Phoenix Advanced pressure monitor II Installation Manual

Page 1
Advanced Pressure Monitor II and Central Display Rough-In Installation Guide
Page 2
Copyright 2011, 2012, 2013 Phoenix Controls
Accel, Phoenix, Phoenix Controls, Usage Based Controls, UBC, Celeris, Theris, Traccel, Zone Presence Sensor and ZPS are registered trademarks, and LabPro, MacroServer, MicroServer and Neutralizer are trademarks of Honeywell International, Inc.
Phoenix Controls products are covered by one or more of the following U.S. patents: 5,251,665 5,304,093 5,545,086 D642894 and other patents pending.
The material in this document is for information purposes only and is subject to change without notice. Phoenix Controls assumes no responsibility for any errors or for consequential damages that may result from the use or misrepresentation of any of the material in this publication.
BACnet is a registered trademark of the American Society of Heating, Refrigerating, and Air­Conditioning Engineers (ASHRAE).
Printed in USA
Page 3
APM2 Rough-In Installation Guide
Table of Contents
Section 1. Advanced Pressure Monitor II Rough-In Installation
1.1 Required Parts to be Supplied by the Installer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Parts Included with Your Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Installation Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.1 Wiring Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.2 Wiring Triple Gang Electrical Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.3 Plumbing Rough-In. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.4 Use of External Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3.5 Remote Annunicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 Plumbing (Finish). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.5.1 Power, Labeled POWER, L1, L2, Ground Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5.2 Analog Output, Labeled ANL OUT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5.3 Analog Input, Labeled DOOR, INPUT2, INPUT1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5.3.1 Measuring Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5.4 Optional Remote Transducer Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5.5 Relay and Annunciator Output, Labeled RELAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5.6 Optional Remote Annunciator Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5.7 Third Party Remote Annunciator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.5.8 Completing the Finish Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Section 2. Fitting an APM2 in an APM100 Enclosure
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1.1 What Is Included In Your Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1.1.1 Not Included - Tools You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2 Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.1 Turn Off Power To the APM100 Unit And Remove It From The Wall . . . . . . . . . . . . . . . . . . . . . . . . 14
2.2.2 Ensure Existing APM1 Enclosure Is Prepared For APM2 Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2.3 Attach the Base APM2 Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2.4 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2.5 Remotely Switching Alarm Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2.6 Modified Pressure Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.2.7 Complete the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Section 3. APM2 Central Display Rough-In Installation
3.1 Required Parts to be Supplied by the Installer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 Parts included with Your Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3 Installation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3.1 Wiring Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.3.2 Wiring Triple Gang Electrical Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
iii
MKT-0262 MPC-1748 Rev 02/13
Page 4
Table of Contents
3.4.1 Power, Labeled POWER, L1, L2, Ground Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.4.2 Completing the Finish Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Section 4. Ancillary Product Specifications
4.1 Model 264 Pressure Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.2 Model 267 Pressure Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
4.3 Remote Annunciator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.4 Pressure Pickup Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.5 Phoenix Recommended Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.5.1 MS/TP Specifications for Alternate Cable Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
iv
MKT-0262 MPC-1748 Rev 02/13
Page 5
APM2 Rough-In Installation Guide
Advanced Pressure Monitor II Rough-In Installation
Required Parts to be Supplied by the Installer

Section 1. Advanced Pressure Monitor II Rough-In Installation

For the Advanced Pressure Monitor II (APM2) to be installed correctly, the rough-in phase of the project must be completed properly. This section will outline the specific considerations the General Contractor must pay attention to so that the final wiring and commissioning will go smoothly.
During rough-in installation, the field wiring and plumbing can be run in the walls and routed between the triple gang electrical box, the Building Management System (BMS), door contact switch, remote sensors (if applicable) power supply, earth ground and so on.
If you’re installing the APM2 monitor, continue to to Section 1.1 Required Parts to be Supplied by the Installer. If you’re installing the APM2 Central Display, refer to APM2 Central Display Rough-In Installation on page 19.

1.1 Required Parts to be Supplied by the Installer

The following is a list of parts required and supplied by the installer for the APM2:
Triple gang-double deep electrical box (RACO 697 or Appleton M3-350), quantity 1
Green grounding screw, quantity 1
Power (18 AWG recommended) and signal wiring (22 AWG recommended), as needed. Refer to Phoenix Recommended Cables on page 33.
0.25" (6 mm) O.D. flame retardent polyethelyne control tubing (such as CPChem UL 1820)—to run from the room(s) to the APM2 (maximum 250 feet [76.2 meters] length)
NOTE: Less that 10% or 10 feet (1.6 meters) of total control tubing can be used in a vertical rise. Maintain
tubing run on the same floor as the APM2.
T-connectors
NOTE: Phoenix Controls recommends no more than five (5) T-connectors in a single run going to any
APM2.
EMT conduit (if required by local code)
•24 Vac Transformer
Door switch SPDT or SPST—normally open, as required
Remote pressure transducers, as needed
Remote Annunciators, as needed
The following is a list of part required and supplied by the installer for the Remote Annunciator and Pressure Pickup Port:
Single gang electrical box, as needed
0.25" (6 mm) O.D. flame retardent polyethelyne control tubing (such as CPChem UL 1820)—to connect between the Pressure Pickup Port and the APM2
MKT-0262 MPC-1748 Rev 02/13
1
Page 6
Advanced Pressure Monitor II Rough-In Installation
Parts Included with Your Order

1.2 Parts Included with Your Order

The following are parts that are included in your order:
Advanced Pressure Monitor II (APM2), including factory calibrated differential pressure sensor, quantity 1
APM2 Faceplate, quantity 1
Pressure Pickup Port (quantity 0, 1 or 2 - depending on order configuration)
0.25" O.D. Tubes, Silicone, with integrated springs and attached brass barbed couplings, quantity 2
Mounting screws, 6-32 x 1/2 Phillips head, quantity 5
Mating Electrical Connectors, Phoenix contact MC plug kit, quantity 1 with 3 green and 2 black connec­tors

1.3 Installation Overview

Each APM2 consists of a room pressure pick-up, a reference space pressure pickup and a room pressure monitor panel, which houses a differential pressure sensor.
The two pressure pickup ports are installed in single gang electrical boxes, which are placed in the room walls.
Standard 0.25" (6 mm) O.D. flame retardent polyethelyne control tubing (such as CPChem UL 1820), maximum 250 feet (76.2 meters) length, is run within the wall from the sensors to the monitor panel. In some code jurisdictions, the tubing must be in EMT conduit. Tubing and conduit is provided by others.
NOTE: Less that 10% or 10 feet (1.6 meters) of total control tubing can be used in a vertical rise. Maintain
tubing run on the same floor as the APM2.
Install in a triple gang-double deep electrical box (RACO 697, Appleton M3-350 or equivalent).
Secure the triple gang-double deep electrical box to the stud(s) by using the mounting hole in the side of the electrical box (see figure below for mounting hole location). Drive the mounting screws from the inside of the electrical box into the wall studs to prevent sharp objects from protruding into the electrical box.
Ensure the mounting is level and flush to the wallboard surface.
2
MKT-0262 MPC-1748 Rev 02/13
Page 7
APM2 Rough-In Installation Guide
Single Gang Electrical Box
1/4" x .170 Tube Barb (Conduit between sensors and monitor panel may be required.)
Reference Pressure Pickup
Room Pressure Pickup
APM2
NOTE: Connecting tubing and electrical boxes are field-supplied.
Triple Gang Double Deep Electrical Box
WALL MOUNT DIMENSIONS
Triple gang double deep electrical box—5.625" (220 mm) W x 3.5" (114.3 mm) H x 3.5" (63.5 mm) D
Single gang electrical box—2" (51 mm) W x 3" (76 mm) H x 3.5" (63.5 mm) D*
* Dimensions are approximate.
Advanced Pressure Monitor II Rough-In Installation
Installation Overview
Electrical Box Mounting Hole
Figure 1-1. Wall Mount Installation Overview

