Pilot Communications PMAC735, PMAC735-A, PMAC735-B, PMAC735-P, PMAC735-E Installation & Operation Manual

PMAC735 Multifunction Measuring Meter
Installation & Operation Manual
V8.2
2
Danger and warning!
This device can be installe d only by professionals.
The manufacturer shall not be held responsible for any accident caused by the failure to comply with the instructions in this manual.
Risks of electric shocks, burning, or explosion
This device can be installe d and maintained only by qualified people.
Before operating the device, isolate the voltage input and power supply and short-circuit
the secondary windings of all current transf ormers.
Put all mechan ical parts, doors , or covers in thei r original posit ions before energizing the
device.
Always supply the device with the correct working voltage during its operation.
Failure to take thes e preventive measures could cause d amage to equipment or injuri es to people.
3
CONTENTS
1. General Information ........................................................................................... 6
1.1 Pictures of the main unit ...................................................................................................... 7
1.2 Picture of the extension module........................................................................................... 7
1.3 Type of the extension module .............................................................................................. 8
1.4 Characteristics ...................................................................................................................... 9
2. Installation and Connection ............................................................................. 10
2.1 Environment....................................................................................................................... 10
2.2 Dimension .......................................................................................................................... 10
2.3 Description of the main unit terminals................................................................................11
2.4 Description of extension module terminals ....................................................................... 12
2.5 Order information............................................................................................................... 16
2.6 Connection.......................................................................................................................... 17
3. Measuring Capability....................................................................................... 20
3.1 Real-time basic electrical parameters ................................................................................ 20
3.2 Power factor symbols.........................................................................................................21
3.3 Demand parameters............................................................................................................ 22
3.4 Energy parameters.............................................................................................................. 23
3.5 Harmonic parameters (optional) ........................................................................................ 24
4. Operation......................................................................................................... 26
4.1 Display and keys ................................................................................................................ 26
4.2 Data query .......................................................................................................................... 27
4.3 Setting................................................................................................................................. 41
4
5. Input/output Characteristics (optional).............................................................52
5.1 Status input......................................................................................................................... 52
5.2 Relay output ....................................................................................................................... 53
5.3 Pulse outputs....................................................................................................................... 54
5.4 Analog output ..................................................................................................................... 56
6. Alarm System (optional)..................................................................................59
7. SOE /Event Log (optional)............................................................................ 61
8. Communication Protocol................................................................................. 62
8.1 Overview ............................................................................................................................ 62
8.2 Abnormal response............................................................................................................. 63
8.3 Relay control ...................................................................................................................... 64
8.4 Register reading.................................................................................................................. 65
8.5 Register setting................................................................................................................... 66
8.6 Description of data types.................................................................................................... 67
8.7 Calculation factors.............................................................................................................. 67
8.8 Communication values and actual values.......................................................................... 68
8.9 List of universal data registers ........................................................................................... 69
8.10 List of real-time measured data registers......................................................................... 72
8.11 List of energy data registers ............................................................................................. 75
8.12 List of demand data registers ........................................................................................... 77
8.13 List of harmonic data registers......................................................................................... 80
8.14 List of max./min. real time data register.......................................................................... 81
8.15 List of SOE and time registers ......................................................................................... 84
8.16 List of configuration registers.......................................................................................... 85
5
8.17 List of energy setting registers......................................................................................... 91
8.18 05H command control relays........................................................................................... 92
9. Maintenance and Trouble Shooting.................................................................. 93
10. Technical Datashee t ....................................................................................... 96
6
1. General Information
PMAC735 is a multi-functional power meter, integrating data acquisition and control int o a whole. It can take the place of numerous meters, relays, transducers, and other components. Besides, it can be used in electric power systems of various voltage classes.
PMAC735 provides one RS485 communication port, so it can be integrated into any electric power monitoring system. The management software or other configuration software with which it is equipped enables the setting to be carried out easily. Furthermore, it provides an optional PROFIBUS communicati on port, whose 1.5 M co mmunication speed can fully meet the de mand for obtaining real-time data on the site.
PMAC735 is really a measuring meter based on true effective values, able to carry out accurate measurement of highly non-linear loads. The complicated sampling technology enables it to measure true effect iv e val ues up to th e 3 1st harmonic. The us er can re ad r e mot ely s o me do zen s o f measured values and minimum/maximum va lues on a display screen or via software.
PMAC735 provides multiple extension modules and advanced software functions to meet the demands of differe nt sites. Its flexible DI/DO configuration facilitates the desig n of the user.
PMAC735 adopts connection realized by terminals that can be pulled out and inserted, thus facilitating on-site wiring and maintenance. Especially for the parts to which current is inputted, PMAC735 uses lockable fixation connections to prevent dangers that may be caused by accidental coming off of connections.
7
1.1 Pictures of the main unit
Side view Rear view
1.2 Picture of the extension module
Rear view
8
1.3 Type of the extension module
Product Model Description
PMAC735-A 4 status inputs and 4 re lay outputs
PMAC735-B 8 status inputs and 2 re lay outputs
PMAC735-E 8 status inputs and 2 pulse outputs
PMAC735-P PROFIBUS communication port
Notes
1. Each PMAC735 main unit can be equipped with one extension module at most.
2. Digital input requires external dry conta ct.
3. The capacity of each relay outpu t node is 250 Vac/5A or 30 Vdc/5 A.
4. For pulse output circuits, refer to the subsequent descriptions.
5. The maximum communication spee d of the PROFIBUS port is 1.5 Mbps.
6. Some of the customized extensio n modules are not included.
9
1.4 Characteristics
The main parameters and characteristics of PMAC735 are as follows:
Up to the 31st harmonic.
Accepting standar d CT and PT inputs.
The voltage that can be directly measured is up to 500 V (phase-phase).
Achieving the class-1 measuring accuracy stipulated by IEC 62053, with bidirectional
four-quadra nt energy va lues.
High-accuracy measurement of current and voltage (0.1%) (typical situation).
Measurement of THD and K factor.
Build-in clock.
Demand calculation and maximum recording.
Large high-contrast LCD screen, easy for operating and setting with password l ock.
Revisable fixed value alarm and relay functions.
RS485 communication, standard MODBUS protocol (extendible PROFIBUS port)
Operating temperature: -20℃~ +60℃.
One optional programmable 4-20 mA analog output.
Multiple optional exte ndible modules, providing flexible on-site c ombinations.
Optional SOE event log.
Standard pluggable connecting terminals,facilitating on-site installati on and maintenance.
Maximum and minimum of instant measurement.
10
2. Installation and Connection
2.1 Environment
1. Storage temperature: -30 ~ +70
2. Operating temperature: -20 ~ +60
3. Humidity: 5% ~ 90%, non-condensing
2.2 Dimension
Panel size: 96.00×96.00 mm Installation size: 89.50×89.50 mm
Depth: 65.00 mm (the depth will be increased by 25.00 mm if an extension module is a dded)
11
2.3 Description of the main unit terminals
No. Code Definition No. Code Definition
1
L/+ Positive pole of power supply
15
RS485+ Positive pole of RS485
2
NC Null
16
RS485- Negative pole of RS485
3
N/- Negative pole of power supply
17
SHLD
Communication shie lded
earth
4
NC Null
18
NC Null
5
FG Earth protection
19
NC Null
6
NC Null
20
A1 Positive analog output
7
\ \
21
AG Negative analog output
8
\ \
22
VN Voltage neutral line
9
I32 Phase C current outgoing line
23
NC Null
10
I31 Phase C current incoming line
24
V3 Phase C voltage
11
I22 Phase B current outgoing line
25
NC Null
12
I21 Phase B current incoming line
26
V2 Phase B voltage
13
I12 Phase A current outgoing line
27
NC Null
14
I11 Phase A current incoming line
28
V1 Phase A voltage
12
2.4 Description of extension module terminals
PMAC735-A: 4 status inputs and 4 relay outputs
No. Code Definition No. Code Definition
29
R42 Negative relay 4 output
36
R11 Positive relay 1 output
30
R41 Positive relay 4 output
37
Scom
Positive status 30V
power supply
31
R32 Negative relay 3 output
38
S4 Status 4 input
32
R31 Positive relay 3 output
39
S3 Status 3 input
33
R22 Negative relay 2 output
40
S2 Status 2 input
34
R21 Positive relay 2 output
41
S1 Status 1 input
35
R12 Negative relay 1 output
42
NC Null
13
PMAC735-B: 8 status inputs and 2 relay outputs
No. Code Definition No. Code Definition
29
R22 Negative rela y 2 output
36
S6 Statu s 6 input
30
R21 Positi ve relay 2 output
37
S5 Statu s 5 input
31
R12 Negative rela y 1 output
38
S4 Statu s 4 input
32
R11 Positive relay 1 output
39
S3 Statu s 3 input
33
Scom
Positive status 30 V
power supply
40
S2 Statu s 2 input
34
S8 Status 8 input
41
S1 Statu s 1 input
35
S7 Status 7 input
42
NC Null
14
PMAC735-E: 8 status in puts and 2 pulse outputs
No. Code Definition No. Code Definition
29
P2-
Negative reactive energy
pulse output
36
S6 Status 6 input
30
P2+
Positive reactive energy pulse
output
37
S5 Status 5 input
31
P1-
Negative active energy pulse
output
38
S4 Status 4 input
32
P1+
Positive active energy pulse
output
39
S3 Status 3 input
33
Scom
Positive status 30 V power
supply
40
S2 Status 2 input
34
S8 Status 8 input
41
S1 Status 1 input
35
S7 Status 7 input
42
NC Null
15
PMAC735-P: Profibus
No. Code Definition No. Code Definition
29
RB Terminal resistor B
36
NC Null
30
P- Negative pole of profibus
37
NC Null
31
P+ Positive pole of profib us
38
NC Null
32
RA Terminal resistor A
39
NC Null
33
SHLD
Communication shie lded
earth
40
NC Null
34
NC Null
41
NC Null
35
NC Null
42
NC Null
Remark:
There should be an resistance (150 Ohms ) connected between terminal 29 and 30. There should be an resistance (150 Ohms ) connected between terminal 31 and 32.
