mitted in any form or by any means, except as permitted in written license agreement with Programma Electric AB.
Programma Electric AB has made every reasonable attempt to ensure the completeness and accuracy of this document.
However, the information contained in this document is subject to change without notice, and does not represent a commitment on the part of Programma Electric AB.
TRADEMARK NOTICES
Programma® is a registered trademark of Programma Electric AB.
All other brand and product names mentioned in this document are trademarks or registered trademarks of their respective
companies.
Programma Electric AB is certified according to ISO 9001.
Programma Electric AB
Eldarvägen 4
SE-187 75 T
weden
S
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0 D o c . N o : B H 0 2 2 4 K E 2 0 0 5
Index ................................................. 109
O D E N A T
P r o g r a m m a E l e c t r i c A B
Z
P - C F 0 2 D R 1 0 0
7
O D E N A T
8
P r o g r a m m a E l e c t r i c A B
Z
P - C F 0 2 D R 1 0 0
d e n A T
O
1 S a f e t y p r e c a u t i o n s
1 Safety precautions
1.1 You must read the following
safety precautions thoroughly
• Always follow the local safety regulations that
apply to work with high-voltage equipment.
• Make certain that all personnel who work with
Oden AT have been trained in its use and that all
applicable safety precautions are taken.
Read and comply with the following instructions
•
as well as the warnings and instructions on the
AT control panel.
Oden
Precaution levels
The manual uses three safety flags to indicate different levels of danger.
All Danger, Warning and Important notes must be
followed for your safety. The safety messages will
be in the following formats:
DANGER
1.2 Precaution level – DANGER
Here are the general precautions for level Danger.
You must also read and follow the additional safety
precautions in each appropriate section of the
manual.
DANGER
The voltages and currents that are generated by Oden AT can cause serious injury.
DANGER
When you are changing the connections
make sure that current not can be generated accidently. Disconnect the mains
supply or switch the miniature breaker F2
to the 0-position.
DANGER
Dangerous voltages can develop at
exposed connectors if the equipment
malfunctions.
Means you may risk possible severe bodily harm or
loss of life. and damage to the test object and/or test
equipment.
WARNING
Means you may risk possible bodily harm and damage to the test object and/or test equipment.
I
mportant
Means you risk damage to the test object and/or the
test equipment.
DANGER
The voltage at the output terminals can
be dangerous. Especially when units are
connected in series.
DANGER
Never use a high-current output while
simultaneously using a low-curret output!
DANGER
Making microhmmeter tests on a breaker. Make certain that the breaker is
closed and grounded on one side before
connecting Oden AT to the breaker.
DANGER
When testing current transformer. Dangerous voltages can appear in the secondary circuits if they are open.
DANGER
A current unit connected to other current
units must also be connected to the contr
ol unit. Otherwise dangerous voltages
might appear in the connector on the con-
ol cable, and the current unit might be
tr
damaged by current flowing backwards.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
9
1 S a f e t y p r e c a u t i o n s
1 0
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
DANGER
This equipment can be used only in electrical systems with single Ground. User
must verify before connecting this unit to
power, that High Voltage Ground and Low
Voltage Protective Ground create a single
protective ground with no measurable
voltage potential existing between these
ground systems. If a voltage potential
is found between the ground systems
please consult local safety regulations.
1.3 Precaution level – WARNING
Here are the general precautions for level Warning. You must also read and follow the additional
safety precautions in each appropriate section of the
manual..
WARNING
All current units used must also be connected to the control unit. Otherwise the
current unit might be damaged.
WARNING
Always use a grounded mains cable to
connect the control unit to the mains.
Always ground Oden AT using a separate
ground cable
WARNING
The current output terminals and connecting points can be hot after generation of high current.
WARNING
Never switch between the 30 and 60 V
settings when Oden AT is generating.
WARNING
When loading Oden AT on a carriage. To
prevent tip-over, the current units must
be loaded onto the carriage from bottom
up.
WARNING
The carriage is primarily intended for
transportation but may also be used
when testing. The carriage must then
be secured to prevent tip over. It should
withstand a horizontal force of 250 N (N
= Newton, approx. 56 lbs of force) in any
direction applied anywhere to the equipment.
If securing is not possible stack the units
on a flat surface that can support the
load of the units. Make sure that the
stack will withstand a horizontal force of
250 N in any direction applied anywhere
to the equipment.
O d e n A T
1 S a f e t y p r e c a u t i o n s
WARNING
The steel brackets mounted on the carriage are only intended for keeping the
Oden AT units in place during transportation. They are not dimensioned to carr y
the weight of a current unit. A current
unit should always rest either on the
loading pallet or ontop of another current
unit.
WARNING
Never try to service Oden AT yourself. If
you open the casings of the current units
or control unit you may be exposed to
dangerously high voltages.
1.3 Precaution level – Important
Here are the general precautions for level Important.
You must also read and follow the additional Important notes in each appropriate section of the manual..
Important!
Make certain that mains outlet and its
fuses and all cables/wiring have sufficient cur
able ratings.
Never connect Oden A
age other than that specified on the dataplates (nameplate) on the contr
and the current units.
Do not connect units that ar
types to each other. Only connect type
S units to type S units, type H to type H
etc.
Disconnect Oden A
age:
When not in use
When it is not attended
During electrical stor
Befor
Clean the Oden A
Do not use liquid or aerosol cleaning
agents.
Do not spill water or other liquids onto
Oden A
If you need to r
please use either the original crate or
one of equivalent str
there is risk for transportation damages.
rent-carr ying capacity, i.e. suit-
T to a mains volt-
ol unit
e of different
T from the mains volt-
ms (lightning)
e cleaning
T with a moist rag.