1.3.1 Wiring Recommendations

APM2 Faceplate
Rough-in Electrical Box
- Raco 697
- Appleton M3-350
APM2
All circuits must conform to the requirements of an NEC Class 2 (dry) circuit.
Use multiple transformers instead of larger transformers when more than 100 VA is required.
Each pressurization zone should have either a dedicated single-phase primary circuit, or a secondary circuit disconnect.
•Refer to Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types.
Use stranded wire for ease of installation.
Follow good wiring practices:
• Locate cables away from sources of electrical interference (EMI/RFI).
• Do not run signal or communication cable in the same conduit or wire way as power cables.
• If signal cable must cross power cables place these at a 90-degree angle.
• Shield or drain wires, if required, should be wrapped with insulating tape to prevent contact with exposed conductors or contacts.
• Maintain a consistent color code or polarity all the way through the wiring system.
• Power supply and signal isolation on I/O devices vary from manufacturer to manufacturer. Verify the wiring device manufacturer’s recommendations for isolating power and signal common connections and maintain polarity.
• Local and national electrical codes take precedence.
3
MKT-0262 MPC-1748 Rev 02/13
Page 8
Advanced Pressure Monitor II Rough-In Installation
Installation Overview
Strip 0.25" (6.4 mm) of insulation from each conductor, twist the strands, insert the conductor fully into the terminal block, and tighten the terminal.
•Test the wire connection by pulling on each conductor.
WARNING: Wiring must be performed by a licensed electrician according to local and state codes.

1.3.2 Wiring Triple Gang Electrical Box

USE ONLY THE KNOCKOUTS ON THE TOP OR BOTTOM AT THE BACK OF THE ROUGH-IN ELECTRICAL BOX. The front knockouts will be inaccessible once the APM2 is installed. Strain relief and seal
box as required.
NOTE: Install power and signal wires into separate knockouts to avoid noise.
Figure 1-2. Wiring in the Triple Gang Electrical Box

1.3.3 Plumbing Rough-In

If the internal pressure sensor will be used, then typically a Pressure Pickup Port is installed in the monitored room and another one is installed in the reference area (typically a hallway). 0.25" nylon tubing is typically used to bring the pressure signal from this point of measurement to the pressure inputs on the back of the APM2.
Install a single gang electrical box anywhere inside the room, typically high on the wall in an inconspicuous area. This will be used for the room pressure signal (room monitor pressure port labeled HIGH). Run 0.25" tubing from this electrical box to the triple gang box that the pressure monitor will be mounted to in the finish stage of the installation.
CAUTION: Be careful in running the tubing in a way that the tube is protected from being damaged by being cut
or penetrated by screws or nails or being crimped so that the pressure signal integrity is affected. Do not tighten strain reliefs so that they crimp the tubing. Tape the open ends of the tubes closed to prevent contamination of the inside of the tubing.
Install a second single gang box on the corridor, ante room or other reference pressure area. This will be used for the low pressure side or reference side pressure signal. This will be run to the triple gang box and connected to the APM2 pressure port labeled LOW.
4
MKT-0262 MPC-1748 Rev 02/13
Page 9
APM2 Rough-In Installation Guide
Advanced Pressure Monitor II Rough-In Installation
Installation Overview
If an external sensor will be used then run the pressure signals (room and reference) to the remote transducer.
Figure 1-3. Pressure Pickup Port Installation

1.3.4 Use of External Transducers

The APM2 has the option to use the internal pressure sensor or external pressure transducers (ordered separately). If external pressure sensors are being used then no tubing needs to be run into the electrical box. Instead the remote pressure transducer will be separately mounted, plumbed and wired. Only the wire for the analog output of that transducer(s) will be run to the APM2. If two rooms are being monitored, you have the choice to use the internal pressure sensor and an external (remote) transducer for the second room, or two external remote transducers may be used and wired to the analog inputs in the back of the unit.
NOTE: See Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types.
Layout the system in terms of wiring:
Power: 24 Vac, 9 VA
Annunciator/relay: remote alarm wiring if being used
Analog output: 0-5 or 0-10 Vdc or 4-20 mA.
Analog Input wiring: there are two analog inputs that can be used to bring signals from remote pressure transducers
Digital Input: the digital input can be used as a door status indication, these would be wired to a door switch mounted in the door jamb.
Once the installation has been planned, locate and mount the electrical box and bring all tubing, power, earth ground, analog input, digital input, relay/annunciator, analog output communications wiring into the triple gang box.
MKT-0262 MPC-1748 Rev 02/13
5
Page 10
Advanced Pressure Monitor II Rough-In Installation
Green LED
Red LED
Acknowledge Switch
Audible Alarm
Soft Silicon
Tubing with
Integrated
Springs
Plumbing (Finish)

1.3.5 Remote Annunicator

If an remote annunciator will be used, then mount a single gang electrical box in the desired location and run wires to it.
Figure 1-4. Remote Annunciator

1.4 Plumbing (Finish)

Use the following procedure for all room types positive, negative or neutral.
The biggest problem that can occur during plumbing is kinking of the often stiff nylon 0.25" tubing that is used for running pressure signals from the APM2 to the monitored spaces. To prevent buckling and collapse of this stiff tubing inside the electrical box, use the supplied soft silicone tubing with integrated springs and tubing adapters to transition from the field tubing to the pressure fittings on the APM2.
6
MKT-0262 MPC-1748 Rev 02/13
Page 11
Advanced Pressure Monitor II Rough-In Installation
Wiring
Attach pressure tubing as follows:
1. Install the supplied silicone tube (with integrated spring) and attached barbed tube adaptor onto the end of the 0.25 field tubing. Thread the tubes, with installed adaptor, through the conduit opening at the bottom of the electrical box.
2. Next push the open end of the soft silicone tubing onto the APM2 pressure tube port labeled "HIGH".
3. For the most pressure stable operation, a Pressure Pickup Port installed in the reference pressure area is also recommended. In this case, install the Pressure Pickup Port in a hallway or reference space.
4. Next push the open end of the soft silicone tubing onto the APM2 pressure tube port labeled "LOW".

