Phoenix PH100-55, PH199-55, PH100-80, PH130-55, PH130-80 Installation Operation & Maintenance

...
Page 1
• Installation • Operation • Maintenance
© 2008 Heat Transfer Products, Inc.
Phoenix Water Heater Models*
PH100-55 / 130-55 / 199-55 PH100-80 / 130-80 / 199-80
PH100-119 / 130-119 / 199-119
Phoenix Sanitizer Booster Models*
130-55SA / 199-55SA
Page 2
1
WARNINGS
n
WARNING
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch: do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the
gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Page 3
2
CONTENTS
CONTENTS
Part 1 – Product and Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Part 2 – How The Phoenix Operates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Part 3 – Prepare Water Heater Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-16
A. Installations Must Comply With: B. Before Locating the Phoenix C. Clearances for Service Access D. Residential Garage Installation E. Exhaust Vent and Intake Air Vent F. Prevent Combustion Air Contamination G. When Removing a Water Heater from an Existing Common Vent System H. Water Chemistry I. Temperature and Pressure Relief Valve J. Potable Expansion Tank K. Water Piping L. Auxiliary Connection
Part 4 – Prepare Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-19
A. Electrical Connection B. Gas Connection C. Gas Piping D. Gas Table E. Dungs Gas Valve
Part 5 – Venting Combustion Air And Condensate Removal . . . . . . . . . . . . . . . . . . . . 19-27
A. Installing Exhaust Vent and Intake Air Vent B. General C. Approved Materials for Exhaust Vent and Intake Air Vent D. Exhaust Vent and Intake Air Vent Pipe Location E. Exhaust Vent and Intake Air Vent Sizing F. Longer Vent Runs G. Exhaust Vent and Intake Air Pipe Installation H. Water Heater Removal from a Common Vent System I. Condensate Removal System J. Diagrams for Venting
Part 6 – Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-31
A. Operating Instructions B. Overall Appliance and Control Operation C. Status Menu D. Test Mode E. Maintenance F. Internal Wiring
Part 7 – Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
A. Shutdown Procedure B. Vacation Procedure C. Failure to Operate
Part 8 – Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32-40
A. Phoenix Error Code B. Phoenix Error C. Phoenix Fault
Page 4
3
PRODUCT AND SAFETY INFORMATION
PART 1: PRODUCT AND SAFETY INFORMATION
n
WARNING
Installer — Read all instructions in this manual, and the Venting section, before installing. Perform steps in the order given.
User — This manual is for use only by a qualified heating installer/service technician. Refer to User’s Information Manual for your reference.
User — Have this water heater serviced/ inspected by a qualified service technician annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
n
WARNING
Failure to adhere to the guidelines on this page can result in severe personal injury, death or substantial property damage.
n
WARNING
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas suppliers' instructions.
• If you cannot reach your gas supplier, call the fire department.
SPECIAL ATTENTION BOXES
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the product.
n
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
n
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
n
CAUTION
CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
DEFINITIONS
Page 5
4
HOW THE PHOENIX OPERATES
PART 2: HOW THE PHOENIX OPERATES
Phoenix Modulation Condensing Technology is an intelligent system that delivers highly efficient water heating, while maximizing efficiency by measuring the Data Parameters of your water heating system.
1. Stainless Steel Water Storage Tank
The Stainless Steel Water storage tank has a combustion chamber submerged into the tank water. When the water heater is fired, the combustion gases heat the combustion chamber walls, transferring the heat directly into the surrounding water. The hot gases are blown into the secondary heat exchanger coils, where even more heat is transferred into the water, wringing even more heat from the gases.
2. Modulating Combustion System
Modulation during the water heating operation is based on the tank temperature. The control monitors the system to regulate the output of the burner during operation to match the system demand. This increase in efficiency allows for substantial fuel savings.
3. Gas Valve
The gas valve senses suction from the blower, allowing gas to flow only if the gas valve is energized and combustion air is flowing.
4. Upper Supply Tank Sensor
This sensor monitors water heater upper portion water temperature (system supply). The control module adjusts the burner firing rate so the outlet temperature is correct.
5. Lower Return Tank Sensor
This sensor monitors the lower portion of the water heater return water temperature (system return). The control module reduces or increases the input, depending on how close the water temperature is to the outlet water temperature set point.
6. Control
The integrated control system monitors the upper and lower water temperature and regulates the fan speed to regulate the unit’s BTU output. This allows the unit to only deliver the amount of heated energy required and nothing more!
7. Burner
Constructed of high grade stainless steel construction, the burner uses pre-mixed air and gas and provides a wide range of firing rates.
8. Condensate drain connection
This is a condensing high efficiency appliance, therefore this unit has a condensate removal system. Condensate is nothing more than water vapor, derived from the combustion products, similar to an automobile when it is initially started. It is very important that the condensate line is sloped away from the water heater and down to a suitable inside drain. If the condensate outlet on the Phoenix is lower than the drain, you must use a condensate removal pump (kit p/n 554200 available from Heat Transfer Products, Inc.) A condensate neutralizer, if required by local authorities can be made up of lime crystals, marble or phosphate chips and will neutralize the condensate. This can be done in the field by the installer or you may purchase one from Heat Transfer Products, Inc. (P/N N1100). It is also very important that the condensate line is not exposed to freezing temperatures or any other type of blockage. Plastic tubing must be the only material used for the condensate line. Steel, brass, copper or others will be subject to corrosion or deterioration. A second vent may be necessary to prevent condensate line vacuum lock if a long horizontal run is used. Also, an increase in pipe size may be necessary to drain properly. Support of the condensation line may be necessary to avoid blockage of the condensate flow.
Page 6
5
HOW THE PHOENIX OPERATES
PART 2: HOW THE PHOENIX OPERATES (CONTINUED)
9. Spark ignition
The burner flame is ignited by applying a high voltage to the system spark electrode. This causes a spark from electrode to ground.
PART 3: PREPARE WATER HEATER LOCATION
A. INSTALLATIONS MUST COMPLY WITH:
Local, state, provincial, and national codes, laws, regulations and ordinances.
National Fuel Gas Code, ANSI Z223.1 – latest edition.
National Electrical Code.
For Canada only: B149.1 or B149.2 Installation Code, CSA C22.1 Canadian Electrical Code Part 1 and any local codes.
B. BEFORE LOCATING THE PHOENIX
1. Check for nearby connection to:
System water piping
Venting connections
Gas supply piping
Electrical power
2. Check area around water heater. Remove any combustible materials, gasoline and other flammable liquids.
3. The Phoenix gas control system components are protected from dripping or spraying water or rain during operation or service.
4. If the Phoenix Water Heater is to replace an existing water heater, check for and correct any existing system problems such as:
n
DANGER
Water temperature over 125 degrees F. can cause severe burns instantly, or death from scalds. Children, disabled, and elderly are at highest risk of being scalded. See instruction manual before setting temperature at water heater. Feel water before bathing or showering! Temperature limiting valves are available.
NOTICE
The Phoenix gas manifold and controls met safe lighting and other performance criteria when undergoing tests specified in ANSI Z21.10.3 — latest edition.
n
WARNING
Failure to keep water heater area clear and free of combustible materials, gasoline and other flammable liquids and vapors can result in severe personal injury, death or substantial property damage.
Page 7
6
PREPARATION
System leaks.
Incorrectly-sized expansion tank.
C. CLEARANCES FOR SERVICE ACCESS
1. If you do not provide minimum clearances, it might not be possible to service the water heater without removing it from the space. (See Fig. 3­1 at right)
D. RESIDENTIAL GARAGE INSTALLATION
Precautions
Take the following special precautions when installing the water heater in a residential garage. If the heater is located in a residential garage, per ANSI Z223.1, paragraph 5.1.9:
Place the Phoenix with a minimum of 18 inches above the floor of the garage to the bottom of the heater to ensure the burner and ignition devices will be no less than 18 inches above the floor.
Locate or protect the water heater so it cannot be damaged by a moving vehicle.
E. EXHAUST VENT AND INTAKE AIR VENT
The Phoenix requires a special vent system, designed for pressurized venting. Phoenix Water Heaters are rated ANSI Z21.10.3 Category IV (pressurized vent, likely to condense in the vent).
You must also install air intake piping from outside to the water heater flue adaptor. The resultant installation is categorized as direct vent (sealed combustion). Note: To prevent combustion air
contamination see Table 3-2 in this section for examples of areas to avoid when con­sidering exhaust vent and intake air vent termination.
03/22/07
LP-179-T
CLEARANCE
ZERO
12" MIN. 12" MIN.
CLEARANCE
CLEARANCE
CLEARANCE
24" MIN.
SERVICE CLEARANCE
Fig. 3-1 Phoenix Top View
PART 3: PREPARE WATER HEATER LOCATION (CONTINUED)
n
WARNING
The space must be provided with combustion/ventilation air openings correctly sized for all other appliances located in the same space as the Phoenix. Failure to comply with the above warnings could result in severe personal injury, death or substantial property damage.
RECOMMENDED SERVICE CLEARANCE
LP-179-W
07/11/07
LP-179-T 03/22/07
MAXIMUM 2"
DIAMETER OF WATER HEATER
PLUS 2" MINIMUM
TO OPEN DRAIN. LINE SHOULD BE AT LEAST 3/4" ID AND PITCHED FOR PROPER DRAINAGE.
Page 8
7
PREPARATION
Intake and exhaust must terminate near each other and may be vented vertically through the roof or through a side wall. The intake and exhuast venting methods are detailed in the Venting Section. Do not attempt to install the Phoenix Water Heater using any other venting means. Be sure to locate the Phoenix such that the air intake and exhaust vent piping can be routed through the building and prop­erly terminated outdoors. The air intake and exhaust vent piping lengths, routing and termination method must all comply with the methods and limits given in the Venting section.
