Pima Wireless AlarmView, AVR, Guardian Installation Manual

AlarmView
Wireless Intruder Alarm System with Visual Verification
Guardian
Wireless Intruder Alarm System
Visual Verification Add-on
Installation Guide
System version 2.09.XX
Table of contents
1
Table of contents
1 Introduction ........................................................................................... 5
1.1 Features ..................................................................................................... 5
1.1.1 The AlarmView system ............................................................................... 5
1.2 The Guardian system .................................................................................... 6
1.3 The AVR Visual Add-on ................................................................................. 7
1.4 Technical specifications ................................................................................. 8
2 Quick Reference Guide ......................................................................... 10
2.1 System components ................................................................................... 10
2.2 The Control Panel ....................................................................................... 10
2.2.1 The buttons ............................................................................................ 11
2.2.2 The display ............................................................................................. 12
2.2.3 Sound indications .................................................................................... 12
2.2.4 LED indications ....................................................................................... 13
2.2.5 The INFO screen...................................................................................... 13
3 System Installation .............................................................................. 14
3.1 General guidelines ...................................................................................... 14
3.2 Quick installation ....................................................................................... 14
3.3 Professional mounting ................................................................................. 16
3.4 Other installation options ............................................................................ 20
3.4.1 Standalone wired siren ............................................................................. 20
3.4.2 How to use the trigger inputs .................................................................... 20
3.4.3 The AVR ................................................................................................. 21
3.4.4 External antenna ..................................................................................... 22
3.5 How to confirm system installation ............................................................... 22
4 Setup and Programming ...................................................................... 23
4.1 The Installer’s menu map ............................................................................ 23
4.2 Accessing the menus .................................................................................. 24
4.3 The Master and Installer passwords .............................................................. 24
4.3.1 How to reset the passwords to factory defaults ............................................ 24
5 Options menu ....................................................................................... 25
5.1 Global Settings .......................................................................................... 25
5.2 Zone bypass .............................................................................................. 25
5.3 Contacts ................................................................................................... 25
6 Event Log menu ................................................................................... 26
6.1 Log entry examples .................................................................................... 26
7 Service menu ....................................................................................... 27
7.1 Tests ........................................................................................................ 27
7.1.1 Zones .................................................................................................... 27
7.1.2 External Siren ......................................................................................... 28
7.1.3 Built-in siren ........................................................................................... 29
7.1.4 Communication ....................................................................................... 29
7.1.5 System self-test ...................................................................................... 29
7.2 Display version .......................................................................................... 30
7.3 System reset ............................................................................................. 30
8 Passwords Menu .................................................................................. 31
8.1 Installer .................................................................................................... 31
8.1.1 Access mode ........................................................................................... 31
9 Set Clock menu .................................................................................... 32
9.1 Time ........................................................................................................ 32
9.2 Date ........................................................................................................ 32
10 Programming menu ............................................................................. 33
Wireless Alarm Systems Installation Guide
2
10.1 Zones/Peripherals ...................................................................................... 33
10.1.1 Zones .................................................................................................... 33
10.1.2 Visual zones (AlarmView and AVR only) ...................................................... 34
10.1.3 Keyfobs/keypads ..................................................................................... 35
10.1.4 Panic button ........................................................................................... 36
10.1.5 External siren ......................................................................................... 36
10.1.6 Built-in siren ........................................................................................... 37
10.2 Contacts ................................................................................................... 37
10.2.1 System name ......................................................................................... 37
10.2.2 Contact 1-6 ............................................................................................ 37
10.3 CMS contacts ............................................................................................ 38
10.4 Communication .......................................................................................... 40
10.5 System options .......................................................................................... 41
10.5.1 Entry/Exit delay ...................................................................................... 41
10.5.2 Arm/Disarm ............................................................................................ 42
10.5.3 PGM output ............................................................................................ 43
10.5.4 Trigger inputs ......................................................................................... 43
10.5.5 Remote access ........................................................................................ 44
10.6 Factory defaults ......................................................................................... 44
10.6.1 Return to defaults .................................................................................... 45
10.6.2 Clear Passwords ...................................................................................... 45
10.6.3 Clear zones ............................................................................................ 45
10.6.4 Initialize all ............................................................................................. 46
10.7 Local programming .................................................................................... 46
10.8 Firmware upgrade ...................................................................................... 46
11 Stop Communication Menu ................................................................... 47
12 Operating the Alarm System Remotely ................................................ 48
12.1 By smartphone app .................................................................................... 48
12.2 By text messages ....................................................................................... 48
12.2.1 Commands ............................................................................................. 48
Table of contents
3
Appendixes
Appendix A System Peripherals ............................................................... 49
Appendix B The SmartView Detector/ Camera ......................................... 50
B.1 How to mount the detector .......................................................................... 50
B.2 How to replace the battery .......................................................................... 50
Appendix C The OutView Camera ............................................................. 51
C.1 How to mount the camera ........................................................................... 51
C.2 How to connect the camera ......................................................................... 51
Appendix D External Siren Indications ..................................................... 53
Appendix E Maintenance & Troubleshooting ............................................ 54
E.1 Cleaning the LCD screen ............................................................................. 54
E.2 Replacing the Control Panel’s battery ............................................................ 54
E.3 SIM card icons and LED behavior .................................................................. 54
Appendix F Glossary of terms .................................................................. 55
Appendix G Event Reporting .................................................................... 57
Appendix H SIA and ContactID Codes ...................................................... 59
H.1 Event codes .............................................................................................. 59
H.2 Device number .......................................................................................... 59
H.3 User number ............................................................................................. 59
Appendix I SMS confirmation messages .................................................. 60
Appendix J Limited Warranty .................................................................. 61
Appendix K Declaration of Conformity ..................................................... 62
Figure index
Figure 1. The AlarmView alarm system diagram ................................................................ 5
Figure 2. The Guardian alarm system .............................................................................. 6
Figure 3. The AVR visual Add-on ...................................................................................... 7
Figure 4. The control panel ............................................................................................ 10
Figure 5. The control panel keys ..................................................................................... 10
Figure 6. Control panel’s back side .................................................................................. 11
Figure 7. The LCD display and buttons ............................................................................. 12
Figure 8. INFO screen example ....................................................................................... 13
Figure 9. The back of the circuit’s cradle .......................................................................... 17
Figure 10. Wall mounting diagram .................................................................................... 18
Figure 11. External siren wiring scheme ............................................................................ 20
Figure 12. Trigger connections ......................................................................................... 20
Figure 13. OutView connection diagram ............................................................................. 52
Wireless Alarm Systems Installation Guide
4
NOTICE AND DISCLAIMER
This guide will help installers and operators in the safe and efficient installation and use of the wireless systems described herein.
Before trying to install and use the systems, read this guide and become familiar with all safety requirements and operating procedures.
The system must not be used for purposes other than those for which it was designed. The use of the software associated with the system is subject to the terms of the license
provided as part of the purchase documents.
PIMA Electronic Systems Ltd.’s exclusive warranty and liability is limited to the warranty and
liability statement provided in this manual and the peripherals guide (P/N 4410399).
This guide describes the maximum configuration of the systems with the maximum number of
functions, including future options. Therefore, not all functions described in this guide may be available in a specific system.
Warnings are given for situations and circumstances in which a possible hazard can arise. Cautions are given for situations or circumstances in which the system can possibly be damaged. Notes are given for situations that need special attention, or to improve the operating procedure. Wrong operation, or failure of the operator to effectively maintain the system, relieves the
manufacturer (and seller) from all or any responsibility for consequent noncompliance, damage, or injury.
The text and graphics contained in the guide are for the purpose of illustration and reference
only. In no event shall manufacturer be liable for any special, direct, indirect, incidental, consequential, exemplary or punitive damages (including, without limitation, any and all damages from business interruption, loss of profits or revenue, cost of capital or loss of use of any property or capital or injury).
Graphic signs in this guide
Icon
Description
Caution
Issues that may cause malfunctions
Warning
Issues that may cause damage and actual bodily harm
Note
Important note
Introduction
5
1 Introduction
This guide will help you to install PIMA’s Wireless Intruder Alarm Systems: the AlarmView, the Guardian and the AVR. The three systems are easy to install, plug-n-play, and provide wireless intruder alarm capabilities, with or without Visual-Verification and optional remote Look-in.
Suitable for residential and small business applications, they present a comprehensive solution for security and personal safety.
PIMA Wireless products also include a range of various peripherals.
The AlarmView’s unique offering incorporates the SmartView PIR /Camera that combines movement detection and image capturing, the OutView Wireless camera and a wide range of regular detectors.
With the Visual Verification, on an alarm event, the cameras transmit both the alarm event and the images to the control panel, which sends them over GPRS/GSM to the Monitoring Station, and optionally to the user’s mobile phone or email.
Note that all three alarm systems have two versions: Single SIM, and Dual SIM. Single SIM systems cannot utilize any of the features of the dual SIM systems.
1.1 Features
1.1.1 The AlarmView system
Figure 1. The AlarmView alarm system diagram
Visual Verification images are sent to the system’s contacts, by MMS and E-mail. See
the AVR section on page 7 for details
Remote Look-in images requests, by text messages from the mobile phones Remote Upload/Download initiation by the IP Receiver (without SMS)
Wireless Alarm Systems Installation Guide
6
Wireless peripherals including movement/smoke detectors, panic buttons, wireless
keypad, key fobs, door contacts, etc.
“SmartView” detector and camera:
“Matched field-of view” between the detector and the camera, with no dead spots Flash correction in lowlight High quality color images
OutView outdoor camera Double and Backup reporting Optional dual SIM End-user notifications by SMS, MMS & E-mail Alarm reporting options:
ContactID and SIA, via GPRS with SMS back-up Images via MMS and E-mail
MMS (Multimedia Messaging Service) requires Internet plan and costs money, including the text messages and emails sent via this service
Remote end-user commands by text messages Built-in Quad Band GSM/GPRS modem, with SMS as backup Advanced wireless visual link:
Two way supervised and secured radio network 128-bit encryption key Supervision report every 10 sec 2.4 GHz FHSS (Frequency Hopping Spread Spectrum) & Diversity receiver (2 antennas)
Supervised 868 MHz link for standard wireless peripherals Three programmable trigger inputs PGM output Graphic, user-friendly menu-driven LCD display Easy battery replacement Smartphone applications for controlling the AlarmView
1.2 The Guardian system
The Guardian is a full featured wireless alarm system, designed to answer the needs of most residential and small office installations. Based on the AlarmView system, it lacks the Visual capabilities, including Visual Verification and look-in image options.
The Guardian peripherals are the same as those of the AlarmView, except visual detectors and cameras.
The Guardian alarm system cannot be upgraded to include the complete enhanced visual features of the AlarmView system.
Figure 2. The Guardian
alarm system
Introduction
7
1.3 The AVR Visual Add-on
Figure 3. The AVR Visual Add-on
The AVR allows adding Visual Verification capacities to any Intruder Alarm System. Based on the AlarmView control panel, it is designed for sending Visual Verification and look-in images by up to six SmartView PIR/Cameras and OutView cameras.
