Specplus SPS2GFSVA332
Page 1 of 2 2' x 4' Recessed Fluorescent, Lens Frame Troffer
Static, 3 Lamp T8 or T5
Features
• 5" deep body.
• 3-1/16" lamp to lens for better lamp obscuration.
• 80.1% efficient.
• Clean contoured interior.
• One-piece housing has ribbed construction for added strength.
• Hemmed over side rails for maximum safety.
• Fixture ends turned-in for safe handling.
• Built-in earthquake clips.
• Slimline door frame with 1000 square inch lens opening.
• Door jamb finished black on four sides for positive light stop.
• True mitered corner steel lens frame.
• Spring loaded rooster head latches.
• 18 gauge steel hinges.
• Flat and regressed aluminum doors available.
• Sky lens options avalible.
• Construction to meet NYC Code or Chicago Plenum requirements is
available.
Mounting Methods Dimensions
exposed T-grid ceiling.
G
(with flat aluminum frame)
plaster ceiling/flanged.
F
(with regressed aluminum frame)
Standard VA Lens
Optional Sky Lens
1/4" max.
24"
drywall kit (see options)
Type “G”
FIxture
Order Catalog Number: FK92X4.
1-1/2" max.
15/16"
or 1"
Support
(by others)
Drywall Kit
(See Options)
Drywall
(by others)
Plaster
Opening
24-1/8"
24-11/16"
exposed T-grid ceiling
(with flat steel frame)
24"
1/4" max.
1-1/8" min.
3-3/4" max.
13/16"
1-1/2" max.
15/16" or 1"
24" (610mm)
6" (152mm)
3-1/2"
(89mm)
47-31/32" (1218mm)
Job Information Type:
Job Name:
2" x 2-1/2" access plate
with two K.O.s
(7/8" dia.)
39-1/4" (997mm)
5" (127mm)
earthquake clip
before
installation
For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595 02/10
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © Philips Group
earthquake clip
installed
(lay-in grid)
Section 1A/Folio E60-32 Rev. B
Cat. No.:
Lamp(s):
Volts/Ballast:

Specplus SPS2GFSVA332
Page 2 of 2 2' x 4' Recessed Fluorescent, Lens Frame Troffer
Static, 3 Lamp T8 or T5
Photometry Sky Lens Options
Model No. SPS2GFSVA33212003
LER = FP - 70.6 IW - 84.4 BF - 0.87
Comparative yearly lighting energy cost per
1000 lumens = $3.40
Report Number: ITL49785
Catalog Number: SPS2GFSVA33212003
Lamps: (3) F32T8
Luminaire: 2' x 4' SpecPlus with regressed
aluminum door frame and extruded
virgin acrylic shielding .095" nominal
thickness (similar to pattern 12).
Ballast: M3-RN-T8-1LL-120
Report is based on 2850 Lumens per lamp.
Efficiency: 80.1%
CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg
Spacing Criteria: 1.2 1.3
Shielding Angles: 90 90
Plane: 0-Deg 90-Deg
Luminous Length: 46.000 21.875
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01 88 84 81 79 77 75 76 74 72
02 81 74 69 70 66 63 67 64 61
03 74 66 60 62 58 54 60 56 53
04 68 59 52 56 50 46 54 49 46
05 63 53 46 50 45 40 49 44 40
06 58 48 41 46 40 36 44 39 35
07 54 44 37 42 36 32 41 35 31
08 50 40 33 38 33 28 37 32 28
09 47 37 30 35 30 26 34 29 26
10 44 34 28 33 27 23 32 27 23
CANDELA DISTRIBUTION
0.0 45.0 90.0 FLUX
0 2694 2694 2694
5 2683 2687 2692 256
15 2592 2627 2658 742
25 2391 2479 2549 1141
35 2059 2194 2292 1365
45 1609 1733 1814 1323
55 1034 1120 1217 1004
65 571 570 631 587
75 317 260 294 309
85 126 108 98 121
90 000
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 3504. 3774. 3950.
55 2776. 3007. 3267.
65 2080. 2077. 2299.
75 1886. 1547. 1749.
85 2226. 1908. 1731.
