
Latch On Function 32
9
o . cAL.
Offset Calibration 32
10
G. cAL.
Gain Calibration 32
11
Act. t.
Action type 32
12
c. re.
Command Reset 32
13
c. S.e.
Command State Error 32
14
c. Ld.
Command Led 32
15
c. HY.
Command Hysteresis 33
16
c. d e.
Command Delay 33
17
c. s. p.
Command Setpoint Protection 33
18
p. b.
Proportional Band 33
19
t.i .
Integral Time 33
20
t.d.
Derivative Time 33
21
t. c.
Cycle Time 33
22
o .Po L.
Output Power Limit 33
23
A L.1
Alarm 1 34
24
A.I.5.0
Alarm 1 State Output 34
25
a1 . r e .
Alarm 1 Reset 34
26
a .1 . s . e .
Alarm 1 State Reset 34
27
a.1.Ld.
Alarm 1 Led 34
28
a .1 . H y .
Alarm 1 Hysteresis 34
29
a .1 . d e .
Alarm 1 Delay 35
30
a .1 . s p .
Alarm 1 Setpoint Protection 35
31
AL. 2
Alarm 2 35
32
a .2. s o .
Alarm 2 State Output 35
33
A2. r e.
Alarm 2 Reset 35
34
a .2. s . e .
Alarm 2 State Error 35
35
a.2.Ld.
Alarm 2 Led 36
36
a.2.HY.
Alarm 2 Hysteresis 36
37
a.2.d.e.
Alarm 2 Delay 36
38
a .2. s . p .
Alarm 2 Setpoint Protection 36
39
AL. 3
Alarm 3 36
40
a .3.5. o .
Alarm 3 State Output 36
41
a .3. re.
Alarm 3 Reset 37
42
a .3.s . e.
Alarm 3 State Error 37
43
a.3.Ld.
Alarm 3 LED 37
Page 49
ATR243 - User manual - 49
44
a .3.HY.
Alarm 3 Hysteresis 37
45
a .3. d e.
Alarm 3 Delay 37
46
a .3.s . p.
Alarm 3 Setpoint Protection 37
47
t.a.
Current Transformer 37
48
L.b.a.t.
Loop Break Alarm Threshold 37
49
L.b.a.d.
Loop Break Alarm Delay 38
50
co o . f.
Cooling Fluid 38
51
p.b.m.
Proportional Band Multiplier 38
52
oud.b.
Overlap / Dead Band 38
53
co.t.c.
Cooling Cycle Time 38
54
c. fLt.
Conversion Filter 38
55
c. frn .
Conversion Frequency 39
56
u . FLt.
Visualization Filter 39
57
tune
Tune 39
58
s. dtu.
Setpoint Deviation Tune 39
59
op.mo.
Operating Mode 40
60
au.ma.
Automatic / Manual 40
61
d G t.i .
Digital Input 40
62
Grad .
Gradient 40
63
m a . ti .
Maintenance Time 40
64
u.m.c.p.
User Menu Cycle Programmed 41
65
ui . tY.
Visualization Type 41
66
d eG r.
Degree 41
67
re t r.
Retransmission 41
68
Lo . L. r.
Lower Limit Retransmission 41
69
up.L.r.
Upper Limit Retransmission 41
70
bd . rt.
Baud Rate 42
71
sL. a d .
Slave Address 42
72
se. d e.
Serial Delay 42
73
L.L. o . p.
Lower Limit Output Percentage 42
Page 50
50 - ATR243 - Manuale d’uso
Introduzione
Grazie per aver scelto un regolatore Pixsys. Con il modello ATR243 Pixsys rende disponibile in un singolo strumento tutte le opzioni relative alla connessione dei sensori e al comando di attuatori, con in aggiunta un’utile alimentazione a range esteso da 24…230 Vac/Vdc. Con le 18 sonde selezionabili e l’uscita configurabile come Relè, Comando SSR, 4…20 mA e 0…10 Volt l’utilizzatore o il rivenditore può gestire al meglio le scorte di magazzino razionalizzando investimento e disponibilità dei dispositivi. La serie si completa con i modelli dotati di comunicazione seriale RS485 Modbus Rtu e con la funzione di controllo del carico tramite trasformatore T.A. La ripetibilità in serie delle operazioni di parametrizzazione viene semplificata dalle Memory Card, dotate di batteria interna che non richiedono cablaggio per alimentare il regolatore.
1 Norme di sicurezza
Prima di utilizzare il dispositivo, leggere con attenzione le istruzioni e le misure di sicurezza contenute in questo manuale. Disconnettere l’alimentazione prima di qualsiasi intervento sulle connessioni elettriche o settaggi hardware. L’utilizzo/manutenzione è riservato a personale qualificato ed è da intendersi esclusiva­mente nel rispetto dei dati tecnici e delle condizioni ambientali dichiarate. Non gettare le apparecchiature elettriche tra i rifiuti domestici. Secondo la Direttiva Europea 2002/96/CE, le apparecchiature elettriche esauste devono essere raccolte separatamente al fine di essere reimpiegate o riciclate in modo eco­compatibile.
2 Identificazione del modello
La serie di regolatori ATR243 prevede tre versioni: facendo riferimento alla tabella seguente è facile risalire al modello desiderato.
Modelli con alimentazione 24…230 Vac/Vdc +/-15% 50/60 Hz – 5,5 VA
ATR243-20ABC 2 setpoint, 2 Relè 5 A oppure 1 Relè + 1 Ssr/V/mA
ATR243-21ABC-T
3 setpoint, 2 Relè 5 A + 1 Ssr/V/mA + RS485 + trasformatore amperometrico*
ATR243-31ABC
4 setpoint, 3 Relè 5 A + 1 Ssr/V/mA + trasformatore amperometrico*
* Modelli con ingresso per T.A. per funzione “Loop Break Alarm”.
Page 51
ATR243 - Manuale d’uso - 51
3 Dati tecnici
3.1 Caratteristiche generali
Visualizzatori
4 display 0,40 pollici
4 display 0,30 pollici Temperatura di esercizio
Temperatura funzionamento 0-45 °C
Umidità 35..95 uR% Protezione IP65 su frontale (con guarnizione) - IP20 cu stodia e morsetti Materiale PC ABS UL94VO autoestinguente Peso 165 g (-20ABC) / 185 g (-21/31ABC)
3.2 Caratteristiche Hardware
Alimentazione
Alimentazione a range esteso
24…230 Vac/Vdc ±15% 50/60 HzConsumo: 5.5 VA.
Ingresso analogico
1: AN1 Configurabile
via software. Ingresso:
Termocoppie tipo K, S, R, J.
Compensazione automatica
del giunto freddo da 0…
50 °C.
Termoresistenze: PT100,
PT500, PT1000, Ni100, PTC1K,
NTC10K (β 3435K).
Ingresso V/I: 0-10 V, 0-20 o
4-20 mA, 0-40 mV, T.A. 50
mA 1024 punti su versione
ATR243-21…/31.
Ingresso Pot: 6 KΩ, 150 KΩ.
Tolleranza (25 °C) +/-0.2% ±1 digit (su F.s.) per termocoppia, termoresistenza e V / mA. Precisione giunto freddo 0.1 °C/°C.
Impedenza: 0-10 V: Ri>110 KΩ 0-20 mA: Ri<5 Ω 4-20 mA: Ri<5 Ω 0-40 mV: Ri>1 MΩ
Uscite relè
2 Relè (ATR243-20...-21).
3 Relè (ATR243-31...).
Configurabili come uscita
comando e allarme.
Contatti 5 A - 250 V~. Carico resistivo.
Uscita SSR/V/mA
1 SSR
Normalizzata 0/4…20mA o
0…10 Volt.
• Deselezionando relè OUT2
su ATR243-20…
Configurabili come uscita
comando o ritrasmissione
setpoint o processo.
12V / 30mA (min. 10.5 V DC). Configurabile: 0-10 V con 9500 punti +/-0.2% (su F. s.) 0-20 mA con 7500 punti +/-0.2% (su F. s.) 4-20 mA con 6000 punti +/-0.2% (su F. s.)
Page 52
52 - ATR243 - Manuale d’uso
3.3 Caratteristiche Software
Algoritmi regolazione
ON-OFF con isteresi.
P, P.I., P.I.D., P.D. a tempo proporzionale. Banda proporzionale
0...9999 °C o °F
Tempo integrale 0,0...999,9 sec. (0 esclude funzione integrale) Tempo derivativo 0,0...999,9 sec. (0 esclude funzione derivativa)
Funzioni del regolatore
Tuning manuale o automatico allarme selezionabile, protezione
set comando e allarme, selezione funzioni da ingresso digitale,
ciclo pre-programmato con Start / Stop.
4 Dimensioni ed installazione
CN1
1 6
MEMORY C.241
15
1116
234
12131415
1 6
Memory Card
12
3
4
5
11 13 14 15 1612
6 7 8 9 10
CN1
1 6
PIXSYS
DIMA DI
FORATURA
FRONTAL PANEL
CUT-OUT
46 X 46 mm
48 mm
48 mm 125 mm10
Suggested thickness / Spessore suggerito 2 ÷ 6 mm
Memory Card (option)
with battery / con batteria
2100.30.003
Memory Card (option)
2100.30.002
Insert / Inserimento Memory Card 42 mm
Page 53
ATR243 - Manuale d’uso - 53
4.1 Montaggio a pannello
1
1
2
2
Modalità di montaggio a pannello, e fi ssaggio per ganci di ancoraggio.
1
2
Per lo smontaggio utilizzare un cacciavite e forzare leggermente i ganci di fi ssaggio per farli uscire dalla guida di ancoraggio.
4.2 Estrazione dell’elettronica
Per estrarre l’elettronica impugnare la parte frontale nelle due apposite zigrinature laterali.
1
1
2
Prima di eff ettuare qualsiasi operazione di confi gurazione o di manutenzione, disinserire l’apparecchio dalla rete.
Page 54
54 - ATR243 - Manuale d’uso
5 Collegamenti elettrici
Benché questo regolatore sia stato progettato per resistere ai più gravosi disturbi presenti in ambienti industriali è buona norma seguire la seguenti precauzioni:
• Distinguere la linea di alimentazioni da quelle di potenza.
• Evitare la vicinanza di gruppi di teleruttori, contattori elettromagnetici, motori di grossa potenza e comunque usare gli appositi filtri.
• Evitare la vicinanza di gruppi di potenza, in particolare se a controllo di fase.
5.1 Schema di collegamento
Di seguito sono riportati i collegamenti dei tre modelli disponibili.
ATR243-20ABC
ATR243-21ABC-T ATR243-31ABC
V/I
5.1.a Alimentazione
10
24...230V AC/DC
SUPPLY
9
Alimentazione switching a range esteso 24…230 Vac/dc ±15% 50/60 Hz – 5,5 VA (con isolamento galvanico).
5.1.b Ingresso analogico AN1
Per termocoppie K, S, R, J.
• Rispettare la polarità.
• Per eventuali prolunghe utilizzare cavo compensato e morsetti adatti alla termocoppia utilizzata (compensati).