By using trigger inputs and a PGM output, the AVR can do the following:
Be Armed and Disarmed Trigger the external Alarm System Serve as a GSM backup communication channel - when triggered by the external Alarm
System (on alarm, for example), the AVR will report the CMS/End-user
The AVR features are:
Six SmartView PIR/Cameras or OutView cameras Trigger inputs: two for Arming and Disarming, one for communication Backup of the
external alarm system
One PGM output. It can be used for cellular backup of the master system alarm
reporting
Optional dual SIM Two way communication with the SmartView and OutView Alarm & image notifications to contacts via MMS/SMS/E-mail Remote look-in images by contact requests (via SMS) Remote Upload/Download initiation by the IP Receiver (without SMS)
Wireless Alarm Systems Installation Guide
8
1.4 Technical specifications
1
General
Number of zones
Up to 30: 23 wireless, 1 hardwired, 6 visual
Wireless Peripherals
Up to 6 key fob remotes, or keypads Up to 6 Panic buttons External siren
Arming modes
AWAY/HOME/PART
Alarm types
Silent, siren or sounder
Built-in siren
Piezoelectric, 85 dBA at 3 m
External siren
1 siren, wireless (indoor/outdoor)
Event log
256 events, non-volatile, with time and date stamp
Codes
8 codes, 4 to 8 digits each (numeric value 1-4):
Master user 4 Regular users (or up to 4 digit code, numeric value 0-9, with
external keypad)
Duress code Limited 24H code Installer code
Special functions
Remote control by SMS from one (predefined) mobile phone,
ensuring privacy and security.
Remote Look-in via MMS Local USB connection for setup and
firmware upgrade
I/O
1 PGM output, 3 trigger inputs + trigger #1 can serve as zone #24
Real-time clock
Time and date stamp
Wireless
Advanced wireless link for visual zones
Frequency Band
2.4 GHz ISM band
TX Power
Up to 100 mW
Transmission method
2-way communication GFSK Frequency Hopping Spread Spectrum (FHSS)
Supervision
Up to 20 seconds
Secured wireless network
48-bit factory set ID code Built-in security using a link key (prevents unauthorized
access)
Data encryption (up to 48-bit)
Expected range2
Up to 100 m (outdoors)
Wireless link for standard peripherals
Frequency
868.6375 MHz
Supervision
Randomly, every 20-50 m + on every transmission
Transmission method
FM, narrow band
Expected Range
Up to 100 m outdoor. Can be extended indoors using the RP-15 Repeater
Communication
Modem
Interface
Quad-band GSM/GPRS
Report destinations
CMS Receivers, mobile phones, Email accounts
Reporting formats
SMS/MMS/Email (by SMTP)/GPRS-IP
1
The specifications of the detectors and accessories can be found in the peripherals guide (P/N 4410399)
2
Range is impacted by building materials and interference
Introduction
9
End user contacts
Reporting options/formats:
GSM/GPRS, SMS/MMS/Email (via mms) notifications Four cellular phone numbers Four email accounts
CMS contacts
Reporting options/formats: GSM/GPRS, SMS/MMS/Email (via mms) notices
Two IP address Two phone numbers Two Email accounts
Others
Physical Characters
Casing
Plastic - PC/ABC 94/V0
Environmental Data
Operating temperature
-10ºC - +49ºC
Storage temperature
-25ºC - +70ºC
Humidity
85%, non-condensed
Electrical Data
Power supply
+12VDC/1A
Current drain
100 mA standby, 0.7A peak
Backup battery
+4.8 VDC, 4 x Ni-MH 2 Ah
Weight:
With battery Without battery
687 gr 577 gr
Dimensions
225 x 138 x 40 mm
The control panel reports on Low Battery condition 9-12 hours after AC loss. 1-4 hours later it will turn off. Overall, the control panel can stay more than 12 hours in standby mode
We recommend using original AC adaptor and backup battery pack from PIMA Electronic Systems
Wireless Alarm Systems Installation Guide
10
2 Quick Reference Guide
2.1 System components
The alarm system consists of the control panel, and depending on the model, wireless zones (23), one hardwired zone, visual zones (6) and wireless peripherals (up to 36).
The
Control Panel: consists of the main circuitry, GPRS/GSM module, two wireless
transceivers - standard and visual dedicated one.
Figure 4. The
control panel
Visual detectors:
SmartView: high quality, supervised, rapid-acquisition camera, with PIR detector. OutView: high resistance outdoor camera, with trigger input from external sources, e.g.,
PIR detectors and magnets.
Wireless detectors: the AlarmView system supports a wide range of wireless detectors,
including door contacts, PIR and Pet-immune motion detectors, Smoke detectors, etc.
Sirens: the control panel has a built-in siren. An external wireless siren (with a strobe)
can also be installed.
Keyfobs/keypads: accessories that are used to arm and disarm the AlarmView. Panic/Medical pendant and wrist watch: accessories that are used to send emergency
and panic signals.
2.2 The Control Panel
The next figures show the control panel’s buttons and parts. The three arming buttons are disabled in the AVR.
Figure 5. The control panel keys
Quick Reference Guide
11
Figure 6. Control panel’s back side
2.2.1 The buttons
The table below details the buttons of the control panel.
Button
Function
Press to…
AWAY
Arm to AWAY (full) mode
HOME
Arm to HOME mode
PART
Arm to PARTIAL mode
Left
Access the menus, Select and Insert
Right
Display the system’s Status, Cancel and Delete
OK
Confirm, Enter
Up
Scroll, type the characters A-Z, 0-9, #+_!@- space
Down
Left
Scroll, Exit, Back, and the numeral 4
Right
Scroll, Enter, Duplicate previous character, and numeral 2
Wireless Alarm Systems Installation Guide
12
2.2.2 The display
The LCD screen displays the status, the current time, and the cellular provider and reception. See the following diagram for details.
Figure 7. The LCD display and buttons
2.2.2.1 The icons
The available icons are:
Transmission of SMS message
Low backup battery
GSM reception level
Battery loss
GSM network error
SIM1 active, fault
AC loss
SIM2 fault3
GPRS transmission
SIM1+2 fault3
2.2.3 Sound indications
The table below lists the sounds the Control Panel sounds.
Tones
Sound
Sounded when
Single beep
A key is pressed
♪-♪
Two beeps
A menu timeout occurs – exit to main menu
♪-♪-♪
Three beeps
Successful command or operation
♪-♪-♪-♪…
Continuous beeps
Entry/Exit delay mode
♪--------♪
Long beep
Illegal command or entry refusal

Chime
Chime is activated
3
Displayed only in dual SIM systems
Quick Reference Guide
13
2.2.4 LED indications
The table below shows the LED color indicators and their meaning.
LED
Color+ Behavior
Indication
Green
Power on
Blank
Power loss
Blue, blinking
Wireless communication is active
Green, blinking
Cellular connection - OK
Off
No cellular connection
Orange, 3 blinks
Message waiting to be processed
Red
System trouble. See LCD display for further information
White, blinking
Alarm triggered - all arming modes. Blinking will stop when re-arming, or entering the system log
2.2.5 The INFO screen
The INFO screen shows a grid of all active zones (up to #30, including visual zones, where available) in several status options. To display it, press the INFO button when the system is disarmed.
Figure 8. INFO screen example
The next table explains the various zone indications. A zone with more than one status toggles between them, at one second interval.
Status
Description
Zones in the above example
Empty cell
Undefined zone
19, 20, 30
1-30
Defined zone, Normal mode
1, 2, 4, 6, 7, 9, 10, 12, 17, 18, 21, 24, 25, 27, 29
Open zone
5, 22, 23
T
Zone tamper open
3, 26
B
Bypassed zone
13, 14
Low battery
11
X
Supervision loss
15
Alarm
8, 16, 28
1 2 4 6 7 10
27
17 1812
21 25
T B X
T
9
B
2924
Wireless Alarm Systems Installation Guide
14
3 System Installation
3.1 General guidelines
The control panel should be installed at a location with optimum wireless reception from
the detectors and peripherals.
A convenient location for mains electricity supply and for user operation, near the main
access point is preferable.
For control panels which are operated using remote keypads, the panel can be
concealed inside a cupboard or loft space in a convenient location for mains electricity supply.
3.2 Quick installation
For quick installation, you can mount the control panel on any flat surface. To do that, do the following:
1. On the back side, release the crosshead (“Philips”)
screw of the battery compartment and remove the cover. The battery lies in the compartment, not connected
2. Connect the battery wires to the socket
System Installation
15
3. Close the compartment and fasten the screw
4. Remove the plastic protector of the connectors
cavity, by applying pressure with a flathead screwdriver
5. Insert the SIM card(s) to the SIM holder: a. In single SIM versions, insert the SIM card into the upper slot (labeled “SIM-1 Main”) b. In dual SIM versions, first insert the backup SIM into the lower slot (labeled “SIM-2
Backup”), and then insert the main SIM into the upper slot (labeled “SIM-1 Main). See the next figure
Do not use PIN Code SIM cards Do not insert SIM cards under power (AC or DC)
6. Plug the AC adapter into its socket, to the left
of the SIM card holder
Do not connect the AC adapter to power before connecting it to the control panel
7. Attach the plastic protector back in place and
pass the AC wires through the wires path
8. Connect the AC adapter to power. Wait for
the Power LED to light up and the LCD screen to show the normal display
9. Ensure good reception of the wireless and GSM communications (see section 7.1.1.2,
on page 28)
Wireless Alarm Systems Installation Guide
16
10. Secure the control panel to the designated surface:
drill two holes, corresponding to the two keyhole hangers on the back plate (see the image below), and fasten the supplied screws, leaving a small space between the screw head and the surface
11. Hang the control panel
3.3 Professional mounting
If the control panel needs to be secured with the tamper protection, do the following steps:
1. Open the cover: insert a small slotted
screwdriver into the two slots at the bottom of the control panel and apply pressure upwards
2. Lift and remove the front cover
System Installation
17
3. Pull out the plastic cradle of the circuit board,
by pulling its two clips on both sides, and turn it over
Figure 9. The back of the circuit’s cradle
4. Connect the battery wires to the socket
SIM-1 Main
SIM-2
Backup
Wireless Alarm Systems Installation Guide
18
5. Insert the SIM card(s) to the SIM holder: a. In single SIM versions, insert the SIM card into the upper slot (labeled “SIM-1 Main”) b. In dual SIM versions, first insert the backup SIM into the lower slot (labeled “SIM-2
Backup”), and then insert the main SIM into the upper slot (labeled “SIM-1 Main). See the previous figure
Do not use PIN Code SIM cards Do not insert SIM cards under power (AC or DC)
6. On the designated surface, drill holes, corresponding to those marked with arrows on the
next figure and insert drywall plugs into them. Note, that the hole in the middle is designated
for the tamper switch’s knockout4
The tamper switch knockout must be secured with a dedicated screw, to comply with EN50131-1 regulation
Figure 10. Wall mounting diagram
7. Route the AC adapter’s plug and wires through the wires path. See the next figure.
8. Secure the back plate to the surface with screws.
4
When the control panel is forcibly removed from the wall, the knockout breaks and the tamper is activated
195mm
70mm
29mm
Tamper switch knockout
System Installation
19
9. Plug the AC adapter into its socket, to the
left of the SIM card holder
Do not connect the AC adapter to power before connecting it to the control panel
10. With the LCD screen facing you, insert the
cradle into the mounted back plate - push it firmly, until the clasps are locked. Ensure the back tamper is pressed against the knockout
11. Tilt the front cover towards top of the
mounted back plate
12. Insert the two jags on the front cover to the
corresponding holes on the back plate, and push it down, until you hear an audible press
13. Press the front cover against the back plate,
until locked
14. Secure the front cover with the two supplied
Philips screws, at the bottom
15. Connect the AC adapter to power. Wait for
the Power LED to light up and the screen to show the normal display
Wireless Alarm Systems Installation Guide
20
3.4 Other installation options
3.4.1 Standalone wired siren
Besides the control panel’s built-in siren, you can also connect any self-powered external siren. To do so, you will need to connect it to an external power source.
