Pittway NOTIFIER LDM, NOTIFIER LDM-R32, NOTIFIER LDM-E32, NOTIFIER LDM-32 Series Manual

12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118
Lamp Driver Modules
For Graphic Annunciation and Control
Used with the System 500, System 5000,
AM2020/AFP1010 and AFP-200
Fire Alarm Control Panels
www.PDF-Zoo.com
Document 15885 10/29/97 Rev:
P/N 15885:F2 ECN 97-407
F
INSTALLATION WARNING
2
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
Table of Contents
Section One: Introduction to the LDM Series 5
Section T wo: LDM Features 6
2.1 The LDM-32 6 Figure 2-1: LDM-32 6
2.2 The LDM-E32 7 Figure 2-2: LDM-E32 7
2.3 Connectors on the LDM-32 and LDM-E32 8
2.4 Switches 9
2.5 Terminal Blocks 9
2.6 Cables 10
2.7 The LDM-R32 11 Figure 2-3: LDM-R32 11
Section Three: Installation 12
3.1 External Cabinets 12
3.2 CHS-4L Chassis 12 Figure 3-1: CHS-4L Mounting 12 Figure 3-2: Installing LDM Modules in CHS-4L 13 Figure 3-3: LDMs Mounted in UL Listed Cab 13 Figure 3-4: Mounting Optional LDM-R32 Relay Mod. 14
Section Four: Wiring Considerations 15
4.1 Limits 15
4.2 Wire Runs 15 Figure 4-1: EIA-485 Communications 15
4.3 Wiring Specifications 15 Figure 4-2: Wiring the Enclosure 16
4.4 EIA-485 Shield in Conduit 16 Figure 4-3: Terminating the Shield - Conduit 16
4.5 EIA-485 Shield Not in Conduit 16 Figure 4-4: Terminating the Shield - No Conduit 16
4.6 EIA-485, Power and Relay Wiring 17 Figure 4-5: Wiring Multiple LDMs (6000 ft. max..) 17 Figure 4-6: Wiring Supervision Terminals 17 UL Power Limited Wiring Requirements 18
4.7 Remote Power Supply Connector 19 Figure 4-7: Remote Power Supply Connections 19
4.8 Lamp/LED Wiring 20 Figure 4-8: Typical LDM-to-Graphics @ 5 VDC 20 Figure 4-9: Typical LDM-to-Graphics @ 24 VDC 20
4.9 Control Switch Wiring 21 Figure 4-10: Optional Zone/Pt. Control Switch Wire 21
www.PDF-Zoo.com
Section Five: Summary - Installing the Lamp Driver Module 22
Section Six: Operating the Lamp Driver Module 24
6.1 Lamp Test/Acknowledge 24
6.2 On Line LED 24
6.3 Graphic Annunciator Lamp/LED 24
15885 Rev. F1 8/2/95 P/N 15885:F1
3
Section Seven: LDM Communications 25
Figure 7-1: LDM-32 Supervision 25
Section Eight: LDM Electrical Ratings & Current Calculations 26
Appendix A: LDM and the System 5000 29
Table A-1: Annunciator Point Assignments 30 AIM-200 Point Assignments 31 Table A-2: LDM Switch Control Functions 32 Figure A-1: Alarm Only Operation w/o 8-Point Shift 33 Figure A-2: Alarm Only Operation with 8-Point Shift 34 Figure A-3: Alarm/Trouble Op. w/o 8-Point Shift 35 Figure A-4: Alarm/ Trouble Op. with 8-Point Shift 36 Figure A-5: Alarm Relays with LDM-R32 37 Figure A-6: Alarm Relays with 8-Point Shift 38 Figure A-7: Alarm & Trbl Relays with LDM-R32 39 Figure A-8: Alarm & Trbl Relays with 8-Point Shift 40
Appendix B: LDM and the AM2020/AFP1010 41
Figure B-1: The EIA-485 Loop 42 Table B-1: Lamp Driver Point Functions 43 Figure B-2: Lamp Driver Alarm Points 45 Figure B-3: Alarm and Trouble Points 46 Figure B-4: Alar m-Only Relay Operation 47 Figure B-5: Alarm & Trbl Relay Operation 48
Appendix C: LDM and the System 500 49
Figure C-1: Connecting the EIA-485 Loop 49 Table C-1: Annunciator Point Assignments 51 Table C-2: LDM Switch Control Functions 52 Figure C-2: Alarm Points Only Operation 5 2 Figure C-3: Alarm Only Operation with CPU Shift 53 Figure C-4: Alarm and Trouble Points Operation 53 Figure C-5: Alarm/Trouble Operation with 8-Pt Shift 54 Figure C-6: Alarm Relays with LDM-R32 54 Figure C-7: Alarm Relays with 8-Point Shift 55 Figure C-8: Alarm and Trouble Relay with LDM-R32 56 Figure C-9: Alarm & Trbl Relays with 8-Point Shift 57
4
www.PDF-Zoo.com
Appendix D: LDM and the AFP-200 58
Table D-1: LDM Switch Control Functions 60 Figure D-1: Display Active Status of Software Zones 61 Figure D-2: Active Status of Zones with 8-Pt Shft 62 Figure D-3: Activation and Trbl Status Annunciation 63 Figure D-4: Activation Operation with 8-Pt Shift 6 4
15885 Rev. F1 8/2/95 P/N 15885:F1
Section One: Introduction to the LDM Series
The LDM Series Lamp Driver Modules, which consist of the LDM-32 master and LDM-E32 expander modules, are used to provide an interface to a custom gr aphic annunciator. The master module provides power and control for a maximum of three expander modules. The LDM-32 and LDM-E32 have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions.
The LDM Series Lamp Driver Modules may be connected to fire alarm control panels (FACP) to provide remote annunciation of the following:
• General system status:
ü General Alarm ü General Trouble ü General supervisory ü Notification Appliance Circuit (NAC) output status ü Municipal tie status ü System silence ü Alarm relay status
• Alarm and trouble status of zones or individual points
• Alarm only status of zones or individual points
The LDM Series Modules also interface to remote control switches which may be used to provide:
• System reset
• System silence
• System acknowledge
• Temporary activation of NAC outputs
• Alarm relay activation
• Other control functions
The LDM Series Modules interface to the host fire alarm control panel via an EIA-485 communications bus circuit. A maximum of 32 LDM-32s may be connected to the power­limited EIA-485 bus, but if other types of devices are also connected to the EIA-485 bus, the maximum number of LDM-32s must be reduced by the total of such de vices. The EIA­485 wiring distance must not exceed 6,000 feet and cannot be T-tapped. Multiple LDM­32s may be used to annunciate duplicate infor mation.
Power to the LDM-32s is typically provided by the host FACP and must be power-limited regulated 24 VDC. External UL listed battery backed power supplies may also be used.
Careful consideration must be given to system battery calculations when power for the LDM modules and lamps or LEDs is provided by the host FACP
in the appropriate FACP technical manual when making these calculations.
15885 Rev. F1 8/2/95 P/N 15885:F1
. Ref er to the specifications
5
www.PDF-Zoo.com
Section Two: LDM Features
2.1 The LDM-32
The Lamp Driver Module LDM-32 has 32 alarm lamp/LED driver outputs which sink current to system common (-) on activation. A single positive (+) voltage is required to supply total operating power f or all lamps or LEDs when all drivers are activated. The LDM-32 pro vides a separate driver for system trouble and inputs for a local lamp test switch. A maximum of 16 external control switches ma y be wired to the LDM-32. DIP switch SW3 is used to enab le or disable the onboard piezo , enab le remote s witch functions, select a flashing LED function for new alarms and troubles, and other functions. Switch SW4 is used to configure the module to annunciate 32 alarms or 16 troubles. A green ON LINE LED flashes to indicate ongoing communications with the host FACP. One LDM-32 supports up to 3 LDM-E32 modules. The LDM-32 is supplied with 4 standoffs and screws for mounting to a CHS-4L chassis or custom backbox.
Output Connectors for Wiring to LEDs
Power­limited
Security Key Switch Terminal
T erminal for max. of 16 external control switches
Address Switches
LDM Program Switch
Alarm or Alarm/Trbl
EIA-485 In (-)
EIA-485 Out (-) EIA-485 Out (+) EIA-485 In (+)
Supervision Inputs (NC)
Common In (-)
Common Out (-)
Power In +24 VDC
Power Out +24 VDC
Earth Ground
Relay Po wer Ribbon Cable Connection
Lamp Po wer (+24 VDC)
System T rouble
Ribbon Cable Connection to LDM-E32
Indicates EIA-485 Communication Active
6
www.PDF-Zoo.com
Figure 2-1: LDM-32
15885 Rev. F1 8/2/95 P/N 15885:F1
2.2 The LDM-E32
Each LDM-E32 expander module provides 32 additional lamp/LED driver outputs from J5, J6, J7 and J8. The expander module has a slide switch SW4 for selecting alarm or alarm and trouble annunciation and an input for a local lamp test switch. In alarm mode, use only one LDM-32 and one LDM-E32 for a maximum of 56 alarm indicators and 8 system status indicators. In alarm/trouble mode, use one LDM-32 and three LDM-E32s for a maximum of 56 alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional control s witch inputs. Multiple sets of LDM-32s with LDM-E32 expanders increase the system annunciation capabilities beyond 56 zones or points. This is possible by various settings of address switches SW1 and SW2 on the LDM-32 (refer to Appendices). Each LDM-E32 is supplied with a 26 conductor expander ribbon cable, 4 standoffs and 4 screws.
Output Connectors
Security Key Switch Terminal
T erminal For max. of 16 External Control Switches
for Wiring to LEDs
Relay Po wer Ribbon Cable Connection
Ribbon Cable Connections to Next LDM-E32
Alarm Only or Alarm/Troub l e Select Switch
Figure 2-2: LDM-E32
15885 Rev. F1 8/2/95 P/N 15885:F1
Ribbon Cable Connection From Previous LDM-32 or LDM-E32
7
www.PDF-Zoo.com
2.3 Connectors on the LDM-32 and LDM-E32 J1 - Switch Matrix
Up to 16 optional external control switches and a local lamp test switch ma y be attached to the LDM-32 and LDM-E32 via J1 as shown in Figure 4-10. To determine which switch function each point will perform in a System 5000, refer to Appendix table A-1 (System
5000). Switch functions on an AM2020/AFP1010 are completely programmable.
J2 - Ribbon Cable Connection Between Master and Expander Modules to J3
A single 26 conductor ribbon cable may be connected from J2 on the LDM-32 or LDM­E32 (see Figure 3-3) to J3 on adjacent LDM-E32s. The ribbon cable carries power, ground and signaling from the LDM-32 to up to three LDM-E32s. The preformed cables are supplied in fixed lengths of 24 and 48 inches.
J3 - Ribbon Cable Connection From J2
This connector supports a single 26 conductor ribbon cable from J2 of the previous LDM-32 or LDM-E32. Refer to Figure 3-3.
J4 - Keyswitch Input
This two pin connector is provided as an input on LDM-32 and LDM-E32 modules f or an external security keyswitch. K eys witch contacts must be Normally Closed. The k eyswitch prevents unauthorized use of remote control switches wired to J1.