1.5 Wiring

ANALOG (ANL) OUTPUT
POWER
L1 24 Vac L2 24 Vac
RELAY
COM COM +15 +15 Vdc NO Normally Open RC Relay COM NC Normally Closed
COM BACnet APM2-xx-ENG-BAC Products
B (+) A (-) GND
Earth Ground
THIS PAGE INTENTIONALLY LEFT BLANK.
COM COM mA Current Output (4-20 mA) Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door DI Digital Input
COM COM Analog Input2 IN2 Analog Input2 (0-5, 0-10Vdc) +15 15 Vdc
COM COM Analog Input1 IN1 Analog Input1 (0-5, 0-10Vdc) +15 15 Vdc
HIGH or room pressure tubing contacts here
REAR VIEW
LOW or re ference pressure tubing
connects here
Figure 1-5. Rear View of the APM2 (BACnet) Showing Wiring and Plumbing Connections
MKT-0262 MPC-1748 Rev 02/13
7
Page 12
Advanced Pressure Monitor II Rough-In Installation
ANALOG (ANL) OUTPUT
COM COM mA Current Output (4-20 mA) Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door DI Digital Input
COM COM Analog Input2 IN2 Analog Input2 (0-5, 0-10Vdc) +15 15 Vdc
COM COM Analog Input1 IN1 Analog Input1 (0-5, 0-10Vdc) +15 15 Vdc
Earth Ground L1 24 Vac L2 24 Vac
HIGH or room pressure tubing connects here
LOW or re ference pressure tubing connects here
POWER
RELAY
COM COM +15 +15 Vdc NO Normally Open RC Relay COM NC Normally Closed
COM NOT AVAILABLE
B (+) A (-) GND
REAR VIEW
Wiring
Figure 1-6. Rear View of the APM2 (Analog) Showing Wiring and Plumbing Connections
The back of the APM2 has electrical connectors labeled with their function. The mating electrical connectors
(supplied) are color coded and labeled with the matching function.

1.5.1 Power, Labeled POWER, L1, L2, Ground Symbol

Starting with the 3 pin Power connector:
1. Connect the 24 Vac lines to L1 and L2.
2. Connect a ground wire, GND, from the ground lug to the GND on the connector.
3. Install Connector.
The APM2 operates at 18-32 Vac, 50/60 Hz and consumes 2.6 W nominal, 9.6 W max.

1.5.2 Analog Output, Labeled ANL OUT

If using the analog output and want Voltage output, connect to the terminals labeled VDC and COM.
If using the analog out and want a 4-20 mA signal, connect to terminals labeled mA and COM. Connect this
output to the BMS system or other monitoring device.
8
MKT-0262 MPC-1748 Rev 02/13
Page 13
APM2 Rough-In Installation Guide
+
-
+ 15 Vdc IN1
COM
APM2
Setra Model 264 Current Output
249
Ohm
Advanced Pressure Monitor II Rough-In Installation
Wiring

1.5.3 Analog Input, Labeled DOOR, INPUT2, INPUT1

There are two analog inputs available for remotely mounted transducer inputs. These are INPUT1 and
INPUT2.
A 15 Vdc (14.8 to 15.2) excitation is available to power up to two transducers. They can source 90 mA max.
combined. It is labeled as +15 on the connectors.
If using this to power a remote transducer, connect this to the positive excitation terminal of the transducer.

1.5.3.1 Measuring Analog Inputs

There are three potential analog inputs that can be measured, 0-5, 0-10 and 4-20 mA.
For 0-5 or 0-10 Vdc inputs connect the positive (+) output of the transducer to terminal labeled IN1, con­nect the common output of the transducer to the terminal labeled COM.
For 4-20 mA loops install a 250 ohm resistor between the terminals labeled In1 or IN2 (whichever input you’re going to) and COM. The monitor will be measuring the voltage across this resistor as 1-5 Vdc cor­responding to 4-20 mA.
If you will be monitoring the status of a door position, then wire the contacts labeled DOOR to the normally open contacts on a door jamb switch. The monitor will show the door "Warning" (when enabled) when the door is open. The door jamb switch should be closed when the door is closed and open when the door is open.

1.5.4 Optional Remote Transducer Wiring

The figure below references the Setra remote sensors equipped with 4-20 mA output. The instruction booklets supplied with the sensors cover both the 3-wire voltage output configuration and 2-wire current configuration. The figure below clarifies the 2-wire 4­20 mA connection between the Setra 264 or 267 and APM2 inputs. The same connection applies to IN2 (AI2).
If the APM2 output is configured for 4-20 mA on the AO, the users can use either 249 or 500 Ohm resistors depending on whether they desire 1-5 or 2-10 Vdc.
Figure 1-7. Optional Remote Transducer Wiring
9
MKT-0262 MPC-1748 Rev 02/13
Page 14
Advanced Pressure Monitor II Rough-In Installation
Wiring

1.5.5 Relay and Annunciator Output, Labeled RELAY

There is an SPDT dry contact available. When an alarm occurs the Normally Open (NO) and the Common (COM) internal contacts will be closed. During no alarm conditions the Normally Closed (NC) and COM are shorted.
This relay can also drive a Remote Annunciator.

1.5.6 Optional Remote Annunciator Wiring

In the figure below, the Remote Annunciator connector is at left, and the APM2 connector is at right.
Figure 1-8. Remote Annunciator Wiring Diagram
To connect +15 Vdc power, connect the +15 Vdc from the relay connector to +15 Vdc, A1 at the Remote Annunciator. This supplies 15 V exc. to the Remote Annunciator for powering the circuit during normal conditions.
To connect power return, connect the COM of relay connector to Ground, A2 at the Remote Annuncia­tor.
On of the relay connector, connect a short jumper between the +15 and relay connector. This will connect the internal 15V supply to the common of the internal alarm relay.
Connect the NO on the relay output to the +15 Vdc Trigger, A3 terminal on the Remote Annunciator.
When an alarm occurs and after the programmed alarm delay times out, the internal relay will supply 15 V to the Remote Annunciator circuit to actuate the audible buzzer and the red LED.
10
MKT-0262 MPC-1748 Rev 02/13
Page 15
APM2 Rough-In Installation Guide
Advanced Pressure Monitor II Rough-In Installation

1.5.7 Third Party Remote Annunciator

The APM2 can drive other annunciators that are powered by a 15V supply, 50 mA max current draw, and accept a 15V trigger. If purchased separately, the Remote Annunciator can also be driven as shown below.
Figure 1-9. 3rd Party Remote Annunciator Wiring Diagram

1.5.8 Completing the Finish Wiring

1. Connect all the electrical connectors matching the wiring connector with the mates on the back of the unit. Connectors are color coded and keyed.
2. Connect the pressure signals to the HIGH and LOW ports on the back of the unit. The springs on the outside of the tubing are there to prevent buckling of the tube. As you push the unit into the electrical box push the black instrument tubing into the conduit tube or into the wall, Ideally the supplied silicone tube is the only tubing in the electrical box after the unit is slid in as far as it will go.
Wiring
Figure 1-10. Connecting Electrical Connectors to Back of APM2
3. Mount the unit cover to the electrical box using four of the supplied mounting screws. Leaving screws slightly loose adjust the cover so that it is square. Securely tighten so that the back of the cover is tight to the finish wall surface.
MKT-0262 MPC-1748 Rev 02/13
11
Page 16
Advanced Pressure Monitor II Rough-In Installation
Wiring
Figure 1-11. Mounting APM2 in Triple Gang Electrical Box
4. Mount the front cover assembly.
Figure 1-12. Installed APM2
12
MKT-0262 MPC-1748 Rev 02/13
Page 17
APM2 Rough-In Installation Guide
Fitting an APM2 in an APM100 Enclosure
Overview

Section 2. Fitting an APM2 in an APM100 Enclosure

2.1 Overview

APM100 pressure monitors from Phoenix Controls can be replaced in the field using the newer APM2 units. However, it is important to order the Retrofit Kit version of the APM2 product for compatibility with the existing enclosure. The APM2 Retrofit Kit includes additional parts and modifications to the standard APM2 product that permits easy installation in the field.
These instructions outline how to replace an APM100 series pressure monitor with APM200 series units. APM100 models installed in the field are housed in a 5-gang single-deep electrical box. The APM2 models require a 3-gang double-deep electrical box for new installations, so it will not fit directly into the APM1 enclosure without this adapter kit.