The wired siren’s current consumption should not exceed 500 mA
To connect the siren:
1. Run the siren’s wires through the opening on
the control panel’s back plate
2. Connect between the siren and the control
panel’s PGM terminals. See the scheme on the right
3. Connect between the siren, the control panel
and the external power source (-)
4. Connect between the siren and the external
power source (+)
Figure 11. External siren wiring scheme
3.4.2 How to use the trigger inputs
5
The alarm system has three inputs listed in the next table, which can be used to arm and disarm it by triggers from external alarm systems. See the next sub-section on the AVR.
Input
Optional Use
TR1
arming to AWAY mode
TR2
arming to HOME mode
TR3
arming to PART mode
When using the triggers for arming and disarming, the control panel’s quick
arming buttons are disabled
Connect the triggers according to the next diagram.
Figure 12. Trigger inputs
5
See section 10.5.4, on page 43 for the triggers’ settings
PGM
-
+
External power source
+
-
+ 12V -
TR1 COM TR2 TR3 COM PGM
From PGM/
ALARM outputs
+ 12V -
TR1 COM TR2 TR3 COM PGM
System Installation
21
3.4.3 The AVR
The AVR adds Visual Verification capacities to any Intruder Alarm System. Based on the AlarmView control panel, it is designed for sending Visual Verification and look-in images by up to six SmartView PIR/Cameras and OutView cameras.
The AVR is defined as “Slave” when connected to an external alarm system (“Master”).
By using trigger inputs and a PGM output, the AVR can do the following:
Be Armed and Disarmed Trigger the external Alarm System Serve as a GSM backup communication channel - when triggered by the external Alarm
System (on alarm, for example), the AVR will report the CMS/End-user
By default, the AVR will use the triggers as follows:
Trigger
Default setting
Connect the input to…
#1
Wired/External zone
External alarm system’s Alarm output. The input will serve as a backup communication channel - when the Alarm output will be triggered (on alarm, for example), the AVR will report the CMS/ end­user. Make sure zone #24 (the wired zone) is set as 24H zone6
#2
AWAY arm
External alarm system’s On/Off output. The input will be used for arming AWAY the AVR (and disarming it) by the external alarm system
#3
Not used
-
3.4.3.1 How to connect the triggers to the external alarm system
Use the following diagram and table to connect the trigger inputs of the AVR.
Figure 13. The AVR trigger inputs
AVR
Alarm system
TR1
PGM/Alarm Output
TR2
On/Off Output
6
“Swinger Shutdown” must be disabled
PGM/Alarm Output
On/Off Output
COM
COM
External Alarm
System (“Master”)
Trigger inputs
AVR (“Slave”)
Wireless Alarm Systems Installation Guide
22
3.4.3.2 How to connect the PGM output to the external alarm system
By default, the PGM output is used by the AVR to report on “Not Ready/Alarm” (open zone,
faults, and alarms) situations. It is set as Normally Closed. See section 10.5.3, on page 43 for details on the PGM output options.
Figure 14. The AVR PGM output
3.4.4 External antenna
The control panel has a model with a connector for external GSM antenna (P/N 6110019), to improve GSM reception where necessary
This control panel model must be ordered separately!
3.5 How to confirm system installation
To make sure all detectors are well identified by the control panel after installation, do the following:
1. Access the Installer menu and select Service -> Tests -> Zone Tests
2. Press the Test button on each detector and check the reception level. See section 7.1.1.2,
on page 28 for details
Zone Input
AVR (“Slave”)
External Alarm
System (“Master”)
PGM Output
Setup and Programming
23
4 Setup and Programming
The alarm system has two menus and two related passwords: Installer and Master User. The two menus have the same sub-menus, except the Programming menu which is exclusive to the Installer.
Programming can also be done remotely, using PIMA’s Programming Tool software7.
Some menus are feature depended and vary between models
4.1 The Installer’s menu map
7
Version 02.00.11.00 and higher
STOP COMM.
BACK
ZONE BYPASS CONTACTS
TESTS ENABLE PROGRAMMING DISPLAY VERSION SYSTEM RESET
MASTER USER DURESS CODE 24H LIMITED CODE
INSTALLER
DATE
ZONES/PERIPHERALS CONTACTS CMS CONTACTS COMMUNICATION SYSTEM OPTIONS FACTORY DEFAULTS LOCAL PROGRAMMING FIRMWARE UPGRADE
PROGRAMMING
BACK
SET CLOCK
BACK
PASSWORDS
BACK
SERVICE
BACK
EVENT LOG
BACK
OPTIONS
BACK
REGULAR USERS
TIME
GLOBAL SETTINGS
Wireless Alarm Systems Installation Guide
24
4.2 Accessing the menus
To access either of the menus:
1. Press the left key (under “MENU”) - a password entry
field will appear
2. Use the numeric/navigation keys to enter a password. See section 2.2.1, on page 11, on how
to enter characters
4.3 The Master and Installer passwords
The next table lists the Master user and Installer passwords and their use.
Password
Default
The password allows
Master user
1111
Changing all passwords except the Installer’s, viewing the event log, setting the time, and changing some system settings
Installer
1234
Changing the Installer password, changing all settings the control panel and all detectors and peripherals
You must change the default passwords during the installation of the system
4.3.1 How to reset the passwords to factory defaults
To reset the passwords to their factory default:
1. Disconnect the control panel from both AC power and backup battery for 10 sec.
2. When you power up the control panel again, the Master User and Installer’s default
passwords (1111, 1234 respectively) can be used for 30 sec. to access the menus
DELETE
ENTER PASSWORD
Options menu
25
5 Options menu
This menu allows changing and controlling the general behavior of the Control Panel as well as setting notifications for the contacts.
5.1 Global Settings
The Global Settings menu allows setting of three features, as explained below. The remote look-in and visual events features allows the end user to maximize the control of all privacy issues.
To change the Global Settings:
1. Access the Installer menu and select Options Global Settings
2. Set/Clear (enable/disable) the options, which are: a. Global Chime: all chime zones
b. Remote Look-in: sending requested look-in images to predefined mobile phones c. Visual Events: sending visual verification images to predefined mobile phones
5.2 Zone bypass
This menu allows bypassing zones until the next disarming of the alarm system
Do not bypass zones unless necessary and only temporarily: bypassed zones do not sound the alarm when opened, nor are reported to the CMS
To bypass zones temporarily, do the following:
1. Access the Installer menu and select Options Zone Bypass
2. Set (enable) the zones to be bypassed. Press the Up/Down
keys to scroll between the zones
3. Clear (disable) zones to un-bypass them
5.3 Contacts
This menu allows setting which of the six available contacts will get notifications on alarms and other system events. The events are set in the “Contact 1-6” menu. See section 10.2.2, on page 37.
To set a contact to receive notifications, do the following:
1. Access the Installer menu and select Options Contacts
2. Press Set to enable a contact, press Clear to disable a contact
GLOBAL SETTINGS ZONE BYPASS CONTACTS
BACK
OPTIONS
GLOBAL CHIME REMOTE LOOK-IN VISUAL EVENTS
GLOBAL SETTINGS
T GLOBAL CHIME T REMOTE LOOK-IN
CANCELSET/CLEAR
GLOBAL SETTINGS
£ ZONE 1 £ ZONE 2
CANCELSET/CLEAR
ZONE BYPASS
T CONTACT 1 T CONTACT 2
CANCELSET/CLEAR
CONTACTS
Wireless Alarm Systems Installation Guide
26
6 Event Log menu
This menu allows you to view the system log. The log keeps the last 256 events. While the alarm system is armed, it can log up to 10 events from the same zone.
Using the “Programming Tool” application, 500 events can be logged and viewed.
To view the Event Log:
1. Access the Installer menu and select Event Log. The first event is
the most recent one
2. Use the Up/Down keys to scroll between the events. See the next section for
details.
3. Press to exit the log
6.1 Log entry examples
The information of a log entry is displayed as follows:
1. Date and time the event was logged
2. Event description
3. Event source
4. Log entry serial number
BACK
EVENT LOG
21/5/14
CANCEL
07:33:20
124
Full Arm (Away) System (AlarmView)
CANCEL
21/05/14 07:33:20 31
Supervision Loss ZONE 11 (Room 6)
CANCEL
02/06/14 22:03:20 105
Alarm from Zone ZONE 20 (Bath)
CANCEL
17/11/14 20:47:20 16
Full Arm (Away) System (AlarmView)
2 3
4
1
2 3
4
1
2 3
4
1
Service menu
27
7 Service menu
The Service menu allows you to perform various tests to verify the installation and the proper operation of the system. The “Enable Programming” menu is a Master user only menu - it enables the user to allow a two hour remote access to the alarm system. If the default Access Code has
not been changed, this option overrides the “Always” access mode. See section 0, on page 44
7.1 Tests
The tests menu allows testing the zones and peripherals of the alarm system and some more options.
Testing the system periodically will ensure the system owner that the system works properly.
7.1.1 Zones
To test the zones:
1. Access the Installer menu and select Service
Tests Zones
2. The zone test screen is made of a grid that shows all
active zones: zones 1-24 are displayed with their number, zones 25-30 are displayed with their RSSI8
level. See the next two sub-sections for full details.
3. Trigger zones 1-24 - when a signal is received in the control panel, the zone number is
replaced by the RSSI reception level.
4. Once the test is complete, press to exit.
7.1.1.1 Zone status options
There are three status options in the zone test display (see the next figure):
a. Number: this is the zone number. It appears in regular zones before testing, and in visual
zones that are at fault
b. Signal strength indicators:
1) Zones 1-24: the indicators appear as the zone is triggered
2) Zones 25-30 (visual zones): the indicators interchange with the zone no.
c. Empty: the zone is disabled
8
Received Signal strength Indication.
BACK
SERVICE
TESTS
ENABLE PROGRAMMING
DISPLAY VERSION SYSTEM RESET
TESTS
ZONES EXTERNAL SIREN BUILT-IN SIREN COMMUNICATION SYSTEM SELF TEST
3 4 5 6 8 9 10
11 12 16 17 20
1
26
Wireless Alarm Systems Installation Guide
28
7.1.1.2 RSSI reception level
The signal strength indicators allow you to determine how good the communication, between the wireless devices and the control panel is. The number of the indicators is the quality of the reception, as explained in the table below. See also the previous figure
Onscreen
Indicators
Reception/Indication
5
Excellent
4
Strong
3
Good
2
Low: see the warning below!
1
Poor: see the warning below!
Numeral
-
1. Zones 1-24: the zone was not triggered
2. Zones 25-30: the (visual) zone is at fault
"Poor and “Low” reception levels are not acceptable. If you get a "poor" signal from any detector, re-locate it and re-test it, until the test result is between "Excellent" and "Good"
7.1.2 External Siren
See also External Siren Indications, on page 53
7.1.2.1 Test
To test the external siren, do the following:
1. Access the Installer menu and select Service Tests
External Siren
2. Press Test
3. Wait 5 sec. The siren will sound the alarm for 3 sec. and its LEDs will flash for few sec.
4. Press to exit
7.1.2.2 Stop siren
If the siren’s tamper switch is tripped continuously, you can use this feature to stop (silent) the siren.