F. PREVENT COMBUSTION AIR CONTAMINATION
Install intake air piping for the Phoenix Water Heater as described in the Venting section. Do not ter­minate exhaust in locations that can allow contamination of intake air.
G. WHEN REMOVING A WATER HEATER FROM AN EXISTING COMMON VENT SYSTEM
At the time of removal of an existing gas water heater, the following steps shall be followed with
PART 3: PREPARE WATER HEATER LOCATION (CONTINUED)
n
WARNING
You must pipe outside air to the water heater air intake. Ensure that the intake air will not contain any of the contaminants below. Contaminated air will damage the water heater, resulting in possible severe personal injury, death or substantial property damage. For example, do not pipe intake air vent near a swimming pool. Also avoid areas subject to exhaust fumes from laundry facilities. These areas will always contain contaminants.
Products to avoid
Spray cans containing fluorocarbons Permanent wave solutions Chlorinated waxes/cleaners Chlorine-based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms Adhesives used to fasten building products and other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction Remodeling areas Garages and workshops
Table 3-2: Corrosive contaminants and sources
n
DANGER
Do not install the Phoenix into a common vent with any other appliance. This will cause flue gas spillage or appliance malfunction, resulting in possible severe personal injury, death or substantial property damage.
n
WARNING
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
Page 9
8
PREPARATION
each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
a. Seal any unused openings in the common venting system. b. Visually inspect the venting system for proper size and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
c. Insofar as is practical, close all building doors and windows and all doors between the space in
which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
d. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust
thermostat so appliance will operate continuously.
e. Test for spillage after 5 minutes of main
burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar, pipe, or aerosol smoke (synthetic smoke).
f. After it has been determined that each
appliance remaining connected to the common venting system properly vents when tested as outlined herein, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous conditions of use.
g. Any improper operation of common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 — latest edition. Correct by resizing to approach the minimum size as determined using the appropriate tables in Table 13 of NFPA54 ANSI Z223.1 2006 of that code. Canadian installations must comply with B149.1 or B149.2 Installation Code.
H. WATER CHEMISTRY
1. Water Hardness
Water hardness is mainly due to the presence of calcium and magnesium salts dissolved in the water. The concentration of these salts is expressed in mg/L, ppm or grains per gallon, as a measure of relative hardness of water. Grains per gallon is the common reference measurement used in the U.S. water heater industry. Hardness expresses as mg/L or ppm may be divided by
17.1 to convert to grains per gallon. Water may be classified as very soft, slightly hard, moderately
PART 3: PREPARE WATER HEATER LOCATION (CONTINUED)
n
CAUTION
Chemical imbalance of your water can cause severe damage to your water heater and associated equipment and may also affect the efficiency. You may have to have your water quality professionally analyzed to determine whether you need to install a water softener. Failure of a heat exchanger due to lime scale build-up on the heating surface, low pH or other chemical imbalance is non-warrantable.
Page 10
9
PREPARATION
hard or hard based on its hardness number. The minerals in the water will precipitate out when the water is heated and will cause accelerated lime and scale accumulation on a heat transfer surface.
If the hardness of the water exceeds the maximum level of 25 grains per gallon, water should be softened to a hardness level no lower than 5 grains per gallon. Water softened as low as 0 to 1 grain per gallon may be under-saturated with respect to calcium carbonate resulting in water that is aggressive and corrosive.
2. pH of Water
pH is a measure of relative acidity, neutrality or alkalinity. Dissolved minerals and gases affect water's pH. The pH scale ranges from 0 to 14. Water with a pH of 7.0 is considered neutral. Water with a pH lower than 7 is considered acidic. Water with a pH higher than 7 is considered alkaline. A neutral pH (around 7) is desirable for most potable water applications. Corrosion damage and heater failures resulting from water pH levels of lower than 6 or higher than 8 are non-warrantable. The ideal pH range for water used in a storage tank or a water heater system is 7.2 to 7.8.
3. Total Dissolved Solids
Total dissolved solids (TDS) is a measure of all minerals and solids that are dissolved in the water. The concentration of total dissolved solids is usually expressed in parts per million (ppm) as measured in a water sample. Water with a high TDS concentration will greatly accelerate lime and scale formation in the hot water system. Most high TDS concentrations will precipitate out of the water when heated. This can generate a scale accumulation on the heat transfer surface that will greatly reduce the service life of a water heater. This scale accumulation can also impede the ability of the heat exchanger to transfer heat into the water. A heat exchanger that is damaged or blocked by lime/scale accumulation must be replaced. Failure of a water heater due to lime scale build up on the heating surface is non-warrantable. The manufacturer of the water heater has no control of the water quality, especially the TDS levels in your system. Total dissolved solids in excess of 2,000 ppm will accelerate lime and scale formation in the heat exchanger. Heat exchanger failure due to total dissolved solids in excess of 2,000 ppm is a non-warrantable condition.
PART 3: PREPARE WATER HEATER LOCATION (CONTINUED)
CAUTION
Failure of a heat exchanger due to lime scale build-up on the heating surface, low pH or other chemical imbalance is non-warrantable.
Page 11
10
PREPARATION
I. TEMPERATURE AND PRESSURE RELIEF VALVE
A temperature and pressure relief valve is installed into the marked port (upper right). We recom­mend a WATTS 100XL-4 valve or equivalent for 100,000 BTU models, 40XL5 valve or equivalent for 130,000 BTU models or above input, meeting the requirements for relief valves for hot water heaters as per ANSI Z21.22B by a nationally recognized lab that maintains a periodic inspection of produc­tion of such listed safety device. The pressure rating of the valve must not exceed the listed work­ing pressure of this appliance, and must be rated to the proper BTU/hr capacity of the water heater. Do not, under any circumstances, thread a cap or plug into the relief valve! Explosion, serious injury or death may result! Relief valve piping must be directed to the floor or to an open drain, but not connected directly. There must be a 6" space between the outlet of relief valve piping and drain or floor. Do not hook up to drain system directly without an air space. The relief valve must be period­ically checked for proper operation.
J. POTABLE EXPANSION TANK
A potable hot water expansion tank is required to offset the water expansion as the water is heated. In most city plumbing systems, the water meter has a no return or back flow device built into the system to prevent back flowing of water back into city mains. Some local codes require back flow preventers on all incoming water supplies. The hot water expansion tank must be listed for potable water use. The expansion tank should be located on the cold inlet piping close to the water heater.
n
CAUTION
The expansion tank must be suitable for hot potable water.
PART 3: PREPARE WATER HEATER LOCATION (CONTINUED)
n
WARNING
Following installation of the T & P Relief Valve, the valve lever MUST be operated AT LEAST ONCE A YEAR by the water heater owner to ensure that waterways are clear.
Certain naturally occurring mineral deposits may adhere to the valve, blocking waterways, rendering it inoperative. When the lever is operated, hot water will discharge if the waterways are clear. PRECAUTIONS MUST BE TAKEN TO AVOID PERSONAL INJURY FROM CONTACT WITH HOT WATER AND TO AVOID PROPERTY DAMAGE. BEFORE operating lever, check to see that a discharge line is connected to the valve, directing the flow of hot water from the valve to a proper place of disposal. If no water flows when the lever is operated, replacement of the valve is required. TURN THE WATER HEATER “OFF”
AND CALL A PLUMBER IMMEDIATELY.
This device is designed for emergency safety relief and shall not be used as an operating control. A relief valve functions, in an emergency, by discharging water. Therefore, it is essential that a discharge line be piped from the valve in order to carry the overflow to a safe place of disposal. The discharge line must be same size as the valve outlet must pitch downward from the valve and terminate at least 6" above a drain where any discharge will be clearly visible.
Page 12
11
PREPARATION
K. WATER PIPING
The domestic water connections must be installed in accordance to all local and national plumbing codes, or any applicable standard which prevails. The inlet and outlet ports of the Phoenix are 1" on 55 gallon models. On the 80 and 119 gallon models, the inlet and outlet ports are 1 ½". On the cold inlet, (bottom left), install a 1" brass tee on 55 gallon models, or a 1 ½" tee on 80 and 119 gallon mod­els. On the run of the 1" brass tee, install with pipe sealant compound, a 1" brass drain cock or equiv­alent. Into the branch of the 1" or a 1 ½" brass tee, install a copper male adapter to match your cop­per plumbing system. For convenience, you may install a sweat shut off valve and a union in the cold inlet piping to ease servicing in the future. If there is a back flow preventer, or any type of a no return valve in the system, then you must install an additional tee here for a suitable potable hot water expansion tank. In the hot outlet, (top left), install a suitable adapter to match the copper tubing of the plumbing system. A thermal trap or heat trap loop may be installed here, to provide additional energy savings and prevent the thermal siphoning of domestic hot water.
L. AUXILIARY CONNECTIONS
The auxiliary connections are additional connections for an air handlers, plate exchangers or other devices that supply hot water. These connections must be installed in accordance with all local and national codes or any applicable standard that prevails. The auxiliary connections are 1" on all Phoenix Models. Never use dielectric unions or galvanized steel fittings. Use only copper or brass fittings. Teflon Sealant must be used on all connections. The top port is the supply outlet and the bottom port is the return inlet.
n
WARNING
Never connect auxiliary connections to any system that uses glycol or other solutions formulated for hydronic systems. These auxiliary connections are to be used only
in a potable water system. Failure to follow this warning could result in death or serious injury.