16
2.5 Order information
Model: PMAC735-①-②-③-④-⑤
Code :
N A B
E P
Basic module 4 status inputs (passive) + 4 relay outputs 8 status inputs (passive) + 2 relay outputs 8 status inputs (passive) + 2 pulse outputs Profibus communication module
Code ②:
H
T
AO
Analysis of the 31st harmonic of current and voltage, T HD, K factor SOE event log One 4-20 mA analog output
Code ③:
A D
AC85-265V50Hz/60Hz DC80-300V DC24 - 48V
Code ④:
V1 V2 V3 V4 V5 V6 V7 V8
Rated Voltage/Current Input: 57.7/100V, 5A Rated Voltage/Current Input: 57.7/100V, 1A Rated Voltage/Current Input: 220/380V, 5A Rated Voltage/Current Input: 220/380V, 1A Rated Voltage/Current Input: 120/ 208V, 5A Rated Voltage/Current Input: 240/ 415V, 5A Rated Voltage/Current Input: 277/ 480V, 5A Rated Voltage/Current Input: 63.5/ 110V, 5A
Code :
17
50Hz 60Hz
50Hz 60Hz
Example: The ordered model is PMAC 735-A-H-AO-V3.
PMAC735-A-H-AO-V3 = PMAC735 basic module+ 4 status inputs + 4 relay outputs + harmonic
analysis + one 4 – 20 mA analog output + rated measurement of 220 V/380 V, 5 A.
Basic Module: Real-time measurement and energy measurement; Demand and its maximum
value, max./min. recording, build-in clock.
2.6 Connection
A. Low voltage 3-phase 4-wire star connection:
18
B. Low voltage 3-phase 3-wire delta connection ( 3 CTs):
C. Low voltage 3-phase 3-wire delta connection ( 2 CTs):
19
D. High voltage 3-phase 4-wire star connection:
E. High voltage 3-phase 3-wire delta connection (3 CTs):
20
F. High voltage 3-phase 3-wire delta connection (2 CTs):
3. Measuring Capability
3.1 Real-time basic electrical parameters
PMAC735 provides voltage, current, power, and frequency etc. basic parameters. The following
data are effective real values, and the refresh rate is 1 second.
Real-time reading Measuring range
Current Each phase 0 – 50,000 A Zero sequence 0 – 50,000 A Degree of unbalance (%) 0 – 100% Voltage Line-line 0 – 500 kV
21
Line-neutral line 0 – 500 kV Degree of unbalance (%) 0 – 100% Active power/Reactive power /Apparent power Single phase 0 - ± 100 MW/Var/VA Total 0 - ± 100 MW/Var/VA Power factor Single phase -1.000 – +1.000 Total -1.000 – +1.000 Frequency 35 – 65 Hz 35 – 65 Hz
3.2 Power factor symbols
The symbols of measuring power factor conform to the stipulations of IEC, and the figure below
describes the relevant definitions.
22
3.3 Demand parameters
Demand refers to the value obtained in the following way: the accumulated electrical parameters
within a period of time divided by the time length. To facilitate the operation of the user,
PMAC735 adopts the fixed-block calculation method in the fixed period of time, and the period
of time is fixed, being 15 minutes.
PMAC735 provides the following demand data and measuring ran ges:
Demand re ading Measuring range
Demand current Three-phase average value 0 – 50,000 A
23
Maximum peak 0 – 50, 000 A Active power/Reactive power /Apparent power Three-phase total 0 - ± 100MW/Var/VA Maximum peak 0 - ± 100MW/Var/VA
The figure below describes demand calculation:
3.4 Energy parameters
PMAC735 can measure bidirectional four-quadrant active and reactive energy, and the maximum
accumulated value is up to 99,999,999.9. The decimal place will not show. When the accumulated
value reaches to maximum, it will overturn automatically.
The polarity of energy is identical to that of power, both conforming to the stipulations of IEC
standards. For the rele vant definitions, please refer to the descriptions of 3.2 Power factor sy mbol.
The table below describes the interrelationships of various types of energy and the symbolic
relationships between energy a nd power:
Active energy input First-quadrant active energy Positive inductive active power
24
Fourth-quadrant active energy Positive capacitive active powe r
Second-quadrant a ctive energy Negative capacitive active power
Active energy output
Third-quadrant active energy Negative inductive active pow er
First-quadrant reactive energy Pos itive inductive reac tive powerReactive energy
input
Second-quadrant reactive energy Positive capacitive reactive power
Third-quadrant reactive energy Negative inductive reactive power
Reactive energy
output
Fourth-quadrant reactive energy
Negative capacitive reactive
power
3.5 Harmonic parameters (optional)
PMAC735 provides optional measurement of complete 31st harmonic for voltage and current as well as their total harmonic content (THD) and K fa ctor of current. The data of har monics are g iven accord ing to t he percent age of fund amental har monics and have one digit after the decimal point. That is to say, when the value of the fundamental harmonic is fixed at 1000, it is 100.0% of the effective value of the fundamental harmonic; others are by analogy. THD refers to the total of higher harmonics except fundamental harmonics, and it is calculated according to the following formula:
ni
i
i
X
THD
2
2
The formula for calculating K factor is as follows:
ni
i
ni
i
ii
K
XXi
1
2
1
2
)(
25
i
: Harmonic order.
i
X
: Percentage of the effective value of each h armonic to that of th e fundamental
harmonic.
n
: Highest harmonic order, w hich should be 31 here.
Attention
1. Each harmonic and THD can be checked through display or communication.
2. K factor can be checked only through communication.
26
4. Operation
4.1 Display and keys
Display instruction
A: THD prompt B: Higher harmonic prompt C: Phase sequence & quadrant prompt D: Real-time data display area E: Real-time data unit F: Communication prompt G: Energy/ programming data area H: Energy unit I: Relay status indication K: Status state indication L: Energy pulse function prompt M: Energy quadrant prompt O: Programming indication P: Real-time data type indication Q: Unbalance rate prompt R: Minimum/maximum value/demand prompt
1: Trademark of the Company 2: Product type
MAX
THD MIN DMD
V
A
W
AB
C
A
B
C
S1
S2
S3
S4 S5 S6
S7 S8 RL1
RL2 RL3
RL4
U nbal
27
Key-press instruction: functio n of each key vary with interface
Display interface of
measured data
Programming interface
Enquiry configuration Modification
configuration
Submenu page-up \ Move the cursor left
Submenu page-down \ Move the cursor right
Main menu page-down Menu turning-down
Decrease the numeric
value at the cursor
Main menu page-up Menu turning-up
Increase the numeric
value at the cursor
Energy page turning
Press the key “Enter” to
enter into modification
Press the key “Enter” to
confirm the modification
Enter into programming
interface
Exit from programming
interface
Exit from programming
interface
4.2 Data query
The real-time measured data are indicated in the form of main menu and submenu.