• Quando si usa il cavo schermato, la schermatura va collegata a terra ad una sola estremità
Page 55
ATR243 - Manuale d’uso - 55
Rosso Red
Bianco White
Rosso Red
Per termoresistenze PT100, NI100.
• Per il collegamento a tre fi li usare cavi della stessa sezione.
• Per il collegamento a due fi li cortocircuitare i morsetti 1 e
3.
• Quando si usa il cavo schermato, la schermatura va collegata a terra ad una sola estremità
• Selezionare il jumper interno JP3 come in fi gura.
ROSSO
BIANCO
ROSSO
Per termoresistenze NTC, PTC, PT500, PT1000 e potenziometri lineari.
Quando si usa il cavo schermato, la schermatura va collegata a terra ad una sola estremità
Per segnali normalizzati in corrente e tensione. Rispettare la polarità. Quando si usa il cavo schermato, la schermatura va collegata a terra ad una sola estremità Selezionare il jumper interno JP3 come in fi gura.
In mancanza della corretta selezione dei Jumper non saranno disponibili i 12 Vdc / 30 mA sul morsetto numero 3 per l’alimentazione del sensore.
5.1.c Esempi di collegamento per ingressi Volt e mA
+12 V
30 mA
Per segnali normalizzati in tensione 0…10 V. Rispettare le polarità.
Page 56
56 - ATR243 - Manuale d’uso
+12 V
30 mA
Per segnali normalizzati in corrente 0/4….20 mA con
sensore a tre fi li.
Rispettare le polarità: A= Uscita sensore B= Massa sensore C= Alimentazione sensore (+12Vdc / 30mA)
Per segnali normalizzati in corrente 0/4….20 mA con
sensore ad alimentazione esterna.
Rispettare le polarità: A= Uscita sensore B= Massa sensore
+12 V
30 mA
Per segnali normalizzati in corrente 0/4….20 mA con
sensore a due fi li.
Rispettare le polarità: A= Uscita sensore C= Alimentazione sensore (+12Vdc / 30mA)
5.1.d Ingresso seriale
Comunicazione RS485 Modbus RTU.
5.1.e Uscita Relè Q1
Portata contatti 5 A / 250 V~ per carichi resistivi.
NB: vedi grafi co nella pagina successiva.
Page 57
ATR243 - Manuale d’uso - 57
5.1.f Uscita Relè Q2 per ATR243-20ABC
Portata contatti 5 A / 250 V~ per carichi resistivi.
Per selezionare Q2 come uscita relè, verificare che non siano inseriti i jumper JP5 e JP7.
NB: vedi grafico nella pagina successiva.
Connettere un carico senza togliere i Jumper danneggia il regolatore.
5.1.g Uscita Relè Q2 per ATR243-21ABC-T e ATR243-31ABC
Portata contatti 5 A / 250 V~ per carichi resistivi.
NB: vedi grafico nella pagina successiva.
5.1.h Uscita Relè Q3 su ATR243-31ABC
Portata contatti 5 A / 250 V~ per carichi resistivi.
NB: vedi grafico qui sotto.
Electrical endurance Q1 / Q2 / Q3:
5 A, 250 Vac, carico resistivo, 105 operazioni. 20/2 A, 250 Vac, cosφ = 0.3, 105 operazioni.
Page 58
58 - ATR243 - Manuale d’uso
5.1.i Uscita SSR
SSR
5
+
4
-
Uscita comando SSR portata 12 V / 30 mA (min. 10.5 V DC).
Inserire JP5 e JP7 e selezionare JP9 come in fi gura per utilizzare l’uscita SSR.
5.1.j Uscita mA / Volt
mA
5
+
4
-
Uscita continua in mA confi gurabile da parametri come comando (parametro
c.out
) o ritrasmissione del
processo-setpoint (parametro
rE t r.
)
Inserire JP5 e JP7 e selezionare JP9 come in fi gura per utilizzare l’uscita continua in mA.
V
5
+
4
-
Uscita continua in Volt confi gurabile da parametri come comando (parametro
c.out
) o ritrasmissione del
processo-setpoint (parametro
rE t r.
)
Inserire JP5 e JP7 e selezionare JP9 come in fi gura per utilizzare l’uscita continua in Volt.
Page 59
ATR243 - Manuale d’uso - 59
5.1.k Ingresso T.A. su ATR243-21ABC-T e ATR243-31ABC
TA
16
15
• Ingresso per trasformatore amperometrico 50mA
(risoluzione 1024 punti).
• Tempo di campionamento 80 ms.
• Confi gurabile da parametri.
Inserire JP4 e JP6 come in fi gura per selezionare l’ingresso T.A.
5.1.l Ingresso digitale su ATR243-20ABC
3
2ID
+12V
Ingresso digitale (parametro
d G ti
.). L’utilizzo dell’ingresso digitale in questa versione è possibile solo con sonde tipo Tc, 0…10 V, 0/4…20 mA e 0…40 mV.
Inserire JP3 come in fi gura per selezionare l’ingresso digitale.
5.1.m Ingresso digitale su ATR243-21ABC-T e ATR243-31ABC
16
15ID
+12V
Ingresso digitale da parametro
d G ti
.
Inserire JP4 come in fi gura per selezionare l’ingresso digitale.
Page 60
60 - ATR243 - Manuale d’uso
6 Funzione dei visualizzatori e tasti
A1
C2
C1
ATR243
PIXSYS
A2
1
3
4
8 9
10
5
6
7
2
6.1 Indicatori numerici (Display)
1
1234
Normalmente visualizza il processo. In fase di configurazione visualizza il parametro in inserimento.
2
1234
Normalmente visualizza i setpoint. In fase di configurazione visualizza il valore del parametro in inserimento.
6.2 Significato delle spie di stato (Led)
3 C1 C2
Si accendono quando l’uscita comando è attiva. C1 con comando relè/SSR/mA/Volt o C1 (apri) e C2 (chiudi) nel caso di comando valvola motorizzata.
4 A1 A2 A3 Si accendono quando l’allarme corrispondente è attivo. 5 MAN
Si accende all’attivazione della funzione “Manuale”.
6 TUN
Si accende quando il regolatore sta eseguendo un ciclo di AutoTuning.
7 REM Si accende quando il regolatore comunica via seriale.
Page 61
ATR243 - Manuale d’uso - 61
6.3 Tasti
8
• Incrementa il setpoint principale.
• In fase di configurazione consente di scorrere i parametri. Insieme al tasto
SET
li modifica.
• Premuto dopo il tasto
SET
incrementa i setpoint di allarme.
9
• Decrementa il setpoint principale.
• In fase di configurazione consente di scorrere i parametri. Insieme al tasto
SET
li modifica.
• Premuto dopo il tasto
SET
decrementa i setpoint di allarme.
10
SET
Permette di visualizzare i setpoint di allarme e di entrare nella funzione di lancio del Tuning. Permette di variare i parametri di configurazione.
7 Funzioni del regolatore
7.1 Modifica valore setpoint principale e setpoint di allarme
Il valore dei setpoint può essere modificato da tastiera come segue:
Premere Effetto Eseguire
1
o
La cifra sul display 2 varia.
Incrementare o diminuire il valore del setpoint principale.
2
SET
Visualizza setpoint di allarme sul display 1.
3
o
La cifra sul display 2 varia.
Incrementare o diminuire il valore del setpoint di allarme.
7. 2 Auto-Tuning
La procedura di Tuning per il calcolo dei parametri di regolazione può essere manuale o automatica e viene selezionata da parametro 57 (
tunE
).
7. 3 Lancio del Tuning Manuale
La procedura manuale permette all’utente maggiore flessibilità nel decidere quando aggiornare i parametri di regolazione dell’argoritmo P.I.D.. La procedura può essere attivata in due modi.
• Lancio del Tuning da tastiera: Premere il tasto
SET
finché il display 1 non visualizza la scritta
tunE
con il display 2 su
o FF
, premere , il display 2 visualizza on.
Il led TUN si accende e la procedura ha inizio.
• Lancio del Tuning da ingresso digitale: Selezionare
tunE
su parametro 61
d Gt .i
. Alla prima attivazione dell’ingresso digitale
(commutazione su fronte) il led TUN si accende, alla seconda si spegne.
Page 62
62 - ATR243 - Manuale d’uso
7.4 Lancio del Tuning Automatico
Il Tuning automatico si attiva all’accensione dello strumento o quando viene modificato il setpoint di un valore superiore al 35%. Per evitare overshoot, il punto dove il regolatore calcola i nuovi parametri PID è determinato dal valore di setpoint meno il valore “Set Deviation Tune” (vedere parametro 58
S.D. t u .
).
Per interrompere il Tuning lasciando invariati i valori PID, premere il tasto
SET
finché il
display 1 non visualizza la scritta
tune
e il display 2 visualizza on. Premendo , il display
2 visualizza
o FF
, il led TUN si spegne e la procedura termina.
7. 5 Soft-Start
All’accensione il regolatore per raggiungere il setpoint segue un gradiente di salita impostato in Unità (es. Grado / Ora). Impostare sul parametro 62
GrA d .
il valore di incremento desiderato in Unità/Ora; alla successiva accensione lo strumento eseguirà la funzione Soft-Start. Se il parametro 59
op.mo.
è impostato su
co n t.
e il parametro 63
m a . ti .
è diverso da 0, dopo l’accensione, trascorso il tempo impostato sul parametro 63, il setpoint non segue più il gradiente, ma si porta alla massima potenza verso il setpoint finale. L’autotuning non funziona mai quando solo il par.
GrA d .
è diverso da 0. Se il parametro
63
m a . ti .
è diverso da 0 e il parametro 57
tune
è impostato su
Auto
, l’autotuning parte
allo scadere del tempo di Soft-Start, mentre se il parametro 57
tune
è impostato
Man.
la
funzione può essere lanciata solamente allo scadere del Soft-Start.
7.6 Regolazione automatico / manuale per controllo % uscita
Questa funzione permette di passare dal funzionamento automatico al comando manuale della percentuale dell’uscita. Con il parametro 60
Au.ma.
è possibile selezionare due modalità.
1 La prima selezione (
en.
) permette di abilitare con il tasto
SET
la scritta
p.---
sul
display 1, mentre sul display due appare
auto.
Premere il tasto per visualizzare
man,
; è ora possibile, durante la visualizzazione
del processo, variare con i tasti
e la percentuale dell’uscita. Per tornare in
automatico, con la stessa procedura, selezionare
auto
sul display 2: subito si spegne il
led TUN e il funzionamento torna in automatico.
2 La seconda selezione (
en.st.
) abilita lo stesso funzionamento, ma con due importanti
varianti:
• Nel caso di temporanea mancanza di tensione o comunque dopo uno spegnimento,
accendendo il regolatore, verrà mantenuto sia il funzionamento in manuale, sia il valore di percentuale dell’uscita precedentemente impostato.
• Nel caso di rottura del sensore durante il funzionamento automatico, il regolatore si
porterà in manuale mantenendo invariata la percentuale di uscita comando generata dal P.I.D. subito prima della rottura.
