Phoenix PHS300-x, PCS300-x, PCS300-x-DOC Installation Manual

PHS/PCS300 SERIES INSTALLATION GUIDE
Section 1. Product Description
The PHS300-x is a room humidity sensor. The PCS300-x is a combination temperature and humidity room sensor. The PCS300-x­DOS has a large LCD display, slider setpoint adjustment, and override button.
Depending on model, the analog outputs are a humidity sensor output (defined in the table below), a 10 KΩ type 2 thermistor sensor, 0-20 KΩ temperature setpoint, and an override contact. All units come standard with a 3.5 mm (1/8"), easy access communication jack providing direct network access. All PCS units also include an internal three position Low/Normal/High test and balance switch.
Model Humidity Sensor Signal
PHS300-x Default: 4-20 mA
Field selectable to: 0-5 or 0-10 Vdc
PCS300-x Default: 4-20 mA
Field selectable to: 0-5 or 0-10 Vdc
PCS300-x-DOS Default: 4-20 mA
Field selectable to: 0-5 or 0-10 Vdc
MODELS PHS300-x, PCS300-x, and PCS300-x-DOS
(where -x defines the enclosure style)
Figure 2. PCS300-x-DOS with display, override, and
slider temperature setpoint
Figure 1. PHS300-x and PCS300-x sensors only
Section 2. General Installation Requirements
For proper installation and subsequent operation of each controller, pay special attention to the following recommendations:
It is recommended that the sensor(s) be kept at room temperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature during shipping/storage to evaporate.
Upon unpacking the product, inspect the contents of the carton for shipping damages. Do not install damaged controllers.
Allow for proper clearance of sensor enclosure, wiring terminals and hardware configuration and maintenance.
Each controller is designed to operate under the following environmental conditions:
• Ambient temperature from 32°F to 122°F (0°C to 50°C)
• Relative humidity from 0% to 95%, non-condensing
Ensure proper ventilation of each sensor and avoid areas where corroding, deteriorating or explosive vapors, fumes or gases may be present.
Do not drop the sensor or subject it to physical shock.
If the controller is used and/or installed in a manner not specified by Phoenix Controls, the functionality and the protection provided by the sensor may be impaired.
CAUTION
Any type of modification to any Phoenix Controls product will void the product's warranty.
NOTE
75 Discovery Way Acton, MA 01720 Tel (978) 795-1285 Fax (978) 795-1111 www.phoenixcontrols.com
©2014 Phoenix Controls Specifications subject to change without notice. Rev. C 650-321-017 08/16 PCS300 SERIES INSTALLATION GUIDE 1 OF 12
Take special care to keep the front and back plate aligned when separating and joining them.
WARNING
Take reasonable precautions to prevent electrostatic discharges to each sensor when installing, servicing or operating the controller. Discharge accumulated static electricity by touching one's hand to a securely grounded object before working with each controller.
2.1 Mounting Instructions
NOTE
Mounting hardware is provided for both junction box and drywall installation.
2.1.1 Junction Box
DO NOT CUT OUT THE ENTIRE JUNCTION BOX DIMENSION. The base plate will not fully cover the opening.
1. Pull the wire through the wall and out of the junction box, leaving about six inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the base to the box using the #6-32 x 1/2" mounting screws provided.
4. Terminate the unit according to the Termination section.
5. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place.
NOTE
In wall-mount applications, the wall temperature and the temperature of the air within the wall cavity can cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and premature failure of the sensor. To prevent these conditions, do the following for the mounting method used:
• Junction box - seal the conduit leading to the electrical box
• Drywall - ensure that the foam insulating pad on the back of the enclosure covers the hole in the wall.
6. Secure the cover by backing out the lock-down screws using a 1/16" Allen wrench until they are flush with the bottom of the cover.
