Lighting Systems EC2-9

Page 1 of 3 Energos Control System 2-Light T8 per 4' (121.92cm) (Nominal) Lens

Feature Specifications - Energos Control System (For standard Energos fixtures consult appropriate EG spec sheets)

Feature Specifications Electrical

Dedicated low voltage (24 VDC) circuit controls the Energos Control Systems. The line voltage circuits control all the standard ballast functions including A/B switch ing, Dimming and Emergency Battery Pack operations.
1. End Cap Sensor Mounting 2. Mid-mounted 8' (243.84cm) Sensor Mounting
ECS occupancy sensors are available in two variations:
• Mounted in the end cap.
• The middle of an 8' (243.84cm) module.
The ECS sysfem confrol-cenfer is fhe Power Pack. The Power Pack, confained in each Masfer Module, inferrupfs fhe circuifs when paramefers dicfafe. The Power Pack can confrol up fo 600 waffs 120 VAC, and 1300 waffs 277 VAC. A maximum of 10 sensors can be used on a single Power Pack. There is no limifafion fo the number of Power Packs fhaf can be "daisy-chained" fo a single ECS circuif.
Emergency baffery packs can be used in conjuncfion wifh ECS for emergency
egress lighfing since all lisfed packs operafe for a minimum of 90 minufes.
EM Packs can be used as momenfary lighfing for emergency circuif for power
fransifions, and smaller packs are recommended for fhis purpose.
Dimming ballasfs can be used in conjuncfion wifh ECS. However, fhe confrol sysfem will only perform ON or OFF operafions and will not affect the level of dim ming sef by fhe dimming ballasfs.
Facfory insfalled ballasf disconnecf allows fhe ballasf fo be disconnecfed from and reconnecfed fo incoming power under load wifhouf fuming fhe enfire circuif off.
Serial Row Linking (SRL)
For every run fhaf SRL is required, order fhe appropriafe SRL end sef from page 2 of this Specification Sheet. Consult Energos Application Guide for more derailed definifions and examples.
provides mulfiple confinuous row communicafion.

Mountings

Cable suspension disfances are on 48" (121.92cm) and 96" (243.84cm) cenfers, and consisf of a 4 1/2" (11.43cm) diamefer canopy finished whife enamel. A 1/16" (0.16cm) diamefer sfainless sfeel aircraff cable accomplishes suspension and is adjusfable from 12" (30.48cm) fo 36" (91.44cm). Power feeds are 18 gauge silver braided cord wifh clear jackef.
Occupancy Sensors:
• Time delay is facfory pre-sef fo 30 minufes.
• Time delay can be field adjusfed from 30 minufes fo a minimum of 30 seconds.
• Daylighf hold-off is facfory pre-sef fo 120 ff-candles (1291.67m-candles).
• Daylighf hold-off is field adjusfable from 120 ff-candles (1291.67m-candles) down fo 10 ff-candles (107.64m-candles).
• Sensors are designed for a defecfion area (sensifivify diamefer) of 16' (487.68cm) when suspended 10' (304.80cm) AFF. Lowering fhe sensor produces a smaller area of detection. See chart and diagram for additional information.

Coverage Diameter

Energos Occupancy Sensor
Coverage Zone Chart
Height of Sensor Broadcast Diameter Task Diameter
10' 0" (304.80cm) 16' 0" (487.68cm) 8' 0" (243.84cm)
9' 0" (274.32cm) 14' 5" (427.99cm) 7' 3" (214.12cm) 8' 0" (243.84cm) 12' 10" (391.16cm) 6' 5" (184.15cm) 7' 0" (213.36cm) 11'3" (336.04cm) 5' 7" (154.18cm)
Job Information
Job Name: Cat. No.:
Lamp(s): Notes:
1 Type:
Lightolier is a Philips group brand
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. www.lightolier.com © 2008 Philips Group • C0808
PHILIPS
Page 2
LIGHTOLIIËR*
Lighting Systems EC2-9

Page 2 of 3 Energos Control System 2-Light T8 per 4' (121.92cm) (Nominal) Lens

Control Ordering Information

Family Series Lamping &
Distribution
Ballast Lamp Shielding Length Voltage Finish Options
(Blank)
T
= Tandem Switch
E
= Emergency
Ordering Instructions
End Cap ECS Systems
1. Order Master 4' (121.92cm) or 8' (243.84cm) ECS Module.
2. Order Power Feed End Set.

ECS Sensor Sample Runs

4' Run:
4' (121.92cm) Master Module with Single Sensor End Set.
8' Run:
8' (243.84cm) Master Module and standard Energos End Set.
8' Run:
8' (243.84cm) Master Module and Dual Sensor End Set.
12' Run:
Sensor End Set, and Intermediate Cable Assembly.
8' (243.84cm) Master Module, 4' (121.92cm) Slave Module, Dual
Continuous Row Mounted ECS Systems:
1. Determine run length
2. Order a minimum of one master per run. Please see Application Guide for master requirements on runs that exceed 16' (487.68cm).
3. Order the required remaining Master and Slave modules to complete the run.
4. Order Power Feed End Set.
5. Order one CABLE ASSEMBLY per MODULE minus one per run.
6. Order additional Single Cable & Cord Sets for every Master Module in run.