T.
eturn your Oden AT,
ength. Otherwise
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
1 1
1 S a f e t y p r e c a u t i o n s
O d e n A T
1 2
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
2 I n t r o d u c t i o n
2 Introduction
2.1 General
Oden AT is intended for use in high-voltage substations and industrial environments, for laboratories
and testing purposes. Oden AT consists of a control
unit equipped with a control panel and can be connected to one, two or three current units mounted
on a carriage. All units are portable and easy to
assemble and connect. Assembly and connection are
explained in chapter 6 ”How to install Oden AT”.
Since Oden AT can incorporate up to three current
units, which can be connected to each other in series
or in parallel,
number of current/voltage combinations. Oden AT is
available in models for 240 V and 400 V mains voltages. There is also a model for operation on 480 V
60 Hz only.
Oden AT is designed to generate short-duration
current, and is protected from overheating. Under
special circumstances, Oden
21,900 amperes.
The current units come in three models: type S, type
H and type X. Each current unit contains a number
of toroidal transformers whose common secondary
side consists of a busbar connected to the HIGH I
output.
For data, see chapter 11 ”Specifications”.
A current unit of type X has, in addition to its
regular high-current output, a low-current output
(0-30V/60V) consisting of two extra windings that
each can provide 30
AC current can be generated in a
AT can generate up to
This output can deliver very high currents.
V. Using a switch the windings
can be connected either in series or in parallel to the
0-30V/60V output, providing either a 30 V or a 60
V output. For data, see chapter 11 ”Specifications”.
The control unit controls the current output (generation) from the current units and is equipped with
sophisticated measurement facilities.
is first generated for a load, the control unit can
sense the phase angle and adapt subsequent generation operations so that they all start at the current’s
zero-cross-over points. This ensures minimized DC
offset in connection with starting.
When current
Current can be generated in many ways:
• Continuously.
• During a preset maximum time.
• As long as you press a button.
• Until an external signal activates the stop input.
• At a lower current (I/30) to avoid unneccesary
heating of the object being tested while the current is being adjusted.
In pulses (both pulse duration and between-pulse
•
pause are user-definable).
The measurement section contains/provides (among other things):
• Timer.
• Digital ammeter (true RMS).
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
1 3
2 I n t r o d u c t i o n
1 4
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
• An additional channel for measuring a voltage or
a second current.
• Direct display of the turns ratio of a current
transformer.
• Provisions for measuring phase angle Z, P, R, X,
S, Q and power factor (cosϕ).
•
Currents and voltages expressed (if so desired) as
percentages of nominal values.
Fast-acting hold function. Measured values can
•
be frozen in response to a signal arriving at the
stop input and/or when the current is interrupted.
In addition to its normal working mode, there are
special Oden
AT settings supporting the following
types of testing:
• Microhm measurement (DC resistance is calculated).
•
Testing of direct acting automatic reclosers.
• Testing of sectionalizers.
2.2 Fields of application
Oden AT is primarily intended for:
• Testing of protective relay equipment (primary
injection testing).
Testing of breakers with overcurrent tripping.
•
• Conducting ratio tests on current transformers.
• Conducting polarity tests on current transform
ers.
Other fields of application include:
Tests requiring high currents.
•
• Measuring the resistance of breakers with normal
operating current.
Testing direct-acting automatic reclosers.
•
• Testing sectionalizers.
• Testing ground grids.
-
Even though Oden AT features outstanding versatil
ity, it is very easy to use because:
• You can start generation whenever desired.
• You can repeat a measurement by simply pressing a button. It is not necessary to clear the
display first.
You can save different settings for Oden AT in
•
ten different memories.
-
O d e n A T
2.3 Reservations
When set at maximum current, Oden AT is designed
only for temporary (short-duration) current generation. Do not use Oden AT for long-term generation
at full current. See the product specifications in
chapter 11.
2 I n t r o d u c t i o n
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
1 5
2 I n t r o d u c t i o n
O d e n A T
1 6
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
MAINS
F2
3 C o n t r o l p a n e l
3 Control panel
3.1 Oden AT control panel
This chapter presents an overview of the Oden AT
control panel. The control panel is divided into a
number of blocks:
1 MAINS
2 CURRENT ADJUST
3 VOLTMETER AND A-METER
4 OUTPUT
5 AUX
6 STOP INPUT
7 OPERATE
8 MENU
9 DISPLAY
More detailed descriptions of the display and the
menu options appear in chapter 4 ”Display” and
chapter 5 ”Menu options”.
MAINS block
This block contains a miniature circuit breaker (F2)
connected to the current generation circuitry. It can
be operated manually and used as a disconnector to
prevent unintentional generation. The mains ON/
OFF switch is on the left-hand side of the casing.
Beside the mains ON/OFF switch is a fuse (F1) used
for the control unit’s internal power supply.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
1 7
3 C o n t r o l p a n e l
1 8
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
CURRENT ADJUST
1 2 3 4 5 6 7 8 9
COARSE
-
I/30
0
10
20
30
40
50
60
70
80
90
100
FINE
20A
200V
AMMETER 2VOLTMETER
OUTPUT
PARALLEL
SE RIES
HIG H I
0-30 V/60 V
AUX.
STOP INPUT
INT
LATCHED
250V
CURRENT ADJUST block
In this block you set (adjust) the generated current.
The <FINE> knob is used to make fine adjustments.
The <+> or <-> buttons are used to make coarse
adjustments. The step 8 and 9 on the COARSE
LED-scale are used only in combination with current units of type H.
The I/30 option enables you to make the settings at
a reduced current, only 1/30 of the real test current,
see section 7.3 ”Setting the desired current”. The sett
ings are approximate and work best on linear loads.
are using and how the current units are connected to
each other.
Important!
The settings in this block must be made
befor
e current generation star ts. Check
carefully to see that what you have specified is correct - if not, the values presented on the display will be incorrect.
HIGH I:
S
elect this if you are usingt the high-current output.
0-30/60 V:
S
elect this if you are using the low-current output
(0-30/60V) on a current unit of type X.
PARALLEL:
S
elect this if the current units are connected
in parallel or if you have only one current unit
connected.SERIES:
Select this if the current units are connected in
series.
