OPERATING AND INSTALLATION INSTRUCTIONS SYSTEM VENTECH PKOM4 PAGE 37
20. List of parameters
ID PARAMETER UNIT
WORKS
SET COMMENT
A01 Operating mode - 0
0 = O
1 = Summer
2 = Winter
3 = Automatic
A02 Damping, outside temperature % 60
A03 Heating limit °C 14 No heating allowed above
A04 Hysteresis K 2
A05 Equipment type - 0/1
0 = Trend
1 = Classic
A06 Switch-on hysteresis, cooling K 1
A07 Switch-on hysteresis, heating K 0,5
A08 Switch-o hysteresis, heating K 0,5
A09 Enable – active cooling - 0
0 = no
1 = yes
A10 Room set-point, override °C 22
A11 Room set-point - cooling °C 26
A12 Room set-point, normal operation °C 22
A13 Room set-point, lowering operation °C 20
A14 Room set-point - holiday °C 18
A15 Room set-point, frost protection °C 15
A16 Room temperature sensor - 0
0 = Display
1 = Room sensor
A17 Room sensor - 0
0 = over A16
1 = extract air sensor
A18 Demand-driven control - 0
0 = no
1 = CO
2
controlled
2 = RF controlled
3 = CO
2
& RF controlled
B11
Min. fresh air volume for enablement of active cooling
°C 25 Cooling not enabled below this
C08 Air volume ventilation level 1 (SUP) m³/h 85
C09 Air volume ventilation level 2 (SUP) m³/h 120
C10 Air volume ventilation level 3 (SUP) m³/h 160
C11 Air volume ventilation level 4 (SUP) m³/h 200
C12 Extract air balance % 0 Balancing extract/supply air
D02 Min. supply air, cooling °C 15
D05
Max. supply air temperature,
heating
°C 40
E07
Supply air volume in defrost
operation
% 40
F01
VHR fresh air temperature before
WRG
°C -8/-3
With enthalpy / standard
exchanger
G01 Min. fresh air temperature Bypass °C 12 No bypass operation below this
J01 CO2 concentration threshold ppm 1000 Increase air volume
J02 Relative humidity high % 70 Increase air volume
J03 Relative humidity low % 30 Reduce air volume
V01 Additional function - 0
0 = none
1 = Solar system
2 = Heating circuit
3 = Duct heating battery
4 = Heating circuit & duct heating
battery
USER
GENERALSPECIALIST