2.1.1 What Is Included In Your Kit

• APM2 model with the pressure range you ordered with 90 degree pressure taps on the rear of the unit for proper seating in the APM100 enclosure
• Stainless steel adapter plate to cover the larger APM100 wall opening
• Four (4) phillips head screws to secure APM2 to the adapter plate
• Four (4) Allen head screws to secure adapter plate to the existing APM100 enclosure
• APM2 white faceplate
• APM2 installation instructions
• APM2 connector kit
• APM2 calibration certificate

2.1.1.1 Not Included - Tools You Will Need

• Small blade terminal screwdriver
• Phillips head screwdriver
• 1/8" Allen wrench
13
MKT-0262 MPC-1748 Rev 02/13
Page 18
Fitting an APM2 in an APM100 Enclosure
Instructions

2.2 Instructions

IMPORTANT: As part of the site preparation, any wiring or tubing coming into the APM100 unit may
need to be moved to accomodate the depth of the APM2.
Figure 2-1. APM100 Display

2.2.1 Turn Off Power To the APM100 Unit And Remove It From The Wall

1. Remove the four allen head screws from the APM100.
CAUTION: Carefully, pull the APM100 out of the APM100 box.
2. Disconnect power and all connectors. Label connectors so it will be clear how to reconnect them to the APM2 unit.
3. Disconnect pressure tubing from the APM100 and label room side and reference side tubing.
14
MKT-0262 MPC-1748 Rev 02/13
Page 19
APM2 Rough-In Installation Guide
Four phillips head screws provided
Fitting an APM2 in an APM100 Enclosure
Instructions

2.2.2 Ensure Existing APM1 Enclosure Is Prepared For APM2 Unit

1. Make sure the wall surface around the existing enclosure is flat and clean with no wall damage or holes beyond the electrical box.
2. A full 5.18" of the center of the existing enclosure will be occupied by the APM2 unit when it is installed. Any wires or tubing in this region of the electrical box should be moved to the outer perimeter of the enclosure so the APM2 can slide in without obstructions. You may need to use the knockouts on either sides, tops or bottom as shown below.
Figure 2-2. APM100 Knockout Locations

2.2.3 Attach the Base APM2 Unit

Mount the base APM2 unit to the adapter plate using the four supplied phillips head screws. Leaving screws slightly loose adjust the cover so that it is square. Securely tighten so that the back of the cover is tight to the finish wall surface.
Figure 2-3. Installing APM2 to the Adapter Plate
15
MKT-0262 MPC-1748 Rev 02/13
Page 20
Fitting an APM2 in an APM100 Enclosure
Instructions

2.2.4 Wiring

POWER
L1 24 Vac L2 24 Vac
RELAY
COM COM +15 +15 Vdc NO Normally Open RC Relay COM NC Normally Closed
COM BACnet APM2-xx-ENG-BAC Products
B (+) A (-) GND
Earth Ground
ANALOG (ANL) OUTPUT
COM COM mA Current Output (4-20 mA) Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door DI Digital Input
COM COM Analog Input2 IN2 Analog Input2 (0-5, 0-10Vdc) +15 15 Vdc
COM COM Analog Input1 IN1 Analog Input1 (0-5, 0-10Vdc) +15 15 Vdc
HIGH or room pressure tubing contacts here
REAR VIEW
LOW or re ference pressure tubing
connects here
Figure 2-4. Rear View of the APM2 Showing Wiring and Plumbing Connections
The back of the APM2 has electrical connectors labeled with their function. The mating electrical connectors (supplied) are color coded and labeled with the matching function.
Refer to the Advanced Pressure Monitor II User’s Guide (MKT-0263) for detailed wiring instructions.

2.2.5 Remotely Switching Alarm Setpoints

The APM100 model uses dry contacts to switch pressure setpoints between positive and negative, whereas the APM2 uses an input voltage: 0, 5 or 10 Volts to switch pressure setpoints between negative-neutral-positive respectively. If this function was used on the APM100 product, adaptations will need to be made to restore their function with other equipment or devices that will generate the 0, 5 or 10 Volt signal.
16
MKT-0262 MPC-1748 Rev 02/13
Page 21
APM2 Rough-In Installation Guide
1/8" Allen head screws supplied
Fitting an APM2 in an APM100 Enclosure
Instructions

2.2.6 Modified Pressure Taps

The APM2 retrofit unit differs from the standard APM100 product. The rear of the unit uses 90º pressure taps instead of straight-through pressure taps. This allows the unit to be installed in the shallower APM100 box. The shallower APM100 box permits enough space for existing pressure tubes in the back to be connected.
Figure 2-5. APM2 Retrofit Kit Pressure Taps

2.2.7 Complete the Installation

1. Complete the installation following the instructions in the Advanced Pressure Monitor II User’s Guide (MKT-0263), which can be obtained from the Partner Login area of http://www.phoenixcontrols.com/.
2. Once wiring and pressure tubes are connected, verify functionality of the APM2 before sliding it into the wall enclosure.
3. Install the adapter plate to the wall enclosure by using the four 1/8" Allen head screws supplied.
Figure 2-6. Installing Adapter Plate to APM100 Box
17
MKT-0262 MPC-1748 Rev 02/13
Page 22
Fitting an APM2 in an APM100 Enclosure
Instructions
4. Mount the front cover assembly.
Figure 2-7. Installed APM2
18
MKT-0262 MPC-1748 Rev 02/13
Page 23
APM2 Rough-In Installation Guide
APM2 Central Display Rough-In Installation
Required Parts to be Supplied by the Installer

Section 3. APM2 Central Display Rough-In Installation

For the APM2 Central Display to be installed correctly, the rough-in phase of the project must be completed properly. This section will outline the specific considerations the General Contractor must pay attention to so that the final wiring and commissioning will go smoothly.
During rough-in installation, the field wiring can be run in the walls and routed between the triple gang electrical box, the Building Management System (BMS), power supply, earth ground and so on.

3.1 Required Parts to be Supplied by the Installer

The following is a list of parts required and supplied by the installer for the APM2 Central Display:
Triple gang-double deep electrical box (RACO 697 or Appleton M3-350), quantity 1
Green grounding screw, quantity 1
Power (18 AWG recommended) and signal wiring (22 AWG recommended), as needed. Refer to Phoenix Recommended Cables on page 33.
EMT conduit (if required by local code)
•24 Vac Transformer

3.2 Parts included with Your Order

The following are parts that are included in your order:
APM2 Central Display, quantity 1
APM2 Faceplate, quantity 1
Mounting screws, 6-32 x 1/2 Phillips head, quantity 5
Mating Electrical Connectors, Phoenix Contact MC plug kit, 2 green connectors

3.3 Installation Overview

Install in a triple gang-double deep electrical box (RACO 697, Appleton M3-350 or equivalent).
Secure the triple gang-double deep electrical box to the stud(s) by using the mounting hole in the side of the electrical box (see figure below for mounting hole location). Drive the mounting screws from the inside of the electrical box into the wall studs to prevent sharp objects from protruding into the electrical box.
Ensure the mounting is level and flush to the wallboard surface.
19
MKT-0262 MPC-1748 Rev 02/13
Page 24
APM2 Central Display Rough-In Installation
Faceplate
Main Unit
Rough-in Electrical Box
- Raco 697
- Appleton M3-350
Electrical Box Mounting Hole
WALL MOUNT DIMENSIONS
Triple gang double deep electrical box—5.625" (142.9 mm) W x 3.5" (88.9 mm) H x 3.5" (88.9 mm) D
* Dimensions are approximate.
Installation Overview
Figure 3-1. Wall Mount Installation Overview