J5, J6, J7 and J8 - Lamp/LED Driver Outputs
Each connector provides 8 driver outputs for a total of 32 drivers on each LDM-32 and LDM-E32. Each driver is rated for a maxim um of 30 volts and a current of 100 mA. Each bipolar Darlington open collector driver output must be current limited by an external resistor. 8-Point Shift and Flash functions are selectable by DIP switch SW3 (refer to Section 2.4). Lamp/LEDs may function in 'alarm only mode' or 'alarm/trouble mode' as selected by switch SW4. Use the charts and examples sho wn in Appendices A and B fo r additional information.
J9 - Lamp Power/System Trouble
Connector J9 is located only on the LDM-32. J9 pin 1 pro vides 24 v olts regulated po wer to all lamps/LEDs used in a custom graphic annunciator. The current limit of J9 pin 1 is dependent upon the current limits of the external power source being used. J9 pin 3 is a driver output for system trouble indication only. J9 pin 2 connects to system common.
J10 - Relay Expander
Cables to the optional LDM-R32 Relay Expander Module which can be used to provide up to 32 dry Form-A (nor mally open) contacts.
J11 - 5 VDC Power
This connector is located only on the LDM-32. J11 pin 1 provides 5 volts regulated power to all lamps/LEDs used in a custom graphic annunciator. The maximum current available from this output is 300 mA. This current is sufficient to power the maximum number of LEDs available with one LDM-32 and three LDM-E32s (from J5, J6, J7, J8 and one system trouble LED)
8
provided the current rating per LED is 2 mA.
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
2.4 Switches SW1 and SW2 - Address Switches
Two rotary BCD switches, located only on the LDM-32, are used to set the LDM Series system address. Switch SW1 represents the 'ones' position and switch SW2 represents the 'tens' position of the address setting. In system configurations of 56 zones or less, the switches must be set to address 01 for all LDMs in the system. For configurations larger than 56 zones, multiple sets of LDMs are required with sequential addresses, the first LDM starting at address 01. Each incremental setting adds 64 zones/points to the system.
SW3 - Function DIP Switch
SW3, which is located only on the LDM-32, is used to set the annunciator functions. Function settings include:
• Number of expanders connected
• 8-Point Shift enabled
• Receive Only communications to host FACP (no system control switches or loss of supervision)
• Receive/Transmit communications to host FACP (system control switches plus supervision)
• Control Switch Disable
• Piezo disable
• Flash Inhibit
Refer to Appendices A and B for additional information.
SW4 - Alarm/Trouble Mode Switch
The Alarm/Trouble mode switch is installed on the LDM-32 and LDM-E32.
The switch
setting on each expander module must match the switch setting of the associated LDM-
32.
'Alarm Only' mode causes the driver outputs to turn on only for alarm conditions per associated zone or point at the host F ACP. Alarm/T rouble mode causes the driver outputs to turn on for both alarm and trouble conditions per associated zone or point at the host FACP. Since this switch affects the assignments of connectors J5, J6, J7 and J8, make certain to review the appendices in this manual for additional information on wiring to the lamp/LED drivers.
www.PDF-Zoo.com
2.5 Terminal Blocks
TB1 - Power, Earth Ground and Supervision
Removable terminal block TB1 appears only on the LDM-32. 24 volts power-limited, regulated, non-resettable power from the host FACP or a compatible UL listed battery backed power supply must be connected to TB1-3 (+) and TB1-5 (-). Ter minals TB1-2 (+) and TB1-4 (-) may be used to daisy chain the 24 volts to other LDMs or devices. Earth ground must be connected to TB1-1. Terminals TB1-6 and TB1-7 provide a supervised input which may be used to supervise local power sources or other devices. A trouble signal is transmitted to the host FACP upon an open circuit across these terminals. The input must be power-limited. If these terminals are not used, a jumper must be installed.
TB2- In/Out
Removable terminal bloc k TB2 appears only on the LDM-32. All LDM-32s m ust connect to the EIA-485 communications bus circuit for proper oper ation. The EIA-485 bus carries commands and data sent between the host FACP and the LDMs. The input must be power-limited.
15885 Rev. F1 8/2/95 P/N 15885:F1
9
2.6 Cables Expander Ribbon Cable (75120)
The Expander Ribbon Cable is supplied with the LDM-E32 to allow for connection to the LDM-32 master module. The cable connects between J2 of the LDM-32 or LDM-E32 and J3 of the next LDM­E32.
The LDM-CBL24 and LDM-CBL48
Cable sets for connecting LDM-32 and LDM-E32 connectors to lamps/LEDs, switches, etc., are provided through the optional LDM­CBL24 (24" long) and LDM-CBL48 (48" long) cabling kits. Each cable has a plug on one end for connection to the LDM modules.
• Each LDM-CBL24 cable kit includes: (4) P/N 75116, 24" cable consisting of 8 stranded,
multicolored conductors. Cables connect to J5, J6, J7 and J8.
(1) P/N 75122, 24" cable consisting of 10 stranded,
multicolored conductors. Connects to J1, optional control switches.
(1) P/N 75117, 24" cable consisting of 2 stranded, single
color conductors. Connects to J1, Lamp Test Switch.
(1) P/N 75118, 24" cable consisting of 3 stranded,
multicolored conductors. Connects to J9 or J11, Lamp Pow er.
KEYSWITCH LDM-32
10
• Each LDM-CBL48 cable kit includes: (4) P/N 75147, 48" cable consisting of 8 stranded,
multicolored conductors. Cables connect to J5, J6, J7 and J8.
(1) P/N 75150, 48" cable consisting of 10 stranded,
multicolored conductors. Connects to J1, optional control switches.
(1) P/N 75148, 48" cable consisting of 2 stranded, single
color conductors. Connects to J1, Lamp Test Switch.
(1) P/N 75149, 48" cable consisting of 3 stranded,
multicolored conductors. Connects to J9 or J11, Lamp Pow er.
• Keylock Control Switch Security: A UL listed key-loc k switch wired to J4 on the LDM-32 should be used to provide access security for all control switches wired to that set of LDM modules.
Control switches will not function
when the key-lock switch is in its closed position.
J4
2
1
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
2.7 The LDM-R32
The LDM-R32 Relay Expander Module provides the LDM-32 or LDM-E32 with 32 dry Form­A (normally open) contacts. The relay module serves as a sla ve to the particular lamp driver annunciator it is connected to - instead of driving lamps or LEDs, the alarm and/or trouble signals from the LDM-32 and LDM-E32 modules are used to activate the relays on the LDM­R32. A maximum of two of these relay modules can be supported by an LDM-32/LDM-E32 operating in alarm-only mode, providing a maximum of 64 alarm relays. In alarm/trouble mode, one, tw o or four LDM-R32 modules may be connected to LDM-32/LDM-E32s, pro viding a maximum of 64 alarm and 64 trouble relays. Includes mounting hardware, one Relay Po wer Cab le and four Relay Expander Ribbon cab les for connection to the master LDM-32/ LDM-E32 module.
www.PDF-Zoo.com
Figure 2-3: LDM-R32
15885 Rev. F1 8/2/95 P/N 15885:F1
11
Section Three: Installation
This section discusses basic requirements and CHS-4L mounting instructions.
3.1 External Cabinets
The CAB-3A and the CAB-3B are UL listed cabinets suitable f or use in graphic annunciator applications. For size and dimensions, refer to the CAB-3 Series Installation Document . Other cabinets such as those provided by custom graphic annunciator manufacturers may be used provided they meet UL requirements as UL listed secured enclosures. Select an appropriate knockout on the enclosure. Mount the cabinet and ground it to a solid metallic earth ground.
3.2 CHS-4L Chassis
The CHS-4L chassis will support one LDM-32 module and up to three LDM-E32 expander modules. The CHS-4L chassis may be mounted inside the CAB-3A and the CAB-3B enclosures. Note that a solid ear th ground connection is required for proper operation as well as to aid in transient protection. Two female-to-female standoffs must be installed to the chassis to secure the LDMs in place. (See Figure 3-1).
12
www.PDF-Zoo.com
Mount the CHS-4L Chassis to a cabinet and secure with the hardware provided. A Grounding Cable Assembly must be connected to the chassis mounting stud for connection to the annunciator's
Earth Ground
be installed on the chassis, connect two female­to-female standoffs (provided) to the upper mounting studs on the chassis.
terminal. For each LDM module to
Figure 3-1: CHS-4L Mounting
15885 Rev. F1 8/2/95 P/N 15885:F1
Slip the bottom edge of the LDM board into the slot on the CHS-4L chassis and move the module toward the standoffs. Secure the LDM to the standoffs with the screws provided. Repeat for installation of additional LDM modules.
Figure 3-2: Installing LDM Modules in CHS-4L
www.PDF-Zoo.com
Connect an expander ribbon cable (P/N 75120) from the LDM-32 connector J2 to J3 of the first LDM-E32 expander module. If multiple LDM-E32 modules are to be used, connect additional cables from J2 to J3 as shown in Figure 3-3. Note: One LDM-32 may support a maximum of three LDM-E32 modules.
Figure 3-3: LDMs Mounted in UL Listed Cabinet
15885 Rev. F1 8/2/95 P/N 15885:F1
13
Figure 3-4: Mounting Optional LDM-R32 Relay Modules
Secure the LDM-R32 to the LDM-32 with the standoffs provided (see below). Attach ribbon cables between the LDM-32 and the LDM-R32 for each group of rela ys needed (connector J5 to J5, J6 to J6, etc.) as illustrated at right. Note: The relay module can also be connected to an LDM-E32.
Chassis
LDM-32
(or LDM-E32)
StandoffStandoff
LDM-32
(or LDM-E32)
LDM-R32
LDM-32
LDM-R32
LDM-R32
Connect the Relay P ower Ribbon Cab le between J10 on the LDM-R32 and J10 on the LDM-
32. this connection supplies the power needed to energize the LDM-R32's rela y coils during activation.
14
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
Section Four: Wiring Considerations
4.1 Limits
A maximum of 32 LDM-32s may be connected to the EIA-485 bus, but if other types of devices are also connected to the EIA-485 bus , the maxim um number of LDM-32s must be reduced by the total of such devices. Total annunciation and switch capability depends upon the number of LDM-E32 expander modules used.
4.2 Wire Runs
Communications between the Fire Alarm Control Panel and the LDM is accomplished over a two-wire EIA-485 serial communications bus which must be power-limited. Communications between the host FACP and LDMs is supervised by the fire alarm control panel. Power supplied by the host control panel or external power supply must be power-limited. It is inherently supervised (loss of power also results in a communication failure at the control panel). Refer to appropriate control panel manual for UL P ower-limited Wiring Requirements.
Lamp Driver
Fire Alarm Control Panel
Two-wire EIA-485 Circuit
(Maximum 6000 ft.)
Power f or LDM
(18 to 14 AWG)
Figure 4-1: EIA-485 Communications
4.3 Wiring Specifications
The EIA-485 circuit cannot be T-tapped; it must be wired in a continuous fashion from the control panel to the LDMs. The maximum wiring distance between the panel and LDMs is 6000 feet. The wiring must be a 18 AWG to 14 AWG twisted shielded pair cable having a characteristic impedance of 120 ohms, +/- 20%. Limit the total wire resistance to 100 ohms on the EIA-485 circuit, and 10 ohms on the LDM power circuit. Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 V
Note: All enclosures, including the FACP backbox, must be connected to earth ground! Never use the shield for grounding purposes. Terminate the EIA-485 shield at the Fire Alarm Control Panel only.
