ELECTRO-TECHNOLOGY FOR INDUSTRY
SPECTRA series ashing lights 5 Joules
P 300 STR / P 300 STS / P 300 STF (Ø 100 mm)
• ashing warning light for universal use
• large variety of mounting methods due to modular design principle:
– surface-mounted devices for mounting directly or on a wall bracket
or a tubular stand
– also for exposed installation locations through combination of wall
bracket and tubular stand
– cable entry at the side or through the base of the housing
• durable, sturdy and functionally reliable due to the use of
high-quality plastic
• optimum illumination due to prismatic coloured lens
• electronic components mechanically protected for highest mounting
security
• also available in a synchronised version (STS) or with adjustable
r =
10 m
Range as
per EN 54
IP 65
Protection
system
+ 50 °C
- 25 °C
Operating
temperature
Electrical data AC P 300 STR P 300 STS
Rated voltage 230 V AC 115 V AC 230 V AC 115 V AC
Rated frequency 50 Hz / 60 Hz 50 Hz / 60 Hz 50 Hz / 60 Hz 50 Hz / 60 Hz
Operating range 207 V – 253 V 100 V – 130 V 207 V – 253 V 100 V – 130 V
Nominal current consumption 35 mA 70 mA 35 mA 70 mA
Electrical data AC/DC P 300 STR P 300 STS P 300 STF
Rated voltage 24 V AC/DC 24 V AC/DC 12 V AC/DC 24 V AC/DC
Operating range 20 V – 28 V 20 V – 28 V 10 V – 15 V 20 V – 28 V
Nominal current consumption 250 mA / 300 mA 250 mA / 300 mA 500 mA / 600 mA 250 mA / 300 mA
Mechanical data P 300 STR P 300 STS P 300 STF
Operating mode ashing light synchronised ashing light multi-frequency ashing light
Light source xenon ash tube xenon ash tube xenon ash tube
Flash energy 5 Joules @ 1 Hz 5 Joules @ 1 Hz 5 Joules @ 1 Hz or 2 Hz
Light intensity (DIN 5037) clear lens 40 cd
Lens colours clear, yellow, amber, red, green, blue
Lens type prismatic
Operating temperature - 25 °C ... + 50 °C
Relative humidity 90% @ + 20 °C
Protection system according to EN 60529 IP 65
Service life of the ash tube light emission still 70% after 5,000,000 ashes
Material polycarbonate (PC), UL 94 VO f1
Design bayonet with anti-tamper locking screw
Mounting surface mounting (wall bracket and tubular stand available as accessories)
Cable entry 1 x 5-7 mm push through grommet (bottom side); 1 x M20 cable entry (sideways)
Connecting terminals screw terminals 1.5 mm
Weight
AC version 300 g 325 g
DC version 325 g 325 g
ash frequency (STF)
2
Dimensions
mounting holes
2 x Ø 5.4 mm
27
cable entry
150
Ø 100
M20
cable entry
Ø 5-7mm
37
20
45°
60°
27.5
Ordering details
Article numbers AC P 300 STR P 300 STS
Lens colour Rated voltage 230 V AC 115 V AC 230 V AC 115 V AC
yellow 213 34 10 3 000 213 34 15 3 000 213 35 10 3 000 213 35 15 3 000
amber 213 34 10 4 000 213 34 15 4 000 213 35 10 4 000 213 35 15 4 000
red 213 34 10 5 000 213 34 15 5 000 213 35 10 5 000 213 35 15 5 000
Article numbers AC/DC P 300 STR P 300 STS P 300 STF
Lens colour Rated voltage 24 V AC/DC 24 V AC/DC 12 V AC/DC 24 V AC/DC
yellow 213 34 40 3 000 213 35 40 3 000 213 36 41 3 000 213 36 40 3 000
amber 213 34 40 4 000 213 35 40 4 000 213 36 41 4 000 213 36 40 4 000
red 213 34 40 5 000 213 35 40 5 000 213 36 41 5 000 213 36 40 5 000
Article numbers for other colours and voltages on request
Options / accessories
Wall
bracket
Article number:
213 92 00 0 000
Tubular
stand
140 mm
Article number:
213 93 00 0 000
only in
combination
Wall
holder
Article number:
282 50 20 0 000
with tubular
stand
See pages 122/123 for further information
Conformity to standards
The visual characteristics of ashing lights conform to the European standard DIN EN 842 ‘Machine safety – visual alarm signals’.
Requirements contained in the DIN EN 981 standard: ‘Machine safety – system of acoustic and visual alarm and information signals’, can be fullled.
The colours ‘red’ for the emergency signal and ‘yellow’ for the warning signal conform to the requirements of IEC 73 / DIN EN 60073 / VDE 0199:
‘Coding of display devices and control elements using colours and supplementary means’.
References to visual alarm devices can be found in the following standards:
EN 60825-1 Radiation safety of laser devices, identical to IEC 825 and DIN-VDE 0837
DIN EN 54 Fire alarm systems
DIN 54113-2 Radiation protection regulations for the technical operation of X-ray equipment up to 500 kV