7.1.2.3 Relearn
If the siren needs to be re-learned with the control panel, call PIMA support for instructions
TEST
RELEARN
EXTERNAL SIREN
STOP SIREN
TEST STOP SIREN
BACKSELECT
EXTERNAL SIREN 1
Service menu
29
7.1.3 Built-in siren
To test the built-in siren, do the following:
1. Access the Installer menu and select Service Tests Built-In Siren
2. Press - the built-in siren will sound briefly
7.1.4 Communication
This menu allows testing the SIM card’s communication setup, by trying to send and receive data. See the next table for complete details.
To test the SIM cards:
1. Access the Installer menu and select Service Tests
Communication
2. Select SIM1 or SIM2 (in dual SIM versions). If the selected SIM is
currently idle, the alarm system will switch to it
3. Select the test type and press
4. Press at the end of the tests
7.1.4.1 Test types
The test types are described in the below table. All tests are replied by either “Passed” or “Failed” message
Test
Process
GPRS Link
Ping a website (www.google.com)
CMS 1-2
Send a test event to the CMS:
a. In SIA/CID over SMS: to mobile phone b. In Visual/CID over Email: to E-mail c. In Visual/CID over GPRS: to PC, mobile phone
Contact 1-6
Send “Periodic Test” by text message:
a. SMS Test: to mobile phone (“SMS Event Report” must be enabled.
See page 37)
b. Email Test: to E-mail (“Email Event” must be enabled. See page 37)
7.1.5 System self-test
The self-test checks the LCD display, the LEDs and the chime
To do the test:
1. Access the Installer menu and select Service Tests System Self Test
2. The LCD display will flicker for eight sec. and the internal sounder will sound a series of beeps
COMMUNICATION
SIM 1(MAIN) SIM 2(BACKUP)
GPRS LINK CMS 1-2 CONTACT 1-6
SIM 1(MAIN) SIM 2(BACKUP)
BACKSELECT
COMMUNICATION
GPRS LINK CMS 1
BACKSELECT
COMMUNICATION
Wireless Alarm Systems Installation Guide
30
7.2 Display version
Use this feature to view the system’s version and RF frequency
To view the system version and frequency:
1. Access the Installer menu and select Service Display Version
The system’s software version and RF frequency will be displayed
2. Press to exit
7.3 System reset
The system reset feature enables to reset the communication channels.
To do a system reset:
1. Access the Installer menu and select Service System Reset
2. Wait for the short process to end. While resetting, the message
UPDATING is displayed
ALARMVIEW.STD.EN
02.09.07.00.000 FREQ:868.635
OK
UPDATING
AlarmView
Passwords Menu
31
8 Passwords Menu
The password menu allows you setting the Installer password. The other passwords on the menu can be set only by the Master User, in the User menu.
8.1 Installer
The Installer password can be 4-8 digits long and contain the numeric values of 1-4, for example
14412311. It cannot be deleted.
You must change the default Installer password during installation
To set the Installer password:
1. Access the Installer menu and select Passwords Installer
2. Select Password and type the desired password
3. Press
You cannot use the Installer password over the wireless keypad, only the
control panel
A minimum of 7 digit password is required to comply with EN requirements
8.1.1 Access mode
There are two options for allowing the installer to access the alarm system remotely, via the Programming Tool application: User Initiated and Always, explained below.
The AlarmView keeps a record of any remote connection and reports it to the CMS.
a. User Initiated: in this mode the Installer cannot access the menu, unless the Master
user permits it by opening a two hour access window (on the User menu: Service Enable Programming)
b. Always: in this mode the Installer can access the system without the need for the
Master user approval
You must change the default Access Code, to be able to connect to the
alarm system remotely in the “Always” mode: as a precaution, if the
default code has not been changed, remote access without the Master user approval is disabled
REGULAR USERS MASTER USER DURESS CODE
BACK
PASSWORDS
24H LIMITED CODE
INSTALLER
PASSWORD ACCESS MODE
BACKSELECT
INSTALLER
Wireless Alarm Systems Installation Guide
32
To define the Installer’s access mode, do the following:
1. Access the Installer menu and select Passwords Installer
Access Mode
2. Select User Initiated or Always
9 Set Clock menu
After a long power failure, or whenever the time is not accurate, the time and date need to be set
9.1 Time
To set the Time, do the following:
1. Access the Installer menu and select Set Clock Time
2. Press to change between 12H (AM/PM) and 24H time
formats
3. Press the up and down arrow keys to set the hour and minute
4. Press the right and left arrow keys to move the cursor between the hours and the
minutes
5. Press to save
9.2 Date
To set the Date, do the following:
1. Access the Installer menu and select Set Clock Date
2. Press to set the date format to either American (MM/DD)
or European (DD/MM)
3. Press the up and down arrow keys to set the date
4. Press the right and left arrow keys to move the cursor between the day, month
and year
5. Press to save
P USER INITIATED ALWAYS
SELECT
INSTALLER 1
CANCEL
TIME DATE
BACK
SET CLOCK
CANCELAM-PM/24H
22 17
:
CANCELDD-MM/MM-DD
16 05 14
/
/
Programming menu
33
10 Programming menu
The programming menu allows you to program the various functions of the alarm system.
10.1 Zones/Peripherals
Enroll and define the wireless detectors and peripherals of the alarm system. Before enrolling, make sure all peripherals have the appropriate batteries.
All three systems, the AlarmView, Guardian and AVR support up to 23 wireless zones and one hardwired. The AlarmView and AVR also support up to six Visual zones.
10.1.1 Zones
To enroll and define a wireless zone:
1. Access the Installer menu and select Programming Zones/
Peripherals Zones
2. Select Zone 1-24
9
3. Select Device ID and press Learn to enroll a detector or a
peripheral. If a number is displayed, the zone already has a device associated with. You can press “Delete”, and enroll a new device
4. Trigger a device or press its Test button. When the device is
detected, press
9
Zone #1 is set as Entry/Exit zone by default
ZONES/PERIPHERALS
BACK
PROGRAMMING
CONTACTS CMS CONTACTS COMMUNICATION SYSTEM OPTIONS FACTORY DEFAULTS LOCAL PROGRAMMING FIRMWARE UPGRADE
ZONES
ZONE 1-24 DEVICE ID
ZONE TYPE ARM SET NAME OPTIONS SWINGER SHUTDOWN STATE
ZONE 1 ZONE 2
BACKSELECT
ZONES 1
DEVICE ID ZONE TYPE
BACKSELECT
ZONE 1 1
CANCELLEARN
LEARN DEVICE ID
A1B2C344
CANCELDELETE
LEARN DEVICE ID
Wireless Alarm Systems Installation Guide
34
Select Zone Type and select the type. The available types are: Normal, Entry/Exit, Follower, 24H, Panic, Medical, and Fire. See
the Glossary of terms, on page 55 for more on each type
5. Glossary of terms
6. Select Arm set and set to which arming mode the zone will be
armed. The available modes are: Home, Away, and Part. Multiple selection is allowed
7. Select Name and give the zone a name. See section 2.2.1, on page 11 for details
8. Select Options and set the zone options. Multiple selection is
allowed. The available options are as follows:
Siren: when the zone is violated, it will trigger the siren
Chime: when the zone is opened while the control panel is disarmed, it will trigger the
control panel’s chime. This is normally used on doors and windows
Force Arm: this zone can be armed when the Force Arm option is enabled. See section
10.5.2, on page 42 and the “Glossary of terms”, on page 54 for more details
9. Select Swinger Shutdown (see the “Glossary of terms”, on page
54) and select between the available options: 1, 2 or 3 alarms, or Disable
10. Select State and set if the zone is Enabled or Disabled.
Zone #24 is a dedicated hardwired zone. As such, it does not have the “Device ID” option. To use this zone Trigger #1 must be set as “Wired/EXT zone”. See
section 10.5.4, on page 43
10.1.2 Visual zones (AlarmView and AVR only)
The alarm system supports up to six visual zones, namely SmartView PIR/cameras.
To enroll and define a visual zone:
1. Access the Installer menu and select Programming Zones/
Peripherals Visual Zones
2. Select Zone 25-30 (Visual)
3. Select Device ID and type the detector’s serial number (8 digits).
If a number is displayed, the zone already has a device associated with. You can press “Delete”, and enroll a new device
P ENTRY/EXIT FOLLOWER
CANCELSELECT
ZONE TYPE 1
x HOME x AWAY
CANCELSET/CLEAR
ARM SET 1
x SIREN x CHIME
CANCELSET/CLEAR
OPTIONS 1
P 3 ALARMS DISABLE
BACKSELECT
SWINGER SHUTDOWN 4
VISUAL ZONES
ZONE 25-30
(VISUAL)
DEVICE ID ZONE TYPE ARM SET NAME OPTIONS SWINGER SHUTDOWN STATE
ZONE 25 (VISUAL) ZONE 26 (VISUAL)
VISUAL ZONES 1
BACKSELECT
DEVICE ID ZONE TYPE
BACKSELECT
ZONE 25 (VISUAL) 1
00000000
DELETEINSERT
DEVICE ID
Programming menu
35
Visual detectors cannot be enrolled automatically, to protect privacy and security
4. Select Zone Type and mark the type. See the previous “Zone”
section for the available options
5. Select Arm set and set the arming mode in which the zone be
armed. See the previous “Zone” section for the available options
6. Select Name and give the zone a name. See section 2.2.1, on page 11 for details
7. Select Options and set the zone options. Multiple selection is
allowed. The available options are as follows:
Siren: when the zone is violated, it will trigger the siren
Force Arm: this zone can be armed when the “Force Arm” option is enabled. See section
10.5.2, on page 42 and the “Glossary of terms”, on page 54 for more details
Visual Verif.: send visual verification images to predefined contacts Remote Look-in: allow predefined contacts to request look-in images by SMS Led Indication: SmartView LED ON when alarmed
8. Select Swinger Shutdown (see the “Glossary of terms”, on page
54) and select between the available options: 1, 2 or 3 alarms, or Disable
9. Select State and select if the zone is Enabled or Disabled
10.1.3 Keyfobs/keypads
The alarm system supports the connection of up to six KF key fobs and RWK wireless keypads. See a separate Peripherals guide (P/N 4410399) for details on these devices.
To enroll and define a key fob or a wireless keypad, do the following:
1. Access the Installer menu and select Programming Zones/
Peripherals Key fobs/ Keypads Key fob/Keypad X
2. Select Device ID and press Learn to enroll the peripheral
10
If a number is displayed11, the zone already has a device associated with. You can press “Delete”, and enroll a new device
3. Press to save the ID
4. Select Name and type a description for the keyfob/keypad
5. Select State and select Enabled or Disabled
10
Or type it: the ID is printed on a label on the keyfobs and keypad
11
Only the first seven digits are displayed (the eighth is always zero). The serial no. is printed on a label on
the detector
33569874
DELETEINSERT
DEVICE ID
P NORMAL ENTRY/EXIT
CANCELSELECT
ZONE TYPE 1
x HOME x AWAY
CANCELSET/CLEAR
ARM SET 1
x SIREN x FORCE ARM
CANCELSET/CLEAR
OPTIONS 1
P 3 ALARMS DISABLE
BACKSELECT
SWINGER SHUTDOWN 4
KEYFOB/KEYPAD 1
DEVICE ID NAME STATE
KEYFOBS/KEYPADS
DEVICE ID NAME
BACKSELECT
KEYFOB/KEYPAD 1 1
CANCELLEARN
LEARN DEVICE ID
A1B2C344
CANCELDELETE
LEARN DEVICE ID
Wireless Alarm Systems Installation Guide
36
10.1.4 Panic button
The alarm system supports the connection of up to six PCP buttons for Panic and Medical issues. See a separate Peripherals guide (P/N 4410399) for details on these devices.
