This manual contains information on the installation
and operation of PWS Series bolt-on cooling units
intended to be door and side mounted on electrical
panels.
These devices are designed to dissipate heat from
sealed electrical panel enclosures and housings.
The temperature of the cooling liquid supplied to
the air/water heat exchanger must be at least 10° C
colder than the heat exchanger inlet air temperature
in order to ensure that the unit function correctly.
Conventions used:
Hint: A hint contains additional information on the
action or instruction being described
WARNING!
If the information following this is not strictly
followed there is a danger to health or life.
WARNING!
If the information following this is not strictly
followed there is a danger to health or life
due to electrical shock.
The technical data specific to each cooling unit,
including installation connections and operational
data, are contained on a separate data sheet
supplied with each unit.
1
Page 4
SECTION 2: RECEIVING INSPECTION
2.1 Unpacking
Prior to and during unpacking the cooling unit,
visually inspect it to determine if any damage has
occurred during shipping. Make sure that it does not
contain any loose components. Before discarding
any packaging materials: Look for loose parts, dented
or scratched panels or fluids.
If any damage is noted it shall be reported
immediately to the delivering carrier and a claim
should be filed with them. Pfannenberg cannot
accept responsibility for freight damage that may
occur; we will assist you in any way possible if the
need arises to file a claim.
In case of a warranty claim, the following information
is required: exact details of the fault (including
photographs, if possible), the cooling unit part
number and serial number are required.
WARNING!
Burrs caused by production may be present
on the metal edges of the cooling unit. Always
wear protective gloves when carrying out
installation or maintenance work.
2.2 Included Items
The following items should be included:
Cooling unit
Mounting cutout
Manual
Technical Data Sheet
PWS Series accessory pack typically includes:
• Sealing strips
• Threaded mounting studs
• Mounting bolts, nuts and washers
• Condensate hose (PWS 7k series only)
• Door contact connector/jumper
2.3 Review of ID Plate
The ID plate is located on the left side of the
cooling unit. The technical data specific to
the cooling unit is located on the ID plate as
shown below.
Power
Consumption
Rated Current
Pre-Fuse T
Air Flow Rate
Water Flow Rate
Part Number
Nominal
Operating
Voltage
(50 Hz Value) (60 Hz Value)
(50 Hz Value) (60 Hz Value)
Model Number
Nominal
Operating
Frequency
(50 Hz Value) (60 Hz Value)
(50 Hz Value)
(60 Hz Value)
Serial #
Rated Cooling
Capacity
Starting
Current
Max Allowable
Water Pressure
2
Page 5
PWS Series Air/Water Heat Exchangers
SECTION 3: HANDLING
3.1 Transporting
The cooling unit shall only be moved in the fully
assembled condition.
If the cooling unit is being shipped with an electrical
panel enclosure it shall be packed separately from
the electrical enclosure.
3.2 Storage
The cooling unit shall not be exposed to
temperatures exceeding +70ºC.
If the device is stored or transported at temperatures
below freezing, the water circuit must be completely
emptied using compressed air.
WARNING!
Failure to observe these requirements
will void the warranty.
SECTION 4: INSTALLATION
4.1 Pre-installation testing
Before mounting the cooling unit to the electrical
panel enclosure it should be tested to verify function.
Note: All devices are checked for leaks before leaving
the factory.
We recommend installing a door contact switch
to turn the device off when the electrical panel
enclosure door is opened.
4.2 Installation onto the electrical panel
Before connecting the cooling unit to the power
supply, verify that the following are correct:
Voltage must be within ± 10% of the value listed on
the ID plate.
Voltage frequency must be within ± 3 Hz of the value
listed on the ID plate
Ambient temperature must be below +55ºC (for
options see “setting the operating parameters”
section)
Place the drilling template supplied with the cooling
unit onto the applicable mounting surface of the
electrical panel enclosure.
WARNING!
Metal chips from drilling and cutting the openings
may damage the electrical panel enclosure. Take
precautions required to prevent chips and debris
from getting into the enclosure.
WARNING!
Watch out for sharp edges created when drilling
and/or cutting the enclosure.
Drill holes in the electrical panel enclosure to
match the unit and cut out air flow openings.
3
Install the two supplied stud bolts (in the accessory
pack) into the top two mounting hole locations of
the cooling unit.
Page 6
WARNING!
Please note the information on the “Thread
Reach for Set Screw” label attached to the
cooling unit. If the noted installed thread depth
is exceeded the cooling unit may be damaged.
Install the cooling unit mounting insulation strips (in
the accessory pack) to the cooling unit as noted on
the individual cooling unit information sheet.
Make sure that the insulation strips are correctly
attached and placed correctly on the cooling unit.
The correct fitting and location of the insulation
strips is required for the proper operation of the
cooling unit.
Attach the cooling unit to the electrical panel
enclosure by use of the stud bolts inserted as
described above.
The cooling unit power supply shall be fused as
indicated on the unit ID plate by means of a series
connected power line connection.
All power connections and / or repairs, if or when
required, shall only be carried out by authorized,
trained electricians.
Power supply connection
PWS 7K series provide a molded cord suitable for the
rated voltage of the unit.
PWS 3k series have hard wire terminal
(PWS 7K series only)
WARNING!
Do not move the cooling unit by the piping.
Doing so will damage the cooling unit and
void the warranty.
The cooling unit is then completely attached to the
electrical panel enclosure from inside the enclosure
by use of the screws and washers supplied in the
accessory pack.
Tighten the fasteners until the cooling unit insulation
strips are compressed to a thickness of 2 mm
(approximately .080”)
Install Drain hose barb (provided in accessory bag
for PWS 3k series only) then attach the condensate
drainage hose to the drain.
Reinstall the cover using the original mounting
screws.
4.3 Power connection
WARNING!
Make sure that the main power supply to the
cooling unit is turned off while making the
power connections.
Both the main power supply voltage and frequency
shall correspond to the nominal values shown on the
cooling unit ID plate.
Connect the main power supply to the cooling unit
as indicated by the label located on the cooling unit
and on the individual cooling unit data sheet.