VOLTMETER AND A-METER 2 block
In this block you make the connections needed to
measure a voltage or a second current. This is use-
ul when (for example) you want to measure phase
f
angles, polarity or a the turns ratio of a current
transformer. You can make your settings using the
<V/A METER> menu option in the MENU block.
An indicator lamp lights up to indicate whether you
have activated the voltmeter or Oden AT’s ammeter
2 (A-METER 2).
WARNING
The VOLTMETER and AMMETER 2 inputs
are internally connected.
OTPUT block
AUX block
This block is not used.
STOP INPUT block
In this block you enter the stop condition. When this
condition is met, the current generation and timer
stops and the measured value can be frozen (held).
Internal detection INT
Hold/Stop takes place when the current is interr
upted by the object being tested.
Voltage mode
The input responds to application or interrup-
tion of voltage.
In this block you specify which current output you
Contact mode
The input responds to the opening or closing
of a contact.
The input responds to application of voltage
orthe closing of a contact.
O d e n A T
STOP INPUT
INT
LATCHED
250V
STOP INPUT
INT
LATCHED
250V
STOP INPUT
INT
LATCHED
250V
STOP INPUT
INT
LATCHED
250V
STOP INPUT
INT
LATCHED
250V
STOP INPUT
INT
LATCHED
250V
STOP INPUT
MAX TIME
OPERATE
MOM.
ON
ON
ON+
TIME
OFF
OFF
SER IAL
AUTO
OFF
3 C o n t r o l p a n e l
The input responds to the interruption of volt-
age or the opening of a contact.
The status lamp adjacent to the connection sockets
lights up:
In the voltage mode — if voltage is present.
•
• In the contact mode — if the contact is closed.
When the preset stop condition is met the
LA
TCHED lamp lights up. Resetting takes place
automatically when you start a new generation or
when you press the <RESET> button in the DISPLAY block.
You can set the stop condition in a number of different ways.
Oden AT is set to respond to the closing of an external
contact.
Oden AT is set to respond to the opening of an external
contact.
Oden AT is set to respond to the opening or closing of an
external contact.
Oden AT is set to respond to the application of a voltage.
You can use the ollowing combinations:
Oden AT is set to respond to the interruption of a voltage.
OPERATE block
Here you can start and stop current generation.
OPERATE: This lamp lights up when current
is generated.
T
emperature alarm:
This lamp will light up if the temperature rises too high and Oden
A
T risks becoming overheated.
<ON+TIME>: Starts current generation.
generation starts the timer is instantaneously reset and restarted.
<MOM ON>:
Current generation starts and
continues as long as you press the
button.
<OFF>:
Stops current genration. Use this
button to turn off current generation.
<AUTO OFF>: Activates the automatic shutoff-
function. Oden AT will automatically stop generating current after
a specified period of time. Press
the button until the MAX
lamp lights up, and enter the
maximum generation time using
the <CHANGE> knob.
This button can also be used to
activate the automatic shutoff
when a stop condition is met.
Press the button until the ST
INPUT lamp lights up, and enter
the desired stop condition in the
STOP INPUT block.
SERIAL: The SERIAL
port (RS232C-port)
is used when you want to transfer test results from
Oden AT to a PC or a printer. See appendix 1.inter.
See appendix 1.
When
TIME
OP
Oden AT is set to respond to the application of a voltage or
the interruption of a voltage.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
1 9
3 C o n t r o l p a n e l
V / A
METER
MENU
CHANGE
ENTER
ESC
AM-
METER
ME-
MORY
APPLI-
CATION
SYSTEM
12.34 s
12.4 A
RESE T
HOLD
O d e n A T
MENU block
In this block you can select special functions and
change the settings for the measuring instruments.
Press the button to the desired menu option. Use
the <CHANGE> knob to select a function or alter a
value. Press the <ENTER> button to confi
choice and/or proceed to the next level. Press the
<ESC> button to cancel and/or go back to the previous level.
<CHANGE> Knob used for selecting and step-
ping in the menus.
<ENTER> Press this to confirm a choice.
Also used for initiating data dump
via the serial port, see appendix 1.
<ESC> Press this button to cancel or
return to the previous level in a
menu.
Also used to activate R, Z,
X, ϕ (phase angle), P, S, Q and
power factor (cosϕ) measurements
or to read the maximum current
during an operation.
The different menu options are described in greater
detail in chapter 5 ”Menu options".
<AMMETER>
In this menu option can you select the range for
ammeter 1 (A-METER 1, measuring the generated
current), and specify whether the measured values
are to be expressed a) in amperes, b)as percentages
of nominal current or c) as ratios. See section 5.2.
<V/A METER>
In this menu option can you choose between using
the voltmeter or the ammeter 2 (A-METER 2, measures a second current), select their ranges and how
the values should be expressed. In this menu option
you can also set the system to measure the turns
ratio of a current transformer
<SYSTEM>
In this menu option can you specify a) the time unit
to be used by the timer
to be used for unstable measured values, and c) the
amount of delay for the automatic shutoff in accordance with the preset stop condition. In addition
2 0
. See section 5.2.
, b) whether or not filtering is
rm your
you can select the language that will be used in the
display and make the desired entries for calibration.
See section 5.2.
<MEMORY>
This menu option enables you to recall or save settings for Oden
AT in 10 memories. See section 5.3.
<APPLICATION>
In this menu option can you set Oden
AT for the fol-
lowing applications:
•
Normal use.
• Microhm measurement.
• Testing of a direct acting automatic recloser.
• Testing of a sectionalizer.
• Generation of a pulse train.
The APPLICATION menu option is described
further in section 5.3. The different applications are
described in detail in chapter 7 ”How to use Oden
A
T” and in chapter 8 ”Application examples”.
DISPLAY block
This block contains the display which presents
times, currents or voltages as well as messages and
menus. Chapter 4 ”Display” describes the display
and its functions in greater detail.