Es: su un estrusore viene mantenuto il comando in percentuale della resistenza (carico)
anche nel caso di guasto sulla sonda in ingresso.
Page 63
ATR243 - Manuale d’uso - 63
7.7 Ciclo pre-programmato
La funzione ciclo pre-programmato si abilita impostando
Pr. c y
oppure
Pc.SS.
nel
parametro 59
oP.Mo
.
Setpoint
Setpoint 2
Max. potenza
Setpoint 1
Mantenimento
Rareddamento naturale
Tempo
Gradiente
Prima selezione (
Pr. c y
): il regolatore raggiunge il setpoint 1 seguendo il gradiente impostato nel parametro 62
Grad .
, poi sale alla massima potenza verso il setpoint 2. Quando il processo lo raggiunge, lo mantiene per il tempo impostato nel parametro 63
m a . ti .
Allo scadere, l’uscita di comando è
disabilitata e lo strumento visualizza
stop
. La partenza del ciclo avviene al ogni accensione dello strumento, oppure da ingresso digitale se abilitato per questo funzionamento (vedi parametro 61
d Gt .i .
).
Setpoint
Setpoint 1
Mantenimento
Rareddamento naturale
Tempo
Gradiente
Seconda selezione (
p.c.s.s.
): la partenza è decisa solo dall’attivazione dell’ingresso digitale, a prescindere dall’impostazione del parametro 61
d Gt .i .
Alla partenza, il regolatore raggiunge il setpoint 1 seguendo il gradiente impostato nel parametro 62
Grad .
Quando il processo lo raggiunge, lo mantiene per il tempo impostato nel parametro 63
m a . t.i .
Allo scadere, l’uscita di comando è disabilitata e lo strumento visualizza
stop
.
Variante (
S.S. cY.
):
Selezionando
S.S. cY.
(Soft Start Cycle) il regolatore si comporta come nella prima selezione
(
Pr. c y
) con due importanti varianti. Se all’accensione il processo è inferiore al SET1, lo strumento regola la potenza dell’uscita al valore percentuale impostato sul parametro 62
GrA d .
Quando il processo supera il SET1 o è trascorso il tempo impostato sul parametro 63
M A . ti .
, il regolatore porta il processo al SET2 alla massima potenza e lo mantiene per un tempo infi nito.
Se sul parametro 59
oP.Mo.
è impostato
S.S. cY.
è possibile selezionare
Hi d E
sul parametro
17
c. S. P.
: in questo modo non viene più visualizzato il SET1, mentre la label del SET2 diventa semplicemente SET. In questa modalità, lanciando il tune manuale durante la regolazione sul SET1 non si vedrà accendersi il led TUN fi nchè non si passerà alla regolazione sul SET2. L’autotuning (automatico e manuale) funziona, ma solo se sta regolando sul SET2. Se viene lanciato durante la regolazione sul SET1, rimane in standby per poi partire appena si passa alla regolazione sul SET2.
Page 64
64 - ATR243 - Manuale d’uso
7.8 Memory Card (opzionale)
È possibile duplicare parametri e setpoint da un regolatore ad un altro mediante l’uso della Memory Card. Sono previste due modalità:
• Con regolatore connesso all’alimentazione: Inserire la Memory Card con regolatore spento. All’accensione il display 1 visualizza
memo
e il display 2 visualizza
----
(solo se nella Memory sono salvati valori corretti).
Premendo il tasto
il display 2 visualizza
Lo a d
. Confermare con il tasto
SET
. Il
regolatore carica i nuovi valori e riparte.
U1
CN1
C1
MEMORY C241
LED ROSSO: acceso in programmazione
Red Light: waiting for programming
LED VERDE: programmazione eseguita
• Con regolatore non connesso all’alimentazione: La memory card è dotata di batteria interna con autonomia per circa 1000 utilizzi
(batteria a bottone 2032, sostituibile). Inserire la memory card e premere il tasto di programmazione. Durante la scrittura dei parametri il led si accende rosso, al termine della procedura si accende verde. è possibile ripetere la procedura senza particolari
attenzioni. NB: non è possibile trasferire i parametri di uno strumento ad uno con codice differente: il LED rimane acceso rosso.
Aggiornamento Memory Card.
Per aggiornare i valori della Memory seguire il procedimento descritto nella prima modalità, impostando
----
sul display 2 in modo da non caricare i parametri sul
regolatore
1
. Entrare in configurazione e variare almeno un parametro. Uscendo dalla
configurazione il salvataggio sarà automatico.
1
Nel caso in cui all’accensione il regolatore non visualizzi
memo
significa che non ci sono dati salvati nella
Memory Card, ma è possibile ugualmente aggiornarne i valori.
Page 65
ATR243 - Manuale d’uso - 65
7.9 Funzione Latch on
Per l’impiego con ingresso
P o t .1
(pot. 6 KΩ) e
Po t.2
(pot. 150 KΩ) e con ingressi normalizzati
(0…10 V, 0...40 mV, 0/4…20 mA), è possibile associare il valore di inizio scala (parametro 6
Lo L.i
) alla posizione di minimo del sensore e quello di fi ne scala (parametro 7
u P.L.i
) alla
posizione di massimo del sensore (parametro 8
La t c.
confi gurato come
Std .
). È inoltre possibile fi ssare il punto in cui lo strumento visualizzerà 0 (mantenendo comunque il campo scala compreso tra
Lo L.i
e
u P.L.i
) tramite l’opzione di “zero virtuale” impostando
u .St.
oppure
u.in.
nel parametro 8
La t c.
Se si imposta
u.in.
lo zero virtuale andrà reimpostato
dopo ogni accensione dello strumento; se si imposta
u .St.
lo zero virtuale resterà fi sso una
volta tarato. Impostando “
dYn.L
” (dynamic limits) permette di superare i limiti inferiore e superiore se in ingresso ci sono valori esterni al 0/4…20mA o 0…10V. Per utilizzare la funzione LATCH ON confi gurare come desiderato il parametro
LA t c
2
. Per la
procedura di taratura fare riferimento alla seguente tabella:
Premere E ff e t t o Eseguire
1
+ contemporanea­mente
Esce dalla confi gurazione parametri. Il display 2 visualizza la scritta
LA t c
.
Posizionare il sensore sul valore minimo di funzionamento (associato a
Lo L.i .
).
2
Fissa il valore sul minimo. Il display visualizza
Lo 
.
Posizionare il sensore sul valore massimo di funzionamento (associato a
u p .L.i .
).
3
Fissa il valore sul massimo. Il display visualizza
Hi G H
.
Per uscire dalla procedura standard tenere premuto
SET
. Nel caso di impostazione con “zero virtuale” posizionare il sensore nel punto di zero.
4
SET
Fissa il valore di zero virtuale. Il display visualizza
ui r t.
NB: nel caso di selezione
u.0.in.
la procedura al punto 4 va eseguita ad ogni ri-accensione.
Per uscire dalla procedura tenere premuto
SET
.
Max
Min Zero
2
La procedura di taratura parte uscendo dalla confi gurazione dopo aver variato il parametro.
Page 66
66 - ATR243 - Manuale d’uso
7.10 Loop Break Alarm da ingresso T.A. (Trasformatore Amp.)
Permette di misurare la corrente sul carico per gestire un allarme in caso di malfun­zionamento (con stadio di potenza in corto oppure sempre aperto). Il trasformatore amperometrico collegato ai morsetti 15 e 16 deve essere da 50 mA (tempo di campionamento 80 ms).
• Impostare sul parametro 47
t.a .
il valore di fondo scala in Ampere del trasformatore
amperometrico.
• Impostare sul parametro 48
L.b.a.t.
la soglia di intervento in Ampere del Loop Break
Alarm.
• Impostare sul parametro 49
L.b.a.d.
il tempo di ritardo per l’intervento del Loop Break
Alarm.
• è possibile associare l’allarme ad un relè, impostando il parametro
AL. 1, AL. 2
oppure
AL. 3
come
L.b.a.
Nel caso un teleruttore o relè allo stato solido dovesse restare sempre chiuso il regolatore segnala il guasto visualizzando
L.b.a.c.
sul display 2 (alternativamente con il setpoint di comando). Nel caso invece lo stadio di potenza dovesse restare sempre aperto, oppure la corrente sul carico fosse inferiore al valore impostato su
L.b.a.t.
, il regolatore visualizza sul display
2
L.b.a.o.
È possibile visualizzare la corrente assorbita in fase di chiusura dello stadio di
potenza.
Premere Effetto Eseguire
1
SET
Questo tasto, in modo ciclico, permette di visualizzare sul display 2 percentuale di uscita, selezione auto / man, setpoint ed allarmi.
Premere
SET
fino alla visualizzazione sul display 1 della scritta
am.t.a.
e sul display 2 della corrente in Ampere (
t.a .
>0). Il valore è mantenuto anche quando non circola corrente sul carico.
Impostando sul parametro 48
L.b.A.t.
il valore 0 è possibile visualizzare la corrente
assorbita senza mai generare il Loop Break Alarm.
7.11 Funzioni da Ingresso digitale
L’ATR243 integra alcune funzionalità relative all’ingresso digitale, che può essere abilitato utilizzando i parametri 59
op.mo.
e 61
d Gt .i .
Parametro 59
op.mo.
NB: Utilizzando le seguenti impostazioni, il parametro 61
d Gt .i .
viene ignorato.
2t.s.
: Cambio setpoint a due soglie: con contatto aperto l’ATR243 regola su SET1; con
contatto chiuso regola su SET2;
2 t . s .i .
: Cambio setpoint a due soglie: la selezione del punto di lavoro viene fatta
agendo con un impulso sull’ingresso digitale;
3 t. s .i .
: Cambio setpoint a tre soglie con impulso sull’ingresso digitale;
4 t. s .i .
: Cambio setpoint a quattro soglie con impulso sull’ingresso digitale;
t. res .
: Funzione personalizzata;
p.c.s.s.
: Ciclo pre-programmato (vedi par. 7.7).
I vari setpoint possono essere impostati durante il funzionamento premendo
SET
.
Page 67
ATR243 - Manuale d’uso - 67
• Parametro 61
d Gt .i .
NB: Le impostazioni su questo parametro sono considerate solo impostando
co n t.
oppure
p r. cY.
sul parametro 59
op.mo.
st.s t.
: Start / Stop; agendo sull’ingresso digitale il regolatore passa alternativamente
da start a stop;
rn.n.o.
: Run N.O. Il regolatore è in start solamente con ingresso chiuso;
rn.n.c.
: Run N.C. Il regolatore è in start solamente con ingresso aperto;
L.c.n.o.
: Con ingresso chiuso blocca la lettura delle sonde;
Lc.n . c.
: Con ingresso aperto blocca la lettura delle sonde;
tune
: Abilita/disabilita il Tuning se il parametro 57
tune
è impostato su
man.
;
a.ma.i.
: Se par. 60
au.ma.
è impostato su
en.
o
en.st.
agendo sull’ingresso il regolatore
passa alternativamente da regolazione automatica a regolazione manuale;
a.ma.c.
: Se par. 60
au.ma.