Keys for main menu page turning:
Keys for submenu page turning:
Menu tree diagram :
For main menu page turning, press and .
For page turning of the submenus under each main menu, press and .
28
Volta g e
Current
Ac tiv e p o w e r
Reactive power
Apparent power
Pow e r facto r
Frequency
Demand and maximum value
Voltage harmonic
Current harmonic
Phase voltage unbalance rate
Phase voltage
Current unbalance rate
Tota l ac tiv e p o w e r Phase active power
Tota l re ac tiv e po w e r Phase reactive power
Total apparent power Phase apparent power
Total power factor Pha s e power fac tor
Average current demand and maximum value Total active power demand and maximum value Total reactive power demand and maximum value Total apparent power demand and maximum value
Tota l v ol tag e ha rmon ic T HD Component of each voltage harmonic
Total current harmonic THD Com ponen t of each current harmonic
Line voltage
Phase current
Main menu Submenus
Line voltage unbalance rate
Maximum value recording
Maxim um value of total active power M ax imum va lu e o f to tal re ac tiv e p o w e r Maximum value of total apparent power Maxim um value of current THD
Maximum value of three phase current
Maxim um value of voltage TH D
Minimum value recording
M in imum v alue o f to tal activ e powe r Minimum value of total reactive power Minimum value of total apparent power Minimum value of current THD
Minimum value of three phase current
Minimum value of voltage TH D
Neutral curren t
29
The procedure of real-time data query is as follows:
The initial power-up interface of the meter is shown as follows:
V
AB
C
A
B
C
S1 S2 S3 S4 RL1 RL2 RL3 RL4
4.2.1 Voltage data query
Press the key continuously, and you will see the following items one by one:
a. Line voltage
V
AB
C
A
B
C
S1 S2 S3 S4 RL1 RL2 RL3 RL4
b. Line voltage unba lance rate
AB
C
A
B
C
S1S2S3
S4
RL1RL2RL3RL4
Unbal
c. Phase voltage
V
A
C
B
S1 S2 S3 S4 RL1
RL2 RL3 RL4
d. Phase voltage unbalance rate
A
C
B
S1 S2 S3 S4 RL1 RL2 RL3 RL4
Unbal
30
4.2.2 Current data query
1. Press the key once, and you will see the current data.
2. Press the key continuously, and you will see the following items one by one : a. Three phase current b. Current unbalance rate c. Neutral current
A
A
C
B
S1 S2 S3 S4 RL1
RL2
RL3 RL4 S1 S2 S3 S4 RL1
RL2
RL3 RL4
Unbal
A
S1 S2 S3 S4 RL1
RL2
RL3 RL4
4.2.3. Active power data query
1. Press the key once, and you will
see total three phase active power.
W
S1 S2 S3 S4 RL1
RL2 RL3 RL4
2. Press the key continuously, and
you will see the single-phase active power.
W
A
C
B
S1 S2 S3 S4 RL1 RL2 R L3 RL4
31
4.2.4. Reactive power data query
1.Press the key once, and you will
see the total three phase reactive power
S1 S2 S3 S4 RL1
RL2 RL3
RL4
2. Press the key continuously, and you
will see the single-phase reactive power
A
C
B
S1 S2 S3 S4
RL1 RL2 RL3 RL4
4.2.5. Apparent power data query
1. Press the key once, and you will see
the total three phase apparent power
S1 S2 S3 S4 RL1 RL2 RL3 RL4
2. Press the key continuously, and you
will see the single-phase apparent power
A
C
B
S1 S2S3S4
RL1 R L2 RL 3 RL4
4.2.6. Power factor query
1. Press the key once, and you will
see the total three phase power factor
S1 S2 S3 S 4
RL1 RL2 RL3 RL4
2. Press the key continuously, and you
will see the single-phase powe r factor
A
C
B
S1 S2 S3 S4 RL1
RL2 RL3
RL4
32
4.2.7. Frequency
Press the key once, and you will see the frequency data.
S1 S2 S3 S4 RL1
RL2 RL3
RL4
33
4.2.8. Demand and maximum value query
1. Press the key once, and you will see the demand parameters.
2. Press the key continuously, and you will see the following items one by one:
Note: The time rec ord of maximum demand is displayed as below format:
1st row: year, month
2nd row: day, hour
3rd row: minute, second
a. Current demand a nd maximum value
MAX
DMD
A
S1 S2 S3 S4 RL1
RL2
RL3 RL4
b. Time record of ma ximum current demand
DMD
S1 S2 S3 S4 RL1 RL2 RL3 RL4
MAX
c. Active power de mand and maximum value
MAX
DMD
W
S1 S2 S3 S4 RL1
RL2 RL 3 RL4
d. Time record of maximum active power
demand
DMD
S1S2S3
S4
RL1 RL2 RL3 RL4
MAX
34
e. Reactive power demand and maximum
value
MAX
DMD
S1 S2 S3 S4 RL1 RL2 RL3 RL4
f. Time record of maximum reactive power
demand
DMD
S1 S2S3S4
RL1 RL2 RL3 RL4
MAX
g. Apparent power demand and maximum
value
MAX
DMD
S1 S2S3S4
RL1 RL2 RL3 RL4
h. Time record of maximum apparent power
demand
DMD
S1 S2 S3 S4 RL1 RL2 RL3 RL4
MAX
4.2.9. Voltage harmonic query
1. Press the key once, and you will
see the voltage harmonics.
THD value
THD
A
C
B
S1 S2 S3 S4 RL1
RL2 RL3
RL4
2. Press the key continuously, and you
will see the component of each harmonic
(take the component of the 18th harmonic as
an example)
A
C
B
S1 S2 S3 S4
RL1 RL2 RL3 RL4
35
4.2.10.Current harmonic query
1. Press the key once, and you will be able to see the current harmonics.
THD value
THD
A
C
B
S1S2S3 S4 RL1 RL2 R L3 RL4
2. Press the key continuously, and you
will see the component of each harmonic (take
the component of the 28th harmonic as an
example)
A
C
B
S1 S 2 S3 S4 RL1
RL2 RL3
RL4
4.2.11. Maximum value recording
1. Press the key once, and you will see the Maximum value of re al time data
2. Press the key continuously, and you will see the following items one by one:
a. Maximum value of three phase current
MAX
A
A
C
B
S1 S2 S3 S 4 RL1
RL2 RL3
RL4
b. Maximum value of total active power
W
S1 S2 S3 S4 RL1 RL2 RL3 RL4
MAX
36
c. Maximum value of total reactive power
S1 S2 S3 S4 RL1R L2 RL3 RL4
MAX
d. Maximum value of tota l apparent power
S1 S2 S3 S4 RL1 RL2 RL3 RL4
MAX
e. Maximum value of current THD
A
C
B
S1 S2 S3 S4 RL1 RL2 RL3 RL4
MAX
THD
f. Maximum value of voltage THD
A
C
B
S1S2S3 S4 RL1RL2RL3RL4
MAX
THD
4.2.12. Minimum value recording
1. Press the key once, and you will see the minimum value of real time data.
2. Press the key continuously, and you will see the following items one by one:
a. Minimum value of three phase current
S1 S2 S3 S4 RL1
RL2 RL 3
RL4
MIN
A
A
C
B
b. Minimum value of total active powe r
S1 S2 S3 S4 RL1
RL2 RL3 RL4
MIN
W
37
c. Minimum value of reactive power
S1 S2 S3 S4 RL1 RL2 RL3 RL4
MIN
d. Minimum value of total apparent power
S1 S2 S3 S4 RL1
RL2 RL3
RL4
MIN
e. Minimum value of current THD
S1 S2 S3 S4 RL1
RL2 RL3
RL4
MIN
THD
A
C
B
f. Minimum value of voltage THD
MIN
S1 S2 S3 S4 RL1 RL2 RL3 RL4
THD
A
C
B
4.2.13. Energy data query:
In any query interface, press the key continuously, and you will see the following items
one by one:
a. First-quadrant active energy
S1 S2 S3 S4 RL1
RL2
RL3 RL4
b. Second-quadra nt active energy
S1S2S3 S4 RL1RL2RL3RL4
38
c. Third-quadrant active energy
S1 S2 S3 S4 RL1 RL2 RL3 RL4
d. Fourth-quadrant active energy
S1 S2 S3 S4 RL1RL2 RL3 RL4
e. First-quadrant reactive energy
S1 S2 S3 S4 RL1 R L2 RL3 RL4
f. Second-quadrant reactive energy
S1 S2 S3 S4 RL1 RL2 RL3 RL4
g. Third-quadrant reactive energy
S1 S2 S3 S4 RL1 RL2 RL3 RL4
h. Fourth-quadrant reactive energy
S1 S2S3S4
RL1RL2RL3RL4
i. Active ener gy input
S1 S2 S3 S4 RL1
RL2 RL3
RL4
j. Active ener gy output
S1 S2 S3 S4 RL1 RL 2 RL 3 RL4
39
k. Reactive energy input
S1 S2 S3 S4 RL1 RL2 RL3 RL4
l. Reactive energy output
S1 S2 S3 S4 RL1 RL2 RL3 RL4
If the meter has the clock function, then, in any query interface, press the key
continuously, you will see the following items after the energy one by one:
Year, month, and day
S1S2S3 S4 RL1 RL2 RL3 RL4
Hour, minute, and second
S1 S2 S3 S4 RL1
RL2
RL3 RL4
40
In any query interface, press the key continuously and you will see the correlative diagnostic message of meter:
Diagnostic message
S1 S2 S3 S4 RL1 RL2 RL3 RL4
Diagnostic explanation: 0 means no fault, 1 means has fault. The first four digits are reserved.
