VALVETRAB compact
Installations Instructions
ZBN 18
RS
ZBFM 5
4,5 Nm
VAL-CP-3C-350
28 59 54 7
VAL-CP-3C-350/O
28 81 02 3
System TN-C
U
N
U
C
U
p
I
n
I
(8/20)µs 120 kA 80 kA 60 kA 40 kA
max
Kurzschlussfestigkeit I
Short circuit withstand
capability I
p
p
L1, L2, L3, PEN
≤
1,4 kV
60 kA 40 kA 30 kA 20 kA
VAL-CP-2C-350
28 59 58 9
VAL-CP-2C-350/O
28 81 05 2
TN-C
L1, L2, PEN
230/400 V AC ... 240/415 V AC 50/60 Hz
≤
1,4 kV
T
IP-Code
max.
Class II
Typ 2
Ø max. L, N,
Ø min. L, N,
6
16 mm 16 mm
6
63 A gL/gG – Serial wiring
125 A gL/gG – Parallel wiring
IEC 61643-1:1998-02
EN 61643-11:2002-12
25 mm
2,5 mm
green - gn
VAL-CP-3C-350VF
28 59 53 4
L1, L2, L3, PEN
350 V AC 50/60 Hz
≤
25 kA
-40 °C ... +80 °C
20
2
2
TN-C
1,5 kV
red - rd
VAL-CP-2C-350VF
28 59 576
TN-C
L1, L2, PEN
≤
1,5 kV
2
16 mm
2
2,5 mm
with Remote ind. contact / mit Signalisierung
VAL-CP-3C-350; VAL-CP-3C-350/VF
VAL-CP-2C-350; VAL-CP-2C-350/VF
U
Wechsler
RS
PDT
Inverseur
C. inversor
12
11
14
max/Imax
AC:
125 V/ 1A
250 V/ 1A
DC: 125 V/ 0,2 A
0,25 Nm
7 mm
without Remote ind. contact / ohne Signalisierung
VAL-CP-3C-350/O
0,14 mm
2
- 1,5 mm
7 mm
2
VAL-CP-2C-350/O
RS
serial wiring / V-Durchgangsverdrahtung
A
DIN V VDE V 0100-534; IEC 60364-5-534
Protection conductor bar
L 1
L 2
L 3
PEN
PAS
PEN
PEN
VALVETRAB
VALVETRAB
VAL-CP-350 ST
VAL-CP-350 ST
28 59 61 5
28 59 61 5
L1L1L2L2L3
S
PE
F1
PAS
FM
VALVETRAB
VAL-CP-350 ST
28 59 61 5
L3
S
2
PE
Ground
RS
L
≤ 0,5 m
L 1
L 2
L 3
PEN
TN-C
⇒⇒⇒⇒ ok
parallel wiring / Anschluss im Stich
B
DIN V VDE V 0100-534
IEC 60364-5-53; CEI 81-8:2002-02
S
PE
PAS
VALVETRAB
VAL-CP-350 ST
28 59 61 5
L1L1L2L2L3
PAS
PEN
PEN
VALVETR AB
VAL-CP-350 ST
28 59 61 5
Protection conductor bar
F1
L 1
L 2
L 3
PEN
⇒⇒⇒⇒ defect
⇒⇒⇒⇒ (a, b
⇒⇒
(a + b
⇒⇒
a
≤ 0,5 m
b
≤ 0,5 m
FM
RS
VALVETR AB
VAL-CP-350 ST
28 59 61 5
L3
S
2
F2
≤≤≤≤ 0,5 m)
L 1
L 2
L 3
PEN
≤≤
0,5 m)
≤≤
L
Backup Fuse / Vorsicherung
F1
A gL/gG
F2
A gL/gG
S2
mm2S
25 6 6
12
11
14
Kabelschuh ⇒ 6 mm2
cable lug ⇒ 6 mm
F1
≤≤≤≤ 40 A
2
TWIN-Aderendhülse ⇒ 2 x 10 mm
TWIN ferrules ⇒ 2 x 10 mm
F1
≤≤≤≤ 63 A
2
Bakkup Fuse / Vorsicherung
F1
A gL/gG
S2
mm
2
25 6 6
35 6 6
40 6 6
50 10 10
63 10 10
2
S
mm
PE
A
✓
✓
✓
✓
✓
35 6 6
40 6 6
50 6 6
2
63 10 10
80 10 10
100 16 16
125 16 16
> 125 125 16 16
mm
PE
Safety
2
B
✓
✓
✓
✓
✓
✓
✓
✓
✓
instructions
see back view

DE
PHOENIX CONTACT GmbH & Co. KG
32823 Blomberg
Fax :++/5235-34 12 00
Phone :++/5235-30 0
www.phoenixcontact.com
EN
PHOENIX CONTACT GmbH & Co. KG
32823 Blomberg
Fax :++/5235-34 15 00
Phone :++/5235-30 0
www.phoenixcontact.com
Installationsanweisung
VAL-CP...C...