è impostato su
en.
o
en.st.
l’ATR243 regola in automatico
con ingresso aperto e in manuale con ingresso chiuso. NB: le funzioni da ingresso digitale NON sono disponibili con sonde di tipo resistivo sul modello ATR243-20ABC.
7.12 Funzionamento in doppia azione (caldo / freddo)
L’ATR243 è adatto alla regolazione anche su impianti che prevedano un’azione combinata caldo-freddo. L’uscita di comando deve essere configurata in P.I.D. caldo (
Act.t.
=
HEAT
e
P. b .
maggiore di 0), e uno degli allarmi (
A L .1, AL.2
oppure
AL.3
) deve essere
configurato come
cooL
. L’uscita di comando va collegata all’attuatore responsabile dell’azione caldo, l’allarme comanderà invece l’azione refrigerante. I parametri da configurare per il P.I.D. caldo sono:
Act.t.
=
HEAT
Tipo azione uscita di comando (Caldo);
P. b .
: Banda proporzionale azione caldo;
t.i
: Tempo integrale azione caldo ed azione freddo;
t.d .
: Tempo derivativo azione caldo ed azione freddo;
t. c.
: Tempo di ciclo azione caldo. I parametri da configurare per il P.I.D. freddo sono (azione associata, per esempio, all’allarme 1):
A L .1
=
cooL
Selezione allarme 1 (Freddo);
P. b . M.
: Moltiplicatore di banda proporzionale;
ou.d.b.
: Sovrapposizione / Banda morta;
co.t.c.
: Tempo di ciclo azione freddo.
Il parametro
p.b.m.
(che varia da 1.00 a 5.00) determina la banda proporzionale dell’azione refrigerante secondo la formula: Banda proporzionale azione refrigerante =
P. b . x P. b . M.
Si avrà così una banda proporzionale per l’azione refrigerante che sarà uguale a quella dell’azione caldo se
P. b . M.
= 1.00, o 5 volte più grande se
P. b . M.
= 5.00. Tempo integrale e Tempo derivativo sono gli stessi per entrambe le azioni. Il parametro
ou.d.b.
determina la sovrapposizione in percentuale tra le due azioni. Per gli impianti in cui l’uscita riscaldante e l’uscita refrigerante non devono mai essere attive contemporaneamente si configurerà una Banda morta
ou.d.b.
≤ 0), viceversa si potrà
configurare una sovrapposizione (
ou.d.b.
> 0).
Page 68
68 - ATR243 - Manuale d’uso
1
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 < 0
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
2
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 x  = COOL
 < 0
 = 0
 (HEAT)
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
3
ACTIVE
ACTIVE
SPV
PV
 x  = COOL
 x  = COOL
 x  = COOL
 < 0
 = 0
 > 0
 (HEAT)
 (HEAT)
 (HEAT)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
COMMAND OUTPUT (HEAT)
ALARM OUTPUT (COOL)
SPV
PV
ACTIVE
ACTIVE
SPV
PV
ACTIVE
ACTIVE
Il parametro
co.t.c.
ha lo stesso significato del tempo di ciclo per l’azione caldo
t. c.
Il
parametro
co o . f.
(fluido di raffreddamento) pre-seleziona il moltiplicatore di banda
proporzionale
P. b . M.
ed il tempo di ciclo
co.t.c.
del P.I.D. freddo in base al tipo di fluido
refrigerante:
c o o . F.
Tipo di fluido
refrigerante
P. b . M . co.t.c
Ai r
Aria 1.00 10
oi L
Olio 1.25 4
H2o
Acqua 2.50 2
Una volta selezionato il parametro
co o . f.
, i parametri
P. b . M., oud.b.
e
co.t.c.
possono
essere comunque modificati.
Page 69
ATR243 - Manuale d’uso - 69
8 Comunicazione Seriale
L’ATR243-21ABC-T con RS485 può ricevere e trasmettere dati via seriale tramite protocollo MODBUS RTU. Il dispositivo può essere configurato solo come Slave. Questa funzione permette il controllo di più regolatori collegati ad un sistema di supervisione. Ciascuno strumento risponderà ad un’interrogazione del Master solo se questa contiene l’indirizzo uguale a quello contenuto nel parametro
SL. A d .
Gli indirizzi permessi vanno da 1 a 254 e non devono esserci regolatori con lo stesso indirizzo sulla stessa linea. L’indirizzo 255 può essere usato dal Master per comunicare con tutte le apparecchiature collegate (modalità broadcast), mentre con 0 tutti i dispositivi ricevono il comando, ma non è prevista alcuna risposta. L’ATR243 può introdurre un ritardo (in millisecondi) della risposta alla richiesta del Master. Tale ritardo deve essere impostato sul parametro 72
se. d e.
Ad ogni variazione dei parametri lo strumento salva il valore in memoria EEPROM (100000 cicli di scrittura), mentre il salvataggio dei setpoint avviene con un ritardo di 10 secondi dall’ultima modifica. NB: modifiche apportate a Word diverse da quelle riportate nella tabella seguente possono causare mal funzionamenti dello strumento.
Caratteristiche protocollo Modbus RTU
Baud-rate
Selezionabile da parametro 70
bd. rt.
:
4.8 k
4.800 bit/Sec.
9.6 k
9.600 bit/Sec.
19.2k
19.200 bit/Sec.
28.8 k
28.800 bit/Sec.
38 .4 k
38.400 bit/Sec.
57.6 k
57.600 bit/Sec.
Formato 8, N, 1 (8 bit, no parità, 1 stop)
Funzioni supportati
WORD READING (max 20 word) (0x03, 0x04) SINGLE WORD WRITING (0x06) MULTIPLE WORDS WRITING (max 20 word) (0x10)
Si riporta di seguito l’elenco di tutti gli indirizzi disponibili e le funzioni supportate:
RO Read Only R/W Read / Write WO Write Only
Modbus Address
Descrizione
Read
Only
Reset value
0 Tipo dispositivo RO EEPROM 1 Versione software RO EEPROM 5 Address slave R/W EEPROM
6 Versione boot RO EEPROM 50 Indirizzamento automatico WO ­51 Confronto codice impianto WO -
500 Caricamento valori di default (scrivere 9999) R/W 0
510 Tempo salvataggio setpoint in eeprom (0-60 s) R/W 10
999 Processo sottoposto al filtro in visualizzazione RO -
Page 70
70 - ATR243 - Manuale d’uso
Modbus Address
Descrizione
Read
Only
Reset value
1000
Processo (gradi con decimo per sensori di temperatura; digit per sensori normalizzati)
RO -
1001 Setpoint 1 R/W EEPROM 1002 Setpoint 2 R/W EEPROM 1003 Setpoint 3 R/W EEPROM 1004 Setpoint 4 R/W EEPROM 1005 Allarme 1 R/W EEPROM 1006 Allarme 2 R/W EEPROM 1007 Allarme 3 R/W EEPROM 1008 Setpoint gradiente RO EEPROM
1009
Stato relè (0 = Off, 1 = On): Bit 0 = Relè Q1 Bit 1 = Relè Q2 Bit 2 = Riservato Bit 3 = SSR
RO 0
1010 Percentuale uscita caldo (0-10000) RO 0
1011 Percentuale uscita freddo (0-10000) RO 0
1012
Stato allarmi (0 = Assente, 1 = Presente) Bit 0 = Allarme 1 Bit 1 = Allarme 2 Bit 2 = Allarme 3
RO 0
1013
Riarmo manuale: scrivere 0 per riarmare tutti gli allarmi. In lettura (0 = Non riarmabile, 1 = Riarmabile) Bit 0 = Allarme 1 Bit 1 = Allarme 2 Bit 2 = Allarme 3
WO 0
1014
Flags errori Bit 0 = Errore scrittura eeprom Bit 1 = Errore lettura eeprom Bit 2 = Errore giunto freddo Bit 3 = Errore processo (sonda) Bit 4 = Errore generico Bit 5 = Errore hardware Bit 6 = Errore L.B.A.O. Bit 7 = Errore L.B.A.C. Bit 8 = Errore tarature mancanti
RO 0
1015 Temperatura giunto freddo (gradi. decimi) RO -
1016
Start / Stop 0 = regolatore in STOP 1 = regolatore in START
R/W 0
1017
Lock conversion ON / OFF 0 = Lock conversion off 1 = Lock conversion on
R/W 0
1018
Tuning ON / OFF 0 = Tuning off 1 = Tuning on
R/W 0
1019
Selezione automatico / manuale 0 = Automatico 1 = Manuale
R/W 0
1020 Corrente T.A. ON (ampere con decimo) RO ­1021 Corrente T.A. OFF (ampere con decimo) RO 1022 Tempo OFF LINE* (millisecondi) R/W
Page 71
ATR243 - Manuale d’uso - 71
Modbus Address
Descrizione
Read
Only
Reset value
1023 Corrente istantanea (Ampere) R/W 0 1024 Stato ingresso digitale R/W 0
1025
Tuning sincronizzato per multizona 0 = Tuning OFF (Funzionamento normale del regolatore) 1 = Uscita comando OFF 2 = Uscita comando ON 3 = Start Tuning 4 = Fine Tuning e comando OFF (Portare la word 1025 al
valore 0)
R/W 0
1099
Processo sottoposto al filtro in visualizzazione e alla selezione del punto decimale
RO
1100 Processo con selezione del punto decimale RO
1101 Setpoint 1 con selezione del punto decimale R/W EEPROM 1102 Setpoint 2 con selezione del punto decimale R/W EEPROM 1103 Setpoint 3 con selezione del punto decimale R/W EEPROM
1104 Setpoint 4 con selezione del punto decimale R/W EEPROM
1105 Allarme 1 con selezione del punto decimale R/W EEPROM
1106 Allarme 2 con selezione del punto decimale R/W EEPROM
1107 Allarme 3 con selezione del punto decimale R/W EEPROM 1108 Setpoint gradiente con sel. del punto decimale RO EEPROM 1109 Percentuale uscita caldo (0-1000) R/W 0
1110 Percentuale uscita caldo (0-100) RO 0
1111 Percentuale uscita freddo (0-1000) RO 0
1112 Percentuale uscita freddo (0-100) RO 0 2001 Parametro 1 R/W EEPROM 2002 Parametro 2 R/W EEPROM 2072 Parametro 72 R/W EEPROM
3000 Disabilitazione controllo macchina da seriale** RO 0
3001 Prima word display 1 (ascii) R/W 0 3002 Seconda word display 1 (ascii) R/W 0
3003 Terza word display 1 (ascii) R/W 0 3004 Quarta word display 1 (ascii) R/W 0 3005 Quinta word display 1 (ascii) R/W 0 3006 Sesta word display 1 (ascii) R/W 0 3007 Settima word display 1 (ascii) R/W 0 3008 Ottava word display 1 (ascii) R/W 0 3009 Prima word display 2 (ascii) R/W 0
3010 Seconda word display 2 (ascii) R/W 0 3011 Terza word display 2 (ascii) R/W 0 3012 Quarta word display 2 (ascii) R/W 0 3013 Quinta word display 2 (ascii) R/W 0 3014 Sesta word display 2 (ascii) R/W 0 3015 Settima word display 2 (ascii) R/W 0 3016 Ottava word display 2 (ascii) R/W 0
Page 72
72 - ATR243 - Manuale d’uso
Modbus Address
Descrizione
Read
Only
Reset value
3017
Word LED Bit 0 = LED C1 Bit 1 = LED C2 Bit 2 = LED A1 Bit 3 = LED A2 Bit 4 = LED A3 Bit 5 = LED MAN Bit 6 = LED TUN Bit 7 = LED REM
R/W 0
3018
Word tasti (scrivere 1 per assumere il controllo dei tasti) Bit 0 = Bit 1 = Bit 2 =
SET
R/W 0
3019
Word relè seriale Bit 0 = Relè Q1 Bit 1 = Relè Q2 Bit 2 = Relè Q3
R/W 0
3020 Word SSR seriale (0 = Off, 1 = On) R/W 0 3021 Word uscita 0...10 V seriale (0…10000) R/W 0 3022 Word uscita 4...20 mA seriale (0…10000) R/W 0
3023
Word stato relè in caso di off-line (solo se controllati da seriale) Bit 0 = Relè Q1 Bit 1 = Relè Q2 Bit 2 = Relè Q3
R/W 0
3024
Word stato uscita SSR / 0…10 V / 4…20 mA in caso di off-line (solo se controllati da seriale) (0…10000)
R/W 0
3025
Word processo seriale. Impostando il parametro 54 è possibile mediare il processo remoto
R/W 0
4001 Parametro 1*** R/W EEPROM
4002 Parametro 2*** R/W EEPROM
4072 Parametro 72*** R/W EEPROM
* Se vale 0 il controllo è disabilitato. Se diverso da 0, è “Il tempo massimo che può trascorrere tra due inter-
rogazioni senza che il regolatore si porti in Off-Line”. In Off-Line il regolatore va in stato di Stop, disabilita l’uscita di comando, ma mantiene gli allarmi attivi.