PWS 3K series has multiple options for connections,
a barb is provided for use with flexible pressureresistant hose and clamp.
Observe flow direction (labels on the device located
next to the water connections) Check for leaks.
Protect the water circuit against contamination and
excessive pressure (please refer to the “Water Quality
Notes“ section. The maximum permissible operating
pressure is 10 Bar.
4
Page 7
PWS Series Air/Water Heat Exchangers
SECTION 4: INSTALLATION CON'T
4.5 Condensation Water Connection
Drainage hose must be secured in place with clamps.
To ensure reliable drainage of condensation water,
please note the following:
The drain hose shall not be kinked. Hose cross-section
must not be constricted in any way. The drainage hose
must slope in the right direction.
To avoid excessive condensation water amounts,
please note the following:
Adjust the cooling water temperature to the cooling
performance required.
Only use the device on sealed electrical panels and
housings.
Set the desired temperature only as low as is really
necessary (to avoid the cooled air from dropping
below the dewpoint).
4.6 Door Contact
To avoid an increased production of condensate
and for safety reasons a door limit switch should be
connected to the terminals provided.
WARNING!
No external voltage may be applied to the door contact
circuit or damage to the cooling unit may result.
In order to prevent any interference from outside
signals, it is recommended that a shielded cable with
a twisted pair leads be used for the connection. The
cable shielding can be connected on one side to the PE
(ground) connection point provided on the cooling unit.
If the use of a shielded cable is not possible, the cable
that is used must not be routed in the immediate
vicinity of potential sources of interference such as
power supply lines , components with a relatively high
electromagnetic emission (EMI), etc.
If no door contact switch is used, the connecting
terminals must be jumpered for the cooling unit to
operate.
5
Page 8
SECTION 5: OPERATING CONDITIONS
5.1 Requirements
Before connecting the cooling unit to the power
supply, verify that the following are correct.
Voltage must be within ± 10% of the value listed on
the ID plate.
Voltage frequency must be within ± 3 Hz of the value
listed on the ID plate
Ambient temperature must be below +55ºC (for
options see Section 6.5)
Make sure that the airflow inside of the electrical
panel enclosure is not restricted by internal
components.
WARNING!
If the cooling unit is being mounted on the door of
the electrical panel enclosure, it must be confirmed
that the door hinges can support the additional
weight of the cooling unit and that the electrical
panel enclosure is securely fastened so that the
panel enclosure will not topple over.
The water valve (1) controls if water is allowed to
flow through the cooling unit.
As the water flows through the heat exchanger (2)
it absorbs the heat from air in the electrical panel
enclosure while also dehumidifying it. This process
lowers the temperature of the air in the electrical
panel enclosure.
This is accomplished by the fan (3) pulling in the hot
air from the electrical panel enclosure and pushing
it through the heat exchanger (2) and back into the
electrical panel enclosure at a lower temperature.
The cooling unit (with water valve and thermostat)
is electronically controlled. To accomplish this a
temperature sensor monitors the temperature inside
the electrical panel enclosure and regulates the
function of the water valve.
B.) Without Water Valve and Thermostat
∞
5.2 Theory of Operation
The cooling units are available in two options:
A.) With Water (solenoid) Valve and Thermostat
B.) Without Water Valve and Thermostat
A.) With Water (solenoid) Valve and Thermostat
∞
1 Water Valve (solenoid)
2 Heat Exchanger (condensor)
3 Fan
4 Thermostat with Temperature Sensor
1 Water Inlet
2 Heat Exchanger (condensor)
3 Fan
The flow of water through the unit is regulated by a
control system provided by the user outside of the
coolling unit.
As the water flows through the heat exchanger (2)
it absorbs the heat from air in the electrical panel
enclosure while also dehumidifying it. This process
lowers the temperature of the air in the electrical
panel enclosure.
This is accomplished by the fan (3) pulling in the hot
air from the electrical panel enclosure and pushing
it through the heat exchanger (2) and back into the
electrical panel enclosure at a lower temperature.
6
Page 9
PWS Series Air/Water Heat Exchangers
SECTION 6: UNIT START-UP
6.1 General
The cooling unit is equipped with an temperature
control system. The temperature of the air pulled in
from the electrical panel enclosure into the cooling
unit is measured by a temperature sensor.
WARNING!
Ambient conditions and temperatures
in the electrical panel must be in accordance
with the values indicated in the cooling unit
information sheet.
WARNING!
Unit must be operated with the cover installed.
Unit can not cool properly when cover
is not in place.
6.2 Setting the Operating Parameters
thermostat then the zero potential two-way switch is
triggered.
This switch is wired to the terminal strip.
Wiring diagram
(Technical sheet)
(Wiring diagram on device)
6.2.2 Units without Water Valve and Thermostat
The cooling unit fan runs continuously.
The cooling water flow is controlled centralized
water flow control supplied by the customer.
The door contact cycles the unit on / off. The door
contact output notifies of an open door condition.
6.2.1 Units with Water (Solenoid) Valve
and Thermostat
The cooling unit fan runs continuously.
The solenoid valve controls cooling water flow
according to the internal temperature setting in the
switch cabinet.
The desired internal temperature of the switch
cabinet is set using the thermostat. Factory setting is
at 35°C / 95°F. Adjustment range min. 8°C / 46.4°F max. 50°C / 122°F.
Electrical panel enclosure internal temperature > the
desired value set using the thermostat
Solenoid valve open Coolant flows.
Electrical panel enclosure internal temperature < the
desired value set using the thermostat .
Solenoid valve shut coolant does not flow.
If door contact is opened then the unit cycles off.
SECTION 7: MAINTENANCE
Pfannenberg air/water heat exchangers are
maintenance-free.
Use of a water filter is essential if the cooling water
is contaminated. Please refer to the “Water Quality
Notes“ section.
Check the condensation water drainage equipment
at regular intervals.
SECTION 8: TROUBLESHOOTING
Condensation water drainage out of the electrical
panel enclosure must be ensured when the device is
installed.