Y
ou can change the settings for the timer, the ammeters
do not want to use the default settings.
<HOLD> Pressing this button freezes
<RESET> This button is used to clear (reset)
and the voltmeter via the MENU block if you
(holds) the measured values.
When the lamp in the <HOLD>
button glows steadily it indicates
that the HOLD function is active.
Freezing takes place a) when the
stop condition is met or b) when
generation is shut of
f, whereupon
the lamp in the <HOLD> button
starts to flash. The frozen value
disappears as soon as you start a
new generation or press the <RESET> button.
the values shown on the display
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
.
O d e n A T
4 D i s p l a y
4 Display
4.1 The display
The display:
• Presents measured values.
• Presents Oden AT´s settings.
• Guides you by providing helpful messages, warn
ings and prompts.
Helps you scroll through menu options by dis-
•
playing directional indicators.
The display is divided into 4 areas. Normal use:
Time
Ammeter 2 /
Ammeter 1
Example:
1.234 s
voltmeter
for details.
Directional indicators
The directional indicators that appear on the display show which direction you can scroll using the
<CHANGE> knob. There are three types of direc-
tional markers:
You can scroll upwards
You can scroll downwards
You can scroll both up and down
When special applications are activated
When a special application is activated this is indicated in the upper right corner.
Example:
Application ”TEST
1.234 s
RECLOSER
RECL.
750 A3.123 V
By pressing the ESC key; Z, ϕ (phase angle) & Z, P,
R, X, S, Q, power factor (cosϕ) or max I1) will appear in the upper area of the display.
1)
Max I is the highest current value that was gener-
eted (minimum time 100 ms) during the injection.
Example:
4.164 m Z
750 A3.123 V
”O.F.” (Overflow) in an area means that the value is
too high.
”- - - ” in a field means that it is impossible to
present a value.
urement signal or that it is impossible to calculate
a value.
The reason can be too low meas-
750 A
See further the descriptions of the application
modes, chapter 8 ”Application examples”.
If you press <ENTER> the measured values will be
dumped via the serial (RS-232) port, see appendix 1
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
2 1
O d e n A T4 D i s p l a y
2 2
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
5 M e n u o p t i o n s
5 Menu options
5.1 General
This chapter explains the menu options available in
the MENU block on the control panel and the settings that you can make there. All settings appear on
the display.
You can only select a menu option while Oden AT is
in the OFF state (i.e. not generating).
There are three ways to exit from a menu option:
•
Press the button of the most recently selected
menu option a second time.
•
Press <ON+TIME>.
• Press <RESET>.w
5.2 AMMETER, V/A METER and
SYSTEM menu options
You can set Oden AT’s first ammeter (A-METER
1) in the <AMMETER> menu option. In the <V/A
METER> menu option you can set Oden AT’s second ammeter (A-METER 2) and Oden AT’s voltmeter. In the <SYSTEM> menu option you can set
the timer, select the desired language for use on the
display, and make certain other settings. The menu
options are described in detail below.
How to set values:
An example of how the display can appear for the
<AMMETER> menu option appears below
line (the menu heading) shows what is to be set. The
second line (right-justified) shows the actual setting.
You can use the <CHANGE>-knob to scroll through
the different menu headings. The directional indicators show the direction or directions in which you
can scroll.
Example:
. The top
RANGE
Auto
• You can scroll upwards.
Select the desired menu heading (RANGE for example) and press <ENTER>.
between flashing arrow-heads < >:
The value will appear
RANGE
< Auto >
You can now change the setting (to the low A range
for example) using the <CHANGE> knob.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
Press <ENTER> to confirm your choice. You can
press the <ESC> button to leave the field without
changing it or to return to the previous level.
2 3
O d e n A T
2 4
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
5 M e n u o p t i o n s
A-METER 1
In this menu option you can make settings for Oden
AT’s first ammeter (A-METER 1). You can select
the range and the unit in which the reading is to be
expressed (amperes, percentage of nominal current
or as a ratio). In addition, you can specify the nominal current itself.
The available settings are listed below.
Ammeter 1
MenuSettingsDescription
RangeAutoRange is selected auto-
matically
LowLow range is selected
HighHigh range is selected
UnitAmpereCurrent reading in Ampere
% of InCurrent reading as percent-
age of nominal current
I1/I2Cur
Nominal
Current
1)
The value for range Low or High depends on your
configuration and on which output you are using,
see section 11.6
Value in AHere you can set the value
rent reading as the ratio
of generated current (I1) to
current measured by AMMETER 2 (I2)
of the nominal current
1)
1)
V/A METER
In this menu option you can select to use the voltmeter or the second ammeter (A-METER 2). You
can also modify the settings for the instruments. You
can select the range and the unit in which the reading is to be expressed (volts/amperes or percentage
of nominal voltage/current). In addition, you can
specify the nominal current/voltage itself and have
the turns ratio for a current transformer displayed.
First in the menu you have to select between A-METER 2 or
VOLTMETER. Select the desired instrument by pressing <ENTER>. The instrument will be
activated and you can now modify its settings.
The available settings are listed in the table below.
V/A Meter
MenuSettingsDescription
A-Meter 2,
Range
A-Meter 2,
Unit
A-Meter 2,
Nom I
V-Meter,
Range
AutoRange is selected auto-
matically.
0 – 2 A0 – 2 A range is selected.
0 – 20 A0 – 20 A range is se-
lected.
AmpereCurrent reading in Am-
pere.
% of InCurrent reading as
percentage of nominal
current
CT ratioRatio for a cur
transformer is presented
as XXXX/In (XXXX=I1x
Im/I2). The value for I2 is
set to In x (factor). I1 is
multiplied with the same
factor
Value in AHere you can set the
value of the nominal current
AutoRange is selected auto-
matically
0 – 0.2 V0 – 0.2 V range is se-
lected
0 – 2 V0 – 2 V range is selected
0 – 20 V0 – 20 V range is se-
lected
0 – 200 V 0 – 200 V range is se-
lected
rent
O d e n A T
5 M e n u o p t i o n s
SYSTEM
In this menu option you can a) select the unit in
which the timer results will be expressed, b) activate
DC-measurement function and c) specify the delay
time for the automatic shutoff (AUTO OFF) function. You can also activate the Auto-Dump function
and select the language that will be used on the
display. Finally you can set the INT level and the
threshold for detection that the genereted current is
interrupted.
The available settings are listed in the table below.
System
MenuSettings Description
TimerSecondsTime displayed in seconds.
CyclesTime displayed in number of
oltage cycles.
mains v
hh:mmTime displayed in hour
utes and seconds. Seconds are
displayed up to 1 min.
DC- Meas-
ement
ur
OFF Delay CyclesSpecif
AutoDump
LanguageEnglish
INT-levelValue in
On/OffOden AT can be set to measure
DC-current (A-meter 1 and 2)
and DC-voltage (V-meter). See
note.
y the number of mains
voltage cycles which the automatic shut-off is to be delayed
(in accordance with the preset
stop condition).
On/OffOden At can be set to automati-
cally dump test data to a P
when the generation is stopped.
See Appendix 1.
Language used on the display.
ench
Fr
German
Spanish
Swedish
eshold for detecting that
The thr
0.7 or 2.1%
of range
the generation has been interrupted can be changed. See
section 11.6 Ammeter 1 ranges.
Note: The DC- measurement function is used
when Oden AT is used together with a
rectifier box. A-meter 1 and 2 shows rectified average value and voltmeter shows
average value.
s, min-
C
5.3 MEMORY and APPLICATION
menu options
In the <MEMORY> menu option, you can store
present settings in one of Oden AT’s 10 memories,
or recall previously stored settings. In the <APPLICATION> menu option, you can change Oden
AT’s mode of operation to support certain applications, like testing direct acting automatic reclosers
or generate pulse trains (pulse-pause-pulse-pause
etc.). These menu options are described in the table
below.
Setting values
Y
ou make all selections and settings using the
<CHANGE>-knob. You confirm your entries by
pressing <ENTER>, whereupon you advance further
into the menu.
the direction (or directions) in which you can scroll.
You can return to the previous level by pressing the
<ESC> button.
You select the item you want to change with the
<CHANGE> knob. Check to see that it is bracketed
by arrow-heads (< >) and then press <ENTER>.
arrow-head brackets will start to flash to indicate
that you can change the item using the <CHANGE>
knob. When you are finished, press <ENTER> to
confirm your entry.
MEMORY
You can save your regular Oden AT settings in
this menu option. Moreover you can, for example,
prepare settings in advance and save them so that
they can be recalled whenever desired. Oden AT has
ten memories numbered 0-9 where you can save settings. The memories retain their contents even when
power to the Oden AT is turned off.
When you start Oden AT, the settings saved in
memory number 0 are loaded automatically. This
means that if you want a specific set of settings to
be used the next time you turn Oden AT on, you can
save them in memory 0 before turning Oden AT off.
There is one additional memory called the standard
memory in which the factory settings are kept, these
factory settings cannot be changed.
The available settings are listed in the table below
The directional indicators show you
The
.
Tip!
Try higher INT-level if trip-time is unexpectively long and try lower INT-level if trip
time is unexpectively short.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
2 5
5 M e n u o p t i o n s
Memory
MenuSettings Description
RECALL or
SAVE
RECALL
0 - 9
RECALL
tandard
S
SAVE
0 - 9
Recalling settings from a memory
1. Press the <MEMORY>-button
ecalls settings from a specific
R
memory.
Recals factory settings.
es settings in specified
Sav
memory.
O d e n A T
2. Turn the <CHANGE>-knob until ”RECALL” ap
pears on the display and press <ENTER>.
Turn the <CHANGE>-knob until the number of
3.
the desired memory appears.
4. Press <ENTER>.
APPLICATION
In this menu option you can change Oden AT’s
mode of operation for different types of tests.
The available settings are listed in the table below.
Application
MenuDescription
“””NORMAL USE”””Configures Oden AT for nor-
mal use.
“””MICROHMETER”””Oden AT will work as a micro-
.
hmeter
“””TEST RECLOSER”””Sets Oden AT to test a direct-
acting automatic recloser.
“””PULSES”””Sets Oden AT to generate a
pulse train.
”SECTIONALIZER”””Sets Oden AT to test a sec-
“”
tionalizer
.
-
2 6
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
6 H o w t o i n s t a l l O d e n A TO d e n A T
Working
position
Transport
p
osition
Rest
position
6 How to install Oden AT
6.1 Safety
DANGER
When you are changing the connections
make sure that current not can be generated accidently. Disconnect the mains
supply or switch the miniature breaker F2
to the 0-position.
WARNING
The current output terminals and connecting points can be hot after generation of high current.
All current units used must also be connected to the control unit. Otherwise the
current unit might be damaged.
Do not connect two or more ODEN AT
systems in parallel or series. This can
damage ODEN AT.
6.2 Loading Oden AT onto a carriage
The components of Oden AT (i.e. the control unit
and the current units) can be mounted on a carriage
for easy transportation. The carriage also serves as
a platform and helps to raise the control unit to a
comfortable working position
WARNING
To prevent tip-over, the current units must
be loaded onto the carriage from bottom
up.
The carriage is primarily intended for
transportation but may also be used
when testing. The carriage must then be
secured to prevent tip over. It should
withstand a horizontal force of 250 N
(N = Newton, approx. 56 lbs of force)
in any direction applied anywhere o the
equipment.
If securing is not possible stack the units
on a flat surface that can support the
load of the units. Make sure that the
stack will withstand a horizontal force of
250 N in any direction applied anywhere
to the equipment.
The steel brackets mounted on the carriage are only intended for keeping the
Oden AT units in place during transportation. They are not dimensioned to carr y
the weight of a current unit. A current unit
should always rest either on the loading
pallet or ontop of another current unit.