tion dieses Gerätes darf nur von einer autorisierten Elektrofachkraft ausgeführt
werden.
Bei der Installation sind landesspezifische Vorschriften und Gesetze einzuhalten.
Insbesondere ist darauf zu achten, dass die auftretende Spannung der Anlage die
Ableiterbemessungsspannung U
Die Angaben zur Vorsicherung sind zu beachten.
Bei Öffnen des Gerätes erlischt der Gewährleistungsanspruch gegenüber dem
Hersteller.
Isolationsmessungen
Ziehen Sie vor einer Isolationsmessung in der Anlage den Schutzstecker. Anderenfalls sind Fehlmessungen möglich. Setzen Sie den Stecker nach der Isolationsmessung wieder in das Basiselement ein.
sind leistungsstarke, steckbare Überspannungsableiter. Die Installa-
nicht übersteigt.
C
Installations instruction
VAL-CP...C...
installed by an authorized electrician.
National laws and regulations must be observed during installation. It is particularly
important to ensure that the voltage that occurs in the plant does not exceed the
rated surge arrester voltage U
Please observe the specifications regarding the backup fuse.
The manufacturer's warranty no longer applies if the device is opened.
Insulation measurements
Unplug the protective plug before performing an insulation measurement in the
system. Otherwise inaccurate measurements are possible. Re-insert the plug into
the base element after the insulation measurement.
are pluggable high-performance surge arresters. They may only be
.
C
PHOENIX CONTACT GmbH & Co. KG
32823 Blomberg
Fax :++/5235-34 12 00
Phone :++/5235-30 0
www.phoenixcontact.com
Conseils d'installation
Les
VAL-CP...C...
électricien expert autorisé peut effectuer l'installation de cet appareil.
Lors de l'installation, il convient de respecter les normes et lois nationales
spécifiques en vigueur. Il faut particulièrement veiller à ce que la tension présente
sur l'installation ne soit pas supérieure à la tension assignée du module U
Respecter les indications concernant le fusible amont.
Le fait d'ouvrir l'appareil supprime le droit à la garantie vis-à-vis du fabricant.
Mesure de l’isolement
Avant toute mesure d’isolement dans l’installation, retirez la fiche, sous peine
d’erreurs de mesures. Remettez la fiche dans l’embase après les mesures.
sont des parafoudres débrochables de haute énergie. Seul un
.
C
PHOENIX CONTACT GmbH & Co. KG
32823 Blomberg
ESFR
Fax :++/5235-34 15 00
Phone :++/5235-30 0
www.phoenixcontact.com
Indicación de instalación
Los módulos
gran capazidad. La instalación de este módulo solo puede efectuarse por un electricista autorizado.
Para la instalación tienen que observarse las prescripciones y las leyes
específicas del país. Especialmente debe tenerse en cuenta que la tensión de la
instalación existente no sobrepase la tensión de dimensionamiento del
descargador U
Observe las especificaciones para el fusible previo.
En caso de abrir el módulo extingue el derecho de garantía frente al fabricante.
Mediciones de aislamiento
Antes de efectuar una medición de aislamiento en la instalación eléctrica, extraiga
la protección enchufable. De otra manera puede dar lugar a mediciones incorrectas. Una ver realizada la medición de aislamiento enchufe de nuevo la protección
enchufable en el elemento de base.
VAL-CP...C...
.
C
son descargadores de sobretensiones enchufables de
TNR. 9660326/20.09.05-04 Printed in Germany © PHOENIX CONTACT 2005