To prevent frost damage the temperature in the
water circuit must not fall below the minimum
permissible water temperature of +1°C anywhere in
the system.
Temperature Monitoring
If the internal temperature of the electrical panel
enclosure deviates more than 10º C from the desired
value set (factory setting 35°C / 95°F) using the
7
If the device is stored or transported at temperatures
below freezing the water circuit must be completely
emptied using compressed air.
Page 10
SECTION 9: DESIGN DATA
Please refer to the cooling unit individual
technical data sheets for the following:
Dimensional Data
Mounting Cutout
Circuit Diagrams
9.1 Water Quality Notes
The following guidelines must be complied with to ensure safe and reliable operation of air/water heat
exchangers.
Cooling water should not contain any sedimentation, should be of low hardness (low carbon hardness in
particular), especially for re-cooling. However, it should not be so soft that it corrodes material/s used in the
exchanger.
When recycling cooling water the saline content due to evaporation of larger quantities of water must not be too
high (increasing concentrations of dissolved substances increase electrical conductivity, resulting in the water
becoming more corrosive).
Constantly remove some enriched water and replace it with an equal amount of fresh water.
Water containing gypsum is unsuitable for cooling, as it tends to cause scale deposits, which are very hard to
remove.
Cooling water should be iron- and manganese-free (deposits leading to piping blockage may otherwise result).
Organic substances (sludge and microbiological contaminants)should only be present in the water in very small
amounts.
Common contamination forms and remedies
Water ContaminationRemedy
Mechanical contamination
Filter water using -Sieve filters
- Gravel filters
- Cartridge filters -Pre-coated filters
Excessive hardnessSoften water using ion exchange
Moderate mechanical contaminant and hardness
promoting substance content
Moderate chemical contaminant contentTreat water using passivation media and / or inhibitors
Biological contamination - sludge bacteria, algaeTreat water with biocides
Treat water using stabilisers or dispersants
8
Page 11
PWS Series Air/Water Heat Exchangers
The characteristics of any additives or system water ought not to deviate greatly from the hydrological
data given below.
Hydrological DataModel: StandardDevice Model: VA
pH value7 - 8.56 - 9
Carboxylic Acid°dH> 3 < 81 - 12
Free carbonic acidmg/dm38 - 151 - 100
Associated carbonic acidmg/dm38 - 15not present
Corrosive carbonic acidmg/dm300 - 400
Sulphidesnot presentnot present
Oxygenmg/dm3< 10< 10
Chloride ionsmg/dm3< 50< 200
Sulphate ionsmg/dm3< 250< 500
Nitrates and nitritesmg/dm3< 10< 100
CSBmg/dm3< 7< 40
Ammoniamg/dm3< 5< 20
Ironmg/dm3< 0.2not present
Manganesemg/dm3< 0.2not present
ConductivitymS/cm< 2200< 4000
Evaporation residuemg/dm3< 500< 2000
Potassium permanganate
consumption
mg/dm3< 25< 40
< 15 split-stream cleansing
Suspended mattermg/dm3< 3 > 3
recommended > 15 constant
cleaning recommended
9
Page 12
9.2 SCCR Determination
Article 409 of the 2005 National Electric Code (NFPA
70) requires Industrial Control Panels (electrical
motor controllers within their panels to achieve a
combination short circuit rating that is higher than
the lowest rated individual component.
panel enclosures) to be marked with a short
circuit current rating. As specified in the National
Electric Code, the Standard for Industrial Control
Equipment, UL508A-2001, Supplement SB, provides
an accepted method for determining the short
circuit current rating of the control panel. The link
to spreadsheets provide guidance for industrial
control panel manufacturers who purchase the
Using the technical data sheet and the information
on the cooling unit ID plate, identify the full load
current conditions for the appropriate voltage. The
installation of the cooling unit should be calculated
as a dedicated branch circuit for determining the
SCCR value. All selections should be evaluated based
on the current UL standards for UL508a.
discreet components and assemble combination
------------------------Over1.850001550 KA30100 KA30200 KA
1
Maximum CC class Fuse size that can achieve this branch circuit SCCR value. Smalller values may be used and still achieve equal rating.
2
Circuit capacity amperes based on UL 484 table 52.1
3
Individual units running amperes can be obtained on each unit's technical data sheet.
3
3 Phase
3
Peak
Let-thru
Current
Max
Fuse
2
50 KA100 KA200 KA
Ip x 10
1
Fuse
Ip x 10
1
Max
3
Max
3
Fuse
1
Ip x 10
3
Example 2: DTS 35xx 460V units has a 5KA IR value
based on UL 484 table 52.1 (see Table 1) and the
amp draw of the unit. If a 15amp Class CC current
limiting feeder circuit is used in combination with
the DTS35xx 460V unit, the maximum allowable
Ipeak of the 15 amp Class CC fuse at an available RMS
fault current of 200 kA is 1700 amps (figure 2). This
value does not exceed the allowable Ipeak of this
unit based on UL SCCR value of Table 52.1. Therefore,
the individual branch circuit SCCR value of this series
combination can support 200 kA IR. (See figure 1.)
Figure 2
10
Page 13
PWS Series Air/Water Heat Exchangers
Figure 1
Option 1: UL 508a reference SB4.2
According to UL508A Supplement SB, if a panel
contains no current-limiting devices, its SCCR
depends on the “weakest” or lowest rated
component or combination within the panel.
However, Supplement SB also states that if currentlimiting fuses are used in the feeder circuit, and if the
highest instantaneous current reached during the
first half cycle of a fault is less than or equal to the
lowest rated SCCR in any branch circuit, the SCCR
of the current limiting fuse can be applied to the
combination.
When the specified branch circuit protection related
to the high fault short circuit current rating is a Class
CC,G,J,L,RK1, RK5 or T fuse, a fuse of a different class
is able to be used at the same high fault rating where
the peak let through current and I2t of the new fuse
is not greater than that of the specified fuse.
