Pfannenberg FLZ 510 Data Sheet

FLZ 510
FLZ 510 – 1K (thermal return) / FLZ 510 – 3K / FLZ 510 – 7K (with capillary sensor)
Setting ranges
-20°C .. +40°C /
-5°F .. +105°F
0°C .. +60°C /
+30°F .. +140°F
Working temperature range -20°C..+80°C / -5°F..+180°F
Max. breaking capacity Value in brackets: inductive load at cos.φ=0.6
Heating: 100V .. 250V AC / 10(2)A Cooling: 100V .. 250V AC / 5(2)A
DC: max. 30W Breaking temperature difference 1K / 3K / 7K (Capillary controller) Tolerance for switching point +/- 3K Type of contact Two-way contact – CO (spring contact) Sensor bimetal or remote sensor with 1.5 capillary
Type of connection 0.5 ... 2.5mm² screw clamps Colour RAL 7035 – grey Protection category IP 20
Assembly Snap fastening for 35mm profile bars in accordance with EN 60715
FLZ 510
gebruikstemperat uur -20°C..+80°C / -5°F..+180°F
Verschil schakelt emperatuur 1K / 3K / 7 K (capillaire regelaar) schakelpunttollera ntie +/- 3K contacttype wisselaar - CO (sprongcontact) Sensor bimetaa l of afstandssensor met 1,5m capi llair Type aansluiting 0,5 ... 2,5mm² schroefkl emmen kleur RAL 7035 grijs beveiliging IP 20
RF
θ θ
nur / only / seul
e
ment / slechts 230V AC
endast / soltanto / solamente / только 230V AC
Монтаж
FLZ 510 - 1K FLZ 510 - 3K
FLZ 510, 1K
Montage Assembly Montage Montage Montering Montaggio Montaje
FLZ 510 - 7K
FLZ 510- 3K / FLZ 510 - 7K
Betriebsanleitung Thermostat FLZ 510 (Wechsler - CO)
Thermostat FLZ 510 (two-way contact – CO) Instructions for Use
Application:
The thermostats are used for the temperature regulation of cooling units, heating appliances, filter ventilators and heat exchangers inside switch cabinets. They detect the adjusted ambient air and open the heat contact and close the cool contact at an increasing temperature.
Safety instructions The thermostats may only be installed by qualified staff. The protective measures and the protection against contact are to be ensured by the installation. The information on the name plate (voltage and current) is to be heeded.
The operational reliability of the thermostat is to be ensured by an operating test.
Installation instructions:
- The thermostat should be assembled in the upper part of the switch cabinet at the maximum possible distance from heat creating components.
- The ventilation slots of the thermostat should not be covered.
- When using the two-way contact as an opener for the temperature setting the highest possible
hysteresis must be added to the required minimum temperature.
For example: - required minimum temperature inside switch cabinet: 10°C (50°F)
- temperature to be set: 15°C (59°F)
- resulting from: 15°C (59°F) = required temperature 10°C + highest possible hysteresis 4K (1K+3K)
Instructions d’emploi du Thermostat FLZ 510 (Contact à deux directions - CO)