Philips FBP90, Lightolier FBP90 Specification

FBP90
600 LUMEN LINEAR FLUORESCENT EM. BALLAST
Page 1 of 2
FBP90
9.4"
(23.9 cm)
2.4"
(6.1 cm)
1.5"
(3.8 cm)
Features
provides 90 minutes of
emergency illumination by
utilizing existing fluorescent
lighting and produces 500-600
lumens initial emergency light
output. The FBP90 can be used
with most 17-40 W (2’-4’)
T8, T10, or T12 fluorescent
lamps without integral starters,
including U-shaped, energy
saving, and 4-pin compacts. It is
also compatible with most 1-,
2-, 3-, and 4-lamp electronic,
standard, energy saving and
dimming AC ballasts. See lamp
operation for specific lamp
types.
Housing: Housing is
constructed of 20 gauge steel
with a high temperature
powder coat paint finish. Slim
housing allows for wireway
channel mounting on most
lighting fixtures.
Operating Temperature
Range:
32°F (0°C) to 131°F (55°C)
Electronics: 120/277 VAC
dual voltage input with surge
protected, solid-state charging
circuitry provides for a reliable
charging system. Charging
system is complete with AC
indicator lamp and test switch.
Electrical Specifications:
I
nput Power: 4 W max.
Battery
Maintenance free, sealed nickel
cadmium battery. Supplies 90
minutes of emergency power.
Estimated service life of 10
years.
Lamp Operation1: Operates
the following lamp types2:
T8 linear fluorescent (two lamp
operation)
T12 linear fluorescent
T9 circline
T12 U-bent
T5 long compact fluorescent
Notes:
1) Consult factory for compatibility, operation and per formance of product with lamp types not listed.
2) See table 1 on back for specif ic lamp performance and operation.
Code Compliance
UL 924 and optional UL damp
location listed. NFPA 70, NFPA
101, NEC, BOCA, OSHA and
IBC illumination standards.
Suitable for use in sealed and
gasketed luminaires.
Warranty
One year full electronics
w
arranty. One year full battery
warranty.
Job Information Type:
Job Name:
Cat. No.:
Notes:
600 LUMEN LINEAR FLUORESCENT EM. BALLAST
O
Ordering Information
FBP90
Series
FBP90 = 600 Lumen Max. Output Fluorescent E mergency B allast for One Lamp Operation
Note
1) Some option combinations may impact UL listing. Consult factor y for specif ics.
Lamp Operation and Performance
Table 1
LAMP
WATT.
TYPE
F20T12 F30T12 F40T12
F40T12/U
F48T10
F17T8
F25T8
F32T8
F32T8/U
F40T8 FC6T9
FC8T9 FC12T9 FC16T9
F39/36BX F40/30BX
NOTES
1) Maximum non -emergency lumen output can var y based on lamp manufacturer, ambient operating temper ature, and ballast manufacturer.
2) Maximum emergency lumen output is based on total output of one or two lamps, and can var y based on lamp manufacturer and ambient operating temperature.
3) Consult factory for compatibility, operation and performance of lamp types not listed.
20 30 40 40
110
17 25 32 32 40 20 22 32 40 39 40
BASE TYPE
G13/Med Bi- Pin G13/Med Bi- Pin G13/Med Bi- Pin G13/Med Bi- Pin R17D/Rec es se d G13/Med Bi- Pin G13/Med Bi- Pin G13/Med Bi- Pin G13/Med Bi- Pin G13/Med Bi- Pin
G10Q/4 -Pin G10Q/4 -Pin G10Q/4 -Pin G10Q/4 -Pin
2G11/4-Pin 2G11/4-Pin
ptions
1
= Special Input Transformer
EX
(specify volt age and frequency)
DL = Damp Location Listing
NON-EMERGENCY
MAX . LUM EN OUTPUT
1275 2350 2650 3100 6200 1350 2150 2950 2700 3725
800 110 0 1950 2700 2850 3150
Accessories (order as a separate item) CCAPS = Wire Cover Kit for E xternal Mounting RTS = Remote Test Plate RTS2 = Remote Test Switch & Pilot Light Kit (includes plate)
EMERGENCY OP.
MAX . LUM EN OUTPUT
500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 500-600 350-450
EMERGENCY
LAMP OPERATION
One One One One One One One One One One One One One One One One
FBP90
Page 2 of 2
Philips Lightolier e: lol.webmaster@philips.com t: (508) 679-8131 w: www.lightolier.com
FBP90 August 28, 2012
Specifications are subject to change without notice. © Koninklijke Philips Electronics N.V., 2012. All rights reserved.
Job Information Type: