Philips 6MIC, 2MIC User Manual

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.philips.com/luminaires
9140053562 February 2016
WARNING – Shut off AC power to branch circuits to which units will be connected. All wiring should be per N.E.C. Articles 501-4(b) and local codes.
To maintain warranty, equipment with batteries must be installed or placed on charge within prescribed period after shipment.
6MIC/2MIC Series
25W-50W Emergency
120V/230V/240V Luminaire
Service Questions Call: 910-259-1000
INSTALLATION AND
OPERATING
INSTRUCTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
All servicing should be performed by qualified personnel only.
Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Do not use this equipment for other than intended use.
Do not use outdoors.
Do not let supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
CAUTION: Halogen cycle lamp(s) are used in this equipment. To avoid shattering: Do not operate lamp in excess of rated voltage, protect lamp against abrasion and scratches and against liquids when lamp is operating, dispose of lamp with care.
Halogen cycle lamps operate at high temperatures. Do not store or place flammable materials near lamp.
CAUTION: “To avoid electrical overload, total connected lamp load (factory and field installed) should not exceed output rating”.
SAVE THESE
Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.philips.com/luminaires
Philips Lighting Canada Ltd. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
www.philips.com/luminaires
9140053579 February 2016
INSTRUCTIONS
GENERAL INSTRUCTIONS
1) Begin the installation process by
determining mounting options.
2) The slotted, circular keyways can be used to
secure the housing to a standard junction box. The junction box must be secured sufficiently to handle the weight of the unit.
3) Additionally, two slotted vertical keyway
slots (Figure 1) may be used to attach the housing to independent anchor supports. Use three #8 toggle bolts (supplied by others) for securing to wallboard or hollow concrete walls. If the wiring is wall recessed, run wires through center hole of housing in preparation for unit wiring.
Figure 1
HOOKUP INSTRUCTIONS
Standard Units:
Connect A.C. service to unit charger leads: Brown = 240 VAC Violet = 230 VAC Black = 120 VAC Light Blue = Common Green = Ground
1. Connect remote lamps, if applicable.
Connect orange lead to RL+ and yellow lead to RL-. Ensure total unit load (including internal lamps) does not exceed unit rating
2. Install battery(ies). Refer to next section and
illustrations.
3. Adjust head(s) to illuminate desired area(s).
4. Close cover. Ensure electrical wires and
membrane switch cable remains inside unit and do not interfere with cover closure.
INSTALLING BATTERIES
1. Units may ship without batteries installed
depending on the wattage of the unit. For lead units, battery wiring harnesses are already connected to PCB assembly and connection to the batteries is required. In the case of Nicad units, connection of battery harness to the PCB is required.
2. Install and wire batteries as appropriate.
(See Page 6 for battery configurations)
3. Tighten straps to secure batteries inside unit.
OPERATING INSTRUCTIONS
1. Normal Power-Up Sequence
At power-up, the red and green LED indicators will alternately flash for one to two seconds. Next, the unit will go through a “Power-up Quick Test” with the green LED flashing quickly. If no power-up faults are detected, the green LED will then flash slowly for approximately 36-72 hours to indicate the unit is in a high rate of charge.
If any faults are detected during ‘Power-up
Quick Test’, these will be indicated by a
flashing red LED indicator (Reference Table
2). The red LED may be accompanied by a buzzer. In the event of a unit error, this buzzer may be disabled by a short press of the test switch and will remain disabled for a period of 196 hours (8 days). After the fault has been corrected, the red LED flash and buzzer will be cleared automatically and the unit will return to normal operation.
Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.philips.com/luminaires
Philips Lighting Canada Ltd. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
www.philips.com/luminaires
9140053579 February 2016
2. Press and hold the ‘TEST’ button. The
lamps should illuminate and the green indicator lamp indicate steady green while the lamps are on.
3. Release ‘TEST’ button. Lamps should
extinguish and the green indicator lamp should be steady green if batteries are in maintenance charge or blinking indicating a high rate of charge.
4. Leave A.C. connected for a minimum of 24
hours before performing any abbreviated testing. Full recharge of batteries may take up to 72 hours.
5. Once energized, the unit will wait 36 hours
while the batteries are charged and then perform an automatic lamp load calculation. The system will then detect and indicate a load loss of 10% and indicate a lamp failure. Replace lamps as required. Upon lamp replacement, run any manual self-test and the system will return to normal operating status.
6. If, after installation and calibration, lamp
load is increased or decreased the system will need to be manually calibrated for the new total load. To re-calibrate, press the test switch four times. The unit will illuminate for 30 seconds and then return to normal operation status.
7. Lamp re-calibration can also be
accomplished with the optional remote
control by pressing in sequence, ‘Silence,
Silence, Cancel, Silence’. The lamps will
illuminate for a brief time and then return to normal operation status.
SELF-TEST / SELF-DIAGNOSTICS
1. This unit’s charge / discharge circuit is
microprocessor controlled. The charging circuit consists of a two stage charging program which will charge the batteries at a high rate of charge and once the batteries approach the correct float voltage, the charger will switch to a maintenance charge mode.
2. The microprocessor controls and detects the
following conditions:
a. Low Voltage Disconnect (LVD) –
Disconnects battery power from unit when battery voltage drops below
87.5% of nominal voltage to protect the batteries from deep discharge.
b. AC Brownout – Disconnects the unit
from line voltage and transfers the unit to emergency mode when the line voltage sags to 80% or below.
c. AC Lock OUT – When line voltage
and battery voltage is removed from the unit, the unit will remain off until line voltage is returned. Used to place the unit into hibernation.
d. Temperature Compensation
Battery voltage temperature compensation is performed by the microprocessor on a continual basis based on unit ambient temperature conditions.
e. Lamp Load Failure Detect
Indicated a load failure when more than 10% of the original load is determined to be removed.
f. Reverse battery connection polarity.
3. For information regarding failure mode
indications, see Failure Codes Table 2 below.
Loading...
+ 5 hidden pages