PART 3: PREPARE WATER HEATER LOCATION (CONTINUED)
n
CAUTION
NEVER USE DIELECTRIC UNIONS OR GALVANIZED STEEL FITTINGS ON ANY DOMESTIC WATER CONNECTIONS OR AUXILIARY CONNECTIONS. USE ONLY COPPER OR BRASS FITTINGS. TEFLON THREAD SEALANT MUST BE USED ON ALL CONNECTIONS.
Page 13
12
PREPARATION
MAX
8.00"
COLD IN
VALVE
SPARCO AQUAMIX SHOWN.
TANK
PHOENIX WITH AIR HANDLER
PREVENTER
EXPANSION
INLET
VALVE MANUFACTURER
COLD WATER
HOT WATER OUTLET
NOTES:
DRAIN
must install a spring check valve)
FOR OTHER VALVES, CONSULT
GAS
AUXILIARY CONNECTION
WITHOUT a check valve, you
HOT OUT
BACKFLOW
BALL VALVE
CIRCULATOR WITH
INTREGAL CHECK VALVE
(if you are installing a circulator
AUXILIARY CONNECTION
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold water inlet of the Phoenix.
3. Gas line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
AIR HANDLER UNITS MOUNTED TO CEILING
*
*
CHECK WITH AIR HANDLER MANUFACTURER
FOR PROPER SIZING.
LP-179-L
7/13/07
PHOENIX WITH AIR HANDLERS ABOVE
NOTE: This drawing is meant to show system piping only. The installer is responsible for all
equipment and detailing required by local codes.
NOTES: FOR AIR HANDLER APPLICATION
1. MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER HEATER TO THE FAN COIL IN THE AIR HAN­DLER.
2. MASSACHUSETTS STATE PLUMBING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP REQUIRED TO ACTIVATE EVERY SIX HOURS FOR 60 SECONDS. THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS.
3. ALL WATER PIPING MUST BE INSULATED.
4. YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR.
Page 14
13
PREPARATION
MAX.
8.00"
OUTLET
VALVE
HOT WATER
TO 140
135
AUXILIARY CONNECTION
PREVENTER
EXPANSION
BACKFLOW
AUXILIARY CONNECTION
COLD WATER INLET
COLD IN
BALL VALVE
DRAIN
VALVE MANUFACTURER
HOT OUT
AIR HANDLER*
FOR OTHER VALVES, CONSULT
GAS
TO 130120
TANK
SPARCO AQUAMIX MIXING VALVE SHOWN.
*
CHECKWITH AIR HANDLER MANUFACTURER FOR PROPER SIZING.
CIRCULATOR ( REQUIRED IN-LINE IF NOT ON AIR HANDLER UNIT) ( SEE NOTE 4)
NOTES:
4. All circulators shall have an integral flow check.
3. Gas line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the check valve and the cold water inlet of the Phoenix.
LP-179-M
4/13/07
PHOENIX WITH AIR HANDLER ON SIDE
NOTE: This drawing is meant to show system piping only. The installer is responsible for all
equipment and detailing required by local codes.
NOTES: FOR AIR HANDLER APPLICATION
1. MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER HEATER TO THE FAN COIL IN THE AIR HANDLER.
2. MASSACHUSETTS STATE PLUMBING CODE REQUIRES AN ELECTRONICALLY TIMED CIRCULATOR PUMP REQUIRED TO ACTIVATE EVERY SIX HOURS FOR 60 SECONDS. THIS CIRCULATOR IS REQUIRED TO BE BRONZE OR STAINLESS.
3. ALL WATER PIPING MUST BE INSULATED.
4. YOU MUST INSTALL A VACUUM RELIEF VALVE PER 248 CMR.
Page 15
CLOSED LOOP RADIANT HEATING
14
PREPARATION
LP-179-N
7/16/07
NOTE: This drawing is meant to show system piping only. The
installer is responsible for all equipment and detailing required by local codes.
This application may not be allowed in Massachusetts. In Massachusetts you must install a vacuum relief valve per
248 CMR.
REVERSE MANIFOLD AND PIPING DIAGRAM FOR PHOENIX
NOTES:
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the check valve and the cold water inlet of the Phoenix. Check with the Manufacturer of the Thermal Expansion tank for proper sizing.
3. Gas Line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
NOTE: This drawing is meant to show system piping only. The installer is responsible for all equipment and
detailing required by local codes. In Massachusetts you must install a vacuum relief valve per 248 CMR.
*You should check with the manufacturer of the brazed plate for correct plate connections. Orientation may vary by manufacturer.
AIR
PRESSURE
ELIMINATOR
AUXILIARY
CONNECTION
VALVE
BALL
*
BRAZED PLATE
CIRCULATOR
(See note 4)
PURGE VALVE
BALL
VALVE
PRESSURE REDUCING VALVE
BALL VALVE
HEAT
RADIANT
BACKFLOW PREVENTER
BALL VALVE
CONNECTION
AUXILIARY
TANK
EXPANSION
( see note 4)
CIRCULATOR
WATER
MAKE-UP
GAUGE
SYSTEM DRAIN
LP-179-U
11/1/07
NOTES:
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the check valve and the cold water inlet of the Phoenix.
3. Gas Line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
EXPANSION TANK
BACKFLOW PREVENTER
SHUT-OFF BALL VALVE
COLD
CHECK VALVE
CIRCULATOR
(SEE NOTE 4)
GAS
COLD WATER
HOT WATER
COLD WATER
HOT WATER OUTLET
GAS
COLD WATER
HOT WATER
GAS
HOT WATER
AUXILIARY CONNECTION
AUXILIARY CONNECTION
Page 16
15
PREPARATION
HOT OUT
LP-179-O
7/13/07
NOTE: This drawing is meant to show system piping only. The installer is responsible for all
equipment and detailing required by local codes. In Massachusetts you must intall a vacuum relief valve per 248 CMR.
PHOENIX WITH STORAGE TANK
PHOENIX WITH STORAGE TANK
GAS
EXPANSION TANK
HOT WATER OUTLET
BACKFLOW PREVENTER
COLD IN
SHUT-OFF BALL VALVE
AUXILIARY CONNECTION
CIRCULATOR
(see note 4)
AUXILIARY
AQUASTAT CONTROL
SPRING CHECK
NOTES:
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the check valve and the cold water inlet of the Phoenix. Check with the Manufacturer of the Thermal Expansion Tank for proper sizing.
3. Gas line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check SPECIAL NOTE: Drains and Check valve connected between the Phoenix and the Storage Tank will
VALVE
DRAIN VALVE
COLD WATER INLET
assist in purging air from system.
CONNECTION
Page 17
16
PREPARATION
LP-179-SA
10/6/09
NOTE: In Massachusetts you must intall a vacuum relief valve per 248 CMR.
NOTICE
The standard Phoenix Water Heater does not meet the required temperature settings for sanitizer booster applications. The maximum temperature setting for the Phoenix Sanitizer Booster is 184°.
PHOENIX SANITIZER BOOSTER INSTALLATION
P/N PH130-55SA / PH199-55SA
#09
#08
#14
#13
#14
#09
3/4" Return
#04
3/4 Gas
#07
180
#06
#05
Return
#01 #03
#02
180
Supply
#10
Pressure Regulator
Pressure Gauge
Thermometer
1' Supply
PHOENIX SANITZER
DISHWASHER
DRAIN VALVE
#01
#02#03
WARNING; INCOMING SUPPLY MUST BE NO FURTHER THAN 5' FROM THE SANITZER
VERY IMPORTANT: INSULATE ALL PIPES ON RECIRCULATION LINE TO AND FROM SANITIZER
THE ITEMS LISTED BELOW ARE THE ITEMS AND PART NUMBERS IN THE VSBK-1200 SANITIZER BOOSTER KIT.
ITEM PART DESCRIPTION PART NUMBER ITEM PART DESCRIPTION PART NUMBER
#01 NIBCO TEE 1"X1"X 1/2" 7000-708 #08 PRESSURE GAUGE #02 FEMALE ADAPTER 1" 7000-709 #09 NIBCO TEE 1" X 1" X 3/4" 712R 7000-728
#03
#04
#05
#06 NIBCO TEE
#07
DIAL
THERMOMETER
EXPANSION TANK
4.5 GAL
GRUNDFOS 3
SPEED PUMP
VACUUM RELIEF
VALVE
7000-710 #10 NIBCO TEE
7000-711 #11 NIBCO TEE 1" X 1/2" X 1"R 7000-730
W/ CHECK VALVE 7000-712 #12
1/2" X 1/2" FITTING
AIR CHAMBER
7000-737 #13
7000-714 #14
REDUCING COUPLING
PRESSURE
REDUCING VALVE
NIBCO MALE
ADAPTERS
1" X 1/2" X 1"
COPPER
7000-716
7000-739
7000-732
7000-733
7000-736
Page 18
17
PREPARATION
PART 4: PREPARE WATER HEATER
A. ELECTRICAL CONNECTION
The Phoenix Water Heater must be wired to a 120 volt circuit by a qualified electrician. It is recom­mended that the Phoenix Water Heater be wired on its own circuit to minimize the possibility of cir­cuit failure due to outside causes. The Phoenix Water Heater requires a maximum of 6 amps at 120 volts in use.
To wire the Phoenix Water Heater
1. Remove the screws on each side of the cover of the Phoenix burner control, then tilt the cover up and remover it from the back plate.
2. Following all local and national wiring codes; route the incoming power wiring through the knockout near the lower right corner of the back plate of the Phoenix burner control from the rear to the inside of the burner control.