, motor control circuits, or SCR power circuits.
RMS
STANDARD ANNEALED COPPER WIRE
Wire Size
A.W.G.
14 64 4110 0.00323 2.58 2.97 12.4 16 51 2580 0.00203 4.09 4.73 7.82 18 40 1620 0.00128 6.51 7.51 4.92
Diameter
in Mils
Cross Section Ohms per 1000 feet
Circ. Mils Sq. Inch @ 77 F. @ 149 F.
15885 Rev. F1 8/2/95 P/N 15885:F1
Pounds
per 1000 ft.
15
www.PDF-Zoo.com
Mount cabinet or backbox and dra w all wiring into enclosure.
Figure 4-2: Wiring the Enclosure
4.4 EIA-485 Shield in Conduit
When the EIA-485 wiring is in conduit, connect the shield to system common. The shield can enter the cabinet, but must be insulated from the cabinet (no electrical contact). Betw een LDMs, wire-nut multiple shields together (which can be inside of the respective LDM enclosure but ensure that the shield does not contact earth ground).
Enclosure
Annunciator
Figure 4-3: Terminating the Shield - Conduit
4.5 EIA-485 Shield Not in Conduit
When the EIA-485 wiring is not in conduit, terminate the shield at the outside of the FACP cabinet. Do not allow the shield to enter or even touch the cabinet housing the LDMs. Between LDMs, wire-nut multiple shields together Ensure that the shield does not touch earth ground at any junction points.
Enclosure
outside of
Annunciator
the respective enclosures.
Figure 4-4: Terminating the Shield - No Conduit
16
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
4.6 EIA-485, Power and Relay Wiring
EIA-485 - TB2, Terminals 1 to 4
• Do not T-tap the EIA-485 circuit. It will not function properly. Wire as shown below. Must be power-limited.
• Leave a 120 ohm resistor installed across the EIA-485 Out terminals at the last LDM on the circuit (see below). All other LDMs should not have a resistor installed.
Power, Earth Grnd and Relay - TB1, Terminals 1 to 7
• Connect Earth Ground (TB1-1) to a mounting screw on the backbox or cabinet.
• 24 VDC Power supplied to the LDM must be power­limited but it need not be supervised by an end-of-line power supervision relay. This power is inherently supervised (the control panel registers a loss of communications during loss of power to the LDM).
Host F A C P
First LDM
ΩΩ
120
ELR
ΩΩ
Part #71244
EIA-485 In (-) EIA-485 Out (-) EIA-485 Out (+) EIA-485 In (+)
N.C. Supervision
Inputs
Common In (-)
Common Out (-)
Power In (+24 VDC)
Power Out (+24 VDC)
Earth Ground
Last LDM
Figure 4-5: Wiring Multiple LDMs (6,000 ft. max run)
Supervision Input - TB1, Terminals 6 & 7
The Supervision Input, which requires a normally-closed condition, can be used for supervising power sources or other devices. It must be power-limited. If emplo yed, a change in status will be transmitted to the host control panel in the event of de vice f ailure or restoral.
If not used, a jumper must be installed across these terminals on TB1.
A trouble signal will
be registered by the control panel if a short circuit does not exist across terminals 6 & 7.
When not using the Supervision
Device to be supervised
Normally Closed Trouble Contacts
5 VDC @ 0.5 mA
Supervision Input
input, jumper terminals 7 and 6 together.
Supervision Input
Figure 4-6: Wiring Supervision Terminals
15885 Rev. F1 8/2/95 P/N 15885:F1
17
www.PDF-Zoo.com
UL Power Limited Wiring Requirements
Po wer limited and nonpower limited circuit wiring must remain separated in the cabinet. All power limited circuit wiring must remain at least 0.25" away from any nonpower limited circuit wiring. Furthermore, all power limited circuit wiring and nonpower limited circuit wiring must enter and exit the cabinet through different knoc kouts and/or conduits. A typical wiring diagram for the LDM-R32 is shown below. If this module is used to drive both power limited and nonpower limited circuits, connect relays 1 to 16 to power limited circuits and connect relays 17 to 32 to nonpower limited circuits or vice versa. Use an appropriate power limited power supply which is UL listed for fire alarm systems to provide po wer f or the power limited circuits.
MPS-24A
TB3 Terminal 3 = +24 VDC TB3 Terminal 4 = Common
MPS-24B
TB2 Terminal 3 = +24 VDC TB2 Terminal 4 = Common CAUTION: The +24 VDC provided on TB2 Terminal 3 is power-limited only when used with the minus return on TB2 T erminal 4.
Do not use the minus return on TB2 Terminal 2 with the
+24 VDC power on TB2 Terminal 3.
Note: Refer to Figure 4-7 for additional information on these power supplies.
18
www.PDF-Zoo.com
Power Limited Circuits
Non-Power Limited Circuits
LDM-R32
15885 Rev. F1 8/2/95 P/N 15885:F1
4.7 Remote Power Supply Connections
The LDMs may be powered by an MPS-24A or an MPS-24B. The power run to the LDMs need not contain a Power Supervision Relay since loss of power is inherently supervised.
MPS-24A Main Power Supply
Connect the power run for the LDMs to MPS-24A TB3, Terminals 1 (+) and 2 (-). Maximum current is 1 amp.
Common (-) to LDM-32 TB1-5
System 5000
24 VDC Power (+)
to LDM-32 TB1-3
MPS-24A
MPS-24B Main Power Supply:
Connect the power run for the LDMs to MPS-24B, TB2, Terminals 1 (+) and 2 (-). No more than 200 mA current can be drawn from these terminals in standby or alarm.
24 VDC Power (+)
to LDM-32 TB1-3
Common (-)
to LDM-32 TB1-5
MPS-24B
Figure 4-7: Remote Power Supply Connections
15885 Rev. F1 8/2/95 P/N 15885:F1
19
www.PDF-Zoo.com
4.8 Lamp/LED Wiring
Figure 4-8 illustrates LEDs being powered by the 5 volt output from LDM-32, J11 pin 1. Figure 4-9 illustrates LEDs being powered by the 24 volt output from LDM-32, J9 pin 3.
Note: All LEDs must be located in the same room as the LDM modules.
Wiring is not supervised
Point Status LEDs:
Use red for alarm points, yellow for trouble points and green for output points
Use 680 ohm, 1/4-watt resistors for each point if using 2 mA LEDs
Note: Use cable kits for wiring from connectors on LDM.
Figure 4-8: Typical LDM-to-Graphics Display
Connection @ 5VDC
Note: All LEDs must be located in the same room as the LDM modules.
System
T rouble LED:
(Y ellow)
Custom Graphic Display
Wiring is not supervised
Point Status LEDs:
Use red for alarm points, yellow for trouble points and green for output points
Use 10K ohm, 1/4-watt resistors for each point if using 2 mA LEDs
Note: Use cable kits for wiring from connectors to LDM.
Figure 4-9: Typical LDM-to-Graphics Display
Connection @ 24 VDC
20
15885 Rev. F1 8/2/95 P/N 15885:F1
System
T rouble LED:
(Y ellow)
Custom Graphic Display
www.PDF-Zoo.com
4.9 Control Switch Wiring
Optional zone/point control switches must be momentary type. Wiring from the LDM to the control switches must be in conduit and in the same room as the LDM since the wires are not supervised. Use the cables supplied in the cable kits to wire the control switches.
Acknowledge/ Lamp T est
Switch #16
Switch #15 Switch #14
Switch #13
Switch #12
Switch #11
Switch #10
Switch #9
Switch #8
Switch #7
Switch #6
Switch #5
Switch (momentary)
1
Switch #4
Switch #3
Switch #2
Switch #1
Figure 4-10: Optional Zone/Point-Control Switch Wiring
Each LDM must be set for Alarm/Trouble Mode by positioning slide switch SW4 to the right, for the optional control switches to function (the Acknowledge/Lamp Test switch will work in either mode). In this configuration, each LDM-32 and LDM-E32 provides 16 alarm drivers, 16 trouble drivers and 16 control switches. The alarm and trouble drivers are assigned to host FACP zones/points via user setup/installation. See Tables in Appendices A and B for additional information. Not all switches must be used - switches can be wired only for desired functions. To determine the function of each switch and driver in a System 5000, refer to Table A-1 and the System 5000 Manual. For AM2020/AFP1010 applications, refer to Table B-1 and the AM2020/AFP1010 Technical Manual.
1
Switches must be UL listed to switch 5 volts DC @ 0.5mA. Switches must be key-lock type, secured in a locked enclosure or a security key switch must be installed to control access. All switches must be installed in the same room as, and no more than 20 feet from, the LDM enclosure. Switch wiring must be in conduit.
15885 Rev. F1 8/2/95 P/N 15885:F1
21
www.PDF-Zoo.com
Section Five: Summary
Installing the Lamp Driver
Note for the System 5000: The LDM begins annunciation of circuits on the module installed
directly after the CPU-5000. To ensure full employment of LDM points, mount the modules that need lamp driver annunciation in the CPU row first, then in the second row, etc. Modules with circuits that are not to be annunciated by the LDM-32 should be installed further down in the cabinet.
• Mounting the cabinet or backbox
Select an appropriate knockout on the enclosure. Mount the cabinet or backbox enclosure. Ground the enclosure to a solid metallic earth ground.
• Wiring the LDM-32
Pull all annunciator wiring into the enclosure. Terminate the shield as shown in Figure 4-3 or 4-4. Connect annunciator wiring to the removable terminal blocks as shown in Figures 4-5 and 4-6. Maintain 0.25" spacing between power-limited and nonpower­limited wiring which must also enter/exit the enclosure through separate knockouts.
Note: A 120 ohm End-of-Line impedance-matching resistor (P/N 71244 supplied with the lamp driver) must be installed at the last annunciator on the EIA-485 circuit. Remo v e the ELRs installed on all LDMs except the last.
• Mounting hardware
If a CHS-4L is to be used in mounting the LDM, connect the chassis to the cabinet as illustrated in Figure 3-1. Secure standoffs (supplied) to the chassis or enclosures as shown in Figure 3-1.
• Mounting the modules
Mount all LDM modules to the chassis or enclosure as shown in Figure 3-2. One or three expanders can be installed when the LDM is configured for Alarm/T rouble operation.
• Connecting expander modules (optional)
Connect an Expander Ribbon Cable from the LDM-32 (connector J2) to the LDM-E32 (connector J3) as illustrated in Figure 3-3.
• Lamp Driver Power
LDM outputs can be powered from 24 VDC or 5 VDC , depending on the loading required. Figures 4-8 and 4-9 illustrate connection of the desired voltage, as well as the System T rouble LED . Connection of LDM operating power from a Main P o wer Supply is illustrated in Figure 4-7. The LDM annunciator can be powered by either the MPS-24A or MPS­24B.
• Control Switches (optional)
If normally-open switches are to be installed on the LDM to permit the execution of system control functions and point-control, refer to Figure 4-10.
22
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
In the Appendices:
The following steps are cov ered in panel-specific appendices. For the System 5000, ref er to Appendix A. For the AM2020/AFP1010, refer to Appendix B. For the System 500, refer to Appendix C. For the AFP-200, refer to Appendix D.