3.3.1 Wiring Recommendations

All circuits must conform to the requirements of an NEC Class 2 (dry) circuit.
Use multiple transformers instead of larger transformers when more than 100 VA is required.
Each pressurization zone should have either a dedicated single-phase primary circuit, or a secondary circuit disconnect.
•See Phoenix Recommended Cables on page 33 for approved cable manufacturers and wire types.
Use stranded wire for ease of installation.
Follow good wiring practices:
• Locate cables away from sources of electrical interference (EMI/RFI).
• Do not run signal or communication cable in the same conduit or wire way as power cables.
• If signal cable must cross power cables place these at a 90-degree angle.
• Shield or drain wires, if required, should be wrapped with insulating tape to prevent contact with exposed conductors or contacts.
• Maintain a consistent color code or polarity all the way through the wiring system.
• Power supply and signal isolation on I/O devices vary from manufacturer to manufacturer. Verify the
• Local and national electrical codes take precedence.
wiring device manufacturer’s recommendations for isolating power and signal common connections and maintain polarity.
20
MKT-0262 MPC-1748 Rev 02/13
Page 25
APM2 Rough-In Installation Guide
APM2 Central Display Rough-In Installation
Installation Overview
Strip 0.25" (6.4 mm) of insulation from each conductor, twist the strands, insert the conductor fully into the terminal block, and tighten the terminal.
•Test the wire connection by pulling on each conductor.
WARNING: Wiring must be performed by a licensed electrician according to local and state codes.

3.3.2 Wiring Triple Gang Electrical Box

USE ONLY THE KNOCKOUTS ON THE TOP OR BOTTOM AT THE BACK OF THE ROUGH-IN ELECTRICAL BOX. The front knockouts will be inaccessible once the APM2 is installed. Strain relief and seal
box as required.
NOTE: Install power and signal wires into separate knockouts to avoid noise.
Figure 3-2. Wiring in the Triple Gang Electrical Box
21
MKT-0262 MPC-1748 Rev 02/13
Page 26
APM2 Central Display Rough-In Installation
Earth Ground L1 24 Vac L2 24 Vac
POWER
COMM
B (+) A (-) GND
REAR VIEW
BACnet Communications
(See Detail A)
DATA +
DATA -
COMM
B (+)
GND
A (-)
DETAIL "A"
GROUND SHIELD - ONE END ONLY
Wiring

3.4 Wiring

Figure 3-3. Rear View of the APM2 Central Display Showing Wiring Connections
The back of the APM2 Central Display has electrical connectors labeled with their function. The mating electrical connectors (supplied) are color coded and labeled with the matching function.

3.4.1 Power, Labeled POWER, L1, L2, Ground Symbol

Starting with the 3 pin Power connector:
1. Connect the 24 Vac lines to L1 and L2.
2. Connect a ground wire, GND, from the ground lug to the GND on the connector.
3. Install Connector.
The APM2 operates at 18-32 Vac, 50/60 Hz and consumes 2.6 W nominal, 9.6 W max.
22
MKT-0262 MPC-1748 Rev 02/13
Page 27
APM2 Rough-In Installation Guide
APM2 Central Display Rough-In Installation

3.4.2 Completing the Finish Wiring

1. Connect all the electrical connectors matching the wiring connector with the mates on the back of the unit. Connectors are color coded and keyed.
2. Mount the unit cover to the electrical box using four of the supplied mounting screws. Leaving screws slightly loose adjust the cover so that it is square. Securely tighten so that the back of the cover is tight to the finish wall surface.
Wiring
Figure 3-4. Mounting APM2 Central Display in Triple Gang Electrical Box
3. Mount the front cover assembly.
Figure 3-5. Installed APM2 Central Display
23
MKT-0262 MPC-1748 Rev 02/13
Page 28
APM2 Central Display Rough-In Installation
Wiring
THIS PAGE INTENTIONALLY LEFT BLANK.
MKT-0262 MPC-1748 Rev 02/13
24
Page 29
APM2 Rough-In Installation Guide
Ancillary Product Specifications
Model 264 Pressure Transducer

Section 4. Ancillary Product Specifications

NOTE: The following specifications are subject to changes without notice.

4.1 Model 264 Pressure Transducer

Table 1. Model 264 Pressure Transducer (Remote Transducer 0-5 V Output)
Model 264 Pressure Transducer
Performance Data
Standard Optional
1
Accuracy
Non-linearity (BFSL) ± 0.96 % FS ± 0.38 % FS ± 0.22 % FS
Hysteresis 0.10% FS 0.10% FS 0.10% FS
RSS (at constant temperature)
± 1.0 % FS ± 0.4 % FS ± 0.25 % FS
Non-repeatability 0.05% FS 0.05% FS 0.05% FS
3
°F (°C)
°F (°C)
2
0 - 150 (-18 - 65)
°F (°C)
0.033 (0.06)
To 0.5" WC 0.60
To 1.0" WC 0.50
0 - +175 (-18 - +79)
-65 - +250 (-54 - +121)
Thermal Effects
Compensated Range °F (°C)
Zero/Span Shift % FS/
Maximum Line Pressure 10 psi
Overpressure Up to 10 psi (range dependent)
Long-term Stability 0.5% FS / year
Position Effect Range Zero Offset (% FS/G)
Unit is factory calibrated at 0g effect in the vertical position
Environmental Data
Temperature
Operating
Storage
Physical Description
Case Fire-retardant glass filled polyster (UL94 V-0 Approved)
Dimensions 2.75" (69.85 mm) W x 5.062" (128.57 mm)H x 2.40" (61.07 mm) D
Mounting
Electrical Connection Screw type terminal strip
Four screw holes on removable zinc-plated steel base (designed for 2.75" snap track)
MKT-0262 MPC-1748 Rev 02/13
25
Page 30
Ancillary Product Specifications
Model 264 Pressure Transducer
Pressure Fittings 3/16" OD barbed brass pressure fitting for 1/4" push-on tubing
Zero and Span Adjustments Accessible on top of case
Weight (approximate) 10 ounces
Pressure Media
Typically air or similar non-conducting gases
Electrical Data—Voltage
Circuit 3-wire (Com, Exc, Out)
Excitation 9 - 30 Vdc
4
Output
Bi-directional output at zero pressure
Output impedance 100Ω
Electrical Data—Current
Circuit 2-wire
7
Output
Bi-directional output at zero pressure
0 - 5 Vdc
2.5 Vdc
4 - 20 mA
12 mA
5
6
8
9
Minimum supply voltage (Vdc) 9+0.02 x (resistance of receiver plus line)
Maximum supply voltage (Vdc) 30+0.004 x (resistance of receiver plus line)
1
RSS of non-linearity, hystereis and non-repeatability.
2
Units calibrated at nominal 70 °F. Maximum thermal error computed from this datum.
3
Operating temperature limits of the electronics only. Pressure media temperatures may be considerably higher.
4
Calibrated into a 50KΩ load, operable into a 5KΩ load or greater.
5
Zero output factory set to within ± 50 mV (± 25 mV for optional accuracies).
6
Span (full scale) output factory set to within ± 50 mV (± 25 mV for optional accuracies).
7
Calibrated at factory with a 24 Vdc loop supply voltage and a 250Ω load.
8
Zero output factory set to within ± 0.16 mA (± 0.08 mA for optional accuracies).
9
Span (full scale) output factory set to within ± 0.16 mA (± 0.08 mA for optional accuracies).
26
MKT-0262 MPC-1748 Rev 02/13
Page 31
APM2 Rough-In Installation Guide
+
SPAN
+
ZERO
INSTALLATION WARNING!
2.750 in.
(69.85 mm)
5.062 in.
(128.57 mm)
4.562 in.
(115.87 mm)
R0.078 in.
(R1.98 mm)
1.624 in.
(41.25 mm)
0.594 in.
(15.08 mm)
1.811 in.
(45.99 mm)
1.187 in.
(30.15 mm)
TYP.
TYP.
TYP.
1.662 in.
(42.21 mm)
0.312 in.
(7.92 mm)
0.385 in.
(9.78 mm)
TYP.
LOW
Model 264
HIGH
Serial Number:
Part Number:
Range:
Excitation:
Output:
Date Code: 3599
0-5 VDC
9-30 Vdc
0-5.0" WC
1015990
2641005WD2DT1C
COM
EXC OUT
PRESSURE PORTS
TOP VIEW
SIDE VIEW
#6 SCREW WIRE CLAMP 3 PLACES
Ancillary Product Specifications
Model 264 Pressure Transducer
Figure 4-1. Model 264 Pressure Transducer
27
MKT-0262 MPC-1748 Rev 02/13
Page 32
Ancillary Product Specifications
Model 267 Pressure Transducer