** Con 1 su questa word, si annullano gli effetti della scrittura su tutti gli indirizzi Modbus da 3001 a 3022. Il
controllo ritorna al regolatore.
*** I parametri modificati usando gli indirizzi seriali dal 4001 al 4072, vengono salvati in eeprom solamente
dopo 10” dall’ultima scrittura di uno dei parametri.
Page 73
ATR243 - Manuale d’uso - 73
9 Accesso alla configurazione
Per parametri di configurazione vedi par. 10.
Premere Effetto Eseguire
1
SET
per 3 secondi
Su display 1 compare
0000
con la 1° cifra lampeggiante, mentre sul display 2 compare
PASS
.
2
o
Si modifica la cifra lampeggiante si passa alla successiva con il tasto
SET
.
Inserire la password
1234
.
3
SET
per conferma
Su display 1 compare il primo parametro e sul secondo il valore.
4
o
Scorre i parametri.
5
SET
o
Si incrementa o decrementa il valore visualizzato tenendo premuto prima
SET
e poi un
tasto freccia.
Inserire il nuovo dato che verrà salvato al rilascio dei tasti. Per variare un altro parametro tornare al punto 4.
6
+ contemporanea­mente
Fine variazione parametri di configurazione. Il regolatore esce dalla programmazione.
9.1 Caricamento valori di default
Questa procedura permette di ripristinare le impostazioni di fabbrica dello strumento.
Premere Effetto Eseguire
1
SET
per 3 secondi
Su display 1 compare
0000
con la 1° cifra lampeggiante, mentre sul display 2 compare
PASS
.
2
o
Si modifica la cifra lampeggiante si passa alla successiva con il tasto
SET
.
Inserire la password
9999
.
3
SET
per conferma
Lo strumento carica le impostazioni di fabbrica.
Spegnere e riaccendere lo strumento.
Page 74
74 - ATR243 - Manuale d’uso
10 Tabella parametri di configurazione
L’elenco dei parametri sotto riportato è completo; alcuni di questi non appariranno sui modelli che non dispongono delle relative risorse Hardware.
1
C.out
Command Output
selezione tipo uscita di comando (vedi tabelle sottostanti)
c. o1
Default (necessario per utilizzo funzione di ritrasmissione di processo e set con uscita Volt / mA)
c. o2
Comando su uscita relè Q2
3
c.SSr
Comando in tensione per SSR
20
c. u A L.
Comando servo-valvole a loop aperto
19
c.4 . 2 0
Comando con segnale 4...20 mA
20
c.0.20
Comando con segnale 0...20 mA
20
c.0.10
Comando con segnale 0...10 V
4
ATR243-20ABC
COMANDO ALLARME 1
c. o1
Q1 Q2
c. o2
Q2 Q1
c.SSr
SSR Q1
c. u A L.
Q1 (apri) / Q2 (chiudi) -
c.4 . 2 0
4 ... 20 mA Q1
c.0.20
0 ... 20 mA Q1
c.0.10
0 ... 10 V Q1
ATR243-21ABC-T
COMANDO ALLARME 1 ALLARME 2
c. o1
Q1 Q2 SSR
c. o2
Q2 Q1 SSR
c.SSr
SSR Q1 Q2
c. u A L.
Q1 (apri) / Q2 (chiudi) SSR -
c.4 . 2 0
4 ... 20 mA Q1 Q2
c.0.20
0 ... 20 mA Q1 Q2
c.0.10
0 ... 10 V Q1 Q2
ATR243-31ABC
COMANDO ALLARME 1 ALLARME 2 ALLARME 3
c. o1
Q1 Q2 Q3 SSR
c. o2
Q2 Q1 Q3 SSR
c.SSr
SSR Q1 Q2 Q3
c. u A L.
Q2 (apri) / Q3 (chiudi) Q1 SSR -
c.4 . 2 0
4 ... 20 mA Q1 Q2 Q3
c.0.20
0 ... 20 mA Q1 Q2 Q3
c.0.10
0 ... 10 V Q1 Q2 Q3
3
Solo su ATR243-20ABC non impostare se si utilizza la funzione di ritrasmissione del processo.
4
Non impostare mai se si utilizza la funzione di ritrasmissione del processo.
Page 75
ATR243 - Manuale d’uso - 75
2
SEN.
Sensor
Configurazione ingresso analogico/selezione sensore
Tc.K
Tc-K (Default) -260 °C ... 1360 °C
Tc. s
Tc-S -40 °C ... 1760 °C
Tc. r
Tc-R -40 °C ... 1760 °C
Tc. j
Tc-J -200 °C ... 1200 °C
Pt
Pt100 -200 °C ... 600 °C
P t1
Pt100 -200 °C ... 140 °C
ni
Ni100 -60 °C ... 180 °C
ntc
NTC10K -40 °C ... 125 °C
Ptc
PTC1K -50 °C ... 150 °C
Pts
Pt500 -100 °C ... 600 °C
P t1 k
Pt1000 -100 °C ... 600 °C
0 .1 0
0..10 Volt
0.20
0..20 mA
4.20
4..20 mA
0.4 0
0..40 mVolt
P o t .1
Potenziometro max. 6 KOhm (Vedi par. 7.9)
Po t.2
Potenziometro max. 150 KOhm (Vedi par. 7.9)
t.A.
T.A. con secondario 50 mA (solo ATR243-21/31ABC)
3
d . P.
Decimal Point
Seleziona il tipo di decimale visualizzato
0
Default
0.0
1 Decimale
0.00
2 Decimali
0.000
3 Decimali
4
Lo .L.S.
Lower Limit Setpoint
Limite inferiore impostabile per il setpoint
-999…+9999 [digit
5
] (gradi.decimi per sensori di temperatura), Default: 0.
5
u p.L.S.
Upper Limit Setpoint
Limite superiore impostabile per il setpoint
-999…+9999 [digit
5
] (gradi.decimi per sensori di temperatura)
Default: 1750.
6
Lo L.i
Lower Linear Input
Limite inferiore range AN1 solo per normalizzati. Es: con ingresso 4...20 mA questo parametro assume il valore associato a 4 mA
-999 bis +9999 [digit
5
], Default: 0.
7
u p.L.i .
Upper Linear Input
Limite superiore range AN1 solo per normalizzati. Es: con ingresso 4...20 mA questo parametro assume il valore associato a 20 mA
-999 bis +9999 [digit
5
], Default: 1000.
Page 76
76 - ATR243 - Manuale d’uso
8
La tc.
Latch On Function
Impostazione automatica dei limiti per ingressi normalizzati e potenziometri. (vedi pa r. 7.9)
di s .
Disabilitato (Default)
std.
Standard
u.0s t.
Zero virtuale memorizzato
u . 0i n
Zero virtuale allo Start
dYn.L
Permette di superare i limiti inferiore e superiore se in ingresso ci sono
valori esterni al 0/4..20mA o 0..10V.
9
o . cAL.
Offset Calibration
Calibrazione offset. Valore che si somma o sottrae al processo visualizzato (es: normalmente corregge il valore di temperatura ambiente).
-999…+1000 [digit
5
] per sensori normalizzati e potenziometri.
-200.0…+100.0 (gradi.decimi per sensori di temperatura), Default 0.0.
10
G. cA L.
Gain Calibration
Calibrazione guadagno AI1. Valore che si moltiplica al processo per eseguire calibrazione sul punto di lavoro.
-99.9%..+100.0%, Default: 0.0. es: per correggere la scala di lavoro da 0...1000°C che visualizza 0...1010°C, fissare il parametro a -1.0
11
Act. t.
Action type
Heat
Caldo (N.A.) (Default)
cooL
Freddo (N.C.)
H.o.o.S.
Blocca comando sopra SPV. Es: uscita di comando disabilitata al raggiungi-
mento del setpoint anche con valore di P.I.D. diverso da zero.
12
c. re.
Command Reset
Tipo di riarmo del contatto di comando (sempre automatico in funzionamento P.I.D.)
a re.
Riarmo automatico (Default)
m re.
Reset manuale
m re.s.
Reset manuale memorizzato (mantiene lo stato del relè anche dopo un
eventuale mancanza di alimentazione)
13
c. S.e.
Command State Error
Stato del contatto per l’uscita di comando in caso di errore
c. o.
Contatto aperto (Default)
c. c.
Contatto chiuso
14
c. Ld.
Command Led
Definisce lo stato del led OUT1 in corrispondenza del relativo contatto
c. o.
Acceso a contatto aperto
c. c.
Acceso a contatto chiuso (Default)
Page 77
ATR243 - Manuale d’uso - 77
15
c. HY.
Command Hysteresis
Isteresi in ON/OFF o banda morta in P.I.D.
-999…+999 [digit
5
] (gradi.decimi per sensori di temperatura)
,
Default
0.0.
16
c. d e.
Command Delay
Ritardo comando (solo in funzionamento ON / OFF). In caso di servo valvola funziona anche in P.I.D. e rappresenta il ritardo tra l’apertura e la chiusura dei due contatti.
-180…+180 secondi (
decimi di secondo
in caso di servo valvola). Negativo: ritardo in fase di spegnimento. Positivo: ritardo in fase di accensione. Default: 0.
17
c. s. p.
