Pfannenberg P 300 STR, P 300 STS, P 300 STF Catalog Page

Visual signaling devices
ELECTRO-TECHNOLOGY FOR INDUSTRY
SPECTRA series ashing lights 5 Joules P 300 STR / P 300 STS / P 300 STF (Ø 100 mm)
• ashing warning light for universal use
or a tubular stand – also for exposed installation locations through combination of wall
bracket and tubular stand – cable entry at the side or through the base of the housing
• durable, sturdy and functionally reliable due to the use of high-quality plastic
• optimum illumination due to prismatic coloured lens
• electronic components mechanically protected for highest mounting security
• also available in a synchronised version (STS) or with adjustable
r =
10 m
Range as per EN 54
IP 65
Protection system
+ 50 °C
- 25 °C
Operating temperature
Electrical data AC P 300 STR P 300 STS
Rated voltage 230 V AC 115 V AC 230 V AC 115 V AC
Rated frequency 50 Hz / 60 Hz 50 Hz / 60 Hz 50 Hz / 60 Hz 50 Hz / 60 Hz
Operating range 207 V – 253 V 100 V – 130 V 207 V – 253 V 100 V – 130 V
Nominal current consumption 35 mA 70 mA 35 mA 70 mA
Electrical data AC/DC P 300 STR P 300 STS P 300 STF
Rated voltage 24 V AC/DC 24 V AC/DC 12 V AC/DC 24 V AC/DC
Operating range 20 V – 28 V 20 V – 28 V 10 V – 15 V 20 V – 28 V
Nominal current consumption 250 mA / 300 mA 250 mA / 300 mA 500 mA / 600 mA 250 mA / 300 mA
Mechanical data P 300 STR P 300 STS P 300 STF
Operating mode ashing light synchronised ashing light multi-frequency ashing light
Light source xenon ash tube xenon ash tube xenon ash tube
Flash energy 5 Joules @ 1 Hz 5 Joules @ 1 Hz 5 Joules @ 1 Hz or 2 Hz
Light intensity (DIN 5037) clear lens 40 cd
Lens colours clear, yellow, amber, red, green, blue
Lens type prismatic
Operating temperature - 25 °C ... + 50 °C
Relative humidity 90% @ + 20 °C
Protection system according to EN 60529 IP 65
Service life of the ash tube light emission still 70% after 5,000,000 ashes
Material polycarbonate (PC), UL 94 VO f1
Design bayonet with anti-tamper locking screw
Mounting surface mounting (wall bracket and tubular stand available as accessories)
Cable entry 1 x 5-7 mm push through grommet (bottom side); 1 x M20 cable entry (sideways)
Connecting terminals screw terminals 1.5 mm
Weight
AC version 300 g 325 g
DC version 325 g 325 g
ash frequency (STF)
2
Dimensions
mounting holes 2 x Ø 5.4 mm
27
cable entry
150
Ø 100
M20
cable entry Ø 5-7mm
37
20
45°
60°
27.5
Ordering details
Article numbers AC P 300 STR P 300 STS
Lens colour Rated voltage 230 V AC 115 V AC 230 V AC 115 V AC
yellow 213 34 10 3 000 213 34 15 3 000 213 35 10 3 000 213 35 15 3 000
amber 213 34 10 4 000 213 34 15 4 000 213 35 10 4 000 213 35 15 4 000
red 213 34 10 5 000 213 34 15 5 000 213 35 10 5 000 213 35 15 5 000
Article numbers AC/DC P 300 STR P 300 STS P 300 STF
Lens colour Rated voltage 24 V AC/DC 24 V AC/DC 12 V AC/DC 24 V AC/DC
yellow 213 34 40 3 000 213 35 40 3 000 213 36 41 3 000 213 36 40 3 000
amber 213 34 40 4 000 213 35 40 4 000 213 36 41 4 000 213 36 40 4 000
red 213 34 40 5 000 213 35 40 5 000 213 36 41 5 000 213 36 40 5 000
Article numbers for other colours and voltages on request
Options / accessories
Wall
bracket
Article number: 213 92 00 0 000
Tubular
stand
140 mm
Article number: 213 93 00 0 000
only in combination
Wall
holder
Article number: 282 50 20 0 000
with tubular stand
See pages 122/123 for further information
Conformity to standards
The visual characteristics of ashing lights conform to the European standard DIN EN 842 ‘Machine safety – visual alarm signals’. Requirements contained in the DIN EN 981 standard: ‘Machine safety – system of acoustic and visual alarm and information signals’, can be fullled. The colours ‘red’ for the emergency signal and ‘yellow’ for the warning signal conform to the requirements of IEC 73 / DIN EN 60073 / VDE 0199:
‘Coding of display devices and control elements using colours and supplementary means’.
References to visual alarm devices can be found in the following standards: EN 60825-1 Radiation safety of laser devices, identical to IEC 825 and DIN-VDE 0837 DIN EN 54 Fire alarm systems DIN 54113-2 Radiation protection regulations for the technical operation of X-ray equipment up to 500 kV
55
Flashing Lights
58 59
Loading...