• Wiring the Point LEDs
Various point wiring schemes based on LDM configuration are illustrated in the particular appendix for the control panel employed.
Note: All LEDs/lamps being driven by the
LDM series must be located in the same
room as the modules.
• Connect the EIA-485 circuit to the CPU.
• Configure the LDM-32
Set the address and DIP switches on the LDM-32 annunciator.
• Programming and testing the LDM-32
After complete installation, the Lamp Driver must be programmed into the control panel. Program the LDM as if it were an annunciator. After programming the fire alarm control panel to accept the annunciators, fully test the LDMs by ensuring that each switch and LED performs its intended function, and that the annunciators can perform the functions outlined in the section, 'Operating the Lamp Driver Module.'
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
23
Section Six:
Operating the Lamp Driver Module
6.1 LAMP TEST/ACKNOWLEDGE
A separate, dedicated lamp test s witch is required for each LDM-32 and LDM-E32. A switch installed for LAMP TEST/ACKNOWLEDGE performs two functions:
1) When pressed, it will light all LEDs wired to the specific LDM module (e xcept the On Line LED) and will sound the integral piezo (if enabled) for as long as the switch is held down.
The Lamp Test switch will light only the LEDs on the module to which it is wired.
2) The s witch connected to the LDM-32, when pressed, acknowledges all status changes (for both the LDM-32 and any LDM-E32 expanders). Flashing LEDs will latch on solid and the piezo will be silenced.
6.2 On Line LED
This green LED , located on the LDM-32 module (lower right corner), flashes during communication with the host control panel.
6.3 Graphic Annunciator Lamps/LEDs
To adhere to standard fire alarm control panel convention and remain consistent with other products that may exist in the system, the following color convention is employed:
Red Alarm LEDs
To indicate an alarm condition for an Initiating Device Circuit, softw are zone or addressable initiating device.
Y ellow Tr ouble LEDs
To indicate a trouble condition exists on an initiating or indicating device circuit or zone. Yellow trouble LEDs also are used to indicate general system trouble conditions such as low battery, earth fault, general system trouble, etc.
Green Controlled Output LEDs
Indicates that power is applied or that the controlled output circuit or device has been activated. Applicab le to notification appliance, relay, speaker, telephone, and time control circuits.
The graphic annunciator may contain a yellow
Alarm
LED which will light for all trouble or alarm conditions (respectively) in the system
(not just for those points of zones mapped to the LDM annunciator/expanders).
24
15885 Rev. F1 8/2/95 P/N 15885:F1
System Trouble
LED and a red
System
www.PDF-Zoo.com
Section Seven: LDM Communications
Receive Only LDM-32s
For duplicate annunciation of system points, LDMs can be configured for Receive Only annunciation. Receive Only LDMs must be set to the same address as the LDM the y duplicate, but are not fully supervisable. Receive Only LDMs intercept information being transmitted to a Receive/Transmit LDM so that this information can be duplicated at an inter mediate display location. When configured for Receive Only operation, LDMs cannot transmit information to the host control panel. Remote Acknowledge, Silence, or Reset cannot be performed. Control switches on Receive Only LDMs are for local lamp test only. If a Receive/ Transmit LDM is located at the end of the EIA-485 bus, it will pro vide supervision of Receive Only LDMs located on the EIA-485 bus between the Receive/Transmit LDM and the FACP. See Figure 7-1.
Receive/Transmit LDM-32
LDMs that are configured to serve as full-function annunciators can both receive status information for annunciation as well as transmit commands to the control panel through custom-wired point control switches. This allows the LDM to initiate control panel switch functions from a remote location in addition to displaying the status of the system.
Fire Alarm
Control Panel
Two-wire EIA-485 Circuit*
* EIA-485 circuit is supervised and power-limited with a characteristic impedance of 120 ohms.
Receive Only LDM-32 set
to Address X
LDM-32 LDM-E32
Full-Function Receive/T ransmit
LDM-32 set to Address X
LDM-32 LDM-E32
www.PDF-Zoo.com
Figure 7-1: LDM-32 Supervision
15885 Rev. F1 8/2/95 P/N 15885:F1
25
Section Eight: LDM Electrical Ratings and
Current Calculations
Lamp Driver Electrical Ratings
LDM modules may use either 24 VDC (regulated) or internal 5 VDC f or po w ering connected LEDs. 5 v olt usage conserves power but is limited in the current a vailable to driv e the LEDs. Refer to Section Four, Figures 4-8 and 4-9 for connection illustrations.
5-volt LED Power Limitations
LED current
desired (m A)
Max # o f
LEDs
Number of Modules
LDM-32 LDM-E32
2 130 1 3
5 66 1 1 10 34 1 0 20 17 1/2 0
Note: The LDM-32 drives 32 LEDs and each LDM-E32 drives 32 more LEDs. An LDM system configured for Alarm and Trouble Display Mode and employing three e xpanders could have as many as 128 LEDs, all of which are activated during Lamp Test.
Maximum Current per Driver: 100 mA Maximum Voltage rating per output driver: 30 VDC Supervised circuit (typical rating): 5 volts DC @ 0.5 mA Bipolar Darlington Open Collector NPN Transistor
Supervision of LDM points
Any LEDs or lamps connected to the LDM-32 or LDM-E32 are not supervised for failure. Therefore, all LEDs or lamps, must be located in the same room as the LDM modules.
(external circuit must limit current)
26
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
Calculating LDM Series Standby and Alarm Currents
Current Draw for LED Power @ 24 VDC
Standby Current:
[ ] # of LDM-32 Modules
X
1
40 mA =
[ ] # of LDM - E32 Mo dul es
Alarm Current:
[ ] # of LDM-32 Modules [ ] # of LDM-E32 Module s [ ] # of LDM-R32 Modules [ ] # of LEDs [ ] # of LEDs
Notes:
1
The 0.040 amps can be reduced to 0.030 for modules with Piezo disable or
Flash Inhibit selected.
2
Use this line for calculations if LEDs are powered from 24 VDC source.
3
Use this line for calculations if LEDs are powered from the 5 VDC source from
J1 on the LDM-32.
2 mA =
X
24 VDC
Standby Total
56 mA =
X
18 mA =
X
288 mA =
X
2
3
[ ] mA per LED =
X
[( ) mA/3] =
X
Alarm Total
24 VDC
=
=
www.PDF-Zoo.com
The LDM series annunciators draw their power from the Fire Alarm Control Panel and must be considered when calculating primary and secondary power requirements.
Refer to the installation manual for the particular control panel employed for the calculation of power requirements for the entire system.
1) Enter Standby Total obtained here into the standby calculation tables.
2) Enter Alarm Current obtained here into the alarm calculation tables.
15885 Rev. F1 8/2/95 P/N 15885:F1
27
Appendix A: LDM and the System 5000
Capabilities
When installed with a System 5000, the LDM Series modules can annunciate the status of initiating and notification circuits, relays, and several system control functions. Each lamp driver output is automatically assigned to one and only one system I/O point:
Optional System 5000 plug in Modules
IZM-8 - Initiating Device Circuits (alarm and trouble) AIM-200 Zones (alarm and trouble) ICM-4/ICE-4 - Notification Appliance Circuits (trouble) CRM-4/CRE-4 - Control Relay Modules TCM-2/TCM-4 - Time Control Modules VCM-4/VCE-4 DCM-4
System Control Switches
Acknowledge Signal Silence System Reset Activate selected system outputs (notification circuits, relays)
Trouble Indication
Communication between the CPU and the LDMs is accomplished over a two-wire EIA-485 serial communication bus. The EIA-485 bus is supervised by the System 5000. Loss of communication results in System Trouble and Module Failure indications at the CPU.
Lamp/LED Driver Operation
Lamp Driver outputs do not latch - they track or f ollow the status of each zone/point that they are assigned to annunciate. Ta ble A-1 defines the ON status of each Lamp Driver output.
Software Required For the LDM to function properly , the CPU must be oper ating under ROM1-5000 P art Number 73085 (or higher).
Programming for Remote Annunciation
After complete installation, the LDM must be programmed into the System 5000 bef ore it will function. Program the LDM as if it were an annunciator . Refer to the System 5000 Installation Manual, Document 15584.
Installation Requirements
The EIA-485 circuit that communicates with the LDM must be connected to the CPU as illustrated below. The CPU must be Revision D or greater. The revision level of the CPU is marked on a label affixed to the upper board.
to LDM TB2 Terminal #4
EIA-485 (-)
Supervised and Power-Limited
(+) EIA-485
to LDM TB2 Terminal #1
System 5000 CPU
28
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
Configuration for the LDM-32 and System 5000
Lamp Driver Mode Switch
Lamp Driver Address
Set in the range 01-04*
Ones
Tens
ALARM/TROUBLE mode
(SW4 set to right side)
DIP Switch (SW3)
(see settings below)
LDM-32
Switch set to ON position
Switch set to
OFF position
ALARM ONLY mode
(SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (for System 5000):
1. Relay Control: Future Use - this switch must be set OFF on the System 5000.
None One Two Three
2. Number of LDM-E32 Expanders Installed: O FF ON OFF ON
3. Number of LDM-E32 Expanders Installed: O FF OFF ON ON
SW4
SW4
4. 8-Point Shift: Set switch ON to shift CPU-5000 LED function annunciation from the first eight annunciator positions on the LDM-32 to the third LDM-E32 expander positions 57 - 64. This shift can only be set on an LDM-32 set for address 1.
5. Receive Only: Set this switch ON for each LDM series that will provide the same information as another LDM series in a different physical location (when two or more sets of LDM series have the same address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: To disable the point I/O control switches on the LDMs from functioning, set this
switch ON. When inhibited, the local Lamp Test switch continues to function. In addition, the Acknowledge/Lamp T est switch will function only in a local capacity, unrecognized by the host System 5000.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events.
Flash Inhibit also disables the piezo from sounding. Flash Inhibit must be ON when using
the relay expander module (LDM-R32).
*The lamp driver can be set for addresses 1, 2, 3 or 4. The actual mapping arrangement for a respective module and its expanders depends on System 5000 annunciator programming. Refer to Document 15584 for details.