NOTE: Some earlier versions of the back plate may require drilling of the hole to increase its size to ½” conduit trade size (7/8” diameter)
3. Connect the line power wire (usually black) to the terminal marked 120V
4. Connect the neutral wire (usually white) to the terminals marked Neut.
5. Connect the ground wire (usually green) to the terminal marked GND
6. Place the cover back on the Phoenix burner control and secure it with the screws you removed
B. GAS CONNECTION
The gas supply shall have a maximum inlet pressure of less than 14" water column (350 mm), ½ pound pres­sure (3.5 kPa), and a minimum of 3.5" water column. The entire piping system, gas meter and regulator must be sized properly to prevent pressure drop greater than
0.5" WC as stated in the National Fuel Gas Code. This
information is listed on the rating plate. It is very impor­tant that you are connected to the type of gas as noted on the rating plate. "LP" for liquefied petroleum, propane gas or, "Nat" natural or city gas. All gas connections
n
WARNING
It is of extreme importance that this unit be properly grounded. It is very important that the building system ground is inspected by a qualified electrician, prior to making this connection. It is very important that the electrical power is only turned on when the Phoenix is completely filled with cold water.
KNOCKOUT
UNION
DRIP LEG
MIN 3/4"
Fig. 4-1
n
WARNING
Failure to follow all precautions could result
in fire, explosion or death!
Page 19
18
PREPARATION
PART 4: PREPARE WATER HEATER (CONTINUED)
must be approved by the local gas supplier, or utility in addition to the governing authority, prior to turning the gas supply on. Do not remove this adaptor! It is mandatory that this fitting is used for
connection to a field fabricated drip leg as shown in the illustration at right per the National Fuel Gas Code. You must ensure that the entire gas line to the connection at the Phoenix Water Heater is
no smaller than ¾". Once all the inspections have been performed, the piping must be leak tested. If the leak test requirement is a higher test pressure than the maximum gas inlet pressure, you must isolate the Phoenix from the gas line to continue leak testing. In order to do this, you must turn off the factory and field-installed gas cocks. This will minimize the possibility of damaging the Phoenix gas valve. Failure to do so may damage the gas valve. In the event the gas valve is exposed to a pressure greater than ½ PSI, 14" water column, the gas valve must be replaced. Never use an open flame (match, lighter, etc.) to check gas connections.
C. GAS PIPING
1. Run the gas supply line in accordance with all applicable codes.
2. Locate and install manual shutoff valves in accordance with state and local requirements.
D. GAS TABLE
Refer to the below table to size the supply piping to minimize pressure drop between meter or regulator and unit.
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3 Inch water Column
Gas Table
It is recommended that a soapy solution be used to detect leaks. Bubbles will appear on the pipe to indicate a leak is present. The gas piping must be sized for the proper flow and length of pipe, to avoid excessive pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load. If you experience a pressure drop greater than 1" WC, the meter, regulator or gas line is undersized or in need of service. You can attach a manometer to the incoming gas drip leg, by removing the cap and installing the manometer. The gas pressure must remain between 3.5" WC and 14" WC during stand-by (static) mode and while in operating (dynamic) mode at full output. If an in-
line regulator is used, it must be a minimum of 10 feet from the Phoenix. It is very important that the gas line is properly purged by the gas supplier or utility. Failure to properly purge the lines or improper line sizing, will result in ignition failure. This problem is especially noticeable in NEW LP
installations and also in empty tank situations. This can also occur when a utility company shuts off service to an area to provide maintenance to their lines. The gas valve must not be replaced with a conventional gas valve under any circumstances. As an additional safety feature in the Phoenix water heater, the gas valve in this appliance has a flanged connection to the swirl plate and blower.
(Nominal Iron Pipe Internal Length of Pipe (Feet)
Size Diameter (inches) (inches) 10 20 30 40 50 60 70 80 90 100 125 150 175 200
3/4 .824 278 190 152 130 115 105 96 90 84 79 72 64 59 55 BTU'S
1 1.049 520 350 285 245 215 195 180 170 160 150 130 120 110 100 PER
1 1/4 1.380 1,050 730 590 500 440 400 370 350 320 305 275 250 225 210
}
HOUR
1 1/2 1.610 1,600 1,100 890 760 670 610 560 530 490 460 410 380 350 320 x1,000
Page 20
19
PREPARATION / VENTING
PART 4: PREPARE WATER HEATER (CONTINUED)
E. DUNGS GAS VALVE
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL
A. INSTALLING EXHAUST VENT AND INTAKE AIR VENT
GAS VALVE
PRESSURE TAP INLET
settings.
or attempt to make any adjustment
analyzer.
: Do not remove this screwCAUTION
OFFSET ADJUSTMENT
to this screw without a combustion
PRESSURE TAP OUTLET
correspond to the chart in combustion
THROTTLE ADJUSTER
NOTE: If for any reason the throttle needs to be adjusted, it is very important that a "COMBUSTION ANALYZER" be used to ensure safe and proper operation. Turn the adjuster to the (+) to increase the gas supply or the (-) to decrease the gas supply. This adjustment will affect CO/CO% levels. Make sure the levels
GAS SHUT-OFF
VALVE
COMBUSTION
AIR
n
DANGER
The Phoenix must be vented as detailed in Venting section. Ensure the exhaust and intake piping comply with these instructions regarding vent system. Inspect finished combustion air intake and exhaust piping thoroughly to ensure all joints are well secured and airtight and comply with all applicable code requirements, as well as with the instructions provided in this manual. Failure to provide a properly installed vent system will cause severe personal injury or death.
Fig. 4-2
LP-179-P
3/13/07
n
WARNING
Do not do a gas conversion on this water heater without an officially approved conversion kit and instructions supplied by Heat Transfer Products, Inc.
Page 21
20
VENTING
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)
B. GENERAL
1. Install the water heater venting system in accordance with these instructions and with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, CAN/CGA B149, and/or applicable provisions of local building codes.
2. This water heater is a direct vent appliance and is listed as a Category IV appliance with Underwriters Laboratories, Inc. VENT AND INTAKE AIR VENT
C. APPROVED MATERIALS FOR EXHAUST VENT AND INTAKE AIR VENT
D. EXHAUST VENT AND INTAKE AIR VENT PIPE LOCATION
1. Determine exhaust vent location:
a. The vent piping for this water heater is approved for zero clearance to combustible
construction.
b. See illustration within this section of clearances for location of exit terminals of direct-vent
n
WARNING
Both exhaust and intake air vents must exit from the same side of the building to assure correct appliance operation.
n
WARNING
Do not use Foam Core Pipe in any portion of the exhaust piping from this water heater. Use of Foam Core Pipe may result in severe personal injury, death, or substantial property damage.
n
WARNING
This vent system will operate with a positive pressure in the pipe. Do not connect vent connectors serving appliances vented by natural draft into any portion of mechanical draft systems operating under positive pressure. Follow the venting instructions below carefully. Failure to do so may result in severe personal injury, death, or substantial property damage.
APPROVED VENTING MATERIAL
Item Material
Standards for Installation in:
United States Canada
Vent or air pipe and
fittings
PVC schedule 40/80 ANSI/ASTM D1785
CPVC and PVC venting must be
ULC-S636 Certified. IPEX is an
approved manufacturer in Canada
supplying vent material listed to
ULC-S636
PVC-DWV ANSI/ASTM D2665
CPVC schedule 40/80 ANSI/ASTM F441
Pipe cement/primer
PVC ANSI/ASTM D2564
IPEX System 636
Cements & Primers
CPVC ANSI/ASTM F493
Page 22
21
VENTING
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)
venting systems.
c. This water heater vent system shall terminate at least 3 feet (0.9 m) above any forced air intake
located within 10 ft (3 m). Note: this does not apply to the combustion air intake of a direct­vent appliance.
d. Provide a minimum of 1 foot distance from any door, operable window, or gravity intake into
any building.
e. Provide a minimum of 1 foot clearance from the bottom of the exhaust above the expected
snow accumulation level. Snow removal may be necessary to maintain clearance.
f. Provide 4 feet horizontal clearance from electrical meters, gas meters, gas regulators, relief
equipment, exhaust fans and inlets. In no case shall the exit terminal be above or below the aforementioned equipment unless the 4 foot horizontal distance is maintained.
g. When adjacent to a public walkway, locate exit terminal at least 7 feet above grade.
h. Do not locate the exhaust directly under roof overhangs to prevent icicles from forming.
i. Provide 4 feet clearance from the inside corner of vertical walls, chimneys, etc., as well as
horizontal corners created by roof overhangs.
2. Determine air intake vent location.
a. Provide 1 foot clearance from the bottom of the intake air vent and the level of maximum snow
accumulation. Snow removal may be necessary to maintain clearances.
b. Do not locate intake air vent in a parking area where machinery may damage the pipe.
c. When venting with a two pipe system, maximum distance between intake air vent and exhaust
vent is 6 feet (1.8 m). Minimum distance between exhaust vent and intake air vent on single water heater is 10” (0.255 m) center-to-center. Minimum distance between exhaust vents and intake air vents on multiple water heaters is 10” (0.255 m) center-to-center.
Page 23
22
VENTING
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)
Location of exit terminals of mechanical draft and direct-vent venting systems.
(Reference: National Fuel Gas Code ANSI Z223.1/NFPA 54 2002).
Fig. 5-2 Multiple Vent Spacing* *Note: Exhaust must extend out 1 foot. There should be no more than 2 vents and 2 intakes then a space of 36” to the
next set of vents. *Note: There must be a minimum of 36” spacing between every 2 kit grouping.