4.2 Model 267 Pressure Transducer

Table 2. Model 267 Pressure Transducer
Performance Data
Standard Optional
1
Accuracy
Non-linearity (BFSL) ± 0.98 % FS ± 0.38 % FS ± 0.22 % FS
Hysteresis 0.10% FS 0.10% FS 0.10% FS
Non-repeatability 0.05% FS 0.05% FS 0.05% FS
RSS (at constant temperature)
Thermal Effects
2
± 1.0 % FS ± 0.4 % FS ± 0.25 % FS
Compensated Range °F (°C)
Zero/Span Shift % FS/
Maximum Line Pressure 10 psi
Overpressure Up to 10 psi (range dependent)
Warm-up Shift ± 0.1% FS Total
Position Effect Range Zero Offset (% FS/G)
Unit is factory calibrated at 0g effect in the vertical position
Environmental Data
Temperature
3
Operating
Storage
Physical Description
Case IP65/NEMA plastic-filled polycarbonate (UL94 V-0 Approved)
Dimensions 6.20" (158 mm) W x 2.68" (68 mm) H x 3.65" (93 mm) D
Electrical Connection Screw type terminal strip
°F (°C)
°F (°C)
°F (°C)
40 - 150 (5 - 65)
± 0.033 (± 0.06)
To 0.5" WC 0.60
To 1.0" WC 0.50
0 - +150 (-18 - +65)
+65 - +180 (-54 - +82)
PG-9/PG13.5 Strain relief, 1/2" conduit opening, or 9-pin D-sub connector
Electrical Termination
NOTE: 9-pin D-sub connector is not suitable for NEMA4/IP-65 environments
Pressure Fittings
Weight (approximate) 9 ounces (255 g)
Pressure Media
Typically air or similar non-conducting gases
3/16" O.D. barbed brass for 1/4" push-on tubing (Standard) Static Pressure Probe (Optional) 1/4" NPTF brass (Optional)
28
MKT-0262 MPC-1748 Rev 02/13
Page 33
APM2 Rough-In Installation Guide
Electrical Data—Voltage
Circuit 3-wire (Exc, Gnd, Sig)
Excitation/Output
Excitation/Output
Bi-directional output at zero pressure Mid-range of specified output
Output impedance 100Ω
Re-ranging 5 position dip switches (inside case)
Electrical Data—Current
Circuit 2-wire protected from miswiring
6
Output
External Load 0 - 800Ω
Bi-directional output at zero pressure 12 mA
Minimum loop supply voltage (Vdc) 9 + 0.02 x (resistance of receiver plus line)
Maximum supply voltage (Vdc) 30 + 0.004 x (resistance of receiver plus line)
(0-5 Vdc output)
(0-10 Vdc output)
9 - 30 Vac / 12 - 40 Vdc 11 - 30 Vac / 13 - 40 Vdc
4 - 20 mA
7
Ancillary Product Specifications
Model 267 Pressure Transducer
Re-ranging 4 position dip switches (inside case)
1
RSS of non-linearity, hystereis and non-repeatability.
2
Units calibrated at nominal 70 °F. Maximum thermal error computed from this datum.
3
Operating temperature limits of the electronics only. Pressure media temperatures may be considerably higher or lower.
4
Calibrated into a 50K Ω load, operable into a 5K Ω load or greater.
5
Zero output factory set to within ± 50 mV (± 25 mV for optional accuracies).
Span (full scale) output factory set to within
6
Calibrated at factory with a 24 Vdc loop supply voltage and a 250 Ω load.
7
Zero output factory set to within ± 0.16 mA (± 0.08 mA for optional accuracies).
± 50 mV (± 25 mV for optional accuracies).
Span (full scale) output factory set to within ± 0.16 mA (± 0.08 mA for optional accuracies).
29
MKT-0262 MPC-1748 Rev 02/13
Page 34
Ancillary Product Specifications
Model 267 Pressure Transducer
2.68 in.
(68 mm)
1.34 in.
(34 mm)
6.10 in.
(155 mm)
5.60 in.
(142 mm)
0.18 in.
(Ø4.5 mm)
0.75 in.
(19 mm)
0.50 in.
(13 mm)
3/16" O.D. PRESSURE FITTING FOR 1/4" PUSH-ON TUBING
1.73 in.
(44 mm)
0.93 in.
(24 mm)
Figure 4-2. Model 267 Pressure Transducer
0.80 in.
(20 mm)
Ø7/8 in.
(Ø22 mm)
1.18 in.
(30 mm)
1.29 in.
(33 mm)
2.36 in.
(60 mm)
30
MKT-0262 MPC-1748 Rev 02/13
Page 35
APM2 Rough-In Installation Guide
4.52 in.
(114.78 mm)
.20 in.
(5.08 mm)
2.77 in.
(70.23 mm)
.74 in. (18.69 mm)
.43 in.
(10.80 mm)
2.68 in.
(68 mm)
1.97 in.
(50 mm)

4.3 Remote Annunciator

Table 3. Remote Annunciator
Enclosure 2.75" W x 4.5" H stainless steel wall cover plate
External Supply 15 Vdc, 50 mA maximum
Display Panel Green and red LED indicators and Acknowledge (ACK) switch
Audible Alarm 0-85 dBA measured 4" from annunciator
Acknowledge Switch Momentarily turns off audible alarm
Ancillary Product Specifications
Remote Annunciator
Figure 4-3. Remote Annunciator
31
MKT-0262 MPC-1748 Rev 02/13
Page 36
Ancillary Product Specifications
2.77 in.
(70.23 mm)
4.52 in.
(114.78 mm)
.20 in.
(5.08 mm)
.82 in.
(21 mm)
Pressure Pickup Port