Option 2: UL 508a reference SB4.3
An alternate method of achieving a high short circuit
rating is by applying a power transformer with an
isolated secondary winding, the short circuit current
rating on the line side of the transformer shall be one
of the following:
For a power transformer rated not more than 10
kVA, and where the short circuit current rating of
all components in the secondary circuit are not
less than 5kA, the short circuit current rating of the
primary overcurrent protective device is able to be
assigned to the line side of the power transformer
circuit.
For a power transformer rated not more that 5kVA
and a 120V maximum secondary voltage, and where
the short circuit current rating of all components in
the secondary circuit are not less than 2kA, the short
circuit rating of the primary overcurrent protective
device is able to be assigned to the line side of the
power transformer circuit.
Option 3: UL 508a reference SB4.2
The combinations listed in the linked spreadsheets
(www.ul.com/controlequipment/shortcircuit.html)
may be applied in a manufacturer’s Listed industrial
control panel without further evaluation or specific
documentation in the manufacturer’s UL Procedure
pages.
The spreadsheets cover the application of individual
components, including a disconnecting means, an
over current protective device, motor controller
and motor overload protection, as a combination
motor controller having specified ratings, including
a short-circuit current rating (SCCR). Each of the
individual components is Listed or Recognized to the
requirements in the applicable component Standard.
The specified ratings for the combination motor
controller may be applied to the end-product
equipment only when all of the specific components
listed are provided in the end-product equipment
and installed according to any applicable conditions
of acceptability.
Components other than those identified in the
combination motor controller and connected in the
power circuit of the combination motor controller
will require additional evaluation.
11
Page 14
SECTION 10: WARRANTY INFORMATION
(WARRANTY IS VALID FOR 1 YEAR)
Warranty becomes null and void:
In case of improper usage of the unit, noncompliance with operating conditions or nonobservance of instructions
the warranty becomes null and void.
If operated in rooms in which corrosives or acids are present in the atmosphere.
In case of damage caused by contaminated or jammed air filters.
If a non-authorized person interrupts the cooling circulation, modifies the unit or changes the serial number.
In case of damage caused by transport or by accidents.
For the exchange of parts by non-authorized companies.
In order to maintain your warranty rights please observe the following when returning the unit.
Enclose an exact description of the fault in the shipping package.
Enclose proof of delivery (delivery note or copy of invoice).
Return the unit together with all accessories; use the original packaging or packaging of equivalent quality, send
the unit freight prepaid and covered by an adequate transport insurance.
12
Page 15
ELECTRO-TECHNOLOGY FOR INDUSTRY
Pfannenberg Incorporated
68 Ward Road, Lancaster, New York 14086
Phone: 716-685-6866
Fax: 716-681-1521
email: sales@pfannenbergusa.com
www.pfannenbergusa.com
Dieses Handbuch enthält Informationen über die
Installation und den Betrieb von PWS Series bolzen
an Kühleinheiten vorgesehen Tür und Seiten an
elektrischen Platten montiert werden.
Diese Geräte sind so ausgelegt, Wärme von
abgedichteten elektrischen Panel Gehäuse und
Gehäuse abzuführen. Die Temperatur der
Kühlflüssigkeit auf den Luft / Wasser
kälter als der Wärmetauscher Zulufttemperatur,
damit die Einheitsfunktion korrekt zu gewährleisten.
Verwendete Konventionen:
Hinweis: Ein Hinweis enthält weitere Informationen
über die Handlung oder Anweisung beschrieben
wird,
Die technischen Daten des jeweiligen Kühleinheit,
einschließlich der Installationsanschlüsse und
Betriebsdaten werden auf einem separaten
Datenblatt enthalten ist, mit jeder Einheit
zugeführt wird.
Page 19
WARNUNG!
Graten durch die Produktion verursacht
werden, können an den Metallkanten der
Kühleinheit vorhanden sein. Tragen Sie
immer Schutzhandschuhe bei der Installation
spannun
Anlaufstrom
ABSCHNITT 2: Eingangsprüfung
2.1 Auspacken
Vor und während der Kühleinheit Auspacken visuell
inspizieren, um zu bestimmen, ob ein Schaden
während des Transports aufgetreten ist. Stellen Sie
sicher, dass es keine losen Komponenten enthält. Vor
jedem Verpackungsmaterial entsorgen: Suchen Sie
nach losen Teile, verbeult oder zerkratzt Platten oder
Flüssigkeiten.
Sollte ein Schaden festgestellt wird unverzüglich
den Spediteur mitgeteilt werden und eine
Forderung soll mit ihnen eingereicht werden.
Pfannenberg kann keine Verantwortung für
Transportschäden übernehmen, die auftreten
können; Wir werden Sie auf jede erdenkliche Weise
unterstützen, wenn die Notwendigkeit, einen
Anspruch Datei entsteht.
Im Falle eines Garantieanspruchs, werden die
folgenden Informationen erforderlich: genaue
Angabe der Störung (einschließlich Fotos, wenn
möglich), sind die Kühleinheit Teilenummer und
Seriennummer erforderlich.
2.2 Enthaltene Einzelteile
Die folgenden Punkte sollten enthalten
sein: Kühlaggregat
Einbauausschnitt
Handbuch
Technisches Datenblatt
PWS
• Dichtleisten
• Gewindebefestigungsbolzen
• Befestigungsschrauben, Muttern und
Unterlegscheiben
• Kondensatschlauch (PWS 7k-Serie)
• Türkontakt
2.3 Überprüfung von ID
Die ID Die technischen Daten spezifisch für
die Kühleinheit auf der ID
Energieverbr
auch
Nennstrom
Pre-Sicherung
TLuftdurchsat
Wasseflussrte
Teilenummer
Betriebs
Modell-Nr
Frequenz
Serial #
Max zulässiger
Wasserdruck
Page 20
PWS
WARNUNG!
Fehler diese Anforderungen werden
zum Erlöschen der Garantie
WARNUNG!
Metallspäne vom Bohren und Schneiden der
Öffnungen können die Schalttafel Gehäuse
beschädigen. Treffen Sie Vorkehrungen
erforderlich Späne und Schmutz zu verhindern,
WARNUNG!