15885 Rev. F1 8/2/95 P/N 15885:F1
29
www.PDF-Zoo.com
Table A-1A: System 5000 CPU Annuncia t or Point Assignments to LDMs
System 5000
CPU Points
Annun cia to r Point #1 Indicates System Alarm Indicates System Troubl e
Annun cia to r Point #2 not us ed
Annun cia to r Point #3 not us ed not used
Annun cia to r Point #4 not us ed
Annun cia to r Point #5
Annun cia to r Point #6
Annun cia to r Point #7
Annun cia to r Point #8
Table A-1B: System 5000 Option Modules Annunciator Point Assignments to LDMs
System 5000
Option Modules
IZM-8 Alarm Status per Circuit Trouble Status per Circuit not used
ICM-4/ICE-4 Indicates A ctivation
CRM-4/CRE-4 Indicates Activation
TCM-2/TCM-4 Indicates Activation
AIM-200
LDM Alarm LED
Red
Indicates that Notification
Circuit 1 has been activated
Indicates that Notification
Circuit 2 has been activated
Indicates that the Remote
Signaling Municipal Tie has
been activated
Indicates that the Alarm Relay
has been activated
LDM Alarm LED
Red
Indicates Alarm Status of
eight software Zones
4
3, 4
3, 4
3, 4
LDM Trouble/Supv LED
Yellow
Indicates that signals have
been silenced
Indicates Supervisory
condition
Indicates trouble status of
4
4
4
LDM Trouble/Supv LED
Indicates Trouble per
Indicates Trouble per
Indicates Trouble per
Indicates Trouble Status of
eight software Zones
circuit
Indicates trouble status of
circuit
Indicates trouble status of
circuit
Indicates Module Trouble, Power F ailure or Disabl ed
Circuit(s)
Yellow
Circuit
Circuit
Circuit
LDM Control Switches
Functions as an
ACKNOWLEDGE
Functions as a SIGNAL
SILENCE
Functions as a SYSTEM
RESET
not used
Controls Notification
Circuit 1
Controls Notification
Circuit 2
Contro ls Remote
Signaling Municipal Tie
Contro ls Alarm Rel ay
LDM Control Switches
Controls Notification Circuit
Controls Relays
Remote Switch Functions
not used
5
5
5
30
www.PDF-Zoo.com
Notes:
1) Control Switches marked 'not used' will still function as local LAMP TEST or local ACKNOWLEDGE switches for their respective points.
2) If Alarm Only Mode is selected, column labeled Yellow LED is not applicable and control switches do not function.
1
If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight System 5000 CPU functions (ACK, SIL, RESET, LAMP TEST, NAC1, NAC2, MUNTIE, RELAY) will be shifted from annunciator points 1 through 8 (as shown above) to points 57 through 64 (provided those points exist in the system and the LDM-32 is set to address 01).
2
Optional control switches are active only if all of these conditions are met:
a) '8-Point Shift' (DIP switch #4) is set to OFF. b) Receive Only (DIP Switch #5) is set to OFF. c) Switch Inhibit (DIP Switch #7) is set to OFF.
3
These Status LEDs are active only when the System 5000 is programmed for Output Status.
4
Use green LEDs to indicate activation on controlled output circuits.
5
These control switches require that the System 5000 be programmed for Output Control.
15885 Rev. F1 8/2/95 P/N 15885:F1
AIM-200 Point Annunciation
The CPU-5000 can be programmed for an alternate method of annunciating the AIM-200. Up to 192 intelligent devices can be annunciated on a single AIM-200 with LDM series annunciators. The System 5000 annunciates the AIM-200 installed directly to the right of the CPU-5000. Note that an annunciator cannot be used to execute man ual ON/OFF control of intelligent AIM-200 points only standard System 5000 zones. The option provides annunciation of up to 256 points for the System 5000, broken down as follows:
Annunciator Address 1:
8 CPU points (CPU point shift not an option). 8 unusable points (redundant AIM-200 points). 48 points mapped to the next six modules installed in the System 5000 (which can also
be AIM-200s for annunciation of their 8 software zones.)
8 CPU points
8 unusable AIM-200
48 points mapped to the next six modules installed.
points
Annunciator Address 2:
Intelligent Detectors, addressed 1-64, on the AIM-200 installed next to the CPU-5000.
Annunciator Address 3:
Addressable Modules, addressed 1-64, on the AIM-200 installed next to the CPU-5000.
Annunciator Address 4:
Intelligent Detectors, addressed 65-96, followed by Addressable Modules, addressed 65-96, on the AIM-200 installed next to the CPU-5000.
The System 5000 Programming Manual, Document 15584, provides programming instructions for this option. Refer to program choice 'AIM(256).'
www.PDF-Zoo.com
Note: AIM-200 detector and module addresses 97, 98 and 99 may be used, but cannot be point-annunciated.
15885 Rev. F1 8/2/95 P/N 15885:F1
31
Notes:
Table A-2A: LDM Series Switch Control Functions
Alarm and Trouble Mode Without 8-Point Shift
LDM Switch Position LDM-32 1st LDM-E32 2nd LDM-E32 3rd LDM-E32
1 ACK Circuit 9 Circuit 25 Circuit 41 2 SIG.SIL. Circuit 10 Circuit 26 Circuit 42 3 RESET Circuit 11 Circuit 27 Circuit 43 4 not used Circuit 12 Circuit 28 Circuit 44 5 NAC 1 Circuit 13 Circuit 29 Circuit 45 6 NAC 2 Circuit 14 Circuit 30 Circuit 46 7 MUN TIE Circuit 15 Circuit 31 Circuit 47 8 Alarm Relay Circuit 16 Circuit 32 Circuit 48
9 Circuit 1 Circuit 17 Circuit 33 Circuit 49 10 Circuit 2 Circuit 18 Circuit 34 Circuit 50 11 Circuit 3 Circuit 19 Circuit 35 Circuit 51 12 Circuit 4 Circuit 20 Circuit 36 Circuit 52 13 Circuit 5 Circuit 21 Circuit 37 Circuit 53 14 Circuit 6 Circuit 22 Circuit 38 Circuit 54 15 Circuit 7 Circuit 23 Circuit 39 Circuit 55 16 Circuit 8 Circuit 24 Circuit 40 Circuit 56
1) Circuit corresponds to a specific I/O module installed in user configured System 5000.
2) Without 8-P oint Shift, the first 8 optional control switches correspond to CPU s witch functions: ACK, RES, NAC 1, NAC 2, MUN TIE, RELAY.
Table A-2B: LDM Series Switch Control Functions
Alarm and Trouble Mode With 8-Point Shift
LDM Switch Position LDM-32 1st LDM-E32 2nd LDM-E32 3rd LDM-E32
1 Circuit 1 Circuit 17 Circuit 33 Circuit 49 2 Circuit 2 Circuit 18 Circuit 34 Circuit 50 3 Circuit 3 Circuit 19 Circuit 35 Circuit 51 4 Circuit 4 Circuit 20 Circuit 36 Circuit 52 5 Circuit 5 Circuit 21 Circuit 37 Circuit 53 6 Circuit 6 Circuit 22 Circuit 38 Circuit 54 7 Circuit 7 Circuit 23 Circuit 39 Circuit 55 8 Circuit 8 Circuit 24 Circuit 40 Circuit 56
9 Circuit 9 Circuit 25 Circuit 41 ACK 10 Circuit 10 Circuit 26 Circuit 42 SIG.SIL. 11 Circuit 11 Circuit 27 Circuit 43 RESET 12 Circuit 12 Circuit 28 Circuit 44 not used 13 Circuit 13 Circuit 29 Circuit 45 NAC 1 14 Circuit 14 Circuit 30 Circuit 46 NAC 2 15 Circuit 15 Circuit 31 Circuit 47 MUN TIE 16 Circuit 16 Circuit 32 Circuit 48 Alarm Relay
Notes:
1) It is assumed that systems with 8-Point Shift selected will be 56 zones/points or less.
2) Circuit corresponds to a specific I/O module installed in user configured System 5000.
3) With 8-Point Shift, the first 8 optional control switches move to the 3rd LDM-E32. The 8 CPU switch functions are assigned to Circuits 57 through 64 as shown in the table above.
32
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
Figure A-1: Alarm Only Operation Without 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms for up to 120 zones (no zone troubles) with the first eight points (P1 through P8) dedicated to the System 5000 functions listed below. (Control switches do not function in Alarm Only configuration).
Address #1
LDM-32 System Functions* 1 - 8 9 - 16 17 - 24 LDM-E32 25 - 32 33 - 40 41 - 48 49 - 56
Address #2
LDM-32 57 - 64 65 - 72 73 - 80 81 - 88 LDM-E32 89 - 96 97 - 104 105 - 112 113 - 120
1
wire to LEDs
view of LDM-32
* System Status Indicators
Notification Circuit #1 ON (Green LED)
System Alarm (Red LED)
not used
1
It is assumed this module/expander annunciates points (circuits) 65-128 and is not functioning as a
Receive Only annunciator.
15885 Rev. F1 8/2/95 P/N 15885:F1
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED) Alarm Relay ON (Red LED)
33
www.PDF-Zoo.com
Figure A-2: Alarm Only Operation with 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms for up to 56 zones (no zone troubles) with the last eight points (P57 through P64) dedicated to the System 5000 function annunciations listed below . (Control Switches do not function in Alarm Only mode).
Address #1
LDM-32 1 - 8 9 - 16 17 - 24 25 - 32 LDM-E32 33 - 40 41 - 48 49 - 56 System Functions*
1
view of LDM-32
* System Status Indicators
Notification Circuit #1 ON (Green LED)
System Alarm (Red LED)
not used
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED) Alarm Relay ON (Red LED)
wire to LEDs
34
www.PDF-Zoo.com
1
It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56
zones/points or a total of 64 annunciator points or less.
15885 Rev. F1 8/2/95 P/N 15885:F1
Figure A-3: Alarm/Trouble Operation Without 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to 120 zones with the first eight points - 16 LEDs (J5: P1 through P8 and J6: P1 through P8) dedicated to System 5000 system status annunciation.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8 1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24 2nd LDM-E32 25 - 28 29 - 32 33 - 36 37 - 40 3rd LDM-E32 41 - 44 45 - 48 49 - 52 53 - 56
Address #2
1
LDM-32 57 - 60 61 - 64 65 - 68 69 - 72 1st LDM-E32 73 - 76 77 - 80 81 - 84 85 - 88 2nd LDM-E32 89 - 92 93 - 96 97 - 100 101 - 104 3rd LDM-E32 105 - 108 109 - 112 113 - 116 117 - 120
view of LDM-32
* System Status Indicators
NAC Ckt #1 ON (Green LED)
Supervisory (Yellow LED)
not used
Signals Silenced (Y ellow LED)
System Tr ouble (Y ellow LED)
System Alarm (Red LED)
not used
NAC Ckt #2 ON (Green LED)
Municipal Tie ON (Red LED)
Alarm Relay ON (Red LED)
NAC Ckt #1 Trbl (Y ellow LED) NAC Ckt #2 Trbl (Yellow LED) Municipal Tie Trbl (Y ellow LED)
Alarm Relay T r bl (Yellow LED)
www.PDF-Zoo.com
1
It is assumed this module/expander annunciates points (circuits) 64-128.
15885 Rev. F1 8/2/95 P/N 15885:F1
35
Figure A-4: Alarm/Trouble Operation with 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to 56 zones with the last eight points (16 LEDs) dedicated to the CPU functions listed below.
Address #1
1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16 1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32 2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48 3rd LDM-E32 49 - 52 53 - 56 System Status Indicators *
view of LDM-32
Signals Silenced (Y ellow LED)
36
www.PDF-Zoo.com
* System Status Indicators
NAC Ckt #1 ON (Green LED)
Supervisory (Yellow LED)
not used
System Tr ouble (Y ellow LED)
System Alarm (Red LED)
1
It is assumed that the '8-Point Shift' will be selected only on systems containing less
not used
than 56 zones/points.
15885 Rev. F1 8/2/95 P/N 15885:F1
NAC Ckt #2 ON (Green LED) Municipal Tie ON (Red LED) Alarm Relay ON (Red LED) NAC Ckt #1 Trbl (Yellow LED) NAC Ckt #2 Trbl (Yellow LED) Municipal Tie T rbl (Yellow LED)
Alarm Relay T r bl (Y ellow LED)
Figure A-5: Alarm Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarm relays for up to 56 zones with the first eight relays dedicated to the System 5000 functions listed below.