Multiple “V” Series Vents
Fig. 5-3 Multiple Stainless Steel Horizontal Vent Kit Installation – Front View
Fig. 5-1 Multiple Vents
Page 24
23
VENTING
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)
E. EXHAUST VENT AND INTAKE AIR VENT SIZING
1. The exhaust and intake vent size is 2" for the PH100 and PH130 and 3" for the PH199.
2. The total combined equivalent length of exhaust vent and intake air pipe should not exceed 85 feet.
a. The equivalent length of elbows, tees, and other fittings are listed in the Friction Loss Table 5-5.
b. For example: If the exhaust vent has two 90° elbows and 10 feet of PVC pipe we will calculate:
Exhaust Vent Pipe Equivalent Length = (2x5)+10=20 feet
Further, if the intake air vent pipe has two 90° elbows, one 45° elbow and 10 feet of PVC pipe, the following calculation applies:
Intake Air Vent Pipe Equivalent Length = (2x5)+3+10=23 feet
Finally, if a concentric vent kit is used we find:
Total Combined Equivalent Length = 20+23+3=46 feet
Therefore, the total combined equivalent length is 46 feet which is well below the maximum of 85 feet.
c. The intake air vent pipe and the exhaust vent are intended to penetrate the same wall or roof
of the building.
d. Effort should be made to keep a minimum difference in equivalent length between the intake
air vent pipe and the exhaust vent.
3. The minimum combined equivalent length is 16 equivalent feet.
F. LONGER VENT RUNS
1. The maximum combined equivalent length can be extended by increasing the diameter of both exhaust vent and intake air vent pipe equally. However, the transitions should begin a minimum of 15 equivalent feet from the water heater.
a. The maximum equivalent length for the increased diameter vent pipes is 125 feet.
Table 5-5
*Friction loss for long radius elbow is 1 foot less.
FRICTION LOSS EQUIVALENT IN PIPING AND FITTINGS
FITTINGS OR PIPING EQUIVALENT FEET
2" 3" 4"
90 DEGREE ELBOW* 5' 5' 3'
45 DEGREE ELBOW 3' 3' 1'
COUPLING 0' 0' 0'
AIR INLET TEE 0' 0' 0'
STRAIGHT PIPE 1' 1' 1'
CONCENTRIC VENT KIT 3' 3' N/A
V500 2" VENT KIT 1' N/A N/A
V1000 3" VENT KIT N/A 1' 1'
V2000 4" VENT KIT N/A 1' 1'
Page 25
24
VENTING
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)
b. Transitions should always be made in vertical sections of pipe to prevent the condensate from
pooling in the vent pipe.
c. If the transition occurs at a distance greater than 15 equivalent feet from the water heater, the
maximum equivalent length will be reduced. See Table 5-7.
G. EXHAUST VENT AND INTAKE AIR PIPE INSTALLATION
1. Use only solid PVC or CPVC pipe. FOAM CORE PIPING IS NOT APPROVED. Refer to chart Section 5-C.
2. Remove all burrs and debris from joints and fittings.
3. All joints must be properly cleaned, primed, and cemented. Use only cement and primer approved for use with the pipe material. Cement must conform to ASTM D2564 for PVC and ASTM F493 for CPVC pipe.
4. Horizontal lengths of exhaust vent must slope back towards the water heater not less than ¼" per foot to allow condensate to drain from the vent pipe. If the exhaust pipe must be piped around an obstacle that results in the creation of a low point, condensate will collect in this low point and form a blockage. This condensate must be drained away using a field-installed condensate drain assembly as shown. (See Fig. 1 Section 5)
5. All piping must be fully supported. Use pipe hangers at a minimum of 4 foot intervals to prevent sagging of the pipe where condensate may form.
6. Do not use the water heater to support any piping.
7. A screened straight coupling is provided with the water heater for use as an outside exhaust termination.
Table 5-7: Vent Termination Kits
TEL = Total Equivalent Length
Table 5-6: Vent Run Transition
Vent
Connection
Reducing Coupling
Vent
Transition
2" 3" x 2" 3"
3" 4" x 3" 4"
Transition
Point
(ft from
water heater)
TEL of
Standard
2" Vent
Pipe (ft)
TEL of Oversized 2", 3" or 4"
Vent Pipe (ft)
Maximum
TEL of all
Vent Pipe (ft)
15 30 95 125
20 40 77-1/2 117-1/2
25 50 60-1/2 110-1/2
30 60 43 103
35 70 26 96
40 80 8-1/2 88-1/2
None 85 0 85
n
WARNING
All joints of positive pressure vent systems must be sealed completely to prevent leakage of flue products into the living space.
Page 26
25
VENTING
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)
8. A screened inlet air tee is provided with the water heater to be used as an outside intake termination.
9. The following information on Table 5-8 lists optional intake air/exhaust vent terminations available from Heat Transfer Products, Inc.
H. WATER HEATER REMOVAL FROM A COMMON VENT SYSTEM
At the time of removal of an existing water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to common venting system are not operating.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch to determine if there is block­age, leakage, corrosion or other deficiencies that could cause an unsafe condition.
3. If practical, close all building doors, windows and all doors between the space in which the appliance remains connected to the common venting system located and other spaces in the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, at maximum speed. Do not operate a summer exhaust fan. Close all fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle or smoke from a cigarette.
6. After it has been determined that each appliance remaining connected to common venting system properly vents when tested as outlined, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z 223.1
I. CONDENSATE REMOVAL SYSTEM
This is a condensing high efficiency appliance, therefore this unit has a condensate removal system. Condensate is water vapor derived from the combustion products, similar to an automobile when it is initially started. It is very important that the condensate line is sloped away from the boiler and down to a suitable inside drain, if the condensate outlet on the water heater is lower than the drain, you must use a condensate removal pump (kit P/N 554200 available from Heat Transfer Products, Inc.) A condensate filter, if required by local authorities can be made up of lime crystals, marble or phosphate chips that will neutralize the condensate. This can be done in the field by the installer or you may purchase one from Heat Transfer Products, Inc. (P/N N1100) It is also very important that
Table 5-8: Vent Termination Kits
Description Stock Code
2" PVC Concentric Vent Termination Kit KGAVT0501CVT 3" PVC Concentric Vent Termination Kit KGAVT0601CVT
2" Stainless Steel Vent Termination Kit V500 3" Stainless Steel Vent Termination Kit V1000
4" Stainless Steel Vent Termination Kit V2000
Page 27
26
VENTING
PART 5: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)
the condensate line is not exposed to freezing temperatures, or any other type of blockage. Plastic tubing must be the only material used for the condensate line. Steel, brass, copper or others will be subject to corrosion or deterioration. A second vent may be necessary to prevent condensate line vacuum lock if a long horizontal run is used. Also, an increase in pipe size may be necessary to drain properly. Support of the condensation line may be necessary to avoid blockage of the condensate flow.
NEUTRALIZER PART# N1100
CONDENSATE
CONDENSATE LINE
LITTLE GIANT CONDENSATE PUMP PART# 554100
CONDENSATE LINE WITH PUMP
TO DRAIN
CONDENSATE NEUTRALIZER PART# N1100
TO DRAIN
OF BLOCKAGE.
1. CONDENSATE LINE MUST BE PITCHED AT LEAST 1/4" PER FOOT TO PROPERLY DRAIN. IF THIS CANNOT BE DONE OR A VERY LONG LENGTH OF CONDENSATE HOSE IS USED YOU MUST INCREASE THE CONDENSATE LINE TO A MINIMUM OF 1" ID AND PLACE A TEE IN THE LINE AFTER THE CONDENSATE NEUTRALIZER TO PROPERLY REDUCE VACUUM LOCK IN THE DRAIN LINE.
2. PLASTIC PIPE SHOULD BE THE ONLY MATERIAL USED FOR THE CONDENSATE LINE. STEEL, BRASS, COPPER OR OTHERS WILL BE SUBJECT TO CORROSION OR DETERIORATION.
3. IT IS ALSO VERY IMPORTANT THAT THE CONDENSATE LINE IS NOT EXPOSED TO FREEZING TEMPERATURES, OR ANY OTHER TYPE
NOTES:
CAUTION
The condensate line must remain unobstructed, allowing free flow of condensate. If condensate is allowed to freeze in the line or if the line is obstructed in any other manor, condensate can exit from the water heater tee, resulting in potential water damage to property.
NOTICE
Use materials approved by the authority having jurisdiction. In the absence of other authority, PVC and CPVC pipe must comply with approved venting material chart in Section 5-C. When installing a condensate pump, select one approved for use with condensing boilers and furnaces. The pump should have an overflow switch to prevent property damage from condensate spillage. Condensate from the Phoenix will be slightly acidic (typically with a pH from 3.2 to 4.5). Install a neutralizing filter if required by local codes.
Fig. 1
INSTALLATION OF CONDENSATE NEUTRALIZER/PUMP
LP-179-K
4/13/07
Page 28
27
VENTING
EXTERIOR WALL
INTAKE
EXHAUST
LEFT SIDE VIEW
SUPPORT BRACKETS MUST BE USED ON ALL HORIZONTAL AND VERTICAL PIPING
1"
MIN.
MIN.
12"
IS GREATER (TYP)
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE WHICHEVER
AND VERTICAL PIPING
SUPPORT BRACKETS
EXHAUST
LEFT SIDE VIEW
INTAKE LEG MUST BE FACING UP
IMPORTANT:
MUST BE USED ON ALL HORIZONTAL
EXTERIOR WALL
INTAKE
CONCENTRIC VENT KIT
PART# KGAVT0501CVT - 2"
KGAVT0601CVT - 3"
MIN.
1"
IS GREATER (TYP)
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE, WHICHEVER IS
ALL HORIZONTAL
LEFT SIDE VIEW
MUST BE USED ON
EXHAUST
V1000 - 3"
AND VERTICAL PIPING
EXTERIOR WALL
V2000 - 4"
VENT KIT
PART# V500 - 2"
SUPPORT BRACKETS
IS GREATER.