Achten Sie auf scharfe Kanten entstehen, wenn
das Bohren und / oder das Gehäuse zu
ABSCHNITT 3: HANDLING
3.1 Transporting
Die Kühleinheit ist nur im vollständig bewegt
werden
Wenn die Kühleinheit mit einer elektrischen Platte
Gehäuse verschifft sie sind getrennt von dem
elektrischen Gehäuse verpackt werden.
3.2 Lagerung
Die Kühleinheit ist nicht ausgesetzt
werden
Wenn das Gerät gespeichert ist, oder bei
Temperaturen unter dem Gefrierpunkt transportiert,
muss der Wasserkreislauf vollständig unter
Verwendung von Druckluft entleert wird.
zusammengebauten Zustand.
Temperaturen über +70 º C.
ABSCHNITT 4: INSTALLATION
4.1 Pre-Installation Testen
Vor der Montage der Kühleinheit an der Schalttafel
Gehäuse sollte es Funktion zu überprüfen, werden
getestet.
Hinweis: Alle Geräte sind auf undichte Stellen
überprüft, bevor sie das Werk verlassen.
Es wird empfohlen, ein Türkontaktschalter der
Installation der Vorrichtung zu deaktivieren,
wenn die Schalttafel Gehäusetür geöffnet wird.
4.2 Die Montage auf der Schalttafel
Anschluss überprüft die Kühleinheit an die
Stromversorgung, dass die folgenden richtig
sind:
Spannung muss innerhalb seines ± auf der ID Platte enthalten ist 10% des Werts.
Spannungsfrequenz muss innerhalb seines ± auf
der ID - Platte 3 aufgeführten Hz des Wertes
Umgebungstemperatur unter +55 sein muss º C
(Optionen siehe „ Einstellen der Betriebsparameter “
Abschnitt)
Platzieren Sie die Bohrschablone mit der
Kühleinheit auf die anwendbaren
Befestigungsfläche der zugeführten
Vor dem
Schalttafel
Die Bohrungen in der Schalttafel Gehäuse des
Geräts anzupassen und Luftstromöffnungen
ausgeschnitten.
Installieren der beiden mitgelieferten
Stiftschrauben (im Beipack) in den beiden oberen
Befestigungsloch Stellen der Kühleinheit.
Page 21
WARNUNG!
Sie nicht die Kühleinheit durch die
Rohrleitung bewegen. Dadurch wird die
Kühleinheit beschädigt werden und die
Installieren des Kühleinheit Befestigungs
Dämmstreifen (im Beipack) an die Kühleinheit, wie
auf dem einzelnen Kühleinheit Informationsblatt
festgestellt.
Achten Sie darauf, dass die Dämmstreifen richtig
angebracht sind und korrekt auf der Kühleinheit
angeordnet. Die richtige Montage und Platzierung
der Dämmstreifen ist für den ordnungsgemäßen
Betrieb der Kühleinheit erforderlich.
Bringen Sie die Kühleinheit an der
Schalttafel
Die Kühleinheit wird dann an der Schalttafel
angebracht Gehäuse vollständig aus dem Inneren
des Gehäuses durch die Verwendung der
Schrauben und Scheiben in der mitgelieferten
Beipack.
Ziehen Sie die Befestigungselemente , bis die
Kühleinheit Isolierstreifen bis zu einer Dicke von 2
mm zusammengedrückt wird (ungefähr .080 “ )
Installieren Ablaufschlauch barb (in Beipackbeutel
vorgesehen für PWS 3k
Setzen Sie die Abdeckung der ursprünglichen
Befestigungsschrauben.
4.3 Leistung Verbindung
oben beschrieben.
Die Kühleinheit Stromversorgung wird kondensiert
sein, wie durch eine Reihe geschalteten
Stromleitungsverbindung auf der Einheits
Alle Stromanschlüsse und / oder Reparaturen,
wenn oder falls erforderlich, dürfen nur von
autorisiertem, ausgebildetem Elektriker
durchgeführt werden.
Stromversorgungsanschluss
PWS 7K Serie bietet eine Formkabel geeignet für die
Nennspannung des Geräts.
PWS 3K Serie haben Terminal harten Draht
(PWS 7K-Serie)
Sowohl der Hauptstromversorgungsspannung und
die Frequenz wird auf die Nennwerte auf der
Kühleinheit ID Platte gezeigt sind, entsprechen.
Verbinden der Hauptstromversorgung an die
Kühleinheit, wie durch das Etikett an der
Kühleinheit und auf dem einzelnen Kühleinheit
Datenblatt angegeben.
Durchflussrichtung beachten (Aufkleber auf dem
Gerät neben den Wasseranschlüsse befinden) auf
Dichtheit prüfen.
Schützen Sie den Wasserkreislauf vor Verschmutzung
und übermäßigen Druck (siehe dazu den „ Water Quality
Hinweise „ Abschnitt. Der maximal zulässige
Betriebsdruck 10 Bar ist.
Page 22
PWS
ABSCHNITT 4: INSTALLATION con't
4.5 Kondensation Wasseranschluss
Ablaufschlauch muss mit Schellen an der Stelle
befestigt werden. Um eine sichere Ableitung von
Kondenswasser zu gewährleisten, beachten Sie
bitte folgendes: Der Ablaufschlauch darf nicht
geknickt werden. Schlauchquerschnitt darf nicht in
irgendeiner Weise eingeschnürt werden. Der
Drainageschlauch muss Neigung in der richtigen
Richtung.
Nach übermäßige Tauwassermengen zu
vermeiden, ist folgendes zu beachten:
Stellen
Sie die Kühlwassertemperatur auf die
Kühlleistung erforderlich ist.
Verwenden Sie das
Gerät nur auf abgedichtete elektrische Platten
und Gehäuse.
Die gewünschte Temperatur nur
so gering wie wirklich notwendig ist (um zu
vermeiden die gekühlte Luft von unterhalb des
Taupunktes dropping).
4.6 Türkontakt
Nach vermeiden, dass eine erhöhte Produktion
von Kondensat und aus Sicherheitsgründen ein
Türendschalters sollte vorgesehen mit den
Anschlüssen verbunden werden.
