Ceramalux®High Pressure Sodium Non-Cycling
1000 Watt ED-25 (Clear) Lamp
featuring ALTO®Lamp Technology
◗ Ordering Information
Ordering Code C1000S52/ALTO NC HPS
ANSI Designation S52
Product Number 157263
Description High Pressure Sodium
TCLP*Compliant
Non-Cycling
Package Quantity 6
◗ Physical Characteristics
Bulb Size ED-25
Bulb Finish Clear
Base Mogul Screw
Max. Overall Length (MOL) 15.08" (383mm)
Light Center Length (LCL) 8.74" (222mm)
Arc Length 8.5" (215mm)
Arc Tube Length 9.6" (243mm)
Arc Tube Material Aluminum Oxide
Operating Position Universal
Maximum Permissible Bulb Temperature 400ºC (752°F)
Maximum Permissible Base Temperature 210ºC (410°F)
Maximum Bulb to Base Eccentricity 3°
Maximum Arc Tube to Base Eccentricity 3°
◗ Operating Characteristics (Photometric)
Approximate Initial Lumens
Approximate Mean Lumen
Rated Average Life, Hours
Correlated ColorTemperature (CCT) 2100 K
CIE Chromaticity Approximate x-.515, y-.420
Color Rendering Index (CRI) 20
Efficacy (LPW) 130
1
2
3
130,000
117,000
30,000
◗ Operating Position
Universal
◗ TCLP*Characteristics
Toxicity Characteristic Leaching Procedure (Federal TCLP) Results
Hg
EPA Limit (mg/l) Max 0.200 5.00
C1000S52/ALTO NC HPS 0.062 <0.31
Mercury (mg/lamps) Max 11
Pb
Philips Lighting Company
200 Franklin Square Drive
P.O. Box 6800
Somerset, NJ 08875-6800
1-800-555-0050
Division of Philips Electronics North America Corporation
A
pdated 1/07 TDS-157263
U
www.philips.com
Philips Lighting
281 Hillmount Road
Markham, Ontario
Canada L6C 2S3
1-800-555-0050
A Division of Philips Electronics Ltd.
Ceramalux®High Pressure Sodium Non-Cycling 1000 Watt ED-25 (Clear) Lamp featuring ALTO
lectrical Data
E
Lamp Watts (Nominal). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000
Lamp Operating Voltage (rms) (Nominal) . . . . . . . . . . . . . . . . . . 275V
Initial Lamp Voltage Range (rms). . . . . . . . . . . . . . . . . . . . . . . . . . 250–300V
Lamp Operating Current (Amps) (rms) (Nominal). . . . . . . . . . 4.7
Maximum Lamp Star ting Current (Amps)(rms) . . . . . . . . . . . . . 8.0
Lamp Current Crest Factor (Maximum) . . . . . . . . . . . . . . . . . . . 1.8
Warm-up Time to 80% of Output . . . . . . . . . . . . . . . . . . . . . . . . 7 Minutes
Re-strike Time for Hot Lamp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Minutes
Ballast Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ANSI S52
Ballast Open Circuit Voltage (Minimum): . . . . . . . . . . . . . . . . . . 456 Vrms
Pulse Peak Volts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2675
Pulse Width @ 90% Peak. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 µs Minimum at 2700 Volts
Pulse Frequency (Minimum)
Lag Ballast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 per Cycle
Lead Circuit Ballast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 per Cycle
Minimum Operating Temperature. . . . . . . . . . . . . . . . . . . . . . . . . -30°C
Reference Ballast Impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77Ω (ohms) minimum at 480V
Maximum Lamp Watts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Minimum Lamp Watts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 750
Maximum Voltage Increase by Fixture . . . . . . . . . . . . . . . . . . . . . 25V
Footnotes:
1) Measured at 100 hours of life in ver tical and horizontal positions.
2) Approximate mean lumen output at 40% of lamp rated average life. Measured in ver tical and hor izontal oper ating positions.
) Rated average life is the life obtained, on the average, from large representative groups of lamps in laborator y tests under controlled conditions at 10 or more operating hours per start.
3
t is based on survival of at least 65% of the lamps and allows for individual lamps or groups of lamps to vary considerably from the average.
I
*The TCLP is the US EPA’sToxicity Characteristic Leaching Procedure.
WARNINGS, CAUTIONS AND OPERATING INSTRUCTIONS
for Ceramalux High Pressure Sodium Lamps
“WARNING:These lamps must be operated in fixtures designed for use with
R
High Pressure Sodium lamps.The fixture wattage rating must match the wattage
indicated on the outer glass bulb. Do not scratch the outer bulb or subject it to pressure
as this could cause the outer bulb to crack or shatter.A partial vacuum in the outer bulb
may cause glass to fly if the glass is struck. Operating the lamp improperly may result in
PERSONAL INJURY, PROPERTY DAMAGE, BURNS AND FIRE.
1) If the outer glass bulb is broken, shut off power immediately and remove the lamp
after it has cooled.
2) Use only auxiliary equipment meeting Philips and/or ANSI standards. Use within
voltage limits recommended by ballast manufacturer.
A. Operate lamp only within specified limits of operation.
B. For total supply load refer to ballast manufacturers electrical data.
3) Protect lamp base, socket and wiring against moisture, corrosive atmospheres and
excessive heat.
4) Replace the lamp if the outer glass bulb has been scratched, cracked or damaged
in any way.
5) If a lamp bulb support is used, be sure to insulate the support electrically so as to
avoid possible decomposition of the bulb glass.
6) Do not use this lamp in a fixture which redirects a substantial portion of the
energy toward the arc tube and its immediate vicinity, as this may lead to very
early lamp failure.
7) Take care in handling and disposing of lamps. If arc tube is broken, avoid skin
contact with any of the contents or fragments.
8) The arc tube of this lamp contains sodium and mercury. Dispose of in accordance
with federal, state and local requirements.
Subject to change without notice)
(
®
Lamp Technology