To enroll and define a Panic/Medical button:
1. Access the Installer menu and select Programming
Zones/Peripherals Panic Buttons
2. Select Panic Button X
3. Select Device ID and press Learn
4. Press the panic button to enroll it
12
. If a number is displayed11, the zone already has a button associated with. You can press “Delete”, and enroll a new one. See a separate peripherals guide (P/N 4410399) for more details on the panic button
5. Select Type and select the button type: Medical or Panic. The
type selected only determines the event reported
6. Select Name and type a name/description for the panic button (see section 2.2.1, on page 11
for instructions)
7. Select State and select if the button is Enabled or Disabled
10.1.5 External siren
See a separate Peripherals guide (P/N 4410399) for complete details on the SIR External Wireless Siren.
To enroll and define the siren:
1. Access the Installer menu and select Programming Zones/
Peripherals Ext. Siren
2. Select Device ID
3. Enter the siren’s serial number and press Insert (see section
2.2.1, on page 11 for instructions). The number is printed on a label
at the back of the siren (and also on the siren’s package)
12
Or type it: the ID is printed on a label on the button
PANIC BUTTON 1
DEVICE ID
NAME STATE
PANIC BUTTONS
TYPE
PANIC BUTTON 1 PANIC BUTTON 2
BACKSELECT
PANIC BUTTONS 1
DEVICE ID TYPE
BACKSELECT
PANIC BUTTON 1 1
CANCELLEARN
LEARN DEVICE ID
A1B2C344
CANCELDELETE
LEARN DEVICE ID
P MEDICAL PANIC
SELECT
TYPE 1
CANCEL
DEVICE ID
CUT OFF OPTIONS (AWAY)
EXT. SIREN
START DELAY
STATE
DEVICE ID START DELAY
BACKSELECT
EXT. SIREN 1
000000
CANCEL
DEVICE ID
INSERT
Programming menu
37
4. If required, select Start Delay and enter a delay in sec. before the
siren will sound the alarm, between 0 (default) and 255
5. Select Cut Off and enter the time, between 5 and 255 sec.
(default - 60)
6. Select Option (Away) and set options, that are available only
while the alarm system is armed to AWAY mode:
a. Arming tones: the siren will beep once when arming the
system, and twice when disarming
b. Entry/Exit tones: in addition to the control panel internal sounder, the siren will
sound clock ticks during the exit and entry delays. See “External Siren Indications”, on page 50 for details
7. Select State and select if the siren is Enabled or Disabled
10.1.6 Built-in siren
The system has an 85 dB internal siren, sufficient for indoor alarm.
To define the built-in siren:
1. Access the Installer menu and select Programming Zones/
Peripherals Built-In Siren
2. Select Cut Off and enter the time, between 5 and 255 sec. (default - 60)
3. Select State and select if the siren is Enabled or Disabled
10.2 Contacts
The system allows defining up to six contacts, for receiving event and fault notifications.
10.2.1 System name
The system name is used to personalize the alarm system in the messages the contacts receive.
To define the name:
1. Access the Installer menu and select Programming Contacts
2. Select System Name. Leave the default name or type a new one
(see section 2.2.1, on page 11 for instructions)
3. Press
10.2.2 Contact 1-6
Define the various details of up to six contacts of the alarm system, as follows:
1. Access the Installer menu and select programming User
Contacts Contact X
2. Select Mobile Phone and enter a mobile phone number
0
DELETE
START DELAY
INSERT
60
DELETE
CUT OFF
INSERT
£ ARMING TONES £ ENTRY/EXIT TONES
CANCELSET/CLEAR
OPTIONS (AWAY) 1
CUT OFF STATE
BACKSELECT
BUILT-IN SIREN 1
SYSTEM NAME
CONTACTS
CONTACT 1-6 EVENT REPORT
SYSTEM NAME CONTACT 1
BACKSELECT
CONTACTS 1
MOBILE PHONE EMAIL (BY MMS)
BACKSELECT
CONTACT 1 1
Wireless Alarm Systems Installation Guide
38
3. Select Email (By MMS) and enter an E-mail address. E-mails are sent via MMS (Multimedia
Message Service) messages and cost money to the end user (by the service provider)
4. Select Contact Name and type a name (see section 2.2.1, on page 11 for instructions)
5. Select Options and set the contact’s options, as described in the
next table
Option
The contact will be…
SMS Remote CMD.*
allowed to send arm, disarm and other commands by SMS. See section 12.2.1, on page 48
Remote Look-in*
allowed to receive look-in images
SMS Event Report*
receiving notifications on alarms and other events by SMS
MMS Visual
receiving visual verification images by MMS
Email Event
receiving notifications on alarms and other events by E-mail
Email Visual
receiving visual verification images by E-mail (sent via MMS)
*
Must be enabled when using the Android app
6. Select Event Report and set the event types that will be reported
to any of the contacts. The options are as follows:
Alarm events: any alarm
Dis/Arm report: arming to any mode and disarming Power report: power loss Service report: actions such as entering the menu
See Appendix G, on page 57 for complete details on the reported events
10.3 CMS contacts
Here you can set two CMS contacts and their options.
To set the CMS contacts, do the following:
1. Access the Installer menu and select Programming CMS
Contacts
2. Select Acct. ID and type the account ID of this alarm system
3. Select CMS X and set the following:
x SMS REMOTE CMD. x REMOTE LOOK-IN
CANCELSET/CLEAR
OPTIONS 1
x ALARM EVENTS x DIS/ARM REPORT
CANCELSET/CLEAR
EVENT REPORT 1
ACCT. ID
CMS CONTACTS
CMS 1-2 EVENT REPORT RETRY OPTIONS
ACCT. ID CMS 1
BACKSELECT
CMS CONTACT 1
Programming menu
39
a. Select Mobile and enter the CMS’s phone number for receiving notifications by SMS b. Select Email (by MMS) and enter the CMS’s E-mail address. Note that E-mails are
sent via MMS (Multimedia Message Service) messages and cost money to the end user (charged by the cellular provider). See section 2.2.1, on page 11 for instructions
c. Select IP and enter the IP address of the IP Receiver in the CMS. You can also enter a
URL address for DDNS services
d. Select Port and enter the port number of the IP receiver
e. Select CMS Protocol and select the relevant option. The
options are listed below
Disable:
reporting to the CMS is disabled
SIA SMS:
events will be sent by SMS, in SIA
CID SMS:
events will be sent by SMS, in ContactID©
E-mail Visual/ CID:
visual and normal events will be sent by E-mail, in ContactID© GPRS-CID:
events to the CMS will be sent as IP over GPRS, in ContactID©
GPRS-Visual/ CID:
visual and normal events will be sent to the CMS, as IP over GPRS, in ContactID©
f. Select Periodic Test and select every how long a test event
will be sent to the CMS for supervision. The options are: Disable (tests), 5 min, 10 min, 60 min, 24 hrs, one week, one month
g. Select GPRS Always ON and select a ping interval in sec. The
options are: 30, 45, 60 or 90. The alarm system will ping a web server to maintain an open session with the IP Receiver. See the “Glossary of terms”, on page 54 for more details
4. Press BACK
CMS 1-2
PERIODIC TEST
MOBILE EMAIL (BY MMS)
CMS PROTOCOL
IP PORT
BACKUP*
GPRS ALWAYS ON
* CMS 2 only
DISABLE
CMS PROTOCOL
SIA SMS CID SMS EMAIL VISUAL/CID GPRS-CID GPRS-VISUAL/CID
P DISABLE SIA SMS
SELECT
CMS PROTOCOL 1
CANCEL
P DISABLE 5 MIN
PERIODIC TEST 1
CANCEL
SELECT
P DISABLE PING 30 SEC
GPRS ALWAYS ON 1
CANCEL
SELECT
Wireless Alarm Systems Installation Guide
40
5. Select Event Report and set which events will the alarm system
report the CMS. The options are: Burglary Alarms, Burglary Restore, Fire alarms, Fire Restore, Arming and Disarming, Service events,
Service Restore, Power loss, Power Restore, Medical alarms, Medical Restore, and Visual alarms (verification images)
6. Select Retry Options and set the two available options. The alarm
system will retry to send events:
Interval Timeout: set the overall interval of the re-tries in
min., between 6-30
Delay Timeout: set the delay between re-tries in sec., between 15-60
Example: if you set an interval of 10 min. and a delay of 15 sec., then for 10 min. the control panel will try to report the CMS, every 15 sec., which is 40 times (10x4)
7. In CMS 2 only, select Backup and set the two backup options,
as follows:
Backup: CMS 2 will serve as backup to CMS 1 in case of a
communication fault with CMS 1
Duplicate: all events will be reported both to CMS 1 and CMS 2 (“Double Report”)
When CMS 2 is set as “Duplicate”, “GPRS Always On” is automatically disabled Sending images may cause the IP Receiver to close the session
10.4 Communication
Set the mode of the SIM card(s) - single or dual13 - and the cellular provider’s details of each card. The alarm system comes with a list of your country’s providers by default.
To set the SIM card(s):
1. Access the Installer menu and select Programming
Communication
2. Select SIM Mode and select between the two following options:
Single SIM (Main): one card will be used Dual SIM: two cards will be used
3. Back in the Communication screen, select SIM1 (main) and
press Select Operator
4. Using the up/down arrow keys , scroll to the provider
that matches the SIM card in use by the alarm system, and press Select
13
See the “Glossary of terms”, on page 49
x BURGLARY REPORT x BURGLARY RESTORE
CANCELSET/CLEAR
EVENT REPORT 1
INTERVAL TIMEOUT DELAY TIMEOUT
BACKSELECT
RETRY OPTIONS 1
P BACKUP DUPLICATE
SELECT
BACKUP 1
CANCEL
SIM MODE
COMMUNIATION
SIM 1 (MAIN) SIM 2 (BACKUP)
SIM MODE SIM1 (MAIN)
COMMUNICATION 1
BACK
SELECT
P SINGLE SIM (MAIN) DUAL SIM
SIM MODE 1
CANCEL
SELECT
SELECT OPERATOR
BACKSELECT
COMMUNICATION 1
OPERATOR #1 OPERATOR #2
BACKSELECT
SELECT OPERATOR (COUNTRY) 1
Programming menu
41
5. Press BACK. If you need to select a different country, scroll to
it, press Select, then repeat on steps 3-4
6. In dual SIM versions, select SIM2 (Backup)
7. Press Select Operator and repeat on steps 4-5
8. Select Options and select between the options, as follows: a. Main SIM Restore: set how many hours after switching
from SIM1 to SIM2 the control panel will try to switch back. The options are 1, 2 and 4 hours.
b. SIM Keep Alive: cellular providers suspend the communication with SIM cards being
idle for a long time. “Long time” varies between the different providers. To avoid this, the control panel will send a “Keep-alive” event in the interval set here. The options are
once every 1-28 days
Some SIM cards may have two options:
PP indicates a Prepaid/Pay As You Go card CN – indicates a Contract card
10.5 System options
Set the system options.
