Philips EasySense, SNS100CMP, 510651 Quick Installation Manual

Page 1
Sensors
EasySense
Ceiling-Mount
Philips EasySense Quick Installation Guide
Commercial Product Name Order Code
EasySense Ceiling-Mount Sensor SNS100CMP (510651)
Connection Color
White Neutral Black Line Green Ground Purple SR+ Brown SR-
Compatible LED Drivers
Sensor Part Number
Driver Model Number Description
XI040C110V054VPT1 Xitanium 40W 0.1-1.1A 27-54V 120-277V SR
XI075C200V054VPT1 Xitanium 75W 0.1-2.0A 27-54V 120-277V SR
Specications available at www.philips.com/XitaniumSR.
Wiring Diagram
XITANIUM SR
LED DRIVER
LED+ LED+
LED-
LED-
RSET2 SGND
NFC ANTENNA
SR-
Connectors
SR+
RED
WHITE
LINE NEUTRAL
GROUND
NC
36-inch 18AWG solid lead wires in plenum-rated jacket from sensor stripped to 3/8". Connect white wire to brown (SR-) and red wire to purple (SR+) on driver. Four drivers per sensor maximum. Polarity must be maintained.
EASYSENSE
Electrical Information
Input Voltage Powered by SR driver low-voltage interface Current Consumption 13mA Nominal Power Consumption 200mW Standby Power < 1 W on luminaire level, including driver standby power
Occupancy Sensing
Type Passive infrared (PIR) Enable/Disable Default enabled Detection O/Auto-on; Red LED indicates “on” Hold Time 1 - 120 minutes Viewing Angle X=72°, Y = 86° ( See detection pattern) Background Light Level O or 5-100% Prolong Time 0 minutes - innity Grace Fading 0-25 sec Response Time/Fading to Switch On/O 0.7Sec
Daylight Sensing
Enable/Disable Default enabled Auto-calibration Upon power-up Viewing Angle 40° (half value sensitivity); 2% cut-o point at 75° Task Tuning Full Light Setting 5-100%
Environment & Approbation
Operating Ambient Temperature Range 0°C to 55°C Operating Humidity 0 – 95% non condensing Storage Temperature -25°C to 85°C Storage Humidity 0-95% non condensing Max Case Temperature (Tcase) 55°C Agency Approbations UL, CSA; Tested and approved for use in plenums; FCC ID:
2AF2N-SNS100; IC: 20659-SNS100
Certication California Title 20 Limited Warranty 5 years Digital Interface Xitanium SR
Other
Status Indicators Red, Yellow. Yellow LED on: Vacancy & Sensor is functional;
Red LED on: Motion is detected
No. Drivers per Sensor Four drivers per sensor maximum; Wiring polarity must be maintained Field Conguration via NFC, parameters set via Philips Field Apps
© 2016 Philips Lighting Holding B.V. All rights reserved. Philips reserves the right to make changes in specications and/or to discontinue any product at any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication. philips.com/easysense
Philips Lighting North America Corporation 10275 W. Higgins Road, Rosemont IL 60018 Tel: 800-322-2086 Fax: 888-423-1882 Customer/Technical Service: 800-372-3331 OEM Support: 866-915-5886
Philips Lighting Canada Ltd. 281 Hillmount Rd, Markham, ON, Canada L6C 2S3 Tel. 800-668-9008
PLt-1621QG_EasySenseCMP QIG 02/16 page 1 of 2 Document #: 4435 290 61451 REV. A
Operation and Conguration via Mobile App
EasySense operates immediately upon installation and energization without further commissioning. If changes from default settings are desired, EasySense can be congured via an app through NFC embedded within the sensor. The “Philips eld app” can be accessed on the Google Play Store. For a complete description of the features and default settings—as well as details on the app and recommended Android phones—refer to www.philips.com/easysense.
FCC and IC
This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Any changes or modications not expressly approved by Philips could void the user’s authority to operate this equipment. This product is intended for commercial use only.
Ce dispositif est conforme à la partie 15 des règles de la Federal Communications Commission (FCC) des États-Unis et d’Industrie Canada (IC) exempts de licence RSS norme(s). Son fonctionnement est assujetti aux deux conditions suivantes : (1) Ce dispositif ne doit pas provoquer de brouillage préjudiciable, et (2) il doit accepter tout brouillage reçu, y compris le brouillage pouvant entraîner un mauvais fonctionnement. Tous les changements ou modications non expressément approuvés par Philips, sont susceptibles d’annuler le droit de l’utilisateur à se servir de cet équipement. Ce produit est exclusivement destiné à un usage commercial.
Connection Color
Red LED+ Blue LED­Orange RSET2 Green SGND
Page 2
Sensor Dimensions (in/mm) Installation
Conguring Sensor Parameters
Step 1: Drill 2.5-inch hole in ceiling. It may be more practical to remove the ceiling tile and drill from the backside depending on material.
Step 3: Compress spring clips on sensor and insert into ceiling hole.
Step 5: Connect the wires from the sensor to the LED Driver in the xture. Connect the white wire from the sensor to the brown (SR-) terminal on the driver. Connect the red wire from the sensor to the purple (SR+) terminal on the driver. Follow xture manufacturer’s instructions for accessing the driver.
Note: Up to (4) drivers maximum can be connected to (1) EasySense. Polarity must be maintained.
EasySense operates upon energization with no further commissioning. See sensor datasheet for sensor presets and parameters that can be changed during installation. Refer to “Operation and Conguration via Mobile App” on last page for further details.
Step 2: Feed wires from sensor into ceiling hole. Wire length provided is 36-inches. Cable jacket provided is plenum-rated. Add additional wire length if necessary (18AWG solid wire recommended).
Step 4: Sensor will clamp into place. Turn sensor to appropriate position.
2.034 [51.65] REF.
Ø 2.500 [63.50] REF.
Ø 2.835 [72.00] REF.
3.193 [81.09] REF.
Note: Remove power from fixtures/drivers before performing any electrical work.