ZONAL LUMEN SUMMARY
ZONE LUMENS % LAMP % FIXT
00-030 2139 25.0 31.2
00-040 3504 41.0 51.2
00-060 5832 68.2 85.2
00-090 6848 80.1 100.0
90-180 0000 0.0 000.0
00-180 6848 80.1 100.0
S1
S2
Ordering Information
Explanation of Catalog Number. Example: SPS2GFSVA332UNVH3
S
Specplus:
Recessed
fluorescent
troffer
SP
SX
Options/Accessories
Special Lenses: Substitute VY for VA (standard) = .125" nominal pattern 12 with 7.8 oz. average weight
per square foot. Substitute VI for VA (standard) = .125" nominal pattern 12 with 6.8 oz. average weight per
square foot. Substitute S1 or S2 for VA (standard) =
further details).
Plaster Frame: Catalog Number: PF24.
Continuous Row Installation: For F type fixtures, half width flanges are required between
fixtures. Order Catalog Number: 2FC TRIM CSP (each joint).
Radio Interference Filter:
Fusing: Internal fast-blow fusing. SUFFIX A.
Internal slow-blow fusing. SUFFIX C.
Electrical Wiring Options: Consult factory.
Drywall Kit: Order Catalog Number: FK92X4. (Request Folio OA30-10 Rev. A).
Chicago Plenum: SUFFIX: C.
Specifications
Performance: In an installation of 3 lamp 32W luminaires in a room cavity ratio of 1, reflectance
80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .84. To prevent glare the VCP shall
be not less than 50 either lengthwise or crosswise (at 100fc level) and the average brightness at 65°
shall not exceed 2299 candelas per square meter. To control veiling reflections, luminaire output in
the 30°-90° zone shall not be less than 68.8%.
Static
Standard Specplus Plus
For NYC Code – Local 3 Manufactured
To order one RIF per fixture; SUFFIX: R.
To order one RIF per ballast; SUFFIX: B.
2
Fixture
Width
Ceiling Type:
G= Grid
(lay-in T bar)
F= Flanged (over
lap) Z spline and
plaster frame
FS = Flat steel
RA= Regressed
FA = Flat aluminum
Sky Acrylic Lens (see Sky Lens sell sheet for
Lens Frame:
frame.
aluminum
frame.
frame.
Lens Shielding
VA=Virgin acrylic
S1=Sky lens 1
S2=Sky lens 2
See options and
consult factory
3
Type:
(standard)
Lamp
Quantity
Specifications (continued)
Materials: Chassis parts are die-formed code gauge cold rolled steel. Housing
over and housing ends turned-in for safe handling.
Finish: Chassis exterior–black baked polyester enamel. Cavity–white baked polyester enamel
minimum 86% reflectance. Phosphate undercoating.
Lenses: VA (standard) extruded virgin acrylic, 3/16" square based female cones, running 45° to the
panel edge, .095" nominal thickness (similar to pattern 12). VY (optional) .125" nominal pattern 12
with 7.8 oz. average weight per square foot. VI (optional) .125" nominal pattern 12 with 6.8 oz. average weight per square foot.
Electrical: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of
ballast, use wire suitable for at least 90°.
Labels: I.B.E.W. UL and ULc Listed.
This product may have a mercury containing lamp.
Manage in accord with Disposal Laws. See: www.lamprecycle.org
Lamp Type/
Fixture Length:
32=32W T8
28=28W T5
54=54W T5
(Nominal 48")
Job Information Type:
Voltage:
120, 277 or
UNV=120-277
1 & 2 Lamp Elec. T8 SO * H
1-3 Lamp Elec. T8 O3 * H3 *
1 & 2 Lamp 28W Elec. T5 – P
1 & 2 Lamp 28W/54W Elec. T5 – PG ††
1-3 Lamp 54W Elec. T5 – P5 ††
LOL T8 Dimming PS –
Other dimming options. Consult factory.
†*Instant Start Standard
††Instant Start (120, 277 or UNV)
††Program Rapid Start (UNV only)
NOTE:
For T8 UNV, you must use HI, H3 Ballast Code.
Ballast Type:
<20THD <10THD
Options:
Add appropriate suffix
to catalog no., ie: (A)
I *
I †
with side rails hemmed
For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595 02/10
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © Philips Group
Section 1A/Folio E60-32 Rev. B