Um jegliche Störungen von außen Signalen zu
verhindern, ist es empfehlenswert, dass ein
abgeschirmtes Kabel mit einer verdrillten Leitung
für die Verbindung verwendet werden. Das
Kabelschirmung kann auf der Kühleinheit vorgesehen
ist an einer Seite mit dem PE (Masse) Anschlusspunkt
angeschlossen werden.
Wenn die Verwendung eines abgeschirmten Kabels
nicht möglich ist, das Kabel, das verwendet wird, darf
nicht in der unmittelbaren Nähe von potentiellen
Störquellen geroutet wird, wie beispielsweise
Stromversorgungsleitungen, Komponenten mit einem
relativ hohen
elektromagnetische Emissionen (EMI),
usw.
Wenn kein Türkontaktschalter verwendet wird,
müssen die Verbindungsklemmen gebrückt werden
für die Kühleinheit zu betreiben.
Page 23
WARNUNG!
Wenn die Kühleinheit auf der Tür des Schalttafel
∞
∞
ABSCHNITT 5: BETRIEBSDATEN
5.1 Bedarf
Vor dem Anschluss überprüft die Kühleinheit
an die Stromversorgung, dass die folgenden
korrekt sind.
Spannung muss innerhalb seines ± auf der ID Platte enthalten ist 10% des Werts.
Spannungsfrequenz muss innerhalb seines ± auf der
ID - Platte 3 aufgeführten Hz des Wertes
Die Umgebungstemperatur muss unter +55 sein º C
(Optionen siehe Abschnitt 6.5)
Achten Sie darauf, dass der Luftstrom im Inneren des
elektrischen Panel Gehäuse nicht durch interne
Komponenten beschränkt ist.
Das Wasserventil (1) steuert, wenn das Wasser
ermöglicht wird, durch die Kühleinheit zu
fließen.
Da das Wasser den Wärmetauscher durchströmt
(2) sie nimmt die Wärme von der Luft in der
Schalttafel Dieses Verfahren senkt die Temperatur
der Luft in dem Schalttafel
Dies wird erreicht durch den Ventilator (3) in der
heißen Luft aus dem Schaltschrank
Die Kühleinheit (mit Wasserventil und
Thermostat) wird elektronisch gesteuert. Um dies
zu erreichen ein
Temperaturfühler überwacht die Temperatur im
Inneren der elektrischen Schalttafel
B.) ohne Wasserventil und Thermostat
Schalttafel
5.2 Theorie der Arbeitsweise
Die Kühlgeräte sind in zwei Varianten verfügbar:
A.) mit Wasser (Solenoid) Ventil und Thermostat
B.) ohne Wasserventil und Thermostat
A.) mit Wasser (Solenoid) Ventil und Thermostat
1 Wasserventil (Solenoid)
2
Wärmetauscher
(Kondensor) 3 Fan
Thermostat 4 mit Temperaturfühler
1 Wasser Einlass
2
Wärmetauscher
(Kondensor) 3 Fan
Der Fluss von Wasser durch die Einheit wird durch
ein Steuerungssystem durch den Benutzer außerhalb
der Coolling Einheit geregelt.
Da das Wasser den Wärmetauscher durchströmt
(2) sie nimmt die Wärme von der Luft in der
Schalttafel Dieses Verfahren senkt die Temperatur
der Luft in dem Schalttafel
Dies wird erreicht durch den Ventilator (3) in der
heißen Luft aus dem Schaltschrank
Schalttafel
Page 24
PWS
WARNUNG!
Umgebungsbedingungen und Temperaturen
in der Schalttafel in Übereinstimmung mit
den angegebenen Werten in der
Kühleinheit Informationsblatt sein muss.
WARNUNG!
Das Gerät muss mit der installierten Abdeckung
betrieben werden.
Das Gerät kann nicht richtig
ABSCHNITT 6: UNIT START-UP
6.1 General
Die Kühleinheit ist mit einem Temperaturregelsystem
ausgestattet. Die Temperatur der Luft, gezogen von
der Schalttafel Gehäuse in die Kühleinheit in wird
durch einen Temperatursensor gemessen.
6.2 Einstellen der Betriebsparameter
6.2.1 Einheiten mit Wasser (Solenoid)
Ventil und Thermostat
Die Kühleinheit Lüfter läuft kontinuierlich.
Das Magnetventil steuert Kühlwasserstrom gemäß
der Innentemperatur
Die gewünschte Innentemperatur des
Schaltschrankes wird den Thermostat verwendet.
Werkseinstellung ist bei 35 ° C / 95 ° F. Einstellbereich
min. 8 ° C / 46,4 ° C - max. 50 ° C / 122 ° F.
Schalttafel-Innentemperatur> der gewünschte Wert
eingestellt den Thermostat
Magnetventil offen Kühlmittel fließt.
Schalttafel Schaltschrank-Innentemperatur <der
gewünschte Wert eingestellt den Thermostat
verwendet.
Magnetventil geschlossen Kühlmittel nicht fließt.
Wenn Türkontakt ausgeschaltet wird dann die Einheit
Zyklus geöffnet.
Temperaturüberwachung
Wenn die Innentemperatur der elektrische
Schalttafel Gehäuse abweicht mehr als 10 º C von
Schaltschrank.
dem Sollwert (Werkseinstellung 35 ° C / 95 ° F) unter
Verwendung des
Page 25
Thermostat dann das Nullpotential Zweiwegeschalter
ausgelöst.
Dieser Schalter ist an die Klemmleiste verdrahtet.
Schaltplan
(Technisches
Arbeitsblatt)
(Schaltbild auf dem Gerät)
6.2.2 Geräte ohne Wasserventil und Thermostat
Die Kühleinheit Lüfter läuft kontinuierlich.
Der Kühlwasserfluss wird zentrale
Wasserflusssteuerung durch die Kunden
geliefert gesteuert.
Die Türkontaktzyklen das Gerät ein / aus. Der
Türkontaktausgang meldet einen offenen Tür
Zustand.