The fifth digit: diagnosis of sampling reference point. The sixth digit: diagnosis of configuration parameter. The seventh digit: diagnosis of accuracy coefficient. The eighth digit: dia gnostic message of exte rnal storage.
Notes
1. All the values concerned are assumed for explanation, and they maybe not comply with logical
relationship.
2. The real-time data concerned when query about energy data are assum ed only for explanation.
41
4.3 Setting
The setting procedure is as follow:
1. Press the key to display PROG.
Enter the correct passw ord (the default password is 1).
CT primary side setting
1. Press the key until CT-PR appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new value,
and the cursor disappears.
CT primary side can be set 49,999
maximum.
CT secondary side setting
Press the key until CT-SE appears;
Hardware factor ca nnot be set, just for read only.
5 or 1 is fixed as CT secondary side
42
PT primary side setting
1. Press the key until PT-PR appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new value,
and the cursor disappears.
PT primary side can be set 500,000
maximum
PT secondary setting
1. Press the key until PT-SE appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new value,
and the cursor disappears.
PT secondary side can be set 200 maximum
Measuring mode setting
1. Press the key until MODE appears;
2. Press the key , and the cursor appears;
3. Press the key to select 4-wire star
connection (4Y) or 3-phase delta connection
(3D);
4. Press the key to confirm the selection,
and the cursor disappears.
43
Communication addr e ss setti ng
1. Press the key until ADDR appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new value,
and the cursor disappears.
Communication baud rate setting
1. Press the key until BAUD appears;
2. Press the key , and the cursor appears;
3. Press the key to select 4800, 9600, 19200,
or 38400;
4. Press the key to confirm the selection,
and the cursor disappears.
The max. /min. of real time data clearance
1. Press the key until CLR-M appears;
2. Press the key , and the cursor appears;
3. Press the key to select YES or NO;
4. Press the key to confirm the selection,
and the cursor disapp ears ( YES means execu ting
clearance).
44
Energy data clearance
1. Press the key until CLR-E appears;
2. Press the key , and the cursor appears;
3. Press the key to select YES or NO;
4. Press the key to confirm the selection,
and the cursor disappear s (Y ES means execut ing
clearance).
Demand data clearance
(Including maximum value of dema nd)
1. Press the key until CLR-D appears;
2. Press the key , and the cursor appears;
3. Press the key to select YES or NO;
4. Press the key to confirm the selection,
and the cursor disapp ears ( YES means execu ting
clearance).
Data record clearance
1. Press the key until CLR-S appears;
2. Press the key , and the cursor appears;
3. Press the key to select YES or NO;
4. Press the key to confirm the selection,
and the cursor disappear s (Y ES means execut ing clearance).
45
If the meter is equipped with energy pulse (i.e. PMAC735E-), you will be able to look up the
relevant object of pulse output and pulse constant.
Object of active energy pulse output
1. Press the key until P1-ob appears;
2. Press the key , and the cursor appears;
3. Press the key to select nULL or IMP or
EXP
4. Press the key to confirm the selection,
and the cursor disappears.
Object of reactive energy pulse output
1. Press the key until P2-ob appears;
2. Press the key , and the cursor appears;
3. Press the key to select nULL or IMP or
EXP
4. Press the key to confirm the selection,
and the cursor disappears.
46
Pulse output constant
1. Press the key until P-NUM appears;
2. Press the key , and the cursor appears;
3. Press the key to modify value;
4. Press the key to confirm new value, and
the cursor disappears.
Note:
1. P1-ob refers to the setting for object of active energy pulse output.
2. P2-ob refers to the setting for object of reactive energy pulse output.
3. nULL: disable; IMP: import quantity; EXP: e xport quantity.
4. P-NUM refers to the setting pulse constant.
47
If the meter is equipped with analog output ( i.e. PMAC735--AO--), you will be able to look up
the relevant object of ana log output and multiple of analog o utput.
Object of analog output
1. Press the key until An-ob appears;
2. Press the key , and the cursor appears;
3. Press the key to select nULL or others;
4. Press the key to confirm the selection, and the cursor disappears.
Note: After re-set the object of analog output, please re-start the device (PMAC735).
Multiple of analog output
1. Press the key until An-MU appears;
2. Press the key , and the cursor appears;
3. Press the key to modify value;
4. Press the key to confirm new value, and the cursor disappears.
Note:
1. nULL: disable;
U1: Phase A voltage; U2: Phase B voltage; U3: Phase C voltage; U12: Line AB voltage ; U23: Line BC voltage ; U31: Line CA voltage ; I1: Phase A current ; I2: Phase B current; I3: Phase C current ; P: Total active power; q: Total reactive power; PF: Total power factor; F: Frequency;
2. In multiple setting, there is one digit of decimal with the displayed data and it is the last digit.
48
Relay 2: Control mode
1. Press the key until R2-MO appears;
2. Press the key , and the cursor appears;
3. Press the key to select RE or LOCAL;
4. Press the key to confirm the selection,
and the cursor disappears.
If the meter is equipped with relays (i.e. PMAC735A-/B-), you will be able to look up the mode
and return time value of each relay.
Relay 1: Control mode
1. Press the key until R1-MO appears;
2. Press the key , and the cursor appears;
3. Press the key to select RE or LOCAL;
4. Press the key to confirm the selection,
and the cursor disappears.
Relay 1: Return time
1. Press the key until R1-RE appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new
value, and the cursor disappears.
49
Relay 2: Return time
1. Press the key until R2-RE appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new
value, and the cursor disappears.
Relay 3: Control mode
1. Press the key until R3-MO appears;
2. Press the key , and the cursor appears;
3. Press the key to select RE or LOCAL;
4. Press the key to confirm the selection,
and the cursor disappears.
Relay 3: Return time
1. Press the key until R3-RE appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new
value, and the cursor disappears.
50
Relay 4: Control mode
1. Press the key until R4-MO appears;
2. Press the key , and the cursor appears;
3. Press the key to select RE or LOCAL;
4. Press the key to confirm the selection,
and the cursor disappears.
Relay 4: Return time
1. Press the key until R4-RE appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new
value, and the cursor disappears.
Recover system default parameters
1. Press the key until RESET appears;
2. Press the key , and the cursor appears;
3. Press the key to select YES or NO;
4. Press the key to confirm the selection,
and the cursor disappears (YES means
executing clearance).
51
Version
1. Press the key until VER appears.
(This item cannot be modified)
Password modification
1. Press the key until CODE appears;
2. Press the key , and the cursor appears;
3. Press the key to modify the value;
4. Press the key to confirm the new
value, and the cursor disappears. (Only the
correct password be entered can this item be
modified)
52
5. Input/output Characteristics (optional)
5.1 Status input
PMAC735A-/B-/E- provides 4 or 8 status input channels, which are used to detect state
information such as breaker position signal s and isolator position signals.
The DC voltage which product provides is not below 30V. On the site, dry nodes or passive
auxiliary nodes can be connected directly. When external nodes are closed, the corresponding
status input channels will be closed.
4 status input signals 8 status input signals
Attention
Since there is a power supply available for detection inside the meter, the external nodes cannot
be further conn ected to any another voltage system. Otherwi se, the status inpu t channels will be
burnt down.
53
5.2 Relay output
PMAC735A-/B- provides two relay operation modes. They are remote control and local control.
The action of relay is different in these two modes. So, users should distinguish the relay is in
remote control mode or in local control mode at first.