Address #1
LDM-32 System Functions* 1 - 8 9 - 16 17 - 24 LDM-E32 25 - 32 33 - 40 41 - 48 49 - 56
Address #2
LDM-32 57 - 64 65 - 72 73 - 80 81 - 88 LDM-E32 89 - 96 97 - 104 105 - 112 113 - 120
1
N.O. contacts
N.O. contacts
Common for TB1 Common for TB2
N.O. contacts
LDM-R32 Lamp Driver Relay Module
* System Functions
System Alarm
not used
not used not used
NAC Circuit #1 ON NAC Circuit #2 ON
Municipal Tie ON
Alarm Relay ON
1
It is assumed this module/expander annunciates points 65-128.
Common for TB4
Common for TB3
N.O. contacts
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
37
Figure A-6: Alarm Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarm relays for up to 56 zones with the last eight relays dedicated to the System 5000 functions listed below.
Address #1
LDM-32 1 - 8 9 - 16 17 - 24 25 - 32 LDM-E32 33 - 40 41 - 48 49 - 56 System Functions*
1
N.O. contacts
Common for TB1 Common for TB2
N.O. contacts
N.O. contacts
Common for TB4 Common for TB3
N.O. contacts
LDM-R32 Lamp Driver Relay Module
38
www.PDF-Zoo.com
* System Functions
System Alarm
not used not used not used
NAC Circuit #1 ON NAC Circuit #2 ON Municipal Tie ON
Alarm Relay ON
1
It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56
circuits.
15885 Rev. F1 8/2/95 P/N 15885:F1
Figure A-7: Alarm and Trouble Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarm and trouble relays for up to 120 zones with the first eight relays dedicated to the System 5000 functions listed below.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24 2nd LDM-E32 25 - 28 29 - 32 33 - 36 37 - 40 3rd LDM-E32 41 - 44 45 - 48 49 - 52 53 - 56
Address #2
LDM-32 57 - 60 61 - 64 65 - 68 69 - 72 1st LDM-E32 73 - 76 77 - 80 81 - 84 85 - 88 2nd LDM-E32 89 - 92 93 - 96 97 - 100 101 - 104 3rd LDM-E32 105 - 108 109 - 112 113 - 116 117 - 120
N.O. contacts
Alarm
Trouble
Common for TB1 Common for TB2
Alarm
N.O. contacts
Trouble
* System Functions
System Alarm
not used
not used not used
System T rouble Signal Silenced
not used
Supervisory
Common for TB4 Common for TB3
N.O. contacts
LDM-R32 Lamp Driver Relay Module
NAC Circuit # 1 ON NAC Circuit #2 ON
Municipal Tie ON Alarm Relay ON NAC Circuit #1 Trouble NAC Circuit #2 Trouble
Municipal Tie T rouble Alarm Relay Trouble
N.O. contacts
Trouble
Alarm
Trouble
Alarm
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
39
Figure A-8: Alarm and Trouble Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarms and troubles for up to 56 zones with the last eight relays dedicated to the CPU functions listed below.
Address #1
1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32 2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48 3rd LDM-E32 49 - 52 53 - 56 System Status Indicators *
1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
N.O. contacts
Alarm
Trouble
Common for TB1 Common for TB2
Alarm
N.O. contacts
Trouble
Common for TB4
Common for TB3
N.O. contacts
Trouble
Alarm
Trouble
Alarm
N.O. contacts
1
40
www.PDF-Zoo.com
LDM-R32 Lamp Driver Relay Module
* System Functions
System Alarm
not used not used not used
System T rouble Signal Silenced
not used
Supervisory
It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56 circuits.
15885 Rev. F1 8/2/95 P/N 15885:F1
NAC Circuit # 1 ON
NAC Circuit #2 ON
Municipal Tie ON Alarm Relay ON NAC Circuit #1 Trouble NAC Circuit #2 Trouble
Municipal Tie Tr ouble Alarm Relay T r ouble
Appendix B: LDM and the AM2020/AFP1010
Capabilities
When installed with an AM2020/AFP1010, the LDM Series modules can annunciate the status of addressable devices, software zones, XP Series Transponder points and several system control functions:
Devices
Intelligent Detectors MMX Monitor Modules and CMX Control Modules BGX Addressable Manual Pull Stations, security devices & all other addressab le devices.
Software Zones
All software zones can be annunciated provided that each zone is mapped to an annunciator point.
System Controls
Acknowledge/Step (the ACK/STEP key) Signal Silence System Reset Lamp Test (test LEDs, printer & CRT terminal output on AM2020/AFP1010 only)
XP Series Transponder System
Power and Audio Supply Supervision Point XPP-1 Form-C Alarm and Trouble Relay Points XPC Control, XPM Monitor and XPR Relay Module Circuit Points
Software Required
The AM2020/AFP1010 is fully compatible with LDM Series modules. The AM2020/AFP1010 must be operating with software of the following part numbers (or greater):
AM2020/AFP1010 Board ROM Part Number
Central Processing Unit (CPU-2020) 73123 Display Interface Assembly (DIA-1) 73132 Loop Interface Board (LIB-200) 73117 (for each LIB-200)
Warning: Each software ROM installed in the AM2020/AFP1010 must be part of the same software combination. For a list of valid software combination numbers, contact the Notifier Technical Services Department.
15885 Rev. F1 8/2/95 P/N 15885:F1
41
www.PDF-Zoo.com
Hardware Required
The AM2020/AFP1010 must include an intelligent Serial Interface Board (SIB-2048). The EIA-485 circuit must be connected to the SIB-2048 as illustrated below.
Figure B-1:
The EIA-485 Loop
Supervised and Power-Limited
The SIB-2048 can support one EIA-485 circuit, capable of spanning 12,000 feet (12 AWG), as illustrated below , provided that the SIB-2048 is located in the center of the span illustrated below. A 120 ohm terminating resistor is required at each end of the twisted pair.
EIA-485 Common
Earth Ground (chassis)
EIA-485 Loop 1 (+) EIA-485 Loop 1 (-) EIA-485 Loop 2 (+) EIA-485 Loop 2 (-)
P5
SIB-2048
LDM-32
LDM-32
Control Panel
24 V P ower
EIA-485 Loop
(6,000 feet Max)
Programming for Remote Annunciation
LDM points must be programmed from the AM2020/AFP1010 before the LDM will function. The AM2020/AFP1010 employs the following format for annunciator points:
24 V Power
EIA-485 Loop
(6,000 feet Max)
A(xx) P(yy)
LDM (Annunciator) address
In the range of 1-32, as set on the
annunciator's rotary decimal switches.
LDM 'Alarm'/Trouble Mode:
LDM-32 LDM-E32 LDM-E32 LDM-E32
points 1-16 points 17-32 points 33-48 points 49-64
LDM (Annunciator) point
First Second Third
For programming the Lamp Driver Series into AM2020/AFP1010 memory, and for mapping system points and software zones to annunciator points, refer to the AM2020/AFP1010 Programming Guide, Document 15334.
42
www.PDF-Zoo.com
LDM 'Alarm" Only Mode:
LDM-32 LDM-E32
points 1-32 points 33-64
15885 Rev. F1 8/2/95 P/N 15885:F1
Operation
LDM points 'track' or follow those system points they are programmed to annunciate; the points do not latch unless latched by the panel. Table B-1 is a list of how the LDM-32 annunciates various AM2020/AFP1010 devices and functions. Note: Control Switches marked 'not used' will still function as local LAMP TEST switches for their respective LEDs.
Table B- 1 : Lamp Driver Point Functions
Alarm and Trouble Mode
Alarm Mode Only
Point Type
Control Module
XPC Circuit XPR Circuit
Monitor Module
XPM Circuit
Intelligent Detector Indicates fire alarm
Software Zone Indicates active status
ACK/STEP key Indicates Fire Alarm Indicated System
SIGNAL SILENCE
key
SYSTEM RESET
key
LAMP TEST key not used not used Functions as a
Red LED Yellow LED Control Switch
Indicates on/off status
of module or circuit
Indicates active status
of module or circuit
status of detector
of software zone
not used Indicates Signals
Indicates Fire Alarm Indicates System
Indicates trouble/
supervisory statu s of
module or circuit
Indicates trouble/
supervisory statu s of
module or circuit
Indicates trouble status
of detector
Indicates trouble/
supervisory statu s of
software zone
Trouble
Silenced
Trouble
Functions as an
ACK/STEP key
Functions as a
SIGNAL SILENCE
Functions as a
SYSTEM RESET
LAMP TEST key
Turn module
on/off
not used
not used
not used
key
key
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
43
Configuration for the LDM-32 and the AM2020/AFP1010
Lamp Driver Mode Switch
Lamp Driver Address
Set in the range 01-32*
Ones
SW4
Tens
ALARM/TROUBLE mode
(SW4 set to right side)
DIP Switch (SW3)
(see settings below)
SW4
Switch set to ON position
Switch set to OFF position
LDM-32
ALARM ONLY mode
(SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (for AM2020/AFP1010):
1. Relay Control: Set to ON when the lamp driver is used to control relays or to provide fan
shutdown (see the Annunciator Control System manual, Document 15842 for more details).
2. Number of LDM-E32 Expanders Installed: OFF ON OFF ON
3. Number of LDM-E32 Expanders Installed: OFF OFF ON ON
None One Two Three
4. 8-Point Shift: This switch must always be set OFF on the AM2020 or AFP1010.
5. Receive Only: Set this switch ON for each LDM series that will provide the same information as
another LDM series in a different physical location (when two or more sets of LDM series have the same address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: Set this switch OFF to enable any control switches wired to the Lamp Driver. If
set ON, switches wired to the Lamp Driver will not execute their intended functions, but will serve only as a local Lamp Test for their respective points.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events.
Flash Inhibit also disables the piezo from sounding. Flash Inhibit must be ON when using
the relay expander module (LDM-R32).
44
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
Wiring the LDM for the AM2020/AFP1010
Figure B-2: Lamp Driver Alarm Points
The LDM-32 and one expander can be configured for up to 64 alarm points by setting Switch SW4 to the 'ALARM ONLY' position.
SW4
Points
P(1) - P(8)
Points Points
P(9) - P(16)
LDM-32 Lamp Driver
Points
P(33) - P(40)
Points Points
P(41) - P(48)
Points
P(17) - P(24)P(25) - P(32)
Points
P(49) - P(56) P(57) - P(64)
www.PDF-Zoo.com
LDM-E32 Expander
15885 Rev. F1 8/2/95 P/N 15885:F1
45
Figure B-3: Alarm and Trouble Points
The LDM-32 and up to three expanders can be configured for up to 64 alarm points and trouble points b y setting Switch SW4 to the 'ALARM/TROUBLE' position.