ECS End Sets

f/1
Single Sensor End Set EC2SE36W
Single Sensor SRL End Set EC2SR36W
Dual Sensor End Set EC2DE36W
Dual Sensor SRL End Set EC2DR36W
Single Cable & Power Cord EGCC36
16' Run:
8' (243.84cm) Master Module, 8' (243.84cm) Slave Module, standard
Energos End Set, and Intermediate Cable Assembly.
16' Run:
8' (243.84cm) Master Module, 8' (243.84cm) Slave Module, Single
Sensor End Set, and Intermediate Cable Assembly.
16' Run:
Sensor End Set, and Intermediate Cable Assembly.
Notes:
1. See page 1 of Specification Sheet or consult Application Guide for the definition of Serial
2. Consult the matching EG specification sheet for Luminaire related specifications (i.e.
8' (243.84cm) Master Module, 8' (243.84cm) Slave Module, Single
Row Linking (SRL).
Housing materials, shielding, mounting dimensions, and photometry).
Lightolier is a Philips group brand
Standard End Set EG2EC36W
SRL Standard
End Set EC2ER36W
Job Information Type:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. www.llghtoller.com © 2008 Philips Group • 00808
PHILIPS
Page 3
LIGHTOLIIÈR*
Lighting Systems EC2-9

Page 3 of 3 Energos Control System 2-Light T8 per 4' (121.92cm) (Nominal) Lens

Ballast Ordering Information Lamp Ordering Information
Design Lamp Type Ballast Factor Start Type THD %
D T8 0.71 Program <10 E T8 0.88 Program <10 H DimT8 1.00/.05 Program <10
Lamp and Ballast System Data
Design
*25°C Rating All data is per 1 lamp on a two lamp system at 277 VAC.
Data is based on Osram Sylvania specifications.
When ordering no lamps provided by Lightolier, use lamp code "Z"
Lamp Type
(T8 or T5)
DA T8 0.71 <10 28 2725 3000 2199 20.0 96.74 24000 Program DB T8 0.71 <10 28 2725 3500 2199 20.0 96.74 24000 Program DC T8 0.71 <10 28 2725 4100 2199 20.0 96.74 24000 Program DD T8 0.71 <10 30 2850 3000 2299 21.5 94.12 24000 Program DE T8 0.71 <10 30 2850 3500 2299 21.5 94.12 24000 Program
DF T8 0.71 <10 30 2850 4100 2299 21.5 94.12 24000 Program DG T8 0.71 <10 32 3000 3000 2420 23.0 92.61 24000 Program DH T8 0.71 <10 32 3000 3500 2420 23.0 92.61 24000 Program
DI T8 0.71 <10 32 3000 4100 2420 23.0 92.61 24000 Program
DJ T8 0.71 <10 32 3100 3000 2501 23.0 95.70 30000 Program DK T8 0.71 <10 32 3100 3500 2501 23.0 95.70 30000 Program
DL T8 0.71 <10 32 3150 4100 2541 23.0 97.24 30000 Program EA T8 0.88 <10 28 2725 3000 2725 25.5 94.04 24000 Program EB T8 0.88 <10 28 2725 3500 2725 25.5 94.04 24000 Program EC T8 0.88 <10 28 2725 4100 2725 25.5 94.04 24000 Program ED T8 0.88 <10 30 2850 3000 2850 27.5 91.20 24000 Program EE T8 0.88 <10 30 2850 3500 2850 27.5 91.20 24000 Program EE T8 0.88 <10 30 2850 4100 2850 27.5 91.20 24000 Program EG T8 0.88 <10 32 3000 3000 3000 29.0 91.03 24000 Program EH T8 0.88 <10 32 3000 3500 3000 29.0 91.03 24000 Program
El T8 0.88 <10 32 3000 4100 3000 29.0 91.03 24000 Program EJ T8 0.88 <10 32 3100 3000 3100 29.0 94.07 24000 Program EK T8 0.88 <10 32 3100 3500 3100 29.0 94.07 24000 Program EL T8 0.88 <10 32 3150 4100 3150 29.0 95.59 24000 Program HG T8 DIM 1.0/0.5 <10 32 2850 3000 2850/ 143 34/8 83.80 NA Program HH T8 DIM 1.0/0.5 <10 32 2850 3500 2850 / 143 34/8 83.80 NA Program
HI T8 DIM 1.0/0.5 <10 32 2850 4100 2850 / 143 34/ 8 83.80 NA Program
Ballast
Factor (BF)
Ballast
THD (%)
Lamp Rated
Wattage
Lamp
Rated
Output
Design Lamp Type Wattage
A T8 28 2725 3000 B T8 28 2725 3500 C T8 28 2725 4100 D T8 30 2850 3000
E T8 30 2850 3500
F T8 30 2850 4100 G T8 32 3000 3000 H T8 32 3000 3500
1 T8 32 3000 4100
J T8 32 3100 3000
K T8 32 3100 3500
L T8 32 3150 4100
Lamp
Color
(Kelvin)
IES Output
(lumens)
System
Input Watts
Rated Output
System
Efficacy
(lum/watt)
(Lumens)
System
Lamp Life
(Hours)
Color(K)
Start Type
Do not alter lumen values or ballast factor light losses when completing calculations using Energos lES files. Eiles have already been adjusfed. The lumen
value for fhe lamp (wifhin a Lighfing Design program) will be fhe lES Oupuf value
shown on fhis fable.
The lamp life fable demonsfrafes fhe effecfs of shortened cycle-times with both
program start and instant start ballasts. The graph shows that instant ballasts are susceptible to shortened lamp life if short cycle periods of less fhan 3 hours are used. Eor cycle periods of greaferfhan 3 hours program sfart ballasf are not required.
Lightolier is a Philips group brand
Lamp Life Table using program sfart and instant start ballasts.