The default cont rol mode of this product is r emote control. Users can chang e the mode through
communication.
Remote control (external) - The relay is controlled by a PC or PLC by using commands
through communica tion.
Local control (internal) - The relay is controlled by one of the electrical parameters inside
the meter, which serves as the response to the control alarm conditions of a set point.
Once the relay has been in the remote control mode, even though the local control conditions
have been set, the relay will not ope rate. The relay mode must be set at local control mode.
The two relay operation modes are as follows:
Normal:
- Remote control: By receiving a command from a PC or PLC, the relay closes. The relay’s
status will be kept until the PC or PLC gives a release command or the meter is
de-energized.
- Local control: When an alarm signal activating the relay is generated, the relay operates.
The relay will not be released until all the alarm conditions activating the relay disappear or
the meter is de-energized. If the power supply for the meter is resumed and the alarm
conditions still exist, the relay will opera te again.
54
Tim e delay reset
- Remote control: By recei v i n g a co mmand from a PC or PLC, t h e r el ay operates. The rel ay’s
operating status will be kept until a special timer overflows or the meter is de-energized. If,
before the timer overflows, there is a new command that makes the relay operates, the timer
will restart.
- Local control: When an alarm signal activating the relay is generated, the relay operates.
The relay’s operating status will be kept within the period of time for timing. When the
timer overflows, the relay will be released and kept released.
5.3 Pulse outputs
PMAC735E provides two pulse output outlets, one for active energy pulse output and the other
for reactive en ergy pu lse o utp ut . The u ser can sel f- def in e the t ype o f en ergy, and the default t ypes
are active energy input and reactive energy input. The user can also forbid pulse outputs.
A typical wiring mode of external acquisiti on equipment is shown as follows:
55
Attention
a. Different pulse acquisition devices have different operating modes. The pulse output
port circuit provided by PMAC735E is adopting the collecting electrode open-circuit mode,
isolated by optically coupled.
b. El ect ri cal c har acter is ti cs: Fo r the co ll ectin g electr odes , o pen -ci rcui t vol tag e: 4
8V≤
V
cc
50V
; Current:
mAI
z
50
.
The pulse outputs of PMAC735E correspond to the signal energy values inputted into the meter,
and they can also be called secondary side energy values. When the user calculates the actual
energy, the pulse outputs should be multiplied by the CT and PT factors. Each pulse does not
represent one kilowatt-hour or kilovar-hour, so the user needs to set a reasonable pulse constant.
The maximum setting range is between 1000 and 40000. The maximum pulse speed does not
exceed 200 ms, which means that, when the accumulated energy of the meter is 1 kwh, the
number of pulse outputs is N. Please note that the energy values here are all secondary side data.
Therefore, when t h er e ar e PTs and CTs, the pri mary side energy corr esp on ding to N puls es sh ould
be 1 kwh×PT×CT .
The maximum settable scope of 220V/5A range is 1000 to 5000, those of 220V/1A and 100V/5A
ranges are both 100 0 to 20000, and that of 100V/1A range is 1000 to 40000.
The step lengths are a ll 100.
56
5.4 Analog output
PMAC735 can provide one optional 4-20 mA analog output, supporting the access of the DCS
system. The user can, through the communication interface, set the parameter value
corresponding to the analog output. The maximum load resistance of the interface should not
exceed 500 Ohms.
On some sites, d ue to different trans missi on cabl es or load ing co nditi ons, th e analo g ou tput at t he
high end appears to be non-linear. PMAC735 provides a settable magnification factor. By
modifying the magnification factor, the user can adjust the proportion fact or of the output curve. The figure below shows the analog output characteristic curve, and the magnification factor is λ:
57
Notes:

PTCTP
P
P
e
8
12
Where:
P
: Measured value of the analog quantity,
unit: mA;
e
P
: Corresponding rated power value, unit:
W/Var;
: Magnification factor of the
corresponding channel. Its rang e is between 1 and 10.
eee
IUP 3
Where:
e
U
: Rated line voltage of the meter
e
I
: Rated current of the m eter
58
The analog output can be set as any of the items in the table below:
Phase-A voltage Phase-B voltage Phase-C voltage
Voltage
Line AB voltage Line BC voltage Line CA voltage
Current
Phase-A current Phase-B current Phase-C current
Active power Total active power
Reactive power Total reactive power
Power factor Total power factor
Frequency System frequency
Magnification factor: The minimum magnification factor is 1, and the maximum is10. Default
factor is 1.
59
6. Alarm System (optional)
PMAC735A-/B- provides multiple relay alarm outputs, any of which can work independently and
support the user’s programming.
Any of the relay output that has been set at local control mode corresponds to alarm about voltage
or current. Each alarm needs 5 parameters programmed, as shown in the table below:
Operation-object
0 – Prohibit 1 - Maximum value of three-phase voltage 2 - Minimum value of three-phase voltage 3 - Maximum value of three-phase line voltage 4 - Minimum value of three-phase line voltage 5 - Maximum value of three-phase current 6 - Minimum value of three-phase current
Operation upper limit value
0% - 120% of rated value
Operation lower limit value
0% - 120% of rated value
Operation time delay
0 – 1200s; 0 means that the relay operates immediately.
Return time 0 – 1200s; 0 means no retu rn.
For example, th e user needs to monitor wheth er there is under-voltage in th ree phases. I f there is
under-voltage in any phase, alarm will be given immediately until normal voltage is resumed.
Then, programming can be carried out according to the following settings:
Operation-object: Minimum value of three-phase volta ge
60
Operation upper limit value: 120
Operation lower limit value: 80 (it is assumed here that under-voltage refers to a voltage lower
than 80% of the rated voltage)
Operation time: 0 s
Return time: 0 s
Other values can be set according to the above procedure, and descriptions will not be given one
by one.
61
7. SOE /Event Log (optional)
PMAC735 provides optional function of recording up to 50 SOE events, and the records can be kept for more than 10 years. The SOE recording function can record the displacements of switch contacts. When an event occurs, the meter will automatically record the type of the event such as closing of status 1. At the same time, the year, month, day, hour, minute, second, millisecond when the event occurs will be recorded precisely, and the resolution is 2 ms. Users can read all the SOE records through communication. For details, refer to “SOE” (event log). A standard structure of SOE event data is as follows:
No. of the relative byte Definition Description
0
Type of event
1 – S1 channel 2 – S2 channel … … … … 8 – S8 channel
1
Status of operation
0 – Off
1 – On
2 – 3 Millisecond
4 – 5 UNIX clock low word
6 – 7 UNIX clock high word
The basis reference of the UNIX clock is 00:00:00 January 1, 1970 (Greenwich Mean Time). For
time conversion, please pay attention to the time difference of your time zone. For example, there
is an 8-hour time difference between the time of Beijing time zone and the standard UN IX.
62
8. Communication Protocol
8.1 Overview
PMAC735 main unit provides the MODBUS-RTU communication protocol, 8 data bits, 1 stop bit,
without check bi t. Each frame d ata packag e contain s the addres s field, fun ctional cod e field, d ata
field, and check field. The maximum length of each data package is 95 bytes.
The length of the ad dress fiel d is 1 byte, and the conten t is slave st ation addr ess. The range o f an
effective slave station address is 1 to 247. If the slave station receives a package in which the
address field information conforms to its own address, it should execute the commands contained
in the package. In the package to which the slave station responds, the field is its own address.
The length of the functional code field is 1 byte, used to tell the slave station to execute what
operations. The functional codes supported by PMAC735 are listed in the table below:
Functional code Meaning Function
0x03 Read register
Obtaining one or more than one current register values inside the current PMAC735.
0x10 Setting register
Writing the designated values into one or more than one registers inside PMAC735.
0x05 Relay control Controlling a relay inside the current PMAC735.
The length of the data field is not fixed, and it will be defined according to the specific function.
The data in the data field adopts the BIG INDIAN mode, with the high bytes in front and the low
bytes at the back.
The check field adopts 16-bit CRC check codes. The transmitting device should make CRC
calculation for each of the data inside the package, and the final results will be stored in the check
63
field. The receiving device should also make CRC calculation for each of the data (except the
check field) inside the package and compare the results with the check field. Only the same
package will be accepted.
8.2 Abnormal response
If the main station sends an illegal package or asks for an invalid data register, an abnormal data response will be generated. This abnormal data response is composed of the slave station address, functional code, trouble code, and check field. When the highest bit of the functional code field is 1, it means that the data frame is an abnormal response at this time. The table below describes the meanings of abnormal functional codes:
Trouble code Description
01H Illegal operation functional code received.
02H Illegal register oper ation or over-long data received.
64
8.3 Relay control
The functional code is 05H .
In this mode, only individual relay can be controlled. The status of a relay can be obtained by reading the relay status register. The relay address starts from 0 in the register. The address of relay 1 is 0, and the rest may be deduced by analogy. Sending sexadecimal FF 00 closes a relay and sending sexadec imal 00 00 releases a relay. All the other values will be invalid.
Control relay format
(Main station→PMAC735)
Response format
PMAC735main station
Slave station address 1 byte Slave station address 1 byte
Functional code 05H 1 byte Functional code 05H 1 byte
Channel address 2 bytes Channel address 2 bytes
Control command 2 bytes Control command 2 bytes
CRC check code 2 bytes CRC check code 2 bytes
65
8.4 Register reading
The functional code is 03H .
The main statio n can read one o r more th an one reg ister v alues, and the reg ister ret urn val ues not defined are 0.
Read register format
Main station→PMAC735
Response format
PMAC735main station
Slave station address 1 byte Slave station address 1 byte
Functional code 03H 1 byte Functional c ode 03H 1 byte
Start address 2 bytes
Byte number (2×number of
registers)
1 byte
Number of registers 2 bytes Data of the first register 2 bytes
CRC check code 2 bytes Data of the second register 2 bytes
…………
CRC check code 2 bytes
Note: The val ues of up to 45 registers can be read at one time.
66
8.5 Register setting
The functional code is 10H .
The main station can set one or more than one register values, and the register operations not
defined are invalid.
Write register format
Main station→PMAC735
Response format
PMAC735main station
Slave station address 1 byte Slave station address 1 byte
Functional code 10H 1 byte Functional code 10H 1 by te
Start address 2 bytes Start address 2 bytes
Number of registers 2 bytes Number of registers 2 bytes
Byte number (2×
number of registers)
1 byte CRC check code 2 bytes
Data of the first register
Data of the second
register
……….
CRC check code 2 bytes
67
8.6 Description of data types
UINT16 Unsigne d 16-digit integer
INT16 Signed 16-digit integer
LUINT32 Unsigned 32-digit integer
LINT32 Signed 32-digit integer
WORD16
Bit denotation word, applicable to on-off and relay status.
D0 refers to the first on-off or relay channel.
D1 refers to the second on-off or relay channel.
The rest bits may be deduced by analogy.
Bit 0 refers to “off”, and bit 1 refers to “on”.
8.7 Calculation factors
Due to the restriction of the value ranges, many of the data registers of PMAC735 use calculation
factors. This means that, if the user wants to obtain the actual values, the corresponding
calculation factors must be multiplied.
For example, th e calculati on factor o f the power f actor regis ter is 0.00 1. When the v alue read by
the user at this time is 892, the current power fa ctor will be: 892 × 0.001 = 0.892.
68
8.8 Communication values and actual values
To ensure that the meter keeps adequate accuracy bits when transmitting data, some of the
real-time data registers of PMAC735 adopt some special processing methods, as shown in the
table below:
No. Content Communication value Actual value
1
Per phase/line volta ge
Average phase/line voltage
Neutral voltage
Secondary side
Communication value *
calculation factor * PT
2
Per phase current
Average phase current
Neutral current
Current demand /
minimum/maximum value
Secondary side
Communication value *
calculation factor * CT
3
Per phase power
Total power
Power demand
Secondary side
Communication value *
calculation factor * PT *
CT
Using secondary side data to transmit numeric values can maintain the calculation accuracy to the
utmost extent. The user must, during processing, pay attention to the transformation ratios of the
corresponding PT and CT.
69
8.9 List of universal data registers
Register address
Definition Data type Description
40001 Phase A voltage
40002 Phase B voltage
40003 Phase C voltage
40004 Line AB voltage
40005 Line BC voltage
40006 Line CA voltage
Calculation factor: 0.01, unit: V
40007 Phase A current
40008 Phase B current
40009 Phase C current
40010 Neutral current
UNIT16
Calculation factor: 0.001, unit: A
40011 Three-phase active power
low word
40012 Three-phase active power
high word
Calculation factor: 0.1, unit: W
40013 Three-phase reactive power
low word
40014 Three-phase reactive power
high word
LINT32
Calculation factor: 0. 1, unit: Var
40015 Three-phase apparent power
low word
LUINT32 Calculation factor: 0.1,
unit: VA
70
40016 Three-phase apparent power
high word
40017 Total power factor INT16 Calculation factor: 0.001.
40018 Frequency UINT16 Calculation factor: 0.01,
unit: Hz
40019 Input active energy low
word
40020 Input active energy high
word
Calculation factor: 0.1, unit: kwh
40021 Input reactive energy low
word
40022 Input reactive energy high
word
Calculation factor: 0.1, unit: kvarh
40023 Output active energy low
word
40024 Output active energy high
word
Calculation factor: 0.1, unit: kwh
40025 Output reactive energy low
word
40026 Output reactive energy high
word
LUINT32
Calculation factor: 0.1, unit: kvarh
40027 On-off status WORD16 When any bit is 0, that means
71
40028 Relay status the corresponding contact is
cut, otherwise is closed.
40029 Va/Vab - THD
40030 Vb/Vbc - THD
40031 Vc/Vca - THD
40032 Ia - THD
40033 Ib - THD
40034 Ic - THD
Calculation factor: 0.001
40035 Ia – K factor
40036 Ib – K factor
40037 Ic – K factor
UINT16
Calculation factor: 0.1
40038 Average phase current
demand
UNIT16 Calculation factor: 0.001,
unit: A
40039
40040
Three-phase active power demand
Calculation factor: 0.1, unit: W
40041
40042
Three-phase reactive power demand
LINT32
Calculation factor: 0. 1, unit: Var
40043
40044
Three-phase apparent power demand
LUINT32 Calculation factor: 0.1,
unit: VA
40045 SOE event counter UINT16 0 – 59, 999
72
8.10 List of real-time measured data registers
Register address
Definition Data type Description
40101 Phase A voltage
40102 Phase B voltage
40103 Phase C voltage
Calculation factor: 0.01, unit: V
40104 Phase voltage unbalance
rate
Calculation factor: 0.001
40105 Average phase voltage
40106 Line AB voltage
40107 Line BC voltage
40108 Line CA voltage
Calculation factor: 0.01, unit: V
40109 Line voltage unbalance
rate
Calculation factor: 0.001
40110 Average line voltage
40111 Neutral voltage
UINT16
Calculation factor: 0.01, unit: V
40112 Phase A current
40113 Phase B current
40114 Phase C current
Calculation factor: 0.001, unit: A
40115 Current unbalance rate Calculation factor: 0.001
40116 Average phase current
40117 Neutral current
UINT16
Calculation factor: 0.001, unit: A
40118 Phase A active power INT16 Calculation factor: 0.1, un it: W
73
40119 Phase B active power
40120 Phase C active power
40121 Total active power low
word
40122 Total active power high
word
LINT32
40123 Phase A reactive power
40124 Phase B reactive power
40125 Phase C reactive power
INT16
40126 Tota l reactive power low
word
40127 Tota l reactive power high
word
LINT32
Calculation factor: 0. 1, unit: Var
40128 Phase A apparent power
40129 Phase B apparent power
40130 Phase C apparent power
UINT16
40131 Total apparent power low
word
40132 Total apparent power high
word
LUINT32
Calculation factor: 0.1, unit: VA
40133 Phase A power factor
40134 Phase B power factor
40135 Phase C power factor
INT16 Calculation factor: 0.001
74
40136 Total power factor
40137 Frequency UINT16 Calculation factor: 0.01, unit: Hz
40138 On-off status
40139 Relay status
WORD16 When any bit is 0, that means the
corresponding contact is cut, otherwise is closed.