Points
Alarm Trouble
1 - 4 1 - 4
Points Points
Alarm Trouble
5 - 8 5 - 8
Alarm Trouble
9 - 12 9 - 12
LDM-32 Lamp Driver
Points
Alarm Trouble
17 - 20 17 - 20
Points Points
Alarm Trouble
21 - 24 21 - 24
Alarm Trouble 25 - 28 25 - 28
First LDM-E32 Expander
SW4
Points
Alarm Trouble
13 - 16 13 - 16
Points
Alarm Trouble
29 - 32 29 - 32
46
Points
Alarm Trouble
33 - 36 33 - 36
Points Points
Alarm Trouble
37 - 40 37 - 40
Second LDM-E32 Expander
Points
Alarm Trouble
49 - 52 49 - 52
Points Points
Alarm Trouble
53 - 56 53 - 56
Third LDM-E32 Expander
15885 Rev. F1 8/2/95 P/N 15885:F1
Alarm Trouble 41 - 44 41 - 44
Alarm Trouble 57 - 60 57 - 60
Points
Alarm Trouble
45 - 48 45 - 48
Points
Alarm Trouble
61 - 64 61 - 64
www.PDF-Zoo.com
Figure B-4: Alarm-Only Relay Operation
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarm relays for up to 64 AM2020 or AFP1010 points.
LDM-32 1 - 8 9 - 16 17 - 24 25 - 32 LDM-E32 33 - 40 41 - 48 49 - 56 57 - 64
N.O. contacts
N.O. contacts
Common for TB1 Common for TB2
N.O. contacts
Common for TB4 Common for TB3
N.O. contacts
LDM-R32 Lamp Driver Relay Module
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
47
Figure B-5: Alarm and Trouble Relay Operation
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarm and trouble relays for up to 64 AM2020 or AFP1010 points.
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16 1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32 2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48 3rd LDM-E32 49 - 52 53 - 56 57 - 58 59 - 60
N.O. contacts
Alarm
Trouble
Common for TB1 Common for TB2
Alarm
N.O. contacts
Trouble
N.O. contacts
Trouble
Alarm
Common for TB4 Common for TB3
Trouble
N.O. contacts
Alarm
LDM-R32 Lamp Driver Relay Module
48
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
Appendix C: LDM and the System 500
Capabilities
When installed with a System 500, the LDM Series modules can annunciate the status of initiating and notification circuits, relays, and several system control functions. Each lamp driver output is automatically assigned to one and only one system I/O point:
Optional System 500 plug in Modules
IZ-4/IZ-4A/IZ-8 - Initiating Device Circuits (alarm and trouble) IC-4/ICE-4/ICR-4L - Notification Appliance Circuits (activation and trouble) CR-4/CRE-4/CR-4L - Control Relay Modules (activation and trouble) TC-2/TC-4 - Time Control Modules (activation and trouble)
System Control Switches
Acknowledge Signal Silence System Reset Activate Notification Circuits 1 and 2, the Remote Signaling Municipal Tie circuit and the Alarm Relay
System 500 Trouble Indication
Communication between the CPU and the LDMs is accomplished over a two-wire EIA-485 serial communication bus. The EIA-485 bus is supervised by the System 500. Loss of communication results in System Trouble and Module Failure indications at the CPU.
Note: 'System Trouble' and 'Module Failure' will also occur if the normally closed supervisory path between TB1 Terminals 6 and 7 on the annunciator is opened (or the jumper has not been installed).
Installation Requirements
The EIA-485 circuit that communicates with the LDM must be connected to the CPU as illustrated below.
Supervised and Power-Limited
EIA-485 (-)
to LDM TB2 Terminal #4
(+) EIA-485
to LDM TB2 Terminal #1
Figure C-1: Connecting the EIA-485 Loop to the CPU-500
15885 Rev. F1 8/2/95 P/N 15885:F1
49
www.PDF-Zoo.com
Configuration for the LDM-32 and System 500
Lamp Driver Mode Switch
Lamp Driver Address
Set in the range 01-04
Ones
Tens
ALARM/TROUBLE mode
(SW4 set to right side)
DIP Switch (SW3)
(see settings below)
LDM-32
Switch set to ON position
Switch set to
OFF position
ALARM ONLY mode
(SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (for System 500):
1. Relay Control: Future Use - this switch must be set OFF on the System 500.
None One
2. Number of LDM-E32 Expanders Installed: OFF ON
3. Number of LDM-E32 Expanders Installed: OFF OFF
SW4
SW4
4. 8-Point Shift: Set switch ON to shift CPU-500 LED function annunciation out of the first eight annunciator positions on the LDM-32 . This switch is intended for systems between 9 and 16 circuits and employing one LDM-32 module (with no expander) where annunciation of all circuits is desired.
5. Receive Only: Set this switch ON for each LDM series that will provide the same information as another LDM series in a different physical location (when two or more sets of LDM series have the same address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: To disable the point I/O control switches on the LDMs from functioning, set this
switch ON. When inhibited, the local Lamp Test switch continues to function. In addition, the Acknowledge/Lamp T est switch will function only in a local capacity, unrecognized by the host System 500.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events.
Flash Inhibit also disables the piezo from sounding. Flash Inhibit must be ON when using
the relay expander module (LDM-R32).
50
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
Annunciator Operation
Annunciator points 'track' or follow those System 500 points they are programmed to annunciate; they do not latch. Table C-1 outlines the annunciation of various System 500 circuits and functions. Note: Control Switches marked 'not used' will still function as local LAMP TEST or local ACKNOWLEDGE switches for their respective points.
Table C-1A: System 500 CPU Annunciator Point Assignments to LDMs
System 5000
CPU Points
Annunciator Point #1 Indicates System Alarm Indicates System Trouble
Annunciator Point #2 not used
Annunciator Point #3 not used not used
Annunciator Point #4 not used
Annunciator Point #5
Annunciator Point #6
Annunciator Point #7
Annunciator Point #8
1
LDM Alarm LED
Red
Indicates that Notification
Circuit 1 has been activated
Indicates that Notification
Circuit 2 has been activated
Indicates that the Remote
Signaling Municipal Tie has
been activated
Indicates that the Alarm Relay
has been activated
LDM Tr ou ble/Supv LED
Yellow
Indicates that signals have
been silenced
Indicates Supervisory
condition
Indicates trouble status of
circuit
Indicates trouble status of
circuit
Indicates trouble status of
circuit
Indicates Modu le Trouble , Power Failure or Disabled
Circuit(s)
LDM Control Switches
Functions as an
ACKNOWLEDGE
Functions as a SIGNAL
SILENCE
Functions as a SYSTEM
RESET
not used
Controls Notification
Circuit 1
Controls Notification
Circuit 2
Controls Remote
Signaling Municipal Tie
Cont rol s Al ar m Rel a y
Table C-1B: System 500 Option Modules Annunciator Point Assignments to LDMs
System 500
Option Modules
IZ-4, IZ-4A, IZ-8 Alarm Status per Circuit Trouble Status per Circuit not used
IC-4/ICE-4/ICR-4L Indicates Activation
CR-4/CRE-4CR-4L Indicates Activation
TC-2/TC-4 Indicates Activation
1
If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight functions (ACK, SIL, RESET, LAMP
LDM Alarm LED
Red
LDM Trouble/Supv LED
Yellow
3
Indicates Trouble per
Circuit
Indicates Trouble per
Circuit
Indicates Trouble per
Circuit
LDM Control Switches
Controls Notification Circuit
Controls Relays
Remote Switch Functions
2
TEST, NAC1, NAC2, MUNTIE, RELAY) will be shifted out of annunciator points 1 through 8. These eight points would then annunciate the status of the first eight zones.
2
Optional control switches are active only if all of these conditions are met:
a) Receive Only (DIP Switch #5) is set to OFF. b) Switch Inhibit (DIP Switch #7) is set to OFF.
3
If an IZ-4, IZ-4A or IZ-8 circuit is programmed on the System 500 as a supervisory point, both the red and yellow LEDs will be illuminated for a supervisory condition. Illumination of the yellow LED alone indicates a trouble condition (open circuit) on the IZ supervisory circuit.
15885 Rev. F1 8/2/95 P/N 15885:F1
51
www.PDF-Zoo.com
Table C-2A: LDM Series Switch Control Functions
Alarm and Trouble Mode Without 8-Point Shift
LDM Switch Po sition LDM-32 1st LDM-E32
1 ACK Circuit 9 2 SIG.SIL. Circuit 10 3 RESET Circuit 11 4 not used Circuit 12 5 NAC 1 Circuit 13 6 NAC 2 Circuit 14 7 MUN TIE Circuit 15 8 Alarm Relay Circuit 16
9 Circuit 1 Circuit 17 10 Circuit 2 Circuit 18 11 Circuit 3 Circuit 19 12 Circuit 4 Circuit 20 13 Circuit 5 Circuit 21 14 Circuit 6 Circuit 22 15 Circuit 7 Circuit 23 16 Circuit 8 Circuit 24
Figure C-2: Alarm Points Only Operation
LDM Series Switch Control Functions Alarm and Trouble Mode With 8-Point
LDM Switch Position LDM-32
Table C-2B:
Shift
1 Circuit 1 2 Circuit 2 3 Circuit 3 4 Circuit 4 5 Circuit 5 6 Circuit 6 7 Circuit 7 8 Circuit 8
9 Circuit 9 10 Circuit 10 11 Circuit 11 12 Circuit 12 13 Circuit 13 14 Circuit 14 15 Circuit 15 16 Circuit 16
This figure illustrates the configuration of LDMs to annunciate alarms for up to 24 zones (no zone troubles) with the first eight points (P1 through P8) dedicated to the System 500 function annunciations listed below. No expander is needed in this mode.
Address #1
LDM-32 System Functions* 1 - 8 9 - 16 17 - 24
wire to LEDs
view of LDM-32
* System Status Indicators
Notification Circuit #1 ON (Green LED)
System Alarm (Red LED)
52
not used
15885 Rev. F1 8/2/95 P/N 15885:F1
Notification Circuit #2 ON (Green LED)
Municipal Tie ON (Red LED) Alarm Relay ON (Red LED)
www.PDF-Zoo.com
Figure C-3: Alarm Only Operation with CPU shift
This figure illustrates the configuration of LDMs to annunciate alarms for up to 24 zones (no zone troubles).
Address #1
LDM-32 1 - 8 9 - 16 17 - 24 not applicable
wire to LEDs
view of LDM-32
Figure C-4: Alarm and Trouble Points Operation
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to 24 zones with the first eight points (J5: P1 through P8 and J6: P1 through P8) dedicated to System 500 functions.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24
view of LDM-32
* System Status Indicators
NAC Ckt #1 ON (Green LED)
Supervisory (Yellow LED)
not used
Signals Silenced (Y ellow LED)
System Tr ouble (Y ellow LED)
System Alarm (Red LED)
not used
15885 Rev. F1 8/2/95 P/N 15885:F1
NAC Ckt #2 ON (Green LED) Municipal Tie ON (Red LED) Alarm Relay ON (Red LED) NAC Ckt #1 Trbl (Y ellow LED) NAC Ckt #2 Trbl (Yellow LED) Municipal Tie Trbl (Y ellow LED)
Alarm Relay T r bl (Yellow LED)
53
www.PDF-Zoo.com
Figure C-5: Alarm/Trouble Operation with 8-Point Shift
This figure illustrates the configuration of LDMs to annunciate alarms and troubles for up to 24 zones.
Address #1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 not used
view of LDM-32
Figure C-6: Alarm Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate rela ys for up to 24 zones with the first eight relays dedicated to the System 500 functions listed below.