Place the first current unit on the bottom loading
pallet of the carriage. Make sure that the current unit
Fig 6.1 Different positions for the Oden AT carriage. Note, in working position the carriage must be secured to prevent tip
over. Secure it to a suitable object e.g. a pole or a table.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 02 7
6 H o w t o i n s t a l l O d e n A TO d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 02 8
is held in place by the steel brackets on the carriage.
Place the next current unit on top of the first. Make
sure that it too is held in place by the brackets. The
control unit should be mounted last.
When the carriage is in the working position the
control unit can be mounted on the uppermost pair
of brackets for easy access to the controls.
When the
carriage is used for transportation or is placed in the
resting position, the control unit should be placed
ontop of the uppermost current unit to ensure stability. See fig 6.1
6.3 Connecting the test object and
the current units to each other
Important!
Do not use old current units (which have
16-pin connectors) together with any
newer cur
(which have 24-pin connetors).
Incor
neous measur
damage to the current units.
When you connect Oden AT to the object being
tested, you should check that the contacts on the
connectors are clean and that the cable clamps are
placed as close together as possible on the object
being tested.
types of cables have different capacities for carrying
high currents.
T
o minimize the voltage drop in the cables from
Oden
AT to the object under test you can:
• Use two or more cables in parallel.
rent units, i.e. type S, H or X
rect connections will result in erro-
ed values and might cause
You must also remember that different
• Use as short cables as possible.
• Use cables with heavier gauge (thicker) conduc
tors.
• Twist cable pairs. When units are connected in
parallel only cables running from the same current unit are to be twisted together.
-
Fig 6.2 Example of how cables can be run
There are three types of current units; type S, type
H and type X. If you want to use two or three cur-
6 H o w t o i n s t a l l O d e n A TO d e n A T
Load
High-current outlet
rent units, you can connect them either in series or
in parallel. The different connection variants are
explained later in this chapter.
• Do not connect units that are of different types to
each other. Only connect type S units to type S
units, type H to type H etc.
•
When using several current units of type X, the
switch 0-30V/60V must be set in the same position on all currentunits.
6.4 Series connection (output HIGH I)
Use series connection when you want a high voltage
at a high load impedance. For more information see
chapter 11 ”Specifications”.
Fig 6.3 Units connected in series
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 02 9
6 H o w t o i n s t a l l O d e n A TO d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 03 0
Load
High-current outlet
0-30 V
0-30V/60V
Low-current
outputs
0
-30/60V s
witch
Switch b
etween
30 V and 60 V
HIG H I
H
igh-cur
rent
outputs
0-30 V/60 V
HIG H I
0-60 V
6.5 Parallel connection (output HIGH I)
Use parallel connection when you need a low
internal impedance in order to be able go generate
high current. For more information, see chapter 11
”Specifications”.
Fig 6.4 Units connected in parallel
6.6 Low-current output (output 030V/60V)
DANGER
The voltage at the output terminals can
be dangerous. Especially when units are
connected in series.
Never use a high-current output while
simultaneously using a low-curret output!
WARNING
Never switch between the 30 and 60 V
settings when Oden AT is generating.
Important!
All type X current units that are connected together must have the same connection setting for the low-cur
0-30 V or 0-60 V.
In addition to its regular high-current output, a type
X current unit (which has an extra winding) has a
low-current output that provides higher voltage (30
V
or 60 V). You select the desired voltage by means
of a switch on the current unit.
rent output, i.e.
Fig 6.5 Current unitof type X
6 H o w t o i n s t a l l O d e n A TO d e n A T
Grounded
mains cable
Ground cable
t
o ground
6.7 Connecting current units to the
control unit
Important!
All current units used must be connected
to the control unit.
Do not connect cur
used.
If two units are connected in series and
three are connected to the control unit the
showed current value will be false.
Current units are connected to the control unit via
cables with a 24-pin onnector
rent units that are not
.
6.8 Grounding Oden AT
DANGER
This equipment can be used only in electrical systems with single Ground. User
must verify before connecting this unit to
power, that High Voltage Ground and Low
Voltage Protective Ground create a single
protective ground with no measurable
voltage potential existing between these
gr
ound systems. If a voltage potential
is found between the ground systems
please consult local safety regulations.
WARNING
Always use a grounded mains cable to
connect the control unit to the mains,
and in addition you must connect a separate ground cable. Connect the control
unit to ground as described in fig. 6.7.
Fig 6.6 Current units connected to control unit
If you should want to connect an old current unit with
a 16-pin connector to the control unit in an Oden AT,
you must use a separately-ordered adapter.
Fig 6.7 Oden AT connected to ground
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 03 1
6 H o w t o i n s t a l l O d e n A TO d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 03 2
6.9 Connecting Oden AT to the
mains
Important!
Make sure that the mains voltage corr
esponds to that specified on the data
plates on the control unit and the current
units.
Make cer
fuses and all cables/wiring have sufficient cur
able ratings.
Make sur
units are functioning when Oden AT is
turned on.
Oden AT is a single phase unit. The mains input
voltage should be connected between one phase
and neutral or between two phases. Next to the
mains inlet on the control unit is a data plate stating
the mains input voltage and to which mains inlet
contacts the voltage should be applied. Make sure
that the input voltage is connected according to the
instructions on te dataplate
The mains switch is located on the left side of the
cntrol unit.
Oden
AT’s power consumption will depend on the
magnitude of the output generated and also on the
mains voltage for which it is intended.
Power consumptions for dif
ations are set forth in chapter 1
Note that power consumption is higher for current
units connecte in series.
tain that mains outlet and its
rent-carr ying capacity, i.e. suit-
e that the fans in the current
ferent operating situ-
1 ”Specifications”.
6.10 Mains power supply
Mains voltage
ODEN AT is designed either for 240 V, 400 V
or 480 V. The 480 V version is for 60 Hz only.