10.5.1 Entry/Exit delay
To set the entry and exit delays, do the following:
1. Access the Installer menu and select Programming System
Options
2. Select Entry/Exit
3. Select Entry Delay and type a value between 5 and 45 sec.
(default - 30)
4. Press
5. Select Exit Delay and type a value between 5 and 255 sec. (default - 5)
ANGOLA AUSTRIA
BACKSELECT
SELECT COUNTRY 1
BACKSELECT
SIM 2(BACKUP) 1
SELECT OPERATOR OPTIONS
OPERATOR #1 OPERATOR #2
BACKSELECT
SELECT OPERATOR (COUNTRY) 1
BACKSELECT
OPTIONS 1
MAIN SIM RESTORE SIM KEEP ALIVE
ENTRY/EXIT
SYSTEM OPTIONS
ARM/DISARM PGM OUTPUT TRIGGER INPUTS REMOTE ACCESS
ENTRY DELAY
ENTRY/EXIT
EXIT DELAY TONE
ENTRY/EXIT ARM/DISARM
BACKSELECT
SYSTEM OPTIONS 1
ENTRY DELAY EXIT DELAY
BACKSELECT
ENTRY/EXIT 1
Wireless Alarm Systems Installation Guide
42
6. Press
7. Select Tone and select between High or Low, for the delay countdown ticking sound
10.5.2 Arm/Disarm
Define the various arming and disarming options. For a detailed explanation of each, see the “Glossary of terms”, on page 54.
The alarm system cannot be armed in the following situations:
The Fault LED is on A zone tamper is open An immediate zone is open “Force Arm (see the “Glossary of terms”, on page 54) is not enabled
10.5.2.1 Options
To set the arming and disarming options, do the following:
1. Access the Installer menu and select Programming System
Options Arm/Disarm
2. Select Option and set the relevant options, listed in the next table
Option
Description
Force Arm
Allows arming with open zones. See “Arming modes”, on the “Glossary of terms”, on page 55
One-Key Arming
Allows arming by only pressing the control panel’s arming buttons (without the need to enter a user code)
WL keypad only
If only the wireless keypad will be used for arming and disarming,
user passwords can be up to four digits, and have the numerals of 0­9
To use both the wireless keypad and the control panel, passwords
can be up to four digits, but have the numerals of 1-4 only
10.5.2.2 Overriding
Overriding allows arming the alarm system even if one of three faults is present: Backup Battery Loss, AC Loss and Zone Supervision Loss. These faults are being reported and logged anyway and must be resolved as soon as possible.
To set the overriding options, do the following:
1. Access the Installer menu and select Programming System
Options Arm/Disarm Overriding
2. Set the relevant faults
OPTIONS
ARM/DISARM
OVERRIDING
FORCE ARM
OPTIONS
ONE-KEY ARMING WL KEYPAD ONLY
OPTIONS OVERRIDING
BACKSELECT
ARM/DISARM 1
x FORCE ARM. x ONE-KEY ARMING
CANCELSET/CLEAR
OPTIONS 1
x BACKUP BAT. LOSS x AC LOSS
CANCELSET/CLEAR
OVERRIDING 1
Programming menu
43
10.5.3 PGM output
The alarm system allows one PGM connection. To set it, do the following:
1. Access the Installer menu and select Programming System
Options PGM Outputs PGM 1
2. Select Trigger Upon and select what will trigger the output, as
listed in the following table
Trigger
The PGM output is triggered when...
Siren Follower
The siren is activated
Entry/Exit
The Entry/Exit delay starts running
Not Ready/Alarm
A zone is open or alarming, a fault occurs
Arm Away, Home, or Part
The alarm system is armed
Power Fault
This fault occurs
Medical, Burglary, Fire
These alarms are set off
Remote SMS
SMS command is received
3. Select PGM 1 Output Type and select the desired output type,
as listed in the following table
Type
Mode
Steady N.O.
Normally Open
Steady N.C.
Normally Close
Pulse Low to High
-
Pulse High to Low
-
4. Select PGM 1 Pulse and type the pulse duration, between 1 and 255 sec.
10.5.4 Trigger inputs
The alarm system allows three input connections, which can be utilized for arming the system by an external alarm system, and more. See section 3.4.1, on page 20 for more details.
To set the trigger inputs options, do the following:
1. Access the Installer menu and select Programming System
Options Trigger Inputs
2. Select Trigger X and select the relevant trigger. The available
options are described in the next table.
TRIGGER UPON
PGM 1
OUTPUT TYPE PULSE
TRIGGER UPON OUTPUT TYPE
BACKSELECT
PGM 1 1
P SIREN FOLLOWER ENTRY/EXIT
SELECT
TRIGGER UPON 1
CANCEL
P STEADY NO STEADY NC
OUTPUT TYPE 1
CANCEL
SELECT
AWAY ARM HOME ARM PART ARM WIRED/EXT ZONE
NOT USED
TRIGGER 1-3
TRIGGER 1 TRIGGER 2
BACKSELECT
TRIGGER INPUTS 1
P NOT USED AWAY ARM
SELECT
TRIGGER 1 1
CANCEL
Wireless Alarm Systems Installation Guide
44
Trigger
The input is triggered upon/by…
Away Arm, Home Arm, Part Arm
Arming to one of these modes Wired/Ext Zone
Signal via the hardwired zone (#24)14
10.5.5 Remote access
Set the parameters for remotely accessing the alarm system, using the “Programming Tool” PC application7 (via GPRS). When accessing remotely there are several limitations:
a. If the control panel is armed you cannot bypass zones, change the global options,
change contacts, and change the system configuration
b. After disarming the control panel the remote session is disconnected, to allow reporting
the event
To set the remote access parameters, do the following:
1. Access the Installer menu and select Programming System
Options Remote Access
2. Select Access Code and type a new code to replace the default one (531902)
3. Select Access Mode and select when remote access is allowed. The available modes are listed in the next table. See section 8.1.1,
on page 31 for more details
Access Mode
Description
Disable
Remote access is disabled
Always
Remote access is enabled, without the need for the Master user’s approval (only if the default Access Code was changed. If the code is the default one, the Master user will have to approve any remote access)
During Disarm
Remote access is enabled, only when the system is disarmed
User Initiated (default)
Remote access is enabled, only after the Master allows a two hour window via the Service Enable Programming menu
10.6 Factory defaults
Use this menu to reset the alarm system. The options on this menu are listed in the next table and the following sections.
Option
What is defaulted?
What is not defaulted?
Return to Defaults
All the parameters, except those on the right
Passwords, Remote Access Code, zones and peripherals’ IDs
14
Only Trigger #1 can be set as and connected to a Wired/External zone
ACCESS CODE
REMOTE ACCESS
ACCESS MODE
ACCESS CODE ACCESS MODE
BACKSELECT
REMOTE ACCESS 1
P DISABLE ALWAYS
SELECT
ACCESS MODE 1
CANCEL
RETURN TO DEFAULTS
FACTORY DEFAULTS
CLEAR PASSWORDS CLEAR ZONES INIT. ALL
Programming menu
45
Option
What is defaulted?
What is not defaulted?
Clear Passwords
All passwords, Remote Access Code
All other parameters
Clear Zones
All zones and peripherals' IDs
Zones and peripherals’ parameters
Init All
Combines the three above options
-
The log is not cleared in any of the above options Bypassed zones are not un-bypassed in any of the above options
10.6.1 Return to defaults
The default settings may vary between various countries and regions
To return to the factory defaults:
1. Access the Installer menu and select Programming Factory
Defaults
2. Select Return to Defaults. A confirmation message will appear
asking you to confirm the action
3. Press YES to confirm
10.6.2 Clear Passwords
To clear (reset) all passwords:
1. Access the Installer menu and select Programming Factory
Defaults
2. Select Clear Passwords. A confirmation message will appear
asking you to confirm the action
3. Press YES to confirm
10.6.3 Clear zones
After performing this action, you will be required to re-enroll all zones and peripherals
To clear all the zones:
1. Access the Installer menu and select Programming Factory
Defaults
2. Select Clear Zones. A confirmation message will appear asking you
to confirm the action
3. Press YES to confirm
RETURN TO DEFAULTS CLEAR PASSWORDS
BACKSELECT
FACTORY DEFAULTS 1
Are you sure ?
YES NO
RETURN TO DEFAULTS CLEAR PASSWORDS
BACKSELECT
FACTORY DEFAULTS 1
Are you sure ?
YES NO
RETURN TO DEFAULTS CLEAR PASSWORDS
BACKSELECT
FACTORY DEFAULTS 1
Are you sure ?
YES NO
Wireless Alarm Systems Installation Guide
46
10.6.4 Initialize all
This action resets all system parameters and zones
To initialize the system:
1. Access the Installer menu and select Programming Factory
Defaults
2. Select Init All. A confirmation message will appear asking you to
confirm the action
3. Press YES to confirm
10.7 Local programming
The Local Programming mode is used for uploading and downloading data via the “Programming Tool” PC application7. See the Programming Tool guide (P/N 4410401) for complete details
To program the alarm system locally, do the following
1. Access the Installer menu and select Programming Local
Programming
2. Run the “Programming Tool” and follow the instructions
3. When you are finished, press
Make sure not to disconnect the USB or power cables during the session, as it may damage the integrity of the alarm system
10.8 Firmware upgrade
Upgrading the Firmware requires the Firmware Upgrade Tool”. See the tool’s guide (P/N 4410401) for more details
To perform a firmware upgrade:
1. Access the Installer menu and select Programming Firmware
Upgrade.
2. A confirmation message will appear asking you to confirm the
action. Press YES to confirm
3. Run the Firmware Upgrade Tool and follow the instructions
4. When you finish, press
When performing Firmware Upgrade, you must follow the correct
procedure, otherwise you can risk system failure, which will make its warranty void
Disconnecting power or disconnecting the USB cable, at any stage
during the upgrade process may result in system failure
RETURN TO DEFAULTS CLEAR PASSWORDS
BACKSELECT
FACTORY DEFAULTS 1
Are you sure ?
YES NO
FACTORY DEFAULTS LOCAL PROGRAMMING
BACKSELECT
LOCAL PROGRAMMING 1
Local programming
Unplug USB cable or
Press OK to exit
FACTORY DEFAULTS FIRMWARE UPGRADE
BACKSELECT
PROGRAMMING 1
Are you sure ?
YES NO
Stop Communication Menu
47
11 Stop Communication Menu
The Stop Communication option allows you to temporarily stop all communication, cancel all pending messages and clear all communication buffers. This option may be used on the following situations:
a. During the installation process b. During testing of the system c. In the event of a false alarm
To stop communication and clear the buffers, do the following:
1. Access the Installer and select Stop Comm.
2. Press Yes to confirm - all messages in queue will be cleared
and will not be sent
3. Press
BACK
STOP COMM.
Are you sure ?
YES NO
Wireless Alarm Systems Installation Guide
48
12 Operating the Alarm System
Remotely
12.1 By smartphone app
The app allows the Master user to control the alarm system, by a simple-to-use application. See our website at http://www.pima-alarms.com/?categoryId=91059, or the system’s User Guide for complete details.
12.2 By text messages
Some operations of the alarm system - arming and disarming, requesting system status, activating and deactivating the PGM output, stopping the siren and requesting look-in images ­are SMS operated.
These operations are processed, only if sent from a contact’s phone, and only if the contact is allowed to perform them (see section 10.2.2, on page 37).
Every SMS message contains the event and the device or user name. For example: "Alarm from Kitchen AlarmView".
The alarm system sends a confirmation message (or fault report) on every text command.
Note, that SMS commands are not case sensitive.
12.2.1 Commands
Following are the available SMS commands:
Action
Command
Arm AWAY
a
Arm HOME
h
Arm PARTI
p
Disarm
d
Open PGM output
1o (Open)
Close PGM output
1c (Close)
Stop siren
b
Request system status
s
Request command list
?
Request look-in image
25i-30i 99i - all zones
System Peripherals
49
Appendix A System Peripherals
Peripheral
Description
P/N
SmartView
PIR/Camera (color)
8812001
OutView
Outdoor camera (color)
8813001
PCP
Panic Button/Pendant
5432004
PIR-S
Standard PIR Detector
5431001
PIR-P
Pet Immune PIR Detector
5431002
PIR-O
Outdoor PIR Detector
5431003
DCM
Door Contact/Magnet
5432001
SM
Smoke Detector
5431004
TD-5
Temperature Detector +5ºC
5436001
WLD
Water Leakage Detector
5436002
REP
Range Extender/Repeater
5435001
DCO
CO² Detector with EU approval
5431005
SIR-B
Outdoor Siren – Blue
5433001
SIR-R
Outdoor Siren – Red
5433002
SIR-O
Outdoor Siren - Orange
5433007
SIR-I
Indoor Siren
5433003
RWK
Remote Wireless Keypad (bi-directional)
5434001
KF-1
Hand-held 1-way Keyfob
5432002
KF-2
Hand-held 2-way Keyfob (bi-directional)
5432003
Wireless Alarm Systems Installation Guide
50
Appendix B The SmartView Detector/
Camera
B.1 How to mount the detector
Do the following steps to mount the detector:
1. Release the screw on the bottom of the bracket of the
detector, and remove the bracket.
2. Drill holes for surface or corner mounting.
3. Insert the supplied wall plugs and fasten the bracket to the
surface with the supplied screws.
4. Place the detector in the mounting bracket and fasten the screw.
5. If you need to adjust the direction of the detector, loosen
the screw and rotate it.
6. Fasten the screw tightly.
B.2 How to replace the battery
When the SmartView batteries are exhausted, do the following to replace them:
Release the screw of the bracket and remove the detector.
1. Release the screw of the cover of the battery
compartment, and remove the cover.
2. Replace the two batteries with new alkaline batteries. See
a sticker on the battery holder for correct polarity.
3. When you insert the batteries, the LED will light up in
blue for 2-4 sec. to indicate correct installation.
4. Close the cover and fasten the screw.
The OutView Camera
51
Appendix C The OutView Camera
C.1 How to mount the camera
Before you mount the OutView camera, make sure it optimally covers the secured area.
Follow the next steps to mount the camera:
1. Use the template on page 11 and drill 3 matching holes on the
mounting surface
2. Insert the supplied wall plugs and mount the bracket, using the
supplied screws
3. Rotate the swiveling bracket’s plastic knob clockwise, to its lower
position
4. Connect the camera to the bracket, by rotating it clockwise
5. Tighten the plastic knob to secure the camera
6. Connect the camera’s cable to the terminal block and to power.
See the next section for details
7. Adjust the field of view of the camera
8. Tighten the bracket’s tilt screws with the supplied Allen wrench
C.2 How to connect the camera
The OutView is supplied connected with a 3-wire cable to a junction box. The box has a terminal block inside it. To connect the OutView, do the following:
1. Open the junction box: push the clasps outside
and remove the lid
2. Pull out the black waterproof isolator, on the side
without the wires
Wireless Alarm Systems Installation Guide
52
3. Puncture a hole in the center of the isolator, for the wires of the AC adapter and the trigger
source
4. Put the required wires through the isolator
5. Connect the AC adapter wires to the Red (+) and Black (-) wires, on the terminal block. See
the next section for a diagram
The positive wire of the AC adapter is marked with stripes
6. Connect the wire from the trigger source to the Yellow wire of the OutView, on the terminal
block. See the next diagram
Two-state triggers, like door contacts and beam detectors, cannot be used
7. Release the screw on the junction box, on the side of the adapter and the trigger wires, and
remove the plastic clip
8. Put the isolator, now with the wires inserted into it, back in its place
9. Replace the clip on the wires and fasten the screw
10. Close the lid and make sure it is fastened by all four clasps
11. Place the junction box in a weatherproof placement
12. Plug the AC adapter to an indoor outlet
Figure 15. OutView connection diagram
If the AC-DC adapter is also used to power the triggering detector,
make sure it does not exceed its power output
The OutView does not report a restore event
Trigger source (N.C.)
OutView
AC-DC
Adapter
Junction box
Red
Black
Yellow
AC-DC Adapter
Trigger source (up to 50 m long)
OutView
(+)
(-)
External Siren Indications
53
Appendix D External Siren Indications
The SIR-B/R/O Wireless External Siren can indicate on various system activities.
If this is the first time the siren is set, before setting the available options, initialize the siren by selecting Service -> Tests -> External Siren -> Test.
The following table describes the activities and their indications:
Action
Beeps
Strobe light/Trigger Inputs
Alarms: Burglary, 24H, Panic, Fire
Siren
Flashes
Arming AWAY
1
3 flashes
Arming HOME/PART
2
2 flashes
Arming with low battery
5
3 flashes, 3 cycles
Arming with tamper condition
5
3 flashes, 3 cycles
Disarming
2
Sequential flashes, 1 cycle
Disarming with low battery
2
Sequential flashes, 2 cycles
Disarming with tamper condition15
2
3 sec. alarm, sequential flashes
15
Siren tone confirmation must be enabled in the control panel
Wireless Alarm Systems Installation Guide
54
Appendix E Maintenance & Troubleshooting
E.1 Cleaning the LCD screen
The LCD screen may occasionally get finger oil stains and accumulate dust. It should be cleaned only with a soft dry cloth or a special LCD screen cleanser. Avoid the use of abrasives of any kind.
Do not use solvents such as kerosene, acetone or thinner. These will harm the external finish and damage the transparency of the window.
E.2 Replacing the Control Panel’s battery
Remove the transformer from the AC outlet or disconnect the power before replacing the backup battery.
For best performance and care, use suitable replacement batteries from Pima Electronic Systems.
For instructions on how to replace the backup battery, see the “Quick installation section, on page 14
E.3 SIM card icons and LED behavior
OK/ Active
Not detected/ At fault
Two SIMs at fault
SIM-1 (Main)
SIM-2 (Backup) LED
-
1
1
2
2
Glossary of terms
55
Appendix F Glossary of terms
Alarm types –
Burglary – alarm caused by violation of intrusion zone Fire – alarm caused by violation of fire zone Tamper – alarm caused by opening tamper protection switch Panic/Medical/Emergency – alarm caused by activation of a panic/medical button
Alarm Restore – closing the alarm event and restoring the system to its previous state
Arming modes and options–
Away – full arming of the system Home – arming of perimeter detectors, as defined by the installer Partial – arming of part of the premises, while leaving the other part unsecured One-Key Arming – arming of the system pressing a single key, without any code Force Arm – arming the system even if it is not ready, under the condition that all open
zones will be closed by the end of the Exit delay. If the zone/s is open when the exit delay expires, an alarm is generated
Bypassing Zones – temporarily ignoring signals from a zone, to allow accessing to
part of the protected area while the system is armed. Zone bypassing can also be used when a zone is at fault, but only until the fault is repaired. Bypassed zones are automatically un-bypassed (that is returning to normal mode) when disarming the alarm system
Chime – bell sound, typically assigned to entry points or back doors, to warn when a
zone is opened while the system is disarmed
CMS Contact – Central Monitoring Station contact Contact – person that receive notifications on system events and faults, and can
perform some actions remotely, by text messages
Control panel – is where the user can activate/deactivate the alarm system as well as
change the various system configurations. This is the heart and brains of the system which also includes the system’s communication module
Detectors/Devices/Peripherals –
Device ID – unique identifier of detectors and peripherals Types:
o PIR (Passive Infrared) Detector heat emission detector of humans and
animals
o Door Contact – magnetically operated detector, usually used on doors and
windows
o Keyfob – small remote control for arming and disarming the system o Smoke Detector – sensing device which detects smoke particles of combustion o Panic button – button that triggers emergency alarm
Disarmed – Normal, standby mode. All zones, except 24 hour zones (Panic, Fire,
Tamper, etc.) are not active
Wireless Alarm Systems Installation Guide
56
Dual SIM mode
16
– The control panel checks the SIM card slots on power-up only, and sets the mode between Single of Dual. When two SIMs are detected, the SIM in the upper slot is defined as Main (SIM1), and the one in the lower as Backup (SIM2)
Entry/Exit Delay – predetermined time to allow entering and exiting the premises
without triggering the alarm
Event Group – a group of events defined by type, for notifying the contacts SIM Swap
16
The control panel automatically swaps from SIM1 to SIM2 (and vise
versa), when one of the following occurs: low GSM reception, GSM/GPRS loss, Jamming, and CMS communication fault (including retries). The control panel will keep trying to send events via SIM 1 and when it does, it will swap from SIM2 back to SIM1. The control panel report on why the swap was
performed. See section E.3, on page 54, for more information
Swinger Shutdown – this feature prevents a zone to repeatedly trigger the alarm, if it
is opened and closed (this is a "swinger") again and again (or left open). With this feature ON, the zone will only trigger the alarm as many times as is designated - once, twice or three times.
System Ready – all zones that are part of the defined arming mode are closed, and
the system can be armed
Users –
Regular – can arm and disarm the system and view its status Master – can change settings relating to the system behavior, change all passwords
except the Installer’s and do everything regular user can
Zone – protected area connected with detector Zone Types –
Normal (Immediate) – intrusion protected zone. Immediately activates the alarm if
violated while the system is armed
Entry/Exit – intrusion protected zone. Activates the alarm if violated while the
system is armed, only after the entry/exit delay expires, to allow entering/exiting the protected area
Follower (Inhibited/Intermediate) intrusion protected zone that “follows” the
entry/exit zones: if violated while any entry/exit zone has already been opened, it will not trigger the alarm. Typically used in zones adjoining the entry/exit route
24 Hr – intrusion protected zone, that will immediately trigger the alarm if opened,
regardless of the system state (armed or disarmed)
Panic (Personal Attack) and Medical – button operated zone, used in panic/distress
or medical situations. Pressing the button will immediately trigger the alarm, regardless of the system state (armed or disarmed). Panic buttons and zones trigger silent alarm
Fire – smoke and heat detectors, that will immediately trigger the alarm in fire/heat
conditions, regardless of the system state (armed or disarmed)
16
For dual SIM versions only
Event Reporting
57
Appendix G Event Reporting
The contacts of the alarm system can be reported on various system events. The events are divided into four groups: alarms, arming and disarming, power loss and service events. See the table below for the full list of the events and their ContactID codes.