Command Setpoint Protection
Consente o meno di variare il valore del setpoint di comando
free
Modificabile dall’utente (Default)
Lo c k
Protetto
18
p. b.
Proportional Band
Banda proporzionale. Inerzia del processo in unità (es: se temperatura in °C) 0 ON / OFF se
t.i .
uguale a 0 (Default)
1-9999 [digit
5
] (gradi per sensori di temperatura)
19
t.i .
Integral Time
Tempo integrale. Inerzia del processo in secondi.
0.0-999.9 secondi (0 = integrale disabilitato), Default 0.0
20
t.d.
Derivative Time
Tempo derivativo. Normalmente ¼ del tempo integrale.
0.0-999.9 secondi (0 = derivativo disabilitato), Default 0.0
21
t. c.
Cycle Time
Tempo di ciclo (per P.I.D. su teleruttore 10 / 15 sec, per P.I.D. su SSR 1 sec.) o tempo servo-motore (valore dichiarato da produttore)
1-300 secondi (Default: 10)
22
o .Po L.
Output Power Limit
Seleziona il valore massimo per la percentuale dell’uscita di comando 0…100 % , Default: 100%. Es: con
c.out
selezionato 0...10 V e impostazione su
o . P o L.
al 90%, l’uscita di
comando può variare da un minimo di 0 V al massimo di 9 V.
5
Dipende dall’impostazione del parametro
sen.
e del parametro
d. p.
Page 78
78 - ATR243 - Manuale d’uso
23
A L.1
Alarm 1
Selezione allarme 1. L’intervento dell’allarme è associato a AL1. (vedi par. 11)
di s .
Disabilitato (Default)
A. AL.
Assoluto / soglia, riferito al processo
b . AL.
Allarme di banda
H. d .AL.
Allarme di deviazione superiore
L. d .AL.
Allarme di deviazione inferiore
A. c.AL.
Assoluto / soglia, riferito al setpoint di comando
s t. A L.
Allarme di stato (attivo in Run / Start)
cooL
Azione freddo (cooling) (vedi par. 7.12)
L. b .A.
Allarme di stato “controllo carico” (Loop Break Alarm)
Es: controlla lo stato dei contattori / SSR o delle resistenze
24
A.I.5.0
Alarm 1 State Output
Contatto uscita allarme 1 e tipo intervento.
n . o. s.
(N.O. Start) Normalmente aperto, operativo dallo start (Default)
n . c. s.
(N.C. Start) Normalmente chiuso, operativo dallo start
n . o. t.
(N.O. Threshold) Normalmente aperto, operativo al raggiungimento
dell’allarme
6
n . c. t.
(N.C. Threshold) Normalmente chiuso, operativo al raggiungimento
dell’allarme
6
25
a1 . r e .
Alarm 1 Reset
Tipo di reset del contatto dell’allarme 1
a re.
Automatic Reset (Default)
m re.
Reset manuale (riarmo/reset manuale da tastiera)
SET
m re.s.
Reset Manuale memorizzato (mantiene lo stato del relè anche dopo un
eventuale mancanza di alimentazione)
26
a .1 . s . e .
Alarm 1 State Reset
Stato del contatto per l’uscita di allarme 1 in caso di errore
c. o.
Contatto aperto (Default)
c. c.
Contatto chiuso
27
a.1.Ld.
Alarm 1 Led
Definisce lo stato del led OUT2 in corrispondenza del relativo contatto
c. o.
Acceso a contatto aperto
c. c.
Acceso a contatto chiuso (Default)
6
All’accensione, l’uscita è inibita se lo strumento è in condizione di allarme. Si attiva solo quando rientrato dalla condizione d’allarme, questa si ripresenta.
Page 79
ATR243 - Manuale d’uso - 79
28
a .1 . H y .
Alarm 1 Hysteresis
Isteresi allarme 1
-999…+999 [digit
7
] (gradi.decimi per sensori di temperatura), Default: 0.0.
29
a .1 . d e .
Alarm 1 Delay
Ritardo allarme 1. -180…+180 secondi. Default: 0. Negativo: ritardo in fase di uscita dall’allarme. Positivo: ritardo in fase di entrata dell’allarme.
30
a .1 . s p .
Alarm 1 Setpoint Protection
Protezione set allarme 1. Non consente all’utente di variare il setpoint
free
Modificabile dall’utente (Default)
Lo c k
Protetto
Hi d e
Protetto e non visualizzato
31
AL. 2
Alarm 2
Selezione allarme 2. L’intervento dell’allarme è associato a AL2. (vedi par. 11)
di s .
Disabilitato (Default)
A. AL.
Assoluto / soglia, riferito al processo
b . AL.
Allarme di banda
H. d .AL.
Allarme di deviazione superiore
L. d .AL.
Allarme di deviazione inferiore
A. c.AL.
Assoluto / soglia, riferito al setpoint di comando
s t. A L.
Allarme di stato (attivo in Run / Start)
cooL
Azione freddo (cooling) (vedi par. 7.12)
L. b .A.
Allarme di stato “controllo carico” (Loop Break Alarm)
Es: controlla lo stato dei contattori / SSR o delle resistenze
32
a .2. s o .
Alarm 2 State Output
Contatto uscita allarme 2 e tipo intervento
n . o. s.
(N.O. Start) Normalmente aperto, operativo dallo start (Default)
n . c. s.
(N.C. Start) Normalmente chiuso, operativo dallo start
n . o. t.
(N.O. Threshold) Normalmente aperto, operativo al raggiungimento
dell’allarme
8
n . c. t.
(N.C. Threshold) Normalmente chiuso, operativo al raggiungimento
dell’allarme
8
7
Dipende dall’impostazione del parametro
sen.
e del parametro
d. p.
8
All’accensione, l’uscita è inibita se lo strumento è in condizione di allarme. Si attiva solo quando rientrato dalla condizione d’allarme, questa si ripresenta.
Page 80
80 - ATR243 - Manuale d’uso
33
A2. r e.
Alarm 2 Reset
Tipo di riarmo del contatto dell’allarme 2.
Are.
Reset automatico (Default)
m re.
Reset manuale (riarmo/reset manuale da tastiera)
SET
m re.s.
Reset manuale memorizzato (mantiene lo stato del relè anche dopo un
eventuale mancanza di alimentazione)
34
a .2. s . e .
Alarm 2 State Error
Stato del contatto per l’uscita di allarme 2 in caso di errore.
c. o.
Contatto aperto (Default)
c. c.
Contatto chiuso
35
a.2.Ld.
Alarm 2 Led
Definisce lo stato del led OUT2 in corrispondenza del relativo contatto.
c. o.
Acceso a contatto aperto
c. c.
Acceso a contatto chiuso (Default)
36
a.2.HY.
Alarm 2 Hysteresis
-999…+999 [digit9] (gradi.decimi per sensori di temperatura), Default: 0.0.
37
a.2.d.e.
Alarm 2 Delay
-180…+180 secondi. Negativo: ritardo in fase di uscita dall’allarme. Positivo: ritardo in fase di entrata dell’allarme. Default: 0.
38
a .2. s . p .
Alarm 2 Setpoint Protection
Non consente all’operatore di variare il valore impostato.
free
Modificabile dall’utente (Default)
Lo c k
Protetto
Hi d e
Protetto e non visualizzato
39
AL. 3
Alarm 3
Selezione allarme 3. L’intervento dell’allarme è associato a AL3. (vedi par. 11)
di s .
Disabilitato (Default)
A. AL.
Assoluto / soglia, riferito al processo
b . AL.
Allarme di banda
H. d .AL.
Allarme di deviazione superiore
L. d .AL.
Allarme di deviazione inferiore
A. c.AL.
Assoluto / soglia, riferito al setpoint di comando
s t. A L.
Allarme di stato (attivo in Run / Start)
cooL
Azione freddo (cooling) (vedi par. 7.12)
L. b .A.
Allarme di stato “controllo carico” (Loop Break Alarm).
Es: controlla lo stato dei contattori / SSR o delle resistenze
9
Dipende dall’impostazione del parametro
sen.
e del parametro
d. p.
Page 81
ATR243 - Manuale d’uso - 81
40
a .3.5. o .
Alarm 3 State Output
Contatto uscita allarme 3 e tipo intervento.
n . o. s.
(N.O. Start) Normalmente aperto, operativo dallo start (Default)
n . c. s.
(N.C. Start) Normalmente chiuso, operativo dallo start
n . o. t.
(N.O. Threshold) Normalmente aperto, operativo al raggiungimento
dell’allarme
10
n . c. t.
(N.C. Threshold) Normalmente chiuso, operativo al raggiungimento
dell’allarme
10
41
a .3. re.
Alarm 3 Reset
Tipo di riarmo del contatto dell’allarme 3.
a re.
Reset automatico (Default)
m re.
Reset manuale (riarmo/reset manuale da tastiera)
m re.
Reset manuale memorizzato (mantiene lo stato del relè anche dopo un
eventuale mancanza di alimentazione)
42
a .3.s . e.
Alarm 3 State Error
Stato del contatto per l’uscita di allarme 3 in caso di errore.
c. o.
Contatto aperto (Default)
c. c.
Contatto chiuso
43
a.3.Ld.
Alarm 3 LED
Definisce lo stato del led OUT3 in corrispondenza del relativo contatto.
c. o.
Acceso a contatto aperto
c. c.
Acceso a contatto chiuso (Default)
44
a .3.HY.
Alarm 3 Hysteresis
Isteresi allarme 3
-999…+999 [digit
11
] (gradi.decimi per sensori di temperatura), Default: 0.0.
45
a .3. d e.
Alarm 3 Delay
Ritardo allarme 3. -180…+180 secondi. Default: 0. Negativo: ritardo in fase di uscita dall’allarme. Positivo: ritardo in fase di entrata dell’allarme.
46
a .3.s . p.
Alarm 3 Setpoint Protection
Protezione set allarme 3. Non consente all’operatore di variare il valore impostato.
free
Modificabile dall’utente (Default)
Lo c k
Protetto
Hi d e
Protetto e non visualizzato
10
All’accensione, l’uscita è inibita se lo strumento è in condizione di allarme. Si attiva solo quando rientrato dalla condizione d’allarme, questa si ripresenta.
11
Dipende dall’impostazione del parametro
sen.
e del parametro
d. p.
Page 82
82 - ATR243 - Manuale d’uso
47
t.a.
Amperometric Transformer
Abilitazione e range di fondo-scala del trasformatore amperometrico.
0 Disabilitato. 1-200 Ampere Default: 0
48
L.b.a.t.
Loop Break Alarm Threshold
Soglia di intervento del Loop Break Alarm.
0.0-200.0 Ampere. Default: 50.0
49
L.b.a.d.
Loop Break Alarm Delay
Tempo di ritardo per l’intervento del Loop Break Alarm.
00.00-60.00 mm.ss (Default: 01.00)
50
co o . f.
Cooling Fluid
Tipo di fluido refrigerante in modalità P.I.D. caldo / freddo
Ai r
Aria (Default)
oi L
Olio
H2o
Acqua
51
p.b.m.