ABSCHNITT 7: MAINTENANCE
Pfannenberg Luft / Wasser
Die Verwendung eines Wasserfilters ist
wesentlich , wenn das Kühlwasser
verunreinigt ist. Bitte beachten Sie die „
Wasserqualität Hinweise „ Abschnitt.
Überprüfen Sie die
Tauwasserentwässerungsanlagen in
regelmäßigen Abständen.
ABSCHNITT 8: FEHLERBEHEBUNG
Kondenswasser Drainage aus dem
Schaltschrank Gehäuse muss gewährleistet
werden, wenn das Gerät installiert ist.
Um zu verhindern, Frostschäden muss die
Temperatur im Wasserkreislauf nicht unter der
minimal zulässigen Wassertemperatur von + 1 °
C überall im System fallen.
Wenn das Gerät unter dem Gefrierpunkt den
Wasserkreislauf bei Temperaturen gelagert
oder transportiert werden, müssen vollständig
mit Druckluft entleert.
Page 26
PWS
Wasserverunreinigung
Abhilfe
mechanische Verunreinigung
Filter mit Wasser -Sieve Filter
- Kiesfilter
- Kerzenfilter -Pre beschichtete Filter
Zu hohe Härte
Wasser erweichen lonenaustausch
Moderate mechanische Verunreinigungen und
Härte Substanzgehalt Förderung
Saures Wasser Stabilisatoren oder Dispergiermittel unter Verwendung
Moderate chemischen Schadstoffgehalt
Saures Wasser Passivierung Medien und / oder Inhibitoren
Bitte beachten Sie die Kühleinheit einzelne
technische Datenblätter für die folgenden:
Dimensionale
Datenmontagea
usschnitt
Schaltpläne
9.1 Wasserqualität Hinweise
Die folgenden Richtlinien sind einzuhalten sicheren und zuverlässigen Betrieb von Luft / Wasser
Kühlwasser sollte keine Sedimentation enthalten, sollte geringer Härte (insbesondere niedriger Karbonathärte),
insbesondere zur Rückkühlung. Es sollte jedoch nicht so weich sein, dass sie Material / s im Wärmetauscher
verwendet korrodiert.
Beim Recycling von Kühlwasser der Salzgehalt aufgrund der Verdampfung größerer Wassermengen dürfen nicht
zu hoch sein (Konzentrationen an gelösten Stoffen erhöhen Erhöhung der elektrischen Leitfähigkeit, im Wasser
entstehende
immer ätzend).
etwas angereicherte Wasser und ersetzen Sie es mit einer gleichen Menge an Frischwasser ständig entfernen.
Wasser Gips enthält, ist nicht geeignet für die Kühlung, da sie Ablagerungen zu verursachen neigt, die sehr schwer
zu entfernen sind.
Kühlwasser sollten eisen Organische Substanzen (Schlamm und mikrobiologische Verunreinigungen) im
Wasser in sehr geringen Mengen vorhanden sein.
Gemeinsame Kontamination Formen und Heilmittel
Page 27
hydrologische Daten
Modell: Standard
Gerätemodell: VA
PH Wert
7-8,5
6 - 9
Carboxylsäurederivate
° dH
> 3 <8
1 bis 12
Freie Kohlensäure
mg /
8-15
1-100
Assoziierte Kohlensäure
mg /
8-15
nicht
Korrosive Kohlensäure
mg /
0
0-400
Sulfide
nicht
nicht
Sauerstoff
mg /
<10
<10
Chloridionen
mg /
<50
<200
Sulphationen
mg /
<250
<500
Nitraten und Nitriten
mg /
<10
<100
CSB mg /
<7 <40
Ammoniak
mg /
<5 <20
Eisen
mg /
<0,2
nicht
Mangan
mg /
<0,2
nicht
Leitfähigkeit
mS / cm <2200
<4000
Abdampfungsrückstand
mg /
<500
<2000
Kaliumpermanganatverbrauch
mg /
<25
<40
Schwebstoffe
mg /
dm3
<3> 3
<15 Split
Die Merkmale der jegliche Zusätze oder Systemwasser sollte nicht stark von den hydrologischen Daten
unten abzuweichen.
Page 28
PWS
Raumkühlgeräte Nennlaststrom, Stromstärke
Einzelphase
3
3 Phase
3
50 KA
100 KA
200 KA
110 bis 120 V
200 bis 208 V
220 - 240 V
254 bis 277 V
440-480 V
Peak
Let-thru
Current
2
Max
Fuse
1
ichp x 10
3
Max
Fuse
1
ichp x
10
3
Max
Fuse
1
ichp x
10
3
9.9
16.0
5.4
8.8 5.0
8.0
6,65
Weni
1.8 Wen
1000
15
50 KA
n / a n / a
16.1
34.0
8.9
18.6 8.1
17.0
---
---
---
---
2000
30
50 KA 15
100 KA
n / a
---
---
---
---
---
---
---
---
Zu
1.8
5000
15
50 KA 30
100 KA 30
200 KA
1
Maximale CC Klasse Sicherungsgröße, die diese Zweigschaltung SCCR Wert erreichen kann. Smalller Werte verwendet werden können und nach wie
vor gleich Bewertung erzielen.
2
Schaltvermögen Ampere basierend auf UL 484 Tabelle 52.1
9.2 SCCR Bestimmung
Artikel 409 des 2005 National Electric Code (NFPA
70) erfordert Industrial Control Panels
(Schaltschrank Wie in der National Electric Code
angegeben, die Norm für industrielle Steuerungs
Ausrüstung, UL508A Der Link zu Tabellen geben
Hinweise für die industrielle Steuerung Panel
Tabelle 1
Motorsteuerungen innerhalb ihrer Platten eine
Kombination Kurzschlussfestigkeit zu erreichen, die
höher als die niedrigste bewerteten
Einzelkomponente ist.