MAINTAIN 12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE, WHICHEVER
10'-0" MIN.
WHICHEVER IS GREATER
12" OVER MAXIMUM
SNOW LEVEL OR 24"
AND COUPLING (EXHAUST)
INTAKE
ROOF VENT WITH TEE (INTAKE)
EXHAUST
SUPPORT BRACKETS MUST BE USED ON ALL HORIZONTAL AND VERTICAL PIPING
LEFT SIDE VIEW
24" MIN.
10'-0" MIN.
GREATER
12" OVER MAXIMUM SNOW LEVEL OR 24"
WHICHEVER IS
NOTE: EXTENDED VENT RUNS WHEN
TRANSITIONING TO A LARGER DIAMETER
MUST ALWAYS TAKE PLACE IN A VERTICAL
POSITION TO PREVENT CONDENSATE
BLOCKAGE.
ROOF VENT WITH
LEFT SIDE VIEW
AND VERTICAL PIPING
MUST BE USED ON ALL HORIZONTAL
CONCENTRIC VENT KIT
SUPPORT BRACKETS
CONCENTRIC VENT KIT PART# KGAVT0501CVT - 2" KGAVT0601CVT - 3"
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the appliance and the balance at 4 foot invervals on the vent pipe.
J. DIAGRAMS FOR VENTING
SIDEWALL VENTING WITH KIT
SIDEWALL VENTING WITH TEE (INTAKE) AND
COUPLING (EXHAUST)
SIDEWALL VENTING WITH
CONCENTRIC VENT KIT
ROOF VENT WITH TEE (INTAKE)
AND COUPLING (EXHAUST)
ROOF VENT WITH
CONCENTRIC VENT KIT
HORIZONTAL VENTING
A - FOR EVERY 1" OF OVER-
HANG THE EXHAUST VENT MUST BE LOCATED 1” VERTICAL BELOW OVERHANG (OVER­HANG MEANS TOP OF BUILD­ING STRUCTURE AND NOT TWO ADJACENT WALLS [CORNER OF BUILDING]).
B - 12" SEPARATION BETWEEN BOTTOM OF EXHAUST OUTLET AND TOP OF AIR INTAKE (TYP.)
C - MAINTAIN 12" MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER (TYP.)
D - MINIMUM 12" BETWEEN VENTS WHEN INSTALLING MULTIPLE VENTS
E. 12" MIN. BEYOND INTAKE
L
NOTE: EXTENDED VENT RUNS WHEN
TRANSITIONING TO A LARGER DIAMETER
MUST ALWAYS TAKE PLACE IN A VERTICA
POSITION TO PREVENT CONDENSATE
BLOCKAGE.
HORIZONTAL VENTING
E
C
SINGLE BOILER
A
D
MULTIPLE BOILERS
Page 29
28
VENTING
PART 6. START-UP PROCEDURE
FOR YOUR OWN SAFETY READ BEFORE OPERATING
1. This appliance does not have pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
2. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas suppliers'
instructions.
• If you cannot reach your gas supplier, call the fire department.
3. Turn on gas shutoff valve (located inside of the down near burner) so that the handle is aligned with the gas pipe. If the handle will not turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
4. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
5. The Phoenix shall be installed so the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, condensate trap, control replacement, etc.)
A. OPERATING INSTRUCTIONS
If you smell gas, STOP. Follow listed safety instructions above. If you do not smell gas, follow the next steps.
1. Turn on all electric power to appliance. Make sure tank is full with cold water and purge all piping. To assure adequate purging, open all hot water faucets.
2. Adjust the temperature setpoint of the Phoenix if desired. The factory default setting is 119°. If changes are ncessary follow “Overall Appliance and Control Operation” in this section.
3. If the appliance fails to start, refer to the Troubleshooting section in the back of this manual.
B. OVERALL APPLIANCE AND CONTROL OPERATION
To adjust temperature of the stored water press and hold {S3} for 2 seconds. The first item is: DU: Water Temperature Set Point – factory set at 119°F, adjustable down by pressing S1 key to 70°F and adjustable up by pressing the {S2} key up to 159°F. The {S3} key is then pressed again momentarily to display DH, the differential which is factory set at 7°F and adjustable down to 1°F by pressing the {S1} key and up to 18°F by pressing the {S2} key. Note: Due to the highly advanced control on this appli­ance which compensates for varying inlet water temperature, the actual differential temperature
n
DANGER
Water temperature over 125 degrees F. can cause severe burns instantly, or death from scalds. Children, disabled, and elderly are at highest risk of being scalded. See instruction manual before setting temperature at water heater. Feel water before bathing or showering! Temperature limiting valves are available.
Page 30
29
VENTING
seen may vary slightly from your setting. The {S3} key is then pressed again momentarily to display the choice of Fahrenheit “F” factory default or Celsius by pressing the {S1} key. When finished, press the {S3} key one final time to place unit back into operation. The control automatically re-starts if no key is pressed for 2 minutes.
C. STATUS MENU
Installers are also able to check the current status of the Phoenix parameters by pressing {S4/RESET} key for 3 seconds. Once activated, the display will show |d1| alternating value of the actual upper sup­ply tank temperature. Actual values are displayed for each function. To view the next value simply press the {S/4} key to go to the next displayed value. Listed below are the values which can be dis­played. These values cannot be changed. To exit this menu, simply press {S3/Program} key to resume normal operation.
Function Value
d1 — Actual Temperature from upper tank sensor d2 — Actual Temperature from lower tank sensor d3 — |0| (Not used) d4 — |308| (Not used)
Function Value
d5 — |nc| (Not used) d6 — Actual Fan speed multiplied by 10 (Example: If fan speed displayed is
|410| RPM x 10 = 4100 actual fan speed)
d7 — Actual Ionization current read from Flame Rectification probe d8 — |0| (Not used) d9 — |1| (Not used) d10 — Actual Status bus communication
|co| = connected, |nc| = not connected
d11 — |32| (Not used) d12 — Power On Hours (Example: Hours x 1000 Ex. 0.1 = 100 hrs. or 1.0 = 1000 hrs. d13 — Total Water Heating Hours (TW – Hrs. x 1000) d14 — |0| (Not used) d15 — Passed Ignition Attempts (Passed ignition x 1000)
D. TEST MODE
This function is intended to simplify the gas valve adjustment if needed. Listed below are the recom­mended limits on each Phoenix Water Heater and the Combustion Settings. Automatic modulation does not take place when the controller is in Test mode, only temperature limitation based on the Phoenix set point. The user will be allowed to increase or decrease the fan speed by pressing in either the {S1/
-
or {S2/+} keys. To activate the Test mode simply press the {S2/+} and {S3/Program} key together for 1 second. Once ac-
tivated, you will see in the display {Ser} and the actual fan speed. The measurement of the combustion levels should always be taken at the highest and lowest fan speed. After 10 minutes, the Test mode stops automatically. To exit Test Mode press {S1/
-
} and {S2/+} key together for 1 second.
PART 6. START-UP PROCEDURE (CONTINUED)
Page 31
30
VENTING
E. MAINTENANCE
The control system requires no periodic maintenance under normal conditions. However, in unusually dirty or dusty conditions, periodic vacuuming of the cover to maintain visibility of the display and indicators is recommended. In dirty environments, construction sites, building constructions, care must be taken to keep the appliance burner cover in place and drywall or saw dust away from appliance.
COMBUSTION SETTINGS
HIGH FIRING RATES and LOW FIRING RATES ON ALL MODELS
Natural Gas Propane LP
low high low high
Carbon Monoxide
(CO%)
0–10 ppm 0 ppm–20 ppm 0–10 ppm 0 ppm–20 ppm
Carbon Dioxide
(CO2%)
8½% – 9½% 8½% – 9½% 9½% – 10½% 9½% – 10½%
Fig. 6-1
Fig. 6-2
PART 6. START-UP PROCEDURE (CONTINUED)
n
CAUTION
In unusually dirty or dusty conditions, care must be taken to keep appliance burner
door in place at all times. Failure to do so VOIDS WARRANTY!
FAN SPEEDS
BTU IGNITION MIN MAX
100,000 3000 2000 5400
130,000 3000 2000 6950
199,000 3000 2000 8500
n
WARNING
Do not do a gas conversion on this water heater without an officially approved conversion kit and instructions supplied by Heat Transfer Products, Inc. Failure to do so could result in death or serious injury.
Page 32
31
WIRING
F. INTERNAL WIRING
PART 6. START-UP PROCEDURE (CONTINUED)
Phoenix
Connector Diagram
Page 33
32
SHUTDOWN / TROUBLESHOOTING
PART 7: SHUTDOWN
A. SHUTDOWN PROCEDURE
If the burner is operating, lower the set point value to 70 degrees F. and wait for the burner to shut off. Continue to wait for the combustion blower to stop so all latent combustion gases are purged from the system. This should take a maximum of 40 to 90 seconds. Disconnect the electrical supply. If the burner is not operating, disconnect the electrical supply.
B. VACATION PROCEDURE
If there is danger of freezing, change the set point to 70 degrees F. DO NO
T turn off electrical
power. If there is no danger of freezing, follow the "Shutdown Procedure".