Proportional Band Multiplier
Moltiplicatore di banda proporzionale. La banda proporzionale per l’azione freddo è data dal valore del parametro 18 moltiplicato per questo valore.
1.00-5.00 (Default: 1.00)
52
oud.b.
Overlap / Dead Band
Sovrapposizione / Banda Morta. In modalità P.I.D. caldo / freddo (doppia azione) definisce la combinazione di banda morta per l’azione di riscaldamento e raffred­damento.
-20.0-50.0% del valore di banda proporzionale (Default: 0). Negativo indica il valore di banda morta, positivo significa la sovrapposizione.
53
co.t.c.
Cooling Cycle Time
Tempo ciclo per uscita refrigerante. 1-300 secondi, Default: 10.
Page 83
ATR243 - Manuale d’uso - 83
54
c. fLt.
Conversion Filter
Filtro ADC: numero di letture del sensore di ingresso per il calcolo della media che definisce il valore del processo. NB: con l’aumento delle medie rallenta la velocità del loop di controllo.
di s .
Disabilitato
2. s . m .
Media con 2 campionamenti
3. s. m .
Media con 3 campionamenti
4. s. m .
Media con 4 campionamenti
5. s. m .
Media con 5 campionamenti
6. s. m .
Media con 6 campionamenti
7. s . m .
Media con 7 campionamenti
8. s. m .
Media con 8 campionamenti
9. s. m .
Media con 9 campionamenti
10.s. m .
Media con 10 campionamenti (Default)
11 . s . m .
Media con 11 campionamenti
12. s . m .
Media con 12 campionamenti
13.s . m .
Media con 13 campionamenti
14.s . m .
Media con 14 campionamenti
15.s . m .
Media con 15 campionamenti
55
c. frn .
Conversion Frequency
Frequenza di campionamento del convertitore analogico-digitale. NB: Aumentando la velocità di conversione diminuisce la stabilità di lettura (es: per transitori veloci come la pressione consigliabile aumentare la frequenza di campionamento).
242H.
242 Hz (Massima velocità di conversione)
123H.
123 Hz
62 H.
62 Hz
50 H.
50 Hz
39 H.
39 Hz
33.2H.
33.2 Hz
19.6H.
19.6 Hz
1 6.7 H.
16.7 Hz (Default) Ideale per filtraggio disturbi 50 / 60 Hz
12.5H.
12.5 Hz
10 H.
10 Hz
8.33H.
8.33 Hz
6.25H.
6.25 Hz
4 .1 7 H .
4.17 Hz (Minima velocità di conversione)
Page 84
84 - ATR243 - Manuale d’uso
56
u . FLt.
Visualization Filter
Filtro in visualizzazione. Rallenta l’aggiornamento del valore di processo visualizzato sul display per facilitarne la lettura.
di s .
Disabilitato e filtro a “forchetta” (massima velocità di aggiornamento
display) (Default)
fi . o r.
Filtro del primo ordine con filtro a “forchetta”
2. s . m .
Media con 2 campionamenti
3. s. m .
Media con 3 campionamenti
4. s. m .
Media con 4 campionamenti
5. s. m .
Media con 5 campionamenti
6. s. m .
Media con 6 campionamenti
7. s . m .
Media con 7 campionamenti
8. s. m .
Media con 8 campionamenti
9. s. m .
Media con 9 campionamenti
10.s. m .
Media con 10 campionamenti (massimo rallentamento di aggiornamento
display)
n u LL
Disabilitato senza filtro a “forchetta”
f. o . 2
Filtro del primo ordine
57
tune
Tune
Selezione tipo autotuning. (Vedi par. 7.2)
diS.
Disabilitato (Default)
Auto
Automatico (Calcolo parametri P.I.D. all’accensione e al variare del set)
Man.
Manuale (Lanciato dai tasti o da ingresso digitale)
sYn c.
Sincronizzato [Vedere word modbus 1025 (solo ATR243-21ABC-T)]
58
s.d.tu.
Setpoint Deviation Tune
Imposta la deviazione dal setpoint di comando come soglia usata dall’ autotuning, per il calcolo dei parametri P.I.D. 0-5000 [digit
12
] (decimi di grado se temperatura), Default: 10.
59
op.mo.
Operating Mode
Selezione funzionamento. (vedi par. 7.7 e 7.11)
co n t.
Regolatore (Default)
p r. cY.
Ciclo pre-programmato
2t.s .
Cambio set da ingresso digitale
2t .s .i .
Cambio set da ingresso digitale con comando ad impulso
3 t . s .i .
Cambio di 3 set da ingresso digitale con comando ad impulso
4 t . s .i .
Cambio di 4 set da ingresso digitale con comando ad impulso
t. res .
Time reset (funzione personalizzata)
p.c.s.s.
Ciclo pre-programmato con Start / Stop solo da ingresso digitale
S.S. cY
Come
p r. cY.
, ma con alcune varianti)
12
Dipende dall’impostazione del parametro
sen.
e del parametro
d. p.
Page 85
ATR243 - Manuale d’uso - 85
60
au.ma.
Automatic / Manual
Abilita la selezione automatico/manuale. (Vedi par. 7.6)
di s .
Disabilitato (Default)
En.
Abilitato
En .St.
Abilitato con memoria
61
d G t.i .
Digital Input
Funzionamento ingresso digitale (sel P59 deve essere
co n t.
o
Pr. cY.
). (Vedi par. 7.11)
di s .
Disabilitato (Default)
st.st.
Ciclo pre-programmato con Start / Stop
rn.n.o.
Run N.O. (abilita regolazione con contatto normalmente aperto)
rn.n.c.
Run N.C. (abilita regolazione con contatto normalmente chiuso)
L.c.n.o.
Lock conversion N.O. (funzione mantenimento visualizzazione)
L.c.n.c.
Lock conversion N.C.
tu n e
Tune (abilita l’auto-tuning manualmente)
a.ma.i.
Automatic / manual impulsive (se abilitato su parametro 60)
a.ma.c.
Automatic / manual contact (se abilitato su parametro 60)
62
Grad .
Gradient
Gradiente di salita per Soft-Start o ciclo pre-programmato.
0 Disabilitato 1-9999 [Digit/hour
13
] (gradi/ora con visualizzazione in decimi per sensori di
temperatura), Default: 0.
63
m a . ti .
Maintenance Time
Tempo mantenimento per ciclo pre-programmato
00.00-24.00 hh.mm. Default: 00.00
64
u.m.c.p.
User Menu Cycle Programmed
Permette di modificare gradiente di salita e tempo di mantenimento dal menù utente, in funzionamento ciclo pre-programmato
SET
di s .
Disabilitato (Default)
Grad .
Solo gradiente
m a . ti .
Solo tempo di mantenimento
ALL
Sia gradiente che tempo di mantenimento
65
ui . tY.
Visualization Type
Definisce la visualizzazione per il display 1 e 2.
1. p . 2. s .
1 Processo, 2 Setpoint (Default)
1. p.2.H.
1 Processo, 2 si spegne dopo 3 sec.
1.s.2.P.
1 Setpoint, 2 Processo
1.s.2.H.
1 Setpoint, 2 si spegne dopo 3 sec.
1.p.2.a.
1 Processo, 2 Ampere (da ingresso T.A.)
13
Dipende dall’impostazione del parametro
sen.
e del parametro
d. p.
Page 86
86 - ATR243 - Manuale d’uso
66
d eG r.
Degree
Selezione tipo gradi
c
Gradi Centigradi (Default)
f
Gradi Fahrenheit
67
re t r.
Retransmission
Ritrasmissione per uscita 0-10 V o 4..20 mA (Selezionare Jumper JP5, JP7 e JP9). Parametri 68 e 69 definiscono il limite inf. e sup. della scala di funzionamento.
di s .
Disabilitato
u o . p.
Ritrasmette il processo in Volt
m a . p.
Ritrasmette il processo in mA
u o . c.
Ritrasmette il setpoint di comando in Volt
m a . c.
Ritrasmette il setpoint di comando in mA
uo.o.p.
Volt uscita percentuale comando
ma.o.p.
mA uscita percentuale comando
uo.a.1
Volt setpoint di allarme 1
ma.a.1
mA setpoint di allarme 1
uo.a.2
Volt setpoint di allarme 2
ma.a.2
mA setpoint di allarme 2
uo.t.a.
Volt T.A.
ma.t.a.
mA T.A.
68
Lo . L. r.
Lower Limit Retransmission
Limite inferiore range ritrasmissione uscita Volt/mA
-999…+9999 [digit
14
] (gradi.decimi per sensori di temperatura), Default: 0.
69
up.L.r.
Upper Limit Retransmission
Limite superiore range ritrasmissione uscita Volt/mA.
-999…+9999 [digit14] (gradi.decimi per sensori di temperatura), Default: 1000.
70
bd . rt.
Baud Rate
Seleziona il baud rate per la comunicazione seriale
4.8 k
4.800 Bit/s
9.6 k
9.600 Bit/s
19.2k
19.200 Bit/s (Default)
28.8 k
28.800 Bit/s
39.4 k
39.400 Bit/s
57.6 k
57.600 Bit/s
71
sL. a d .
Slave Address
Seleziona l’indirizzo dello slave per la comunicazione seriale. 1 – 254. Default: 254
14
La visualizzazione del punto decimale dipende dall’impostazione del parametro
sen.
e del parametro
d. p.
Page 87
ATR243 - Manuale d’uso - 87
72
se. d e.
Serial Delay
Seleziona il ritardo seriale
0 – 100 millisecondi. Default: 20
73
L.L. o . p.
Lower Limit Output Percentage
Seleziona il valore minimo per la percentuale dell’uscita di comando. 0 – 100%, Default: 0%. Es: con
c.out
selezionato 0...10 V e impostazione su
L.L. o .P.
al 10%, l’uscita di comando
può variare da un minimo di 1 V al massimo di 10 V.
11 Modi d’intervento allarme
11.a Allarme assoluto o allarme di soglia (selezione
a . AL.
)
1
Alarm Spv
Pv
O
On On
O
Hysteresis parameter  > 0
Time
Alarm output
Allarme assoluto con regolatore in funzionamento caldo (par. 11
Act.t.
selezionato
Heat
) e valore di isteresi maggiore
di “0” (par. 28
A.1.HY.
> 0). *
2
Alarm Spv
O
On On
O
Hysteresis parameter  < 0
Time
Alarm output
Allarme assoluto con regolatore in funzionamento caldo (par. 11
Act.t.
selezionando
Heat
) e valore di isteresi minore
di “0” (par. 28
A.1.HY.
< 0). *
3
Alarm Spv
O
On On
O
Hysteresis parameter  > 0
Time
Alarm output
Allarme assoluto con regolatore in funzionamento freddo (par. 11
Act.t.
selezionando
Heat
) e valore di isteresi
maggiore di “0” (par. 28
A.1.HY.
> 0). *
Page 88
88 - ATR243 - Manuale d’uso
4
Time
O O
On On
Alarm Spv
Pv
Hysteresis
parameter
 < 0
Alarm
output
Allarme assoluto con regolatore in funzionamento freddo (par. 11
Act.t.
selezionato
cooL
) e valore di isteresi minore di
“0” (par. 28
A.1.HY.
