Philips LPS 100 User Manual

27
OTHER ASPECTS
5
5 1
EMERGENCY
LIGHTING
Fluorescent lamps can be dimmed with dimmable HF electronic ballasts, such as the Philips HF-REGULATOR types. Philips HF-REGULATOR ballasts can be controlled by a 1-10 V DC input from various types of regulating systems. In Fig. 15, an example is shown of an electronic potentiometer (LPS 100) regulating the dimming level via the +/- DC input on the HF-REGULATOR ballast. It can be seen that a total number of up to 100 HF-R ballasts powered by different phases can be controlled (see Fig. 16). The control wiring must be dealt with like 230 V wiring. For more information on the installation of different control systems, contact your local sales agent.
5 2
HF BALLASTS AND DIMMING
Fig. 15. LPS 100 potentiometer.
5
28
5.2 HF ballasts and dimming
Hint: The dimming control wiring in the installation should be kept separate from the mains wiring when the length of the wires exceeds 5 m. Otherwise, interference between mains and dimming wiring might occur.This could cause light flicker or 100 Hz light modulation. Tip: If separation of the wiring is not possible, use shielded control wiring.
Fig. 16. Manual HF regulation.
N
L
-
HFR
ballast
N
L
-
+
HFR
ballast
L1 L2 L3
N
C
C
LPS 100
to lamps
to lamps
-
+ L1 L2L3N
HFR luminaire
HFR luminaire
to other
HFR luminaires
+
4 3 2 1
Loading...