Event
Text
Alarms
Zone alarm
Alarm from Zone +
zone no. (zone name)
Zone alarm restore
Zone Alarm Restore +
zone no. (zone name)
Fire alarm
Fire Alarm +
zone no. (zone name)
Fire alarm restore
Fire Alarm Restore +
zone no. (zone name)
Gas alarm
Gas Alarm +
zone no. (zone name)
Gas alarm restore
Gas Alarm Restore +
zone no. (zone name)
Panic alarm
Panic Alert +
button name
Panic alarm restore
Panic Alert Restore +
button name
Tamper alarm
Tamper +
zone no. (zone name)
or
System
(system name)
Tamper alarm restore
Tamper Restore +
zone no. (zone name)
or
System (system name)
Disarm with Duress code
Duress +
System (system name)
Zone bypassed
Zone Bypassed +
zone no. (zone name)
Zone un-bypassed
Zone Unbypassed +
zone no. (zone name)
Bell cancel
Bell cancel +
user
17
Arm and disarm
Arm to Away mode
Full Arm (Away) +
User no. (user
name)/Peripheral no. (peripheral name)
Arm to Home mode
Perimeter Arm (Home) +
User no. (user name)/
Peripheral no. (peripheral name)
Arm to Part mode
Part Arm +
User no. (user name)/ peripheral no.
(peripheral name)
Disarm
Disarm +
User no. (user name)
Disarm after alarm18
Disarm After Alarm +
User no. (user name)
Disarm failed
Disarm Failed +
User no. (user name)
Full/Perimeter/Part arm failed
Full/Perimeter/Part Arm Failed +
User no. (user
name)/peripheral no. (peripheral name)
Service
AC loss
AC Loss +
System (system name)
AC restore
AC Restore +
System (system name)
Backup network error
Backup Network Error +
System (system name)
Backup network restore
Backup network rest
System (system name)
Backup SIM failure
Backup SIM failure +
System (system name)
Backup SIM restored
Backup SIM Restored +
cause of switching event
Communication loss
Communication Loss +
Source
Communication restore
Comm. Restore +
Source
Date was set
Set Date + MASTER CODE/INSTALLER
End remote programming
End Remote Prog +
System (system name)
17
Only to CMS contacts and only to the contact who cancelled the bell
18
This action is not logged
Wireless Alarm Systems Installation Guide
58
End system programming
End System Prog +
System (system name)
Main SIM failure
Main SIM failure +
System (system name)
Main SIM restored
Main SIM Restored +
cause of switching
The cause may be one of the following:
SIM not inserted Pin code needed Low reception GSM loss GPRS loss Jamming Session open failure CMS1 Tx failure CMS2 Tx failure Keepalive failure
Periodic test
Periodic Test
Peripheral battery low
Accessory Battery + Zone
Peripheral battery restore
Accessory Batt. Rest + Zone
PGM close
PGM Close
PGM open
PGM Open
Remote look-in failed
Remote Look-In Failed
Remote look-in request
Remote Look-In Request
Remote programming
Remote Programming +
System (system name)
RF interference
RF Interference
RF interference restore
RF Interference Rest
SIM Switched to Backup
SIM Switched to Back +
cause of event
SIM switched to main
SIM Switched To Main +
cause of switching event
Status report
Status Report
Supervision loss
Supervision Loss +
zone no. (zone name)
Supervision restore
Supervision Restore +
zone no. (zone name)
System battery loss
System Battery Loss +
System (system name)
System battery low
System Battery +
System (system name)
System battery low restore
System Battery Rest +
System (system name)
System peripheral restore
Syst Periph Restore+ Zone
System peripheral trouble
Syst Periph Trouble + Zone
System programming
System Programming +
System (system name)
Time was set
Set Time + MASTER CODE/INSTALLER
User code changed
User Code Changed +
User no. (user name)
User code deleted18
User Code Deleted +
User no. (user name)
Zone trouble
Zone Trouble +
zone no. (zone name)
Zone trouble restore
Zone Trouble Restore +
zone no. (zone name)
SIA and ContactID Codes
59
Appendix H SIA and ContactID Codes
H.1 Event codes
H.1.1 ContactID
101
Emergency
110
Fire
120
Panic
121
Duress
122
Silent
123
Audible
130
Burglary
131
Perimeter
132
Interior
134
Entry/Exit
137
Tamper/CP
301
AC loss
302
Low system battery
321
Bell
344
RF receiver jam detect
350
Communication trouble
351
Telco fault
381
Loss of supervision RF
383
Sensor tamper
384
RF low battery
401
O/C by user
406
Cancel
408
Quick arm
441
Armed home
456
Partial arm
459
Recent close
570
Bypass
602
Periodic test report
607
Walk test mode
641
Senior watch trouble
H.1.2 SIA
AR
AC Restore
AT
AC Trouble
BA
Burglary Alarm
BB
Burglary Bypass
BC
Burglary Cancel
BR
Burglary Restore
BT
Burglary Trouble / Jamming
BZ
Missing Supervision
CF
Forced Closing
CL
Closing Report
CR
Recent Close
FA
Fire Alarm
FR
Fire Restore
HA
Holdup Alarm (duress)
LR
Phone Line Restore
LT
Phone Line Trouble
OP
Opening Report
PA
Panic Alarm
QA
Emergency Alarm
RP
Automatic Test
RX
Manual Test
RY
Exit from Manual Test
TA
Tamper Alarm
TR
Tamper Restore
XR
Sensor Battery Restore
XT
Sensor Battery Trouble
YR
System Battery Restore
YT
System Battery Trouble
YX
Service Required
H.2 Device number
Control Panel
00
Wireless Zones
01-24
Wireless Video Zones
25-30
Hardwires Zones
51-53
Remote Control Keyfobs/Panic
31-50
Wireless Keypads
61-63
Built-in Keyboard
00
External Wireless Siren
70
GSM/GPRS Modem
80
Local USB Access
71
H.3 User number
Regular User
01-25
Master User
26
Duress code
27
24H code
28
Installer code
29
Wireless Alarm Systems Installation Guide
60
Appendix I SMS confirmation messages
Every time an SMS command/info message from a confirmed telephone number is received in the control panel, it is replied with a confirmation (or error) message. The next table lists the various messages.
Command/info
Confirmation message
Error message
Arming
Armed AWAY/HOME/PARTIAL by User Name
Armed AWAY/HOME/PARTIAL failed
Disarming
Disarmed by User Name
Disarm failed
xx25-30 (look-in image)
Picture from Zone No.
Operation failed Stop bell
Bell canceled by User Name
-
Status
Away/Home/Part/Disarm
state
PGM #1 Opened/Closed
-
? (command list)
Away: A,a Home: H,h Part: P,p Disarm: D,d Image: xxI, xxi zone 25-
30, all- 99
PGM Open: 1O,1o PGM Close: 1C,1c Stop Bell: B,b Status: S,s Help: ?
-
Limited Warranty
61
Appendix J Limited Warranty
PIMA Electronic Systems Ltd. ("the Manufacturer") warrants its products hereinafter referred to as "the Product" or "Products" to be in conformance with its own plans and specifications and to be free of defects in materials and workmanships under normal use and service for a period of twelve (12) months from the date of shipment by the Manufacturer. The Manufacturer's obligations shall be limited within the warranty period and its option, to repair or replace the product or any part thereof. The Manufacturer shall not be responsible for dismantling and/or reinstallation charges. To exercise the warranty, the product must be returned to the Manufacturer freight prepared and insured. The warranty does not apply in the following cases: improper installation, misuse, failure to follow installation and operating instructions, alteration, abuse, accident or tampering, and repair by anyone other than the Manufacturer.
The warranty is exclusive and expressly in lieu of all other warranties, obligations or liabilities, whether written, oral, express or implied, including any warranty of merchantability or fitness for a particular purpose, or otherwise. In no case shall the Manufacturer be liable to anyone for any consequential or incidental damages for breach of this warranty or any other warranties whatsoever, as aforesaid.
This warranty shall not be modified, varied or extended, and the Manufacturer does not authorize any person to act on its behalf in the modification, variation or extension of this warranty. This warranty shall apply to the Product only. All products, accessories or attachments of others used in conjunction with the Product, including batteries, shall be covered solely by their own warranty, if any. The Manufacturer shall not be liable for any damage or loss whatsoever, whether directly, indirectly, incidentally, consequentially or otherwise, caused by the malfunction of the Product due to products, accessories, or attachments of others, including batteries, used in conjunction with the Products. The Manufacturer does not represent that its Product may not be compromised and/or circumvented, or that the Product will prevent any death, personal and/or bodily injury and/or damage to property resulting from burglary, robbery, fire or otherwise, or that the Product will in all cases provide adequate warning or protection. User understands that a properly installed and maintained alarm may only reduce the risk of events such as burglary, robbery, and fire without warning, but it is not insurance of a guarantee that such will not occur or there will be no death, personal damage and/or damage to property as a result.
The Manufacturer shall have no liability for any death, personal and/or bodily injury and/or damage to property or other loss whether direct, indirect, incidental, consequential or otherwise, based on a claim that the Product failed to function. However, if the Manufacturer is held liable, whether directly or indirectly, for any loss or damage arising under this limited warranty or otherwise, regardless of cause of origin, the Manufacturer's maximum liability shall not in any case exceed the purchase price of the Product, which shall be fixed as liquidated damages and not as penalty, and shall be the complete and exclusive remedy against the Manufacturer.
Warning: The user should follow the installation and operation instructions and among other things test the product and the whole system at least once a week. For various reasons, including, but not limited to, changes in environmental conditions, electric or electronic disruptions and tampering, the Product may not perform as expected. The user is advised to take all necessary precautions for his/her safety and the protection of his/her property.
* Patent Pending Technology
Wireless Alarm Systems Installation Guide
62
Appendix K Declaration of Conformity
Declaration of Conformity
63
Hereby, Company: PIMA Electronic Systems Ltd. Address: 5 Hatzoref Street, Holon 5885633 Country: Israel Telephone number: +972.3.6506414 Fax number: +972.3.5500442
PIMA Electronic Systems Ltd. declares that the AlarmView system is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
Federal Communications Commission (FCC) Part 15 Statement
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information.
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer’s instructions, may cause interference to radio and television reception. It has been type tested a nd found to comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
If using an indoor antenna, have a quality outdoor antenna installed. Reorient the receiving antenna until interference is reduced or eliminated. Move the receiver away from the control/communicator. Plug the control/communicator into a different outlet so that it and the receiver are on different branch circuits. If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. The user or installer may find the following booklet prepared by the Federal Communications Commission helpful:
“Interference Handbook.” This booklet is available from the U.S. Government Printing Office, Washington, DC 20402. The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or
User’s Guide. Unauthorized changes or modifications could void the user’s authority to operate the equipment.
RoHS compliance - All our products are lead-free PIMA Electronic Systems is ISO 9001 certified
All data contained herein is subject to change without prior notice. PIMA Electronic Systems Ltd. * Patent Pending Technology
This guide and the information contained herein are proprietary to PIMA Electronic Systems Ltd. Only PIMA Electronic Systems Ltd. or its customers have the right to use the information.
No part of this guide may be re-produced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of PIMA Electronic Systems Ltd.
PIMA Electronic Systems Ltd. owns patents and patent applications, trademarks, copyrights, or other intellectual property rights covering the subject matter in this guide.
The furnishing of this guide to any party does not give that party or any third party any license to these patents, trademarks, copyrights or other intellectual property rights, except as expressly provided in any written agreement of PIMA Electronic Systems Ltd.
Copyright © 2014 by PIMA Electronic Systems Ltd. All rights reserved. E&OE
Wireless Alarm Systems Installation Guide
64
Pima Electronic Systems Ltd.
5 Hatzoref street, Holon 5885633 ISRAEL Tel: +972.3.650.6414
Fax: +972.3.550.0442 E-mail: support@pima-alarms.com sales@pima-alarms.com
www.pima-alarms.com
Distributed and Supported by:
4 4 1 0 3 7 5
*4410375*
Version: XX en, B2 (Nov 2014)
Loading...