75
8.11 List of energy data registers
Register address
Definition Data type Description
40201 Input active energy low word
40202 Input active energy high word
Calculation factor: 0.1, unit: kwh
40203 Input reactive energy low word
40204 Input reactive energy high word
Calculation factor: 0.1, unit: kvarh
40205 Output active energy low word
40206 Output active energy high word
Calculation factor: 0.1, unit: kwh
40207 Output reactive energy low word
40208 Output reactive energy high word
Calculation factor: 0.1, unit: kvarh
40209 First-quadrant active energy low
word
40210 First-quadrant active energy high
word
40211 Second-quadrant active energy low
word
40212 Second-quadrant active energy high
word
40213 Third-quadrant active energy low
word
40214 Third-quadrant active energy high
word
LUINT32
Calculation factor: 0.1, unit: kwh
76
40215 Fourth-quadrant active energy low
word
40216 Fourth-quadrant active energy high
word
40217 First-quadrant reactive energy low
word
40218 First-quadrant reactive energy high
word
40219 Second-quadrant reactive energy
low word
40220 Second-quadrant reactive energy
high word
40221 Third-quadrant reactive energy low
word
40222 Third-quadrant reactive energy high
word
40223 Fourth-quadrant reactive energy
low word
40224 Fourth-quadrant reactive energy
high word
Calculation factor: 0.1, unit: kvarh
77
8.12 List of demand data registers
Register address
Definition Data type Description
40301 Average current demand UNIT16 Calculation factor: 0.001, unit: A
40302 Total active power demand
low word
40303 Total active power demand
high word
Calculation factor: 0.1, unit: W
40304 Total reactive power demand
low word
40305 Total reactive power demand
high word
LINT32
Calculation factor: 0. 1, unit: Var
40306 Total apparent power demand
low word
40307 Total apparent power demand
high word
LUINT32 Calculation factor: 0.1, unit: VA
40308 Maximum averag e cu r r ent
demand
UNIT16 Calculation factor: 0.001, unit: A
40309 Date of max. current demand:
year, month
UNIT16 High byte: year, low byte: m onth
40310 Time of max. current demand:
day, hour
UNIT16 High byte: day, low byte: hour
40311 Time of max. current demand: UNIT16 High byte: minute,
78
minute, second low byte: second
40312 Maximum total active power
demand low word
40313 Maximum total active power
demand high word
LINT32
Calculation factor: 0.1, unit: W
40314 Date of max. total active
power demand: y ear, month
UNIT16 High byte: year, low byte: month
40315 Time of max. total active
power demand: da y, hour
UNIT16 High byte: day, low byte: hour
40316 Time of max. total active
power demand: minute, second
UNIT16 High byte: minute,
low byte: second
40317 Maximum total reactive
power demand low word
40318 Maximum total reactive
power demand high word
LINT32 Calculation factor: 0. 1, unit: Var
40319 Date of max. total reactive
power demand: y ear, month
UNIT16 High byte: year, low byte: m onth
40320 Time of max. total reactive
power demand: da y, hour
UNIT16 High byte: day, low byte: hour
40321 Time of max. total reactive
power demand: minute, second.
UNIT16 High byte: minute,
low byte: second
79
40322 Maximum total apparent
power demand low word
40323 Maximum total apparent
power demand high word
LUINT32 Calculation factor: 0.1, unit: VA
40324 Date of max. total apparent
power demand: y ear, month
UNIT16 High byte: year, low byte: m onth
40325 Time of max. total apparent
power demand: da y, hour
UNIT16 High byte: day, low byte: hour
40326 Time of max. total apparent
power demand: minute, second
UNIT16 High byte: minute, low byte:
second
80
8.13 List of harmonic data registers
Register address
Definition Data type Description
40401 Va/Vab – THD
40402 Vb/Vbc – THD
40403 Vc/Vca – THD
40404 Ia – THD
40405 Ib – THD
40406 Ic – THD
UNIT16 Calculation factor: 0.001
40407 Ia – K factor
40408 Ib – K factor
40409 Ic – K factor
UNIT16 Calculation factor: 0.1
40410 2nd harmonic component of Va/Vab
40411 2nd harmonic component of Vb/Vbc
40412 2nd harmonic component of Vc/Vca
40413 2nd harmonic component of Ia
40414 2nd harmonic component of Ib
40415 2nd harmonic component of Ic
40416 3rd harmonic compone nt of Va/Vab
40417 3rd harmonic component of Vb/Vbc
40418 3rd harmonic compone nt of Vc/Vca
40419 3rd harmonic component of Ia
40420 3rd harmonic component of Ib
UINT16 Calculation factor: 0.001
81
40421 3rd harmonic component of Ic
40422 4th harmonic component of Va/Vab
40423 4th harmonic component of Vb/Vbc
40424 4th harmonic component of Vc/Vca
40425 4th harmonic component of Ia
40426 4th of harmonic component Ib
40427 4th of harmonic component Ic
… … … … … … … … … … … … … … … … … …
40584 31st harmonic component of Va/Vab
40585 31st harmonic component of
Vb/Vbc
40586 31st harmonic component of Vc/Vca
40587 31st harmonic component of Ia
40588 31st harmonic component of Ib
40589 31st harmonic component of Ic
UINT16 Calculation factor: 0.001
8.14 List of max./min. real time data register
Register address
Definition Read/write
attribute
Description
40601 Ma ximum phase A current RO
40602 Ma ximum phase B current RO
Calculation factor: 0.001, unit: A
82
40603 Ma ximum phase C current RO
40604 Maximum total active power
low word
RO
40605 Maximum total active power
high word
RO
Calculation factor: 0.1, unit: W
40606 Maximum total reactive
power low word
RO
40607 Maximum total reactive power
high word
RO
Calculation factor: 0.1, unit: Var
40608 Maximum total apparent
power low word
RO
40609 Maximum total apparent
power high word
RO
Calculation factor: 0.1, unit: VA
40610 Maximum Ia-THD RO
40611 Maximum Ib-THD RO
40612 Maximum Ic-THD RO
40613 Maximum Va-THD RO
40614 Maximum Vb-THD RO
40615 Maximum Vc-THD RO
Calculation factor: 0.001
Register address
Definition Read/write
attribute
Description
40616 Minimum phase A current RO
40617 Minimum phase B current RO
Calculation factor: 0.001, unit: A
83
40618 Minimum phase C current RO
40619 Minim um total active power
low word
RO
40620 Minim um total active power
high word
RO
Calculation factor: 0.1, unit: W
40621 Minim um total reactive
power low word
RO
40622 Minimum total reactive
power high word
RO
Calculation factor: 0. 1, unit: Var
40623 Minimum total apparent power
low word
RO
40624 Minimum total apparent
power high word
RO
Calculation factor: 0.1, unit: VA
40625 Minimum Ia-THD RO
40626 Minimum Ib-THD RO
40627 Minimum Ic-THD RO
40628 Minimum V a-THD RO
40629 Minimum Vb-THD RO
40630 Minimum Vc-THD RO
Calculation factor: 0.001
84
8.15 List of SOE and time registers
Register address Definition Read/write attribute Description
40701 Year R/W 0 – 99
40702 Month R/W 1 – 12
40703 Day R/W 1 – 31
40704 Hour R/W 0 – 23
40705 Minute R/W 0 – 59
40706 Second R/W 0 – 59
40707 UNIX clock low word R/W
40708 UNIX clock high word R/W
40709 UNIX clock millisec ond R/W 0 – 999
40710 SOE event counter RO 0 – 59, 999
40711 – 40714 1st event log RO
40715 – 40718 2nd event log RO
… … … … … … … … … … … … … … …
40907 – 40910 50th event log RO
Notes concerning writing/reading:
1. The 6 time registers starting from 40701 must be written and read simultaneously, and the
writing/reading must begin with 40701, otherwise the writing/re ading will be invalid.
2. The two Unix time registers starting from 40707 must be written/read simultaneously, and
the writing/reading must begin with 40707, otherwise the writing/reading will be invalid.
3. The SOE event counte r 40710 is only allowed to be read alone.
4. The event records must be read from the starting point of each event, and the number of
register must be an integral multiple of 4, otherwise the reading will be invalid.
85
8.16 List of configuration registers
Register address
Definition Read/write
attribute
Description
41001 CT primary side setting R/W 1 ~49,999
41002 CT secondary side setting RO 5 or 1
41003 PT primary side setting
low word
R/W
41004 PT primary side setting
high word
R/W
1 ~500,000
41005 PT secondary side setting R/W 1 ~200
41006 Measuring mode R/W 0 – 4-line star connection
1 – 3-phase delta connection
41007 Communication address R/W 1 ~247
41008 Communication baud rate R/W 0 – 4800
1 – 9600 2 – 19200 3 – 38400
41009 Reserved
41010 Clear max. /min. real time
data
WO FF clearance
41011 Clear energy data WO FF clearance
41012 Clear demand data WO FF clearance
41013 Clear event logging WO FF clearance
86
41014 – 41015 Reserved
41016 Return time of relay 1 R/W 0 –1200s
0 means blocking.
41017 Return time of relay 2 R/W 0 – 1200s
0 means blocking.
41018 Return time of relay 3 R/W 0 – 1200s
0 means blocking.