Address #1
LDM-32 System Functions* 1 - 8 9 - 16 17 - 24
N.O. contacts
54
System Alarm
not used not used not used
NAC Circuit #1 ON NAC Circuit #2 ON Municipal Tie ON Alarm Relay ON
Common for TB1 Common for TB2
N.O. contacts
Common for TB4
Common for TB3
LDM-R32 Lamp Driver Relay Module
15885 Rev. F1 8/2/95 P/N 15885:F1
N.O. contacts
N.O. contacts
www.PDF-Zoo.com
Figure C-7: Alarm Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate rela ys for up to 24 zones.
Address #1
LDM-32 1 - 8 9 - 16 17 - 24 not used
N.O. contacts
Common for TB1 Common for TB2
N.O. contacts
N.O. contacts
Common for TB4
Common for TB3
N.O. contacts
LDM-R32 Lamp Driver Relay Module
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
55
Figure C-8: Alarm and Trouble Relays with LDM-R32
This figure illustrates the configuration of the LDM-R32 Relay Expander to activate alarm and trouble relays for up to 24 zones with the first eight relays dedicated to the System 500 functions listed below..
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8
1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24
N.O. contacts
Alarm
Trouble
Common for TB1 Common for TB2
Alarm
N.O. contacts
Trouble
* System Functions
System Alarm
not used not used not used
System Tr ouble Signal Silenced
not used
Supervisory
Common for TB4 Common for TB3
N.O. contacts
LDM-R32 Lamp Driver Relay Module
NAC Circuit # 1 ON NAC Circuit #2 ON
Municipal Tie ON Alarm Relay ON NAC Circuit #1 Trouble NAC Circuit #2 Trouble
Municipal Tie T rouble Alarm Rela y T rouble
N.O. contacts
Trouble
Alarm
Trouble
Alarm
56
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
Figure C-9: Alarm and Trouble Relays with 8-Point Shift
This figure illustrates the configuration of the LDM-R32 to activate alarm and trouble relays for up to 24 zones.
Address #1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16
1st LDM-E32 17 - 20 21 - 24 not used
N.O. contacts
Alarm
Trouble
Common for TB1 Common for TB2
Alarm
N.O. contacts
Trouble
N.O. contacts
Trouble
Alarm
Common for TB4 Common for TB3
Trouble
N.O. contacts
Alarm
LDM-R32 Lamp Driver Relay Module
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
57
Appendix D: LDM and the AFP-200
Capabilities
When installed with an AFP-200, LDM Series modules can annunciate the status of 99 software zones and seve ral system control functions. Each lamp driv er output is automatically assigned to one and only one system I/O point:
Software Intelligent Detectors Zones: MMX Monitor Modules
CMX Control Modules BGX Addressable Manual Pull Stations
System Control Switches: Acknowledge
Signal Silence System Reset Drill
Trouble Indication
Communication between the AFP-200 and the LDMs is accomplished over a two-wire EIA-485 serial communication bus. The EIA-485 is supervised by the AFP-200. Loss of communication results in System Trouble and Annunciator 1 (2) No Answer message on the panel's 80 character LCD display.
Lamp/LED Driver Operation
Lamp Driver outputs do not latch - they track or follow the status of those point they are programmed to annunciate. Table D-1 outlines the annunciation of the various zones and functions.
Programming for Remote Annunciation
After complete installation, the LDM must be programmed into the AFP-200 before it will function. Program the LDM as if it were an ACS annunciator. Refer to the AFP-200 Programming Manual, Document 15511.
Installation Requirements
Regulated power (24 VDC) and the EIA-485 circuit that communicates with the LDMs must be connected to the AFP-200 as illustrated below.
To LDM TB1-3
58
To LDM TB1-5
AFP-200 Main Circuit Board (Top edge)
15885 Rev. F1 8/2/95 P/N 15885:F1
To LDM TB2-4
To LDM TB2-1
www.PDF-Zoo.com
Configuration for the LDM-32 and the AFP-200
Lamp Driver Mode Switch
Lamp Driver Address
Set in the range of 01 or 02
Ones
Tens
ALARM/TROUBLE mode
(SW4 set to right side)
DIP Switch (SW3)
(see settings below)
LDM-32
Switch set to ON position
Switch set to
OFF position
ALARM ONLY mode
(SW4 set to left side)
LDM-32 DIP Switch (SW3) settings (f or AFP-200):
1. Relay Control: Future Use - this switch must be set OFF on the AFP-200.
None One Two Three
2. Number of LDM-E32 Expanders Installed: O FF ON OFF ON
3. Number of LDM-E32 Expanders Installed: O FF OFF ON ON
SW4
SW4
4. 8-Point Shift: Set switch ON to shift AFP-200 LED function annunciation from the first eight annunciator positions on the LDM-32 to the third LDM-E32 expander positions 57 - 64. This shift can only be set on an LDM-32 set for address 1 (system using less than 56 software zones).
5. Receive Only: Set this switch ON for each LDM series that will provide the same information as another LDM series in a different physical location (when two or more sets of LDM series have the same address, all but one must be configured as Receive Only.)
6. Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7. Switch Inhibit: To disable the point I/O control switches on the LDMs from functioning, set this
switch ON. When inhibited, the switches will serve as local Lamp Test switches only. In addition, the Acknowledge/Lamp T est switch will function only in a local capacity, unrecognized by the host AFP-200.
8. Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events.
Flash Inhibit also disables the piezo from sounding..
the relay expander module (LDM_R32).
15885 Rev. F1 8/2/95 P/N 15885:F1
Flash inhibit must be ON when using
59
www.PDF-Zoo.com
Table D-1A: LDM Series Switch Control Functions
Alarm and Trouble Mode Without 8-Point Shift
LDM Switch Po si t ion LDM-32F 1st LDM-E32F 2nd LDM-E32F 3rd LDM-E32F
1 ACK not used not used not used 2 SIG.SIL. not used not used not used 3 RESET not used not us e d not used 4 DRILL not used not us e d not used 5 not used not us ed not use d not used 6 not used not us ed not use d not used 7 not used not us ed not use d not used 8 not used not us ed not use d not used
9 not used not us ed not use d not used 10 not used not us ed not use d not used 11 not used not us ed not use d not used 12 not used not us ed not use d not used 13 not used not us ed not use d not used 14 not used not us ed not use d not used 15 not used not us ed not use d not used 16 not used not us ed not use d not used
A second LDM-32 set to address 02 with expanders would not support control switches.
60
Table D-1B: LDM Series Switch Control Functions
Alarm and Trouble Mode With 8-Point Shift
LDM Switch Position LDM-32F 1st LDM-E32F 2nd LDM-E32F 3rd LDM-E32F
1 not used not used not used not used 2 not used not used not used not used 3 not used not used not used not used 4 not used not used not used not used 5 not used not used not used not used 6 not used not used not used not used 7 not used not used not used not used 8 not used not used not used not used
9 not used not used not used ACK 10 not used not us ed not used SIG.SIL. 11 not used not us ed not used RESET 12 not used not us ed not used DRILL 13 not used not us ed not used not used 14 not used not us ed not used not used 15 not used not us ed not used not used 16 not used not us ed not used not used
It is assumed that systems with 8-Point Shift selected will be 56 zones or less.
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
Figure D-1: Display Active Status of Software Zones Only
This figure illustrates configuration of the LDM to annunciate the Active state of all 99 software zones (no zone troubles) with the first eight points (P1 through P8) dedicated to the AFP­200 system function LEDs listed below.
Address #1
LDM-32 System Functions* 1 - 8 9 - 16 17 - 24 LDM-E32 25 - 32 33 - 40 41 - 48 49 - 56
Address #2
LDM-32 57 - 64 65 - 72 73 - 80 81 - 88 LDM-E32 89 - 96 97 - 99
1
wire to LEDs
view of LDM-32
* System Status Indicators
System Alarm
not used
It is assumed this module/expander annunciates zones 65-99 and is not functioning as a 'Receive Only' annunciator.
15885 Rev. F1 8/2/95 P/N 15885:F1
61
www.PDF-Zoo.com
Figure D-2: Active Status of Software Zones with 8-Point Shift
This figure illustrates configuration of the LDM to annunciate the Active state for up to 56 zones (no zone troubles) with the last eight points (P57 through P64) dedicated to the AFP­200 system function LEDs listed below.
Address #1 LDM-32 1 - 8 9 - 16 17 - 24 25 - 32 LDM-E32 33 - 40 41 - 48 49 - 56 System Functions*
1
view of LDM-32
* System Status Indicators
wire to LEDs
1
software zones or a total of 64 annunciator points or less.
62
www.PDF-Zoo.com
System Alarm
not used
It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56
15885 Rev. F1 8/2/95 P/N 15885:F1
Figure D-3: Activation and Trouble Status Annunciation
This figure illustrates wiring the LDM to annunciate the active and trouble states for all 99 zones with the first eight points (J5: P1 through P8 and J6: P1 through P8) dedicated to AFP-200 functions listed below.
Address #1
LDM-32 System Status Indicators * 1 - 4 5 - 8 1st LDM-E32 9 - 12 13 - 16 17 - 20 21 - 24 2nd LDM-E32 25 - 28 29 - 32 33 - 36 37 - 40
3rd LDM-E32 41 - 44 45 - 48 49 - 52 53 - 56
Address #2
LDM-32 57 - 60 61 - 64 65 - 68 69 - 72 1st LDM-E32 73 - 76 77 - 80 81 - 84 85 - 88
2nd LDM-E32 89 - 92* 93 - 99*
view of LDM-32
* System Status Indicators
not used
not used not used
Signals Silenced (Yellow LED)
System Tr ouble (Y ellow LED)
System Alarm (Red LED)
1
It is assumed that this module/expander annunciates points 64-99.
not used
Zones 90-99 are special functions: Z90 Presignal Time Run Z94 Time Started/Release Z98 Tornado
Z91 Time Started/Release Z95 Time Ctl Active Z99 Prealarm Z92 Time Started/Release Z96 Time Ctl Active Z93 Time Star ted/Release Z97 Holiday Active
15885 Rev. F1 8/2/95 P/N 15885:F1
not used not used
not used
Supervisory (Yellow LED)
Pre-Alarm AC Fail (Yellow LED) Panel T rouble
63
www.PDF-Zoo.com
Figure D-4: Activ ation/Trouble Operation With 8-Point Shift
This figure illustrates configuration for the LDM to annunciate active and trouble states for the first 56 software zones with the last eight points (16 LEDs) dedicated to the AFP-200 functions listed below.
Address #1
1
LDM-32 1 - 4 5 - 8 9 - 12 13 - 16 1st LDM-E32 17 - 20 21 - 24 25 - 28 29 - 32 2nd LDM-E32 33 - 36 37 - 40 41 - 44 45 - 48 3rd LDM-E32 49 - 52 53 - 56 System Status Indicators *
view of LDM-32
1
circuits.
64
www.PDF-Zoo.com
* System Status Indicators
not used
not used not used
Signals Silenced (Y ellow LED)
System T rouble (Y ellow LED)
System Alarm (Red LED)
not used
It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56
15885 Rev. F1 8/2/95 P/N 15885:F1
not used not used not used
Supervisory (Yellow LED)
Pre-Alarm
AC Fail (Yellow LED)
Panel T rouble
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
65
66
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
67
LIMITED WARRANTY
68
www.PDF-Zoo.com
15885 Rev. F1 8/2/95 P/N 15885:F1
Loading...