C. FAILURE TO OPERATE
Should the burner fail to light, the control will perform two more ignition trials prior to entering a lockout state. Note that each subsequent ignition trial will not occur immediately. After a failed igni­tion trial, the blower must run for approximately 10 seconds to purge the system. Therefore, a time period of approximately 40 to 90 seconds will expire between each ignition trial. If the burner lights during any one of these three ignition trails, normal operation will resume. If the burner lights, but goes off in about 4 seconds, check the polarity of the wiring. See electrical connection section in Part 4. If the burner does not light after the third ignition trial, the control will enter a lockout state. This lock­out state indicates that a problem exists with either the appliance, the controls, or the gas supply. Under such circumstances, a qualified service technician should be contacted immediately to prop­erly service the appliance and correct the problem. If a technician is not available, depressing the {S4/RESET} button once will remove the lockout state so additional trials for ignition can be per­formed. The unit will try to re-light once every 6 minutes.
PART 8: TROUBLESHOOTING
A. PHOENIX ERROR CODE
An error code may occur in the installation of the Phoenix. This condition may lead to a lock out condition of the controller, which will need to be manually reset through the {S4/RESET} button. These temporary codes will help the installer correct the problem before going into a lock out condition, which will require a manual reset.
B. PHOENIX ERROR
1. When an error condition occurs the controller will display an error code on the display module.
2. These error codes and several suggested corrective actions are included in Table 8-2.
3. In the case of |E00|, |E13|, and |E14| this error, if uncorrected, will go into a fault condition as described
in Paragraph C.
C. PHOENIX LOCKOUT
1. When a fault condition occurs the controller will illuminate the red “fault” indication light and display
a fault code in the format (Example: |F00|) on the display module.
2. Note the fault code and refer to Table 8-3 for an explanation of the fault code along with several suggestions for corrective actions.
3. Press the reset key to clear the fault and resume operation. Be sure to observe the operation of the unit to prevent a recurrence of the fault.
Page 34
33
TROUBLESHOOTING
n
CAUTION
This appliance has wire function labels on all internal wiring. Observe the position of each wire before removing it. Wiring errors may cause improper and dangerous operation. Verify proper operation after servicing.
n
WARNING
When servicing or replacing any components of this water heater be certain that:
• The gas is off.
• All electrical power is disconnected
n
WARNING
Do not use this appliance if any part has been under water. Improper or dangerous operation may result. Contact a qualified service technician immediately to inspect the heater and repair or replace any part of the water heater which has been under water.
n
DANGER
When servicing or replacing components that are in direct contact with the heater water, be certain that:
• There is no pressure in the heater. (Pull the release on the relief valve to relieve pressure in the water heater.)
• The heater water is not hot
• The electrical power is off
PART 8: TROUBLESHOOTING (CONTINUED)
Page 35
34
TROUBLESHOOTING
PART 8: TROUBLESHOOTING (CONTINUED)
Code Description Duration Corrective Action
E13
Combustion Fan Speed Low. The combustion air fan speed less than 70% of expected.
60 Sec.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
E14
Combustion Fan Speed High. The combustion air fan speed is more than 130% of expected.
60 Sec.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
LE0
Water level in tank is low
Until
Corrected
1. Be sure all air is bled from system.
2. Inspect low level switch and wiring for damage and repair as necessary.
FLU
Blocked Vent Pressure Switch Open
Until
Corrected
1. Assure that the vent is not blocked
2. Check the blocked vent pres­sure switch operation by applying a jumper. (If the switch is not function­ing properly, replace it.)
LOU
24 volt low
Until
Corrected
1. Check line voltage. Must be between 100-128 volts.
2. If available, connect PC and using HTP service software check the 24v supply display in the lower left corner of the screen. The number displayed here must be greater than 128 and should be greater than
250. Use this as a troubleshooting guide as you follow the steps below.
3. Remove 10 pin Molex connector from customer connection board. If LOU code clears, then the problem is with external sensor wiring. Examine external sensor wiring for shorts to ground repairing as necessary. If LOU code is still present and the boiler is so equipped, disconnect high gas pressure switch, then low gas pressure switch, then UL 353 low water cutoff in this order one at a time to see if LOU code clears. Replace faulty part. Check low voltage wire harness in boiler for shorts to ground.
4. If LOU only occurs when burner tries to light, check gas valve for excessive current draw.
5. If LOU is present with the low voltage harness disconnected from the 926 control board, replace the 926 control board.
Table 8-2: 926 Control Board Error CodesTable 8-1:Phoenix Resistance Table for Supply Temperature Sensor
Phoenix Resistance Table for
Supply Temperature Sensor
High/Low Temp.
Sensor Temp. (°F)
Resistance
(ohms)
32 32550
41 25340
50 19870
59 15700
68 12490
77 10000
86 8059
95 6535
104 5330
113 4372
122 3605
131 2989
140 2490
149 2084
158 1753
167 1481
176 1256
185 1070
194 915
202 786
212 667
Page 36
35
TROUBLESHOOTING
Code Description Remedy
F00
High temperature switch limit exceeded (194°)
1. Try reset, if F00 repeats, create a demand for hot water (n DANGER: use caution to prevent burn injury) If
water is above 194° test upper and lower temperature sensor with an ohmmeter. (Refer to resistance chart,
this section.) Replace bad sensor. If water is below 194° test high temperature switch and wiring with ohmmeter. Switch should be closed at this point, if not, replace switch.
2. If unit did reset successfully, let the PHOENIX run and go into the status menu to check the upper and lower temperature sensor. If either reading displayed does not make sense, check appropriate sensor with ohmmeter. (Refer to resistance chart this section.) Replace bad sensor. Do an OHMs reading on both sensors to check continuity.
F01
Vent temperature limit exceeded
1. Inspect all flue piping. If the flue is damaged or shows signs of overheating then repair or replace the flue parts as necessary before proceeding.
2. If the flue piping system is intact, not damaged and there is no sign of the flue overheating such as discoloration or melting, then push the red reset button on the flue switch.
3. Be sure the Phoenix is connected to a water supply and full of water.
4. Push the RESET button on the Phoenix control panel. The appliance should light. If the appliance lights proceed to step 5. If the appliance does not light and the display again begins to flash F01, inspect the wiring to the flue switch, repairing or replacing as necessary. If the wiring is intact, replace the flue switch using care to mount the new flue switch in the same position and mounting holes as the old one. If the display flashes a code other than F01, follow the troubleshooting guide for that code.
5. Observe operation for 5 minutes. Place the probe of an exhaust analyzer into the flue system within 6 feet of the Phoenix appliance. The exhaust temperature should not rise above 190 Deg. F after several minutes of operation.
6. If the flue temperature is below 190 Deg. F and the appliance again goes into lockout displaying F01, replace the flue switch using care to mount the new flue switch in the same position and mounting holes as the old one. If the display flashes a code other than F01, follow the troubleshooting guide for that code.
7. If the flue temperature increases to over 190 Deg. F, Consult the HTP factory for further assistance.
F02
Interrupted or shorted upper temperature sensor
Check the electrical connection to the appropriate temperature sensor, if connection is okay, replace bad sensor.
F03
Interrupted or shorted lower temperature sensor
F05
Upper temperature sensor exceeds 194°F
If water in tank is not greater than 194°F, check wiring and repair if faulty. If the wiring is okay, check appropriate sensor with ohmmeter and compare to reading in resitance chart. If reading does not agree with water temperature, replace bad sensor.
F06
Lower temperature sensor exceeds 194°F
F09
No flame detected – The Phoenix will make three attempts at ignition before the control goes into this lockout condition. Will reset in 1 hour.
1. Watch the igniter through the observation window provided.
2. If there is no spark, check the spark electrode for the proper ¼” gap.
3. Remove any corrosion from the spark electrode and flame rectifier probe.
4. If there is a spark but no flame, check the gas supply to the water heater.
5. If there is a flame, check the flame sensor.
6. Check any flue blockage or condensate blocks.
F10
Loss of Flame Signal – The Phoenix will relight 4 times before the control goes into this lockout condition. Will reset in 1 hour.
1. Monitor the gas pressure to the unit while in operation.
2. Assure that the flame is stable when lit.
3. Check to see if the green light on the display module is out while the water heater is running.
4. If the green light doesn’t come on or goes off during operation check the flame signal on the status menu.
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.
6. If the flame rectifier probe continues to read low, replace it.
F11
False Flame Signal – The water heater will lock out if it senses a flame signal when there should be none present.
1. Turn the gas off to the unit at the service valve.
2. If the flame signal is still present replace the igniter.
3. If the flame signal is not present after turning off the gas supply, check the gas valve electrical connection.
4. If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or replace the gas valve.
5. Turn the gas on at the service valve after corrective action is taken.
F13
Combustion Fan Speed Incorrect – The water heater will lock out if it senses that the fan speed is less than 70% of expected rate for more than 60 seconds.
1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.
Table 8-3: 926 Control Board FAULT Codes
PART 8: TROUBLESHOOTING (CONTINUED)
NOTE: IF YOU REPLACE A PART TO REMEDY A FAULT, IT IS RECOMMENDED THAT YOU CYCLE
THE UNIT AT LEAST THREE OR FOUR TIMES TO ASSURE THE FAULT HAS BEEN RESOLVED.