41019 Return time of relay 4 R/W 0 – 1200s
0 means blocking.
41020 – 41021 Reserved
41022 Active energy pulse output R/W 0 – Off
1 – Active energy input 2 – Active energy output
41023 Reactive energy pulse
output
R/W 0 – Off
1 – Reactive energy input 2 – Reactive energy output
41024 Pulse output constant R/W 220 V/5 A, range:
1000 – 5000 100 V/5 A, 220 V/1 A, range: 1000 – 20000 100 V/1 A, range: 1000 – 40000 The step length is 100.
87
41025 Objects of analog output R/W 0 – Off
1 – Phase A voltage 2 – Phase B voltage 3 – Phase C voltage 4 – Line AB voltage 5 – Line BC voltage 6 – Line CA voltage 7 – Phase A current 8 – Phase B current 9 – Phase C current 10 – Total active power 11 – Total reactive power 12 – Total power factor 13 – Frequency
41026 Analog output factor R/W 10 – 100
41027 – 41030 Reserved
41031 Control mode of relay 1 R/W 0 – Local control
1 – Remote control
41032 Operation-object of relay 1 R/W 0 – Disable
1 – Maximum value of three-phase phase voltage 2 – Minimum value of three-phase phase voltage 3 – Maximum value of three-phase line voltage
88
4 – Minimum value of three-phase line voltage 5 – Maximum value of three-phase current 6 –Minimum value of three-phase current
41033 Operation upper limit
value of relay 1
R/W 0 – 120%
41034 Operation lower limit
value of relay 1
R/W 0 – 120%
41035 Action time delay of relay
1
R/W 0 – 1200s
41036 Control mode of relay 2 R/W 0 –Local control
1 –Remote control
41037 Operation-object of relay 2 R/W 0 – Disable
1 – Maximum value of three-phase phase voltage 2 – Minimum value of three-phase phase voltage 3 – Maximum value of three-phase line voltage 4 – Minimum value of three-phase line voltage 5 – Maximum value of three-phase current
89
6 – Minimum value of three-phase current
41038 Operation upper limit
value of relay 2
R/W 0 – 120%
41039 Operation lower limit
value of relay 2
R/W 0 – 120%
41040 Action time delay of relay
2
R/W 0 – 1200s
41041 Control mode of relay 3 R/W 0 – Local control
1 – Remote control
41042 Operation-object of relay 3 R/W 0 – Disable
1 – Maximum value of three-phase phase voltage 2 – Minimum value of three-phase phase voltage 3 – Maximum value of three-phase line voltage 4 – Minimum value of three-phase line voltage 5 – Maximum value of three-phase current 6 – Minimum value of three-phase current
41043 Operation upper limit
value of relay 3
R/W 0 – 120%
90
41044 Operation lower limit
value of relay 3
R/W 0 – 120%
41045 Action time delay of relay
3
R/W 0 – 1200s
41046 Control mode of relay 4 R/W 0 – Local control
1 – Remote control
41047 Operation-object of relay 4 R/W 0 – Disable
1 – Maximum value of three-phase phase voltage 2 – Minimum value of three-phase phase voltage 3 – Maximum value of three-phase line voltage 4 – Minimum value of three-phase line voltage 5 – Maximum value of three-phase current 6 – Minimum value of three-phase current
41048 Operation upper limit
value of relay 4
R/W 0 – 120%
41049 Operation lower limit
value of relay 4
R/W 0 – 120%
41050 Action time delay of relay
4
R/W 0 – 1200s
91
8.17 List of energy setting registers
Register address
Definition Read/write
attribute
Description
41101 First-quadrant active energy low
word
41102 First-quadrant active energy
high word
41103 Second-quadrant active energy
low word
41104 Second-quadrant active energy
high word
41105 Third-quadrant active energy
low word
41106 Third-quadrant active energy
high word
41107 Fourth-quadrant active energy
low word
41108 Fourth-quadrant active energy
high word
41109 First-quadrant reactive energy
low word
41110 First-quadrant reactive energy
high word
WO 0 – 999, 999, 999
Calculation factor: 0. 1
92
41111 Second-quadrant reactive energy
low word
41112 Second-quadra nt reactive energy
high word
41113 Third-quadrant reactive energy
low word
41114 Third-quadrant reactive energy
high word
41115 Fourth-quadrant reactive energy
low word
41116 Fourth-quadrant reactive energy
high word
8.18 05H command control relays
Register address Definition Read/write attribute Description
00 Channel of relay 1
01 Channel of relay 2
02 Channel of relay 3
03 Channel of relay 4
WO
FF00 – Close 0000 – Release
93
9. Maintenance and Trouble Shooting
Possible prob lem
Possible cause Possible solution
The meter has no
indication after the
control power supply
is imposed.
The power supply
fails to be imposed
on the meter.
Check if the correct working voltage has
been imposed on the L/+ and N/-
terminals of the meter.
Check if the fuse for the control power
supply has been burnt down.
The voltage
measurement is not
correct.
Check if the neutral point has been
connected reliably.
Check if the measured voltage matches
the rated parameter of the m eter.
Check if the transforma tion ratio of the
PT has been set correctly.
The measured value is not correct or does not conform to the expectation.
The current
measurement is not
correct.
Check if the measured current matches
the rated parameter of the m eter.
Check if the transforma tion ratio of the
CT has been set correctly.
94
The power
measurement is not
correct.
Check if the measurement mode has been
set correctly.
Check if the phase sequence
corresponding to the voltage and the
current is correct.
Check if the current terminals of the same
name are wrong.
There is no change in
the on-off status.
The on-off
operating voltage is
not correct.
Check if the types of external nodes
match the rated parameters of the meter.
Check if the external connection is
correct.
The relay does not
receive the control
command.
Check if the communication link is
correct.
The working mode of the relay is not correct.
Check if the current relay is under the correct mode.
The relay doest not
operate.
The operating time has not been set correctly.
Check the setting of the operating time of the relay. For the specific information, refer to the content re garding relays of the operation manual.
95
No analog output.
The analog is set as
“disable” or wrong
object.
Check through communication the setting
of analog.
No pulse output or
incorrect pulse output
The setting of the
pulse object or
constant is wrong.
Check through communication the setting
of pulse.
The communication
address of the meter
is not correct.
Check if the address of the meter is
consistent with its d efinition or if there
are more than two identical addresses in
the same network.
The communication speed of the meter is not correct.
Check if the communication speed of the meter is consistent with its definition.
The communication link has not been connected to the terminal resistor.
Check if the 120-Ohm resistor has been connected.
The communication link suffers interference.
Check if the communication-shielding layer has been earthed effectively.
There is no
communication
between the upper end
device and the meter.
The communication line is interrupted.
Check if the communication cable has been disconnected.
96
10. Technical Datasheet
Structural dimensions
Panel:
mm00.9600.96
Installation:
mm50.8950.89
Depth of main body:
mm00.65
Depth of extension module:
mm00.25
Type of displa y
LCD
Connection of terminals
Standard 5.08-mm p luggable terminals. The cur rent terminals are
equipped with fasteners to prevent accidental coming off.
Working power supply
85-265 VAC/45-65 Hz, 100-300 VDC
Weight
0.5Kg
Measuring accuracy
Voltage
0.2%, typical measure 0.1%
Current
0.2%, typical measure 0.1%
Active Power
0.5%
Power factor
0.5%
Frequency
0.01Hz
Active Energy
1%
97
Environment
Operating temperatur e
-20~ +60
Storage temperature
-30~ +70
Relative humidity
5% ~ 90% RH, non-condens ing
EMC
Electrostatic Discharge Immunity Test IEC 61000-4-2,L evel 4
Radiated immunity test IEC 61000-4-3,L evel 3
Electrical fast transient/b urst immunity test IEC 61000-4-4,L evel 4
Surge immunity test (1, 2/50μs8/20μs)
IEC 61000-4-5,L evel 3
Conducted emissions EN 55022,Class B
Radiated emissions EN 55022,Class B
98
Notice:
PILOT reserves the right to modify this manual without prior notice in vi ew of continued
improvement.
Technical Consulting: +86 15916202620
After-sale Services: +86 15916202 800
Email: pilot166@pmac.com.cn
Zhuhai Pilot Technology Co., Ltd.
Add: No. 15, Keji 6 Road, Chuangxin Haian, Tangjia High-tech Zone, Zhuhai, Guangdong, 519085 China
Tel: +86 -756-3629687/ 3629688
Fax: +86-756-3629600/ 3629670
http://www.pmac.com.cn
Loading...