Pfannenberg Quadro F12-SIL Catalog Page

PRODUCTS VISUAL SIGNALING DEVICES
FLASHING LIGHT 10 J Quadro F12-SIL
Integrated safety in sturdy Quadro-Design.
• To signal dangerous situations in safety-relevant application such as process and plant safety, e.g.
- leaks/gas warning, high-pressure/overfi lling and machine safety, e.g. as
- start-up warning, muting indication, machine stop delay warning
• By means of integrated self-monitoring of the devices the normative required, regular inspection of warning devices is ensured.
• The warning devices can be implemented in Safety Instrumented Sys­tems (SIS) up to SIL 2/PLd.
We would be more than happy to provide all safety-technical key data.
IP 66
Schutzarten
IP 67 IK08
impact-proof housing
+55 °C
–30 °C
operating temperature
10
Years
warranty
PRODUCT Quadro F12-SIL
DATA
Rated voltage
Operating range 195–253 V 95–127 V 18–30 V
Nominal current consumption
Alarm contact
max. switching power (AC) 1,500 VA
recommended min. load
Flash rate 1 Hz = 60 flashes/min Flash energy 10 J Light intensity (DIN 5037) Max. viewing distance 348 m Operating temperature –30 °C ... +55 °C Storage temperature –40 °C ... +70 °C Relative humidity 100 % Protection system (EN 60529) IP 66 | IP 67, mounting arbitrary Impact resistance (EN 50102) IK08 Protection class II Service life of the light source light emission still 70 % after 8,000,000 flashes
Material
Cable entry 2x M20 bottom side / 2x M20/M32 sideways Connecting terminal cage clamp 0.08–2.5 mm
Mounting
Weight 600 g
1
with a clear lens
flashing light 250 mA 350 mA 700 mA
diagnostics channel 100 mA 100 mA 65 mA
contact version positively driven contact (1 x NC, 1 x NO) switching current max. 6 A switching voltage max. 250 V AC
1
lens
housing polycarbonate (PC), RAL 7035
external lugs 113 x 153 mm – M5 or 127.1 x 127.1 mm – M5
internal holes 113 x 113 mm
230 V 115 V 24 V
AC 50 | 60 Hz AC 50 | 60 Hz DC
>50 mW
225 cd
polycarbonate (PC)
2
DIMENSIONS
130
80
130
130
VISUAL SIGNALING DEVICES
113
25
47
2x M20 (M32 prepared)
Additional mounting possible via external lugs (included).
CONNECTION DIAGRAMS
alarm output S1 (NC) alarm output S2 (NO)
115/230 V AC
115/230 V AC
operating voltage flashing light
operating voltage flash monitoring
2x M20 prepared
alarm output S1 (NC) alarm output S2 (NO)
37
113
24 V DC
24 V DC
39
mounting holes
operating voltage flashing light
operating voltage flash monitoring
ARTICLE NO.
Quadro F12-SIL
LENS COLOUR 230 V AC 24 V DC
21041103601 21041803601 21041104601 21041804601 21041105601 21041805601
Article numbers for other colours and voltages on request.
CONFORMITY TO STANDARDS
The visual characteristics of flashing lights conform to the European standard DIN EN 842; “Machine safety – visual alarm signals”. Requirements contained in the DIN EN 981 standard; “Machine safety – system of acoustic and visual alarm and information signals”, can be fulfilled.
The colours “red” for the emergency signal and “yellow” for the warning signal conform to the requirements of IEC 73 / DIN EN 60073 / VDE 0199; “Coding of
display devices and control elements using colours and supplementary means”.
The visual alarms fulfill the requirements to the functional safety according to: EN 61508 Functional safety of electrical/electronic/programmable electronic safety-related systems EN 61511 Functional safety - Safety instrumented systems for the process industry sector The devices can be used in safety related control systems in accordance with the following standards: EN ISO 13849-1 Safety of machinery – Safety related parts of control systems – part 1 EN 62061 Safety of machinery – Functional safety of electrical/electronic/programmable electronic safety-related systems
Loading...