< 0). *
11.b Allarme assoluto o allarme di soglia riferito al setpoint di comando
(selezione
a . c. AL.
)
1
O O
Time
Alarm Spv
Hysteresis parameter  > 0
Alarm
output
Comand Spv
Allarme assoluto riferito al set di comando, con regolatore in funzionamento caldo (par. 11
Act.t.
selezionando
Heat
) e valore di isteresi
maggiore di “0” (par. 28
A.1.HY.
> 0). Il set di comando può essere variato con la pressione dei tasti freccia da frontale o con comandi su porta seriale RS485. *
11.c Allarme di Banda (selezione
b . AL.
)
1
Pv
Alarm Spv
O O
On On On
Hysteresis parameter  > 0
Time
Alarm output
Allarme di banda valore di isteresi maggiore di “0” (par. 28
A.1.HY.
> 0). *
2
Pv
Alarm Spv
O O
On On On
Hysteresis
parameter  < 0
Hysteresis parameter  < 0
Time
Alarm output
Comand Spv
Allarme di banda valore di isteresi minore di “0” (par. 28
A.1.HY.
< 0). *
* L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per gli allarmi 2 e 3 sui modelli che li
prevedono.
Page 89
ATR243 - Manuale d’uso - 89
11.d Allarme deviazione superiore (selezione
H. d .AL.
)
1
Pv
Comand Spv
Alarm Spv
O O
On On
Hysteresis parameter  > 0
Time
Alarm
output
Allarme di deviazione superiore e valore di setpoint allarme maggiore di “0” e valore di isteresi maggiore di “0” (par. 28
A.1.HY.
> 0). **
2
Pv
Comand Spv Alarm Spv
O O
On On
Hysteresis parameter  > 0
Time
Alarm
output
Allarme di deviazione superiore valore di setpoint allarme minore di “0” e valore di isteresi maggiore di “0” (par. 28
A.1.HY.
> 0). **
11.e Allarme deviazione inferiore (selezione
L. d .AL.
)
1
Pv
Comand Spv
Alarm Spv
O O
On On
Hysteresis parameter  > 0
Time
Alarm output
Allarme di deviazione inferiore valore di setpoint allarme maggiore di “0” e valore di isteresi maggiore di “0” (par. 28
A.1.HY.
> 0). **
2
Pv
Comand Spv
Alarm Spv
O O
On On
Hysteresis parameter  > 0
Time
Alarm output
Allarme di deviazione inferiore valore di setpoint allarme minore di “0” e valore di isteresi maggiore di “0” (par. 28
A.1.HY.
> 0). **
** a) L’esempio è riferito all’allarme 1; la funzione è abilitabile anche per gli allarmi 2 e 3 sui modelli che li
prevedono. b) Con isteresi minore di “0” (
A.1.HY.
< 0) la linea tratteggiata si sposta sopra il setpoint di
allarme.
Page 90
90 - ATR243 - Manuale d’uso
12 Tabella segnalazioni anomalie
In caso di mal funzionamento dell’impianto il controllore spegne l’uscita di regolazione e segnala il tipo di anomalia riscontrata. Per esempio il regolatore segnalerà la rottura di un’eventuale termocoppia collegata visualizzando
e -05
(lampeggiante) sul display 1 e
una breve descrizione
prb.
(sonda) sul display 2.
Per le altre segnalazioni vedere la tabella sottostante.
Causa Cosa fare
E- 01
SYS.E
Errore in programmazione cella EEPROM.
Contattare Assistenza.
E-02
SYS.E
Guasto sensore temperatura giunto freddo o temperatura ambiente al di fuori dei limiti ammessi.
Contattare Assistenza.
E-04
SYS.E
Dati di configurazione errati. Possibile perdita della tarature dello strumento.
Verificare che i parametri di configurazione siano corretti.
E-05
prb.
Termocoppia aperta o temperatura fuori limite.
Controllare il collegamento con le sonde e la loro integrità.
E-08
SYS.E
Tarature mancanti. Contattare Assistenza.
13 Configurazione EASY-UP
Per semplificare il più possibile il lavoro di parametrizzazione della catena di controllo, Pixsys presenta una nuova modalità a codici che consente di configurare con un unico e semplice passaggio ingressi sonda e/o uscite di comando. La modalità EASY-UP tramite il codice presente sulla documentazione tecnica allegata al sensore o all’attuatore (SSR, val­vola-motorizzata, ecc…) configura sullo strumento i relativi parametri (esempio per una PT100 il parametro “SEN”, e la scala di utilizzo “Valore minimo di set” e “Valore massimo”). I codici possono essere utilizzati in sequenza per settare sia ingressi che uscite comando o modalità di ritrasmissione del segnale.
Password 2200
P2
SEN.
Sensor
PT
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 500,
Password 2201
P2
SEN.
Sensor
PT
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 250,
Password 2202
P2
SEN.
Sensor
ptc
,
P4
Lo .L.S.
Lower Limit Setpoint -50,
P5
u p.L.S.
Upper Limit Setpoint 150,
Page 91
ATR243 - Manuale d’uso - 91
Password 2203
P2
SEN.
Sensor
ntc
,
P4
Lo .L.S.
Lower Limit Setpoint -40,
P5
u p.L.S.
Upper Limit Setpoint 125,
Password 2301
P2
SEN.
Sensor
tc. j
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 400,
Password 2351
P2
SEN.
Sensor
tc. k
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 800,
Password 2352
P2
SEN.
Sensor
tc. k
,
P4
Lo .L.S.
Lower Limit Setpoint -100,
P5
u p.L.S.
Upper Limit Setpoint 600,
Password 2401
P2
SEN.
Sensor
4.20
,
P4
Lo .L.S.
Lower Limit Setpoint 0,
P5
u p.L.S.
Upper Limit Setpoint 100,
P6
Lo L.i
Lower Linear Input 0,
P7
u p.L.i .
Upper Linear Input 100,
Password 4400
P1
C.out
Command Output
c.SSr
,
P21
t. c.
Cycle Time 1,
P57
tune
Tune
Auto
,
Password 4600
P1
C.out
Command Output
c.vaL.
,
P21
t. c.
Cycle Time 60,
P57
tune
Tune
Auto
,
Password 6501
P1
C.out
Command Output
c. 01
,
P67
re t r.
Retransmission
m a . p
,
P68
Lo . L. r.
Lower Limit Retransmission -100,
P69
up.L.r.
Upper Limit Retransmission 250,
Page 92
92 - ATR243 - Manuale d’uso
Password 6502
P1
C.out
Command Output
c. 01
,
P67
re t r.
Retransmission
v o . p
,
P68
Lo . L. r.
Lower Limit Retransmission -100,
P69
up.L.r.
Upper Limit Retransmission 250,
Note / Aggiornamenti
Page 93
ATR243 - Manuale d’uso - 93
Tabella delle configurazioni dei parametri
1
C.out
Command Output 74
2
SEN.
Sensor 75
3
d . P.
Decimal Point 75
4
Lo .L.S.
Lower Limit Setpoint 75
5
u p.L.S.
Upper Limit Setpoint 75
6
Lo L.i
Lower Linear Input 75
7
u p.L.i .
Upper Linear Input 75
8
La tc.
Latch On Function 76
9
o . cAL.
Offset Calibration 76
10
G. cAL.
Gain Calibration 76
11
Act. t.
Action type 76
12
c. re.
Command Reset 76
13
c. S.e.
Command State Error 76
14
c. Ld.
Command Led 76
15
c. HY.
Command Hysteresis 77
16
c. d e.
Command Delay 77
17
c. s. p.
Command Setpoint Protection 77
18
p. b.
Proportional Band 77
19
t.i .
Integral Time 77
20
t.d.
Derivative Time 77
21
t. c.
Cycle Time 77
22
o .Po L.
Output Power Limit 77
23
A L.1
Alarm 1 78
24
A.I.5.0
Alarm 1 State Output 78
25
a1 . r e .
Alarm 1 Reset 78
26
a .1 . s . e .
Alarm 1 State Reset 78
27
a.1.Ld.
Alarm 1 Led 78
28
a .1 . H y .
Alarm 1 Hysteresis 79
29
a .1 . d e .
Alarm 1 Delay 79
30
a .1 . s p .
Alarm 1 Setpoint Protection 79
31
AL. 2
Alarm 2 79
32
a .2. s o .
Alarm 2 State Output 79
33
A2. r e.
Alarm 2 Reset 80
34
a .2. s . e .
Alarm 2 State Error 80
35
a.2.Ld.
Alarm 2 Led 80
36
a.2.HY.
Alarm 2 Hysteresis 80
37
a.2.d.e.
Alarm 2 Delay 80
38
a .2. s . p .
Alarm 2 Setpoint Protection 80
39
AL. 3
Alarm 3 80
40
a .3.5. o .
Alarm 3 State Output 81
41
a .3. re.
Alarm 3 Reset 81
42
a .3.s . e.
Alarm 3 State Error 81
43
a.3.Ld.
Alarm 3 LED 81
Page 94
94 - ATR243 - Manuale d’uso
44
a .3.HY.
Alarm 3 Hysteresis 81
45
a .3. d e.
Alarm 3 Delay 81
46
a .3.s . p.
Alarm 3 Setpoint Protection 81
47
t.a.
Amperometric Transformer 82
48
L.b.a.t.
Loop Break Alarm Threshold 82
49
L.b.a.d.
Loop Break Alarm Delay 82
50
co o . f.
Cooling Fluid 82
51
p.b.m.
Proportional Band Multiplier 82
52
oud.b.
Overlap / Dead Band 82
53
co.t.c.
Cooling Cycle Time 82
54
c. fLt.
Conversion Filter 83
55
c. frn .
Conversion Frequency 83
56
u . FLt.
Visualization Filter 84
57
tune
Tune 84
58
s.d.tu.
Setpoint Deviation Tune 84
59
op.mo.
Operating Mode 84
60
au.ma.
Automatic / Manual 85
61
d G t.i .
Digital Input 85
62
Grad .
Gradient 85
63
m a . ti .
Maintenance Time 85
64
u.m.c.p.
User Menu Cycle Programmed 85
65
ui . tY.
Visualization Type 85
66
d eG r.
Degree 86
67
re t r.
Retransmission 86
68
Lo . L. r.
Lower Limit Retransmission 86
69
up.L.r.
Upper Limit Retransmission 86
70
bd . rt.
Baud Rate 86
71
sL. a d .
Slave Address 86
72
se. d e.
Serial Delay 87
73
L.L. o . p.
Lower Limit Output Percentage 87
Page 95
Page 96
Read carefully the safety guidelines and programming instructions contained in this
manual before using/connecting the device.
Prima di utilizzare il dispositivo, leggere con attenzione le informazioni
di sicurezza e settaggio contenute in questo manuale.
PIXSYS s.r.l.
www.pixsys.net
sales@pixsys.net - support@pixsys.net
online assistance: http://forum.pixsys.net
2300.10.081-RevG
Software Rev. 1.28