Unter Verwendung der technischen Datenblatt und
die Informationen über die Kühleinheit ID Platte
identifizieren die Volllaststrombedingungen für die
entsprechende Spannung. Die Installation der
Kühleinheit soll zur Bestimmung des SCCR Wertes
als dedizierte Verzweigungsschaltung berechnet
werden. Alle Auswahlen sollten auf der Grundlage
der aktuellen UL
Beispiel 2: DTS 35xx 460V Wenn eine 15amp
Klasse CC Stromzuführung Begrenzungsschaltung
wird in Verbindung mit der DTS35xx 460V Einheit,
die maximal zulässigen verwendet
Ipeak der 15 Dieser Wert nicht überschreitet den
zulässigen Ipeak dieses Geräts basierend auf UL
SCCR Wert von Tabelle 52.1. Daher kann der
einzelne Zweigschaltung SCCR Wert dieser
Reihenkombination 200 kA IR unterstützen. (Siehe
Abbildung 1.)
Figur 2
Page 29
Abbildung 1
Option 1: UL 508a Referenz SB4.2
Nach UL508A Supplemente SB, wenn eine Platte
enthält keine Strom - Begrenzungseinrichtungen,
hängt ihre SKKR auf den „ schwächsten “ oder
niedrigsten bewertete Komponente oder
Kombination innerhalb der Platte. Jedoch
Supplement SB stellt auch fest, dass , wenn Strom Begrenzungs Sicherungen in der Speiseschaltung
verwendet werden, und wenn der höchste
Momentanstrom während des ersten Halbzyklus
eines Fehlers erreicht sind , kleiner oder gleich den
niedrigsten bewertete SKKR in jeder
Verzweigungsschaltung, die SCCR
der Strombegrenzungs Sicherung kann auf die
Kombination angewendet werden.
Wenn der angegebene Zweigschaltung des hohe
Fehlerbezogenen Schutznennstrom Kurzschluss eine
Klasse CC, G, J, L, RK1, RK5 oder T
Option 2: UL 508a Referenz SB4.3
Ein alternatives Verfahren zur Herstellung einer
hohe Kurzschlussleistung zu erreichen, ist durch
einen Leistungstransformator mit einer isolierten
Sekundärwicklung, dem Kurzschlussstrom auf der
Leitungsseite des Transformators wird die
Anwendung einer der folgenden sein:
Zum ein Leistungstransformator nicht mehr als 10
kVA und wo der Kurzschlussstrom aller
Komponenten in dem Sekundärkreislauf ist nicht
weniger als 5 kA, der Kurzschlussstrom der
Primärüberstromschutzeinrichtung in der Lage,
bewerten mit der Leitungsseite zugeordnet werden
der Stromtransformatorschaltung.
Für einen Leistungstransformator nicht mehr
bewertet, dass 5kVA und eine 120V maximale
Sekundärspannung, und wobei der Kurzschlussstrom
aller Komponenten in dem Sekundärkreislauf nicht
weniger ist als 2kA, die Kurzschlussfestigkeit der
Primärüberstromschutzeinrichtung in der Lage ist, zu
sein, auf der Leitungsseite des
Stromwandlerschaltung zugeordnet.
Page 30
PWS
Option 3: UL 508a Referenz SB4.2
Die Kombinationen in den verknüpften
Tabellen aufgelistet
(www.ul.com/controlequipment/shortcircuit.h
tml)kann in einem Hersteller angewandt
werden ‚ s Listed Industrie Bedienfeld ohne
weitere Bewertung oder spezifische
Dokumentation in dem Hersteller ‘ s UL
Verfahren Seiten.
Die Tabellen umfassen die Anwendung der
einzelnen Komponenten, einschließlich einer
Trenneinrichtung, eine
Überstromschutzeinrichtung, Motorsteuerung
und Motorüberlastschutz, wie eine
Kombination Motorsteuerung angegebenen
Bewertungen aufweist, einschließlich eines
Kurzschlussstromstärke (SCCR). Jedes von
den
Einzelkomponenten werden in der jeweiligen
Komponente Norm zu den Anforderungen
Listed oder Recognized.
Die angegebenen Bewertungen für die
Kombination Motorsteuerung können nur das
Endprodukt Ausrüstung angewandt werden,
wenn alle der spezifischen Komponenten
aufgeführt sind in dem Endprodukt
Ausrüstung bereitgestellt und installierten
gemäß anwendbaren Bedingungen
die
Akzeptanz.
Andere Komponenten als diejenigen
identifiziert, in der Kombination und
Motorsteuerung in der Leistungsschaltung
der Kombinationsmotorsteuerung
verbunden sind
erfordert zusätzliche
Auswertung.
Page 31
ABSCHNITT 10: GARANTIEINFORMATIONEN
(Garantie gilt für 1 Jahr gültig)
Garantie erlischt:
Bei unsachgemäßer Benutzung des Gerätes, Nichteinhaltung von Betriebsbedingungen oder Nichtbeachtung von
Anweisungen wird die Garantie null und nichtig.
Wenn in Räumen, in denen betrieben ätzenden oder Säuren sind in der
Atmosphäre vorhanden. Im Fall eines durch verunreinigte oder gestaute
Luftfilter verursacht wird.
Wenn eine nicht autorisierte Person den Kühlkreislauf unterbricht, ändert das Gerät oder ändert sich die
Seriennummer. Im Falle einer durch den Transport oder durch Unfälle verursacht wurden.
Für den Austausch von Teilen durch nicht autorisierte Unternehmen.
Um Ihre Garantierechte beachten Sie bitte die folgenden zu halten, wenn das Gerät zurück.
Schließen Sie eine genaue Beschreibung des Fehlers in der Versandverpackung.
Beilegen Zustellnachweis (Lieferschein oder eine Kopie der Rechnung).
Bringen Sie das Gerät zusammen mit allem Zubehör; Verwenden Sie die Originalverpackung oder eine
gleichwertige Verpackung, schicken Sie das Gerät Fracht durch eine angemessene Transportversicherung Prepaid
Page 32
ELEKTROTECHNIK FÜR DIE INDUSTRIE
Pfannenberg GmbH
68 Wird Road, Lancaster, New York 14086
Telefon: 716-685-6866
Fax: 716-681-1521
Email: sales@pfannenbergusa.com
www.pfannenbergusa.com