2.1.2 Drywall Installation
1. Place the base plate against the wall where you want to mount the sensor.
2. Using a pencil mark out the two mounting holes and the area where the wires will come through the wall.
3. Drill two 3/16" holes in the center of each marked mounting hole. Insert a drywall anchor into each hole.
4. Drill one 1/2" hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out of the 1/2" hole, leaving about six inches free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided.
8. Terminate the unit according to the Termination section.
9. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place.
10. Secure the cover by backing out the lock-down screws using a 1/16" Allen wrench until they are flush with the bottom of the cover.
2 OF 12 PCS300 SERIES INSTALLATION GUIDE 650-321-017 08/16 ©2014 Phoenix Controls Specifications subject to change without notice. Rev. C
2.2 General Wiring Recommendations
CAUTION
Turn off power before any kind of servicing. Please note that there may be multiple power sources.
2.2.1 Phoenix Controls Wiring Recommendations
Use cables recommended by Phoenix Controls (refer to Phoenix Controls Cables on page 12).
Stranded wire of at least 22 AWG is strongly recommended for all wire connections. Larger gauge wire may be required for long runs.
Follow good wiring practices:
Do not run the signal cable in the same conduit or wireway as the power cables.
If the signal cable must cross power cables, it is best to do so at a 90-degree angle.
Maintain a consistent color code or polarity all the way through the wiring system.
All wiring must comply with the National Electric Code (NEC) and local codes.
Do NOT run this device's wiring in the same conduit as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to supply highly inductive loads such as motors, contactors and relays.
Tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. If you are experiencing any of these difficulties, please contact your Phoenix Controls Representative.
Local and national electrical codes take precedence.
Sensor connections:
Remove the front plate from the back plate to facilitate the wiring process.
Use a small flat screwdriver to tighten the terminal connector screws once the wires have been inserted.
The board connectors accept wires or flat cables ranging from 22 to 14 AWG (0.64-1.63 mm diameter) per pole. However, power cables must remain between 18 and 14 AWG (1.02-1.63 mm diameter).
Power connections:
Power type cables (i.e., for power, 2- and 3-wire voltage and current inputs and outputs, as well as triac outputs) should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires.
Do not connect the universal inputs, analog/digital outputs or common terminals to earth or chassis ground (unless stated otherwise).
CAUTION
Phoenix Controls does not recommend wiring the sensor with power applied as accidental arcing may damage the product and will void the warranty.
©2014 Phoenix Controls Specifications subject to change without notice. Rev. C 650-321-017 08/16 PCS300 SERIES INSTALLATION GUIDE 3 OF 12
2.2.2 PHS300-x, PCS300-x, and PCS300-x-DOS Wiring
Figure 3. PHS300-x, PCS300-x, and PCS300-x-DOS connections
NOTE
PHS300-x, PCS300-x, and PCS300-x-DOS Wiring with Jumper in: 4 to 20 mA Setting
The PHS300-x and PCS300-x do not have OVR or SET terminals and the EXT-OVR and SEN terminals are non-functional.
Terminal Applicable to: Option Description
OVR1 and OVR2 PCS300-x-DOS
only
SET1 and SET2 PCS300-x-DOS
only
SEN1 and SEN2 PCS300-x and
PCS300-x-DOS
EXT-OVR PCS300-x-DOS
only
O Occupancy override status:
N.O. contact output (300 mA @ 24 Vdc)
S Temperature setpoint:
0 -20 KΩ output
Temperature sensor:
10K-2 thermistor output
D External "person" icon override:
Bypass control (from Phoenix valve) indication; "person" icon is solid (occupied) when this pin is switched to power ground (see Bypass/External "Person" Icon Control on page 7 )
VOUT All Not used
V+ All Humidity sensor: 4-20 mA output
GND All 24 Vdc power (see Specifications on page 10 for details)
4 OF 12 PCS300 SERIES INSTALLATION GUIDE 650-321-017 08/16 ©2014 Phoenix Controls Specifications subject to change without notice. Rev. C