ODEN AT by itself is a single-phase equipment but
can of course be connected between two phases in a
3 phase system.
There is also a 400 V / 240 V version available. It
is a 400 V version that also can be supplied from
240 V single-phase standard mains outlet. Please
note that it can only be used on a 400 V system having a neutral.
outlet, the mains supply fuse normally is rated 10 A
or 16 A. This will limit the highest output current
but it is still possible to get several kA for a short
time with a slow 16 A fuse. No-load output voltage
at 240 V supply is 60% of values specified in the
Voltage – Current diagrams. Article no is BH-90120
and includes a mains adapter box.
Input Current
The input current is directly dependent on the output
current and the ratio is stated for each configuration
in the operators’ guide. It can also be calculated for
a 400 V or a 480 V 60 Hz version as:
Output current x Open circuit voltage
and for a 240 V version as:
Output current x Open circuit voltage
Calculated or specified values refer to worst case,
i. e. when current setting is on its maximum. If
settings only need to be at 50% to get the output current, input current is 50% of value above.
1)
Open circuit voltage: Output voltage with current
setting on maximum and no load connected
When supplied from a single-phase
1)
1)
/400
/240
Mains cable and connectors
The inlet and connectors on the mains cable are of
the European CEE standard type. However this connector is not usable in some countries. GE energy
cannot deliver suitable connectors for all countries.
Therefore you might need to replace the male connector on the mains cable. At ODEN AT's inlet is
information about how mains supply should be
connected.
Connector on a control unit for 400 V
Connector on a control unit for 240 V
6 H o w t o i n s t a l l O d e n A TO d e n A T
6.11 Current cables and conductors
Available cable sets
Please note:
• How important it is to twist the cables if possible.
Values stated for twisted cables presuppose
that each cable is twisted over the entire length.
See section ”How to arrange the cable sets”.
• That it is possible to use several cable sets in
parallel, for instance one set for each current
This will decrease impedance and increase
unit.
continuous current capability. Divide impedance
by number of sets in parallel. A separate end-bar,
ordering no. BH 90-100 can be used to interconnect the cable set to get a single bolt connection
to the test object.
Standard multi-cable sets
Cable sets consist of up to six pairs of 120 mm2
cables in parallel. At each end there is an end-bar interconnecting the cables. The bar also enables single
bolt connection to ODEN AT and the test object. See
figure below.
Impedance of the cable set is very dependent onhow
cables are arranged. See section Hwt arrange the
cable sets
Multi-cable 6 x 120 mm2 with end-bar
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 03 3
6 H o w t o i n s t a l l O d e n A TO d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 03 4
Length 2 x 0.5 m (distance to test object 0.5 m)
Number
of cables
1 pair120 mm
2 pairs240 mm
3 pairs360 mm
4 pairs480 mm
6 pairs720 mm
Total cross section
area
2
(1 x 120)
2
(2 x 120) 0.21 < 0.53 -3 200 700 4.6GA-12205
2
(3 x 120) 0.18< 0.46-4 800 1 050 6.0GA-12305
2
(4 x 120) 0.16 < 0.40-6 400 1 400 7.3GA-12405
2
(6 x 120) 0.14< 0.35-9 600 2 100 10.0GA-12605
Impedance
cables twisted
(mW)
Impedance
cables not
twisted (mW)
Impedance
cables 1 m
apart (mW)
Max. current in 20
sec. (A)
Max. cont.
current (A)
Weight
(total set)
(kg)
Article
number
Length 2 x 1.0 m (distance to test object 1.0 m)
Number
of cables
1 pair120 mm
2 pairs240 mm
3 pairs360 mm
4 pairs480 mm
6 pairs720 mm
Total cross section
area
2
(1 x 120)
2
(2 x 120)0.32< 0.80 - 3 200 700 7.3GA-12210
2
(3 x 120)0.25 < 0.63 - 4 800 1 050 10.0 kGA-12310
2
(4 x 120)0.21 < 0.53 - 6 400 1 400 12.7 kGA-12410
2
(6 x 120)0.18 < 0.45 -9 600 2 100 18.1 kGA-12610
Impedance
cables twisted
(mW)
Impedance
cables not
twisted (mW)
Impedance
cables 1 m
apart (mW)
Max. current in 20
sec. (A)
Max. cont.
current (A)
Weight
(total set)
(kg)
Article
number
Length 2 x 1.5 m (distance to test object 1.5 m)
Number
of cables
1 pair120 mm
2 pairs240 mm
3 pairs360 mm
4 pairs480 mm
6 pairs720 mm
GE Energy can supply the Multi-Cable Sets with
other lengths than specified above.
“L” refers to length of the set (maximum distance to
the test object)
Impedance can be calculated:
6 H o w t o i n s t a l l O d e n A TO d e n A T
Number
of cables
1 pair120 mm
2 pairs240 mm
3 pairs360 mm
4 pairs480 mm
6 pairs720 mm
Total cross section
area
2
(1 x 120) (L x 0.43) + 0.1 1 600 A350 A(L x 2.7) + 1.9 kg
2
(2 x 120)(L x 0.22) + 0.13 200 A700 A(L x 5.4) + 1.9 kg
2
(3 x 120)(L x 0.14) + 0.14 800 A1 050 A(L x 8.1) + 1.9 kg
2
(4 x 120)(L x 0.11) + 0.16 400 A1 400 A(L x 10.8) + 1.9 kg
2
(6 x 120)(L x 0.07) + 0.19 600 A2 100 A(L x 16.2) + 1.9 kg
Impedance, cables twisted 1)
(mW)
Max. current in
20 sec.
Max. cont. current Weight (total set)
1) Impedance can be up to 2.5 times higher if the cables are running close together but not twisted and up to 4 times higher
if they are 1 meter apart.