4.4 Pressure Pickup Port

Table 4. Pressure Pickup Port
Cover Stainless steel standard wall cover plate
Mounting Standard single gang electrical box (2 screws included)
Dimensions 2.77" (70.23 mm) W x 4.52" (114.78 mm) H x 1.02" (26.08 mm) D
Pressure Fitting 1/4" flexible push-on tubing (Standard)
Figure 4-4. Pressure Pickup Port
32
MKT-0262 MPC-1748 Rev 02/13
Page 37
APM2 Rough-In Installation Guide

4.5 Phoenix Recommended Cables

Ancillary Product Specifications
Phoenix Recommended Cables
Cable
Ty p e
2C Round
2C Round
TP No FTT-10 (4500’)
TP Yes FTT-10 (4500’)
TSP No I/O signal
2 TSP No I/O signal
3C Round
3C or 4C Round
4C Round
5C Round
Plenum
Rated
No 24 Vac power to
Yes 24 Vac power to
No Signal 22 Belden 8443 1: Red
Yes Signal 22 Belden 88444 Windy City
No Signal 22 Belden 8444 Manhattan
No Signal 22 Belden 8445 Manhattan
Function
LOSEA or Pneumatic (110’
max at load
24 Vac power to HiSea (288’ max
1, 2
at load
LOSEA or Pneumatic (110’
max at load
24 Vac power to HiSea (288’ max
at load
TP1250 (425’)
FTT-10 (8800’) 16 Windy City
TP1250 (425’)
FTT-10 (8800’) 16 Windy City
wiring
wiring
)
1, 2
)
1
2
Wire
Gauge
18 Belden 9409 1: Red
1, 2
)
14 Belden 9411
18 Belden 82740 Windy City
1, 2
)
14 Windy City
22 Windy City
22 Windy City
22 Belden 9501 1: Black&Red Twisted
22 Belden 9502 1: Black&Red
Primary
Vendor/Part #
NP007960
107500
109600
105500
109500
Alternate
Vendor/Part #
NP002360
Connect-Air W221P-1002
Connect-Air W221P-2001
004380
M13304
M13305
Color Code Notes
2: Black
1: Red 2: Black
1: White/Blue stripe 2: Blue/White stripe
1 : W h i t e / B l u e s t r i p e 2: Blue/White stripe
2: Black&White
2: Black 3: Green
1: Red 2: Black 3: Green 4: White (not used as 3C)
1: White 2: Green 3: Black 4: Red
1: White 2: Brown 3: Black 4: Red 5: Green
Must be stranded
Must be stranded
For more alternatives visit: echalon.com
For more alternatives visit: echalon.com
Shielded Pair
Two Twisted Pair, Shielded
Must be stranded
Must be stranded
Must be stranded
Must be stranded
33
MKT-0262 MPC-1748 Rev 02/13
Page 38
Ancillary Product Specifications
Phoenix Recommended Cables
Cable
Ty p e
8C No Signal 22 Belden 9421 Manhattan
8C Yes Signal 22 Comtran 4956 1: White
3C MS/TP
3C MS/TPYe s Shielded 22 Connect-Air
4C MS/TP
4C MS/TP
4C MS/TP
Plenum
Rated
No Shielded 22 Belden 3106A
Yes Armored
Yes Armored
Yes Armored
Function
Shielded
Shielded
Shielded
Wire
Gauge
22 Belden 1269A
22 Belden 123107A
24 Belden 82842
Primary
Vendor/Part #
(120 ohm)
W223C­2060YPC
(100 ohm)
(100 ohm)
(100 ohm)
Alternate
Vendor/Part #
M13308
See specifications below for alternate cable solutions
See specifications below for alternate cable solutions
See specifications below for alternate cable solutions
See specifications below for alternate cable solutions
See specifications below for
lternate cable
a solutions
Color Code Notes
1: White 2: Orange 3: Black 4: Red 5: Green 6: Yellow 7: Blue 8: Brown
2: Orange 3: Black 4: Red 5: Green 6: Yellow 7: Blue 8: Brown
1: White with Orange stripe 2: Orange with White stripe 3: Blue with White stripe
1: Black 2: White 3: Red
1: Red 2: Blue 3: Black 4: Yellow
1: White with Blue stripe 2: Blue with White stripe 3: White with Orange stripe 4: Orange with White stripe
1: White with Blue stripe 2: Blue with White stripe 3: White with Orange stripe 4: Orange with White stripe
No substitutes
No substitutes
Shielded with drain
Foil shield with drain wire
Foil and braided shield with drain
Foil and braided shield with drain
Foil and braided shield with drain Low smoke
34
MKT-0262 MPC-1748 Rev 02/13
Page 39
APM2 Rough-In Installation Guide
Ancillary Product Specifications
Phoenix Recommended Cables
Cable
Ty p e
4C MS/TP
4C MS/TP
1
Load is 96 VA when power is provided by a 100 VA transformer with external 4 amp slow blow fuse.
2
Load is 100 VA when power is provided by a 100 VA transformer with internal circuit breaker.
Plenum
Rated
Yes Shielded 24 Belden 82729
Yes Shielded 24 Belden 88102
Function
Wire
Gauge
Primary
Vendor/Part #
(100 ohm)
(100 ohm)
Alternate
Vendor/Part #
See specifications below for alternate cable solutions
See specifications below for alternate cable solutions
Color Code Notes
1: White with Blue stripe 2: Blue with White stripe 3: White with Orange stripe 4: Orange with White stripe
1: White with Blue stripe 2: Blue with White stripe 3: White with Orange stripe 4: Orange with White stripe
Shield with drain
Shield with drain