Page 37
36
TROUBLESHOOTING
G
F
E
K
FRONT
LINE
GAS
VENT
EXHAUST
INTAKE
AIR
CONDENSATE
LINE
RIGHT SIDE
H
INLET
SENSOR
LOWER TEMP
SENSOR
UPPER TEMP
SAFETY
HIGH LIMIT
HOT WATER OUTLET
COLD WATER
LOW WATER CUT-OFF
LEFT SIDE
B
C
DA
TEMP/PRESSURE
RELIEF VALVE
AUX. CONNECTION
AUX. CONNECTION
L
M
J
*ALL DIMENSIONS ARE APPROXIMATE, A SUFFIX OF "LP" DENOTES PROPANE GAS
PHOENIX WATER HEATER AND SANITIZER BOOSTER DIMENSIONS
MODEL*
(SEE ADDITIONAL NOTE )
GAL. A B C D E G F H J
K
LM
PH100-55/130-55/199-55 55 23" 52" 45" 5" 13-1/4" 6" 9-3/4" 3-7/8" 45" 36" 13" 45"
PH100-80/130-80/199-80 80 23" 72" 64" 5-3/4" 15-1/4" 6" 11-3/4" 5-7/8" 64" 36" 13" 64"
PH100-119/130-119/199-119 119 27" 74" 65" 7-1/2" 17" 10-1/8" 13-1/2" 7-1/2" 66" 40" 14-1/4" 66"
PH130-55SA / PH199-55SA 55 23" 52" 45" 5" 13-1/4" 6" 9-3/4" 3-7/8" 45" 36" 13" 45"
PHOENIX WATER HEATER SPECIFICATIONS
MODEL*
SEE
ADDITIONAL
NOTE
BTU'S
AIR INTAKE/
EXHAUST
VENT SIZE
INLET/
OUTLET
SIZE
AUXILIARY
CONN.
GAS
LINE
CONN.
SYSTEM
RELIEF
PIPE SIZE
SHIPPING
WEIGHT
MAX.
TEMPERATURE
LIMIT
PH100-55 100,000 2" 1" NPT
1"
3/4" 3/4"
175 LBS.
160
PH130-55 130,000 2" 1" NPT
1"
3/4" 3/4"
175 LBS
160
PH199-55 199,000 3" 1" NPT
1"
3/4" 3/4"
175 LBS
160
PH100-80 100,000 2" 1-1/2" NPT
1"
3/4" 3/4"
235 LBS.
160
PH130-80 130,000 2" 1-1/2" NPT
1"
3/4" 3/4"
235 LBS
160
PH199-80 199,000 3" 1-1/2" NPT
1"
3/4" 3/4"
235 LBS
160
PH100-119 100,000 2" 1-1/2" NPT
1"
3/4" 3/4"
405 LBS.
160
PH130-119 130,000 2" 1-1/2" NPT
1"
3/4" 3/4"
405 LBS.
160
PH199-119 199,000 3" 1-1/2" NPT
1"
3/4" 3/4"
405 LBS.
160
PHOENIX SANITIZER BOOSTER SPECIFICATIONS
PH130-55SA 130,000 2" 1" NPT
1"
3/4" 3/4
175 LBS
184
PH-199-55SA 199,000 3" 1"
1"
3/4" 3/4
175 LBS
184
LP-179-B
10/5/09
Page 38
37
TROUBLESHOOTING
LP-179-J
12/3/08











,7(0
7(03(5$785($1'35(6685(5(/,()9$/9(
39&3/8*
39&7(( 3
137[+26(%$5%
&21'(16$7(+26(
&$%/(&/$03
/2&.,1*&/$03&RQGHQVDWH+RVH
7+(502',6&)/8((&2
+26(%$5%[%ORFNHG9HQW3UHVVXUH6ZLWFK

3/$67,&78%,1*,'%ORFNHG9HQW3UHVVXUH6ZLWFK

75$3$'$37(5

$,5,1/(7$'$37(5%7821/<

/2:(57(03(5$785(6(1625 3

61$3%86+,1*

833(57(03(5$785(6(1625

/2::$7(5&872))6(1625352%(

+,*+/,0,76$)(7<
'(6&5,37,21
3$57
73
3
3 3
3
3
3
3
3

)

3
3
3
Page 39
38
TROUBLESHOOTING
LP-179-H
REV. 10/6/09
24
23
22
20
21
18
17
19
16
2526
27
29
28
30
31
32
2
2
15
14
13
12
7
11
ITEM
#
COMBUSTION BLOWER KIT
1
(includes items 2, 3 & 4)
2 GASKET - Blower 7100P-037 18 GASKET - Sight Glass 7100P-021
3 GAS VALVE ADAPTER PLATE 7100P-035 19 OUTER GASKET - Sight Glass 7100P-023
M5 x 12MM PHILLIPS COUNTERSUNK SCREW -
4
Gas Valve Adapter Plate
5 GAS VALVE KIT (includes items 6, 7, 8 & 9) 7100P-039 (100/130 BTU) 21
6 HOUSING COVER - Swirl Plate 7100P-016 23 GASKET - Mounting Plate 7100P-026
7 SWIRL PLATE 7100P-042 (100/130 BTU) 24 MOUNTING PLATE 7100P-027
8 HOUSING - Swirl Plate 7100P-017 26 GASKET - Spark Electrode 7100P-028
M4 x 20MM PHILLIPS HEAD SCREW -
9
Gas Valve
10 BLOCKED VENT PRESSURE SWITCH 7250P-150 28 BURNER KIT (includes item 29) 7100P-032 (100/130 BTU)
11 TUBE - Air Inlet 7100P-018 7100P-031 (199 BTU)
12 GAS VALVE PIPING ASSEMBLY 7100P-020 29 INNER GASKET - Burner 7100P-030
WIRING HARNESS to Tank Sensors
13
(not shown)
CONTROL BOARD (Note: You must specify
14
the Model Number of your unit when ordering.
WIRING HARNESS to Control Board
15
(not shown) CONTROL BOARD DISPLAY
16
(w/Ribbon Cable)
DESCRIPTION PART #
5
9
7100P-015 17
7250P-484 20
7100P-040 (199 BTU) 22 GASKET - Flame Rectification Probe 7100P-028
7100P-092 (199 BTU) 25
7250P-717 27
7100P-013 (55 GAL.) 30 OUTER GASKET - Burner 7100P-011
7100P-014 (80/119 GAL.) 31 ADAPTER MANIFOLD 7100P-033
7350P-008 32
7100P-001 33 M8 FLANGED NUT 7100P-085
7100P-009 34 BURNER COVER 7100P-038
10
6
4
8
ITEM
#
SIGHT GLASS KIT (includes items 18 & 19)
FLAME RECTIFICATION PROBE (includes items 21 & 22)
M4 x 12 SOCKET HEAD CAP SCREW ­w/M4 Lock Washer
SPARK ELECTRODE (includes items 26 & 27)
M4 x 12 SOCKET HEAD CAP SCREW, w/M4 Lock Washer
M8 BRASS NUT, SS LOCK WASHER, FLAT WASHER
33
1
3
DESCRIPTION PART #
34
7100P-022
7100P-024
N/A
7100P-029 7100P-081 (LP ONLY)
N/A
7100P-034
Page 40
39
TROUBLESHOOTING
WATER HEATER INSPECTION AND MAINTENANCE SCHEDULE
Inspection Activities
Piping 1st Year 2nd Year 3rd Year 4th Year*
Near Heater Piping Check heater and system piping for any sign of leakage, make sure they are properly supported
Vent Check condition of all vent pipe and joints
Gas Check gas piping, test for gas leaks and signs of aging, make sure all pipes are supported properly.
System
Visual Do a full visual inspection of all system components
Functional Test all functions of the system (Heat, Safeties)
Temperatures Verify safe settings on water heater or Anti-Scald Valve
Temperatures Verify temperature settings programmed
Electrical
Connections Check wire connections, make sure they are tight
Smoke and CO detector Verify devices are installed and working properly, change batteries if necessary
Circuit breakers Check to see that the circuit breaker is clearly labeled, exercise circuit breaker
Chamber and Burner
Combustion Chamber
Check burner tube, and combustion chamber coils, clean according to maintenance section of
manual, also vacuum combustion chamber
Spark Electrode Clean with Scotch-Brite , Set gap at 1/4" (see Fig 14-2 Part 14 in Troubleshooting section)
Flame Probe
Clean with Scotch-Brite, Check ionization in µA (d7 on status menu in Start-up Procedures) record
high fire and low fire
* NOTE : CONTINUE MAINTENANCE BEYOND THE 4TH YEAR IS REQUIRED ON A YEARLY BASIS.
Date last completed
Page 41
40
TROUBLESHOOTING
WATER HEATER INSPECTION AND MAINTENANCE SCHEDULE (CONTINUED)
Condensate 1st Year 2 Year 3 Year 4 Year*
Condensate Neutralizer Check condensate neutralizer, replace if necessary
Condensate Hose
Disconnect condensate hose, clean out dirt, fill with water to level of outlet and re-install (Note: you must
verify the flow of condensate, making sure that the hose is connected properly during final inspection.)
Gas
Pressure Measure incoming gas pressure (from 3.5" to 14" W.C.)
Pressure Drop Measure drop in pressure on light off (no more than 1" W.C.)
Check gas pipe for leaks Check piping for leaks, and verify they are all properly supported
Combustion
Check CO/CO2 Levels
Check levels of CO and CO2 in Exhaust (See Fig. 6-1 in Startup Procedure for ranges) record at high
and low fire
Safeties
ECO (Energy Cut Out) Check continuity on Flue and Water ECO, replace if corroded
Water Pressure Switch Check operation , check for signs of leakage, replace if corroded
Thermistors Check wiring, verify through ohms reading
Final Inspection
Check List
Verify that you have completed the entire check list WARNING: FAILURE TO DO SO COULD RESULT
IN DEATH OR SERIOUS INJURY.
Homeowner Review, with the homeowner what you have done
* NOTE : CONTINUE MAINTENANCE BEYOND THE 4TH YEAR IS REQUIRED ON A YEARLY BASIS.
Date last completedInspection Activities
Page 42
41
Page 43
42
Page 44
© 2004–2009 Heat Transfer Products, Inc. www.htproducts.com LP-179 REV. 10/6/09
Loading...