4.5.1 MS/TP Specifications for Alternate Cable Solutions

1. An MS/TP (EIA-485) network shall use shielded, twisted-pair cable with characteristic impedance between 100 and 130Ω..
2. Distributed capacitance between conductors shall be less that 100 pF per meter (30 pf per foot).
3. Distributed capacitance between conductors and shield shall be less that 200 pF per meter (60 pF per foot).
4. Foil or braided shields are acceptable. The maximum recommended length of an MS/TP segment is 1200
2
meters (4000 feet) with AWG 18 (0.82 mm
conductor area) cable.
5. The use of greater distances and/or different wire gauges shall comply with the electrical specifications of EIA-485 for MS/TP cable requirements.
35
MKT-0262 MPC-1748 Rev 02/13
Page 40
Ancillary Product Specifications
Phoenix Recommended Cables
THIS PAGE INTENTIONALLY LEFT BLANK.
MKT-0262 MPC-1748 Rev 02/13
36
Page 41
APM2 Rough-In Installation Guide
Index
Numerics
15 Vdc 9 24 Vac 5 24 Vac Transformer 1, 19 249 or 500 Ohm Resistors 9 3 pin Power Connector 8, 22 3-gang Double-deep Electrical Box 13 3rd Party Remote Annunciator Wiring 11 5-gang Single-deep Electrical Box 13 9 VA
Power 5
A
Adapter Plate
Stainless Steel 13 Adapter Plate Install 17 Alarm Setpoints
Remotely Switching 16 Alternate Cable Solutions
MS/TP Specifications 35 Analog Input 9 Analog Input Wiring 5 Analog Output 5, 8 Ancillary Product 25 ANL OUT 8 Annunciator 5
Remote 31 APM100 Enclosure 13 APM100 Pressure Monitors 13 APM2 Calibration Certificate 13 APM2 Central Display 1, 19 APM2 Connector Kit 13 APM2 Front Cover 18 APM2 Pressure Monitor 13 APM2 Retrofit Kit 13 APM2 White Faceplate 13 Attach
Base Unit 15 Audible Buzzer
Remote Annunciator 10
B
Base APM2 Unit 15 BMS 1, 19 Building Management System 1, 19
C
Cables
Phoenix Recommended 33 Calibration Certificate
APM2 13
Central Display
APM2 1, 19
Certificate
APMS Calibration 13 Complete Installation 17 Conectors
Label 14 Connect Power Return 10 Connections
Plumbing and Wiring 7, 8, 16, 22 Connector Kit
APM2 13 Cover
APM2 Front 18
Install Front 12, 23 Current
Model 264 Electrical Data 26
Model 267 Electrical Data 29
D
Data
Model 264 Environmental 25
Model 264 Performance 25
Model 267 Environmental 28
Model 267 Performance 28 Description
Model 264 Physical 25
Model 267 Physical 28 Digital Input 5 Dimensions
Model 264 Pressure Transducer 25
Model 267 28
Wall Mount 3 Door 9 Door Switch
SPDT 1, 19
SPST 1, 19
E
Effect
Model 264 Position 25
Model 267 Position Effect 28 Effects
Model 264 Thermal 25
Model 267 Thermal 28 Electrical Box 1, 19
3-gang Double-deep 13
5-gang Single deep 13
Appleton M3-350 1, 2, 19
RACO 697 1, 2, 19 Electrical Connectors (supplied) 8, 16, 22 EMT Conduit 1, 2, 19
IX-1
MKT-0262 MPC-1748 Rev 02/13
Page 42
Enclosure
APM100 13 External Sensor 5 External Transducers
Use of 5
F
Faceplate
APM2 White 13 Field Wiring 1, 19 Finish Plumbing 6
Pressure Tubing 7 Finish Wiring 11, 23 Front cover
Install 11, 23
G
General Contractor 1, 19 Ground 8, 22
I
Included Parts 2, 19
0.25" O.D. Tubes 2
Advanced Pressure Monitor II 2, 19
APM2 2, 19
Barbed Couplings 2
Faceplate 2, 19
Mating Electrical Connectors 2, 19
Mounting Screws 2, 19
Phoenix Contact MC plug kit 2, 19
Pressure Pickup Port 2, 19 Input1 9 Input2 9 Inputs
Measuring Analog Inputs 9 Install
Adapter Plate 17
Unit to Electrical Box 11, 23 Install Fron Cover 11, 23 Install Front Cover 12, 23 Installation 2, 19
Complete 17
Overview 2, 19
Pressure Pickup Port 5
Remote Annunciator 6
Rough-in 1, 19 Installer Required Parts 1, 19 Instructions 14
J
Jumper 10
K
Kit
APM2 Connector 13
APM2 Retrofit 13
L
L1 8, 22 L2 8, 22
Label Connectors 14
M
Measuring Analog Inputs 9
COM 9 IN1 9
Media
Model 264 Pressure 26 Model 267 Pressure 28
Model 264 Electrical Data
Current 26
Voltage 26 Model 264 Environmental Data 25 Model 264 Performance Data 25 Model 264 Physical Description 25 Model 264 Position Effect 25 Model 264 Pressure Media 26 Model 264 Pressure Transducer 25 Model 264 Pressure Transducer Dimensions 25 Model 264 Thermal Effects 25 Model 267 Dimensions 28 Model 267 Electrical Data
Current 29
Voltage 29 Model 267 Environmental Data 28 Model 267 Performance Data 28 Model 267 Physical Description 28 Model 267 Position Effect 28 Model 267 Pressure Media 28 Model 267 Pressure Transducer 28 Model 267 Thermal Effects 28 Modified 17 Modified Pressure Taps 17 MS/TP 35 MS/TP Specifications
Alternate Cable Solutions 35
O
Optional Remote Annunciator Wiring 10 Optional Remote Transducer Wiring 9 Output
Relay and Annunciator 10
P
Phoenix Recommended Cables 33 Plate
Adapter 13 Plumbing 1
Finish 6 Plumbing Rough-In 4, 22 Polyethelyne Control Tubing 1 Port
Pressure Pickup 32 Power 5, 8, 22
Turn Off 14 Power Return
Connect 10 Power Wiring 1, 19 Pressure Monitor
AMP2 13
APM100 13
IX-2
MKT-0262 MPC-1748 Rev 02/13
Page 43
APM2 Rough-In Installation Guide
Pressure Pickup Port 1, 4, 32 Pressure Pickup Port Installation 5 Pressure Signals 5, 11 Pressure Taps 17 Pressure Transducer
Model 264 25 Model 267 28
Pressure Tubing 14
R
Recommendations
Wiring 3, 20 Relay 5, 10 Relay and Annunciator Output 10 Relay Connector 10
COM 10 Relay Output
NO 10 Remote Alarm 5 Remote Annunciator 10, 31
Third Party 11 Remote Annunciators 1 Remote Annunicator Installation 6 Remote Pressure Tansducers 1 Remote Transducer 5 Remotely Switching Alarm Setpoints 16 Required Parts
Installer 1, 19 Room Pressure Signal 4 Rough-in
Wiring 4, 21 Rough-in Installation 1, 19 Rough-in Plumbing 4, 22
S
Sensors
Setra Remote 9 Setpoints 16 Setra Remote Sensors 9 Side
Reference 14 Signal Wiring 1, 19 Signals
Pressure 11 Single Gang Electrical Box 1 Specifications
Ancillary Product 25 Stainless Steel Adapter Plate 13
Room Side 14
Turn Off Power 14
U
Use of External Transducers 5
V
Voltage
Model 264 Electrical Data 26 Model 267 Electrical Data 29
W
Wall Mount Dimensions 3 Warni ng 9 Wiring 7, 17, 22
3rd Party Remote Annunciator 11 Dedicated Single-phase Primary Circuit 3, 20 Electrical connectors 7, 22 Finish 11, 23 Knockouts 4, 21 Multiple Transformers 3, 20 NEC Class 2 3, 20 Optional Remote Annunciator 10 Optional Remote Transducer 9 Power 1, 19 Relay Connector 10 Secondary Circuit Disconnect 3, 20 Signal 1, 19 Stranded Wire 3, 20
System Layout 5 Wiring and Plumbing Connections 7, 8, 16, 22 Wiring Practices 3, 20 Wiring Recommendations 3, 20 Wiring Rough-in 4, 21 Wiring Triple Gang Electrical Box 4, 21
T
T-connectors 1 Too l s N ee d ed 1 3 Tr a n s d u c e r
Model 264 Pressure 25 Model 267 Pressure 28
Tr a n s f o r m e r
24 Vac 1, 19
Tu b i n g
Polyethelyne control 1 Pressure 14 Reference Side 14
IX-3
MKT-0262 MPC-1748 Rev 02/13
Page 44
THIS PAGE INTENTIONALLY LEFT BLANK.
MKT-0262 MPC-1748 Rev 02/13
IX-4
Page 45
Page 46
For additional information and a listing of our global offi ces, please visit our Web site at www.phoenixcontrols.com or call (800) 340-0007.
Phoenix Controls is a business of Honeywell International, Inc. © 2010 Phoenix Controls 2/13 Printed in U.S.A. MKT-0262 MPC-1748
Loading...