Example, customised Multi-Cable sets, length
2 x 5.0 m
Number of
cables
1 pair120 mm
2 pairs240 mm
3 pairs360 mm
4 pairs480 mm
6 pairs720 mm
Cross section areaImpedance
cables twisted
(mW)
2
(1 x 120) 2.2 < 5.5 < 8.8 1 600 A350 A15.4 kg
2
(2 x 120)1.2 < 3.0 < 4.8 3 200 A700 A28.9 kg
2
(3 x 120)0.8< 2.0< 3.2 4 800 A1 050 A42.4 kg
2
(4 x 120)0.65 < 1.6 < 2.6 6 400 A1 400 A55.9 kg
2
(6 x 120)0.45 < 1.1 < 1.8 9 600 A2 100 A82.9 kg
Impedance cables not twisted
(mW)
Impedance
cables 1 m
apart (mW)
Max. current
in 20 sec.
Max.
continuous
current
Weight
(total set)
Standard 2 X 5 M (single pair) cable set with
clamps)
Just increasing cross-section area helps only to a
certain extent. When resistance is low, the major
part of the impedance is caused by the reactance.
Minimising the magnetic flux will reduce the reactance:
• Best is if a cable from a current unit terminal can
be twisted together with a cable from the other
terminal on the same curr
ent unit. This guarantee opposite current with same value which will
almost neutralise the magnetic flux.
• f cables not can be twisted, keep cables with
same current direction away from each other as
much as possible
Avoid loops or “windows”.
•
Current unit with twisted 2 pairs Multi-Cable Set
It is sometimes not possible or practical to twist the
cables. However any action to keep cables with opposite current direction close together and to minimise loops helps. If the distances to the test object
terminals are different it is better to use cables with
different lengths in order to avoid loops.
6 H o w t o i n s t a l l O d e n A TO d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 03 7
6 H o w t o i n s t a l l O d e n A TO d e n A T
6.13 How To Arrange Bars
Copper-bars are in many cases a better solution than
cables at high currents and short distances and at
long load times. Bars must be specially designed for
the actual test objects and in general this work must
be the users responsibility. Here are some guidelines:
• Proper cross section area. Not less than 500 mm
- 1000 mm2 (depends on the actual current). Take
eventual heating into consideration.
• As close to the bar as possible (preferably maximum 1 mm) there should be another bar carrying
the same amount of current in the opposite direc-
This will neutralise the magnetic flux. Even
tion.
if this arrangement slightly increases the length,
it still is a gain because impedance due to magnetic flux is a bigger problem than the resistance.
• Do not use bars thicker than 10 mm and arrange
the bars with their flat sides close together. The
reason is that the magnetic flux (and the reactance) will be more ef
current is forced to flow close to the current with
opposite direction.
fective neutralised if the
Make parallel connections between the terminals of
the current units. Contact must be good, preferably
use bars. Connect the cable set between the bars and
the test object.
2
• Loops (windows) that allow magnetic flux must
be avoided).
Joints must have low resistance
•
Example:
Two copper bars have the cross section 10 mm x
50 mm and they are mounted 5 mm from each other
(the flat sides close together). Per meter of this arrangement the impedance is:
90 m at 50 Hz (R = 73 m and X = 54 m)
98 m at 60 Hz (R = 73 m and X = 65 m)
To get equal current from all current units.
When units are connected in parallel care must be
taken that one unit does not supply the major part
of the current. Otherwise its thermal protection can
trip.
Method 1
There should be no parallel connections between
the terminals of the current units. Make sure that the
cable impedance between each current unit and test
object is equal (same number of cables and same
length).
Method 2
If number of cables used can not be evenly divided
by the number of current units.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 03 8
O d e n A T
7 H o w t o u s e O d e n A T
7 How to use Oden AT
This chapter describes the functions that you can
perform using Oden AT. Complete test procedures
are described in the next chapter, chapter8 ”Application examples”.
7.1 How to generate current
1. Connect Oden AT to the object under test as
described in chapter 6.
2. Turn on Oden AT using the mains switch on the
side of the control unit.
3.
Specify the desired settings in the OUTPUT
block on the control panel.
Which output are you using?
• Specify HIGH I if you are using the high current output.
• Specify 0-30V/60V if you are using the output
0-30V/60V (only available on type X current
unit).
re current units connected in series or in parallel?
A
• Specify PARALLEL if you are using a single
current unit.
• Specify PARALLEL if you are using several
current units connected in parallell.
• Specify SERIES if you are using several current
units connected in series.
Set the circuit breaker F2 in the I position.
4.
5. Press <ON+TIME>. The value of the output
current will appear on the display.
6. Adjust (set) the current using the coarse or fine
adjustment controls.
7.
If time test is included, press the <OFF> button
to shut off the current.
8. Press <ON+TIME> to start a new generation
with the correct current.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
3 9
7 H o w t o u s e O d e n A T
4 0
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7.2 Rules of thumb when generating
current
When you generate current there are rules which can
be useful to follow:
• To reduce voltage drop, the current cables running to the object being tested should be as short
as possible and have sufficient heavy-gauge
(thick) cross-area.
age drop further by twisting cables of different
polarity together (see fig 6.2), thereby making it
possible to inject higher currents.
• If the object being tested has a low impedance
connect the current units in parallel. Connect
them in series if the object has high impedance.
To avoid unneccesary heating of objects being
•
tested, current can be generated in brief intervals.
It might be best to use manually-controlled (momentary) injection or time-limited injection.
Oden AT, it is also possible to make a coarse
adjustment of the current using the I/30 function
(which uses only 1/30th of the real test current).
• When operating time is measured, the value
of the injected current or applied voltage must
exceed the lowest operating limit by an ample
gin (1.2 - 2 times is the rule of thumb here).
mar
You can reduce the volt-
With
7.3 Setting the desired current
Low currents:
1. Connect the object being tested to a suitable
Oden AT output.
2. Press <ON+TIME>.
3. Adjust the current using the coarse adjustment
buttons or the fine adjustment knob. The value
of the current will be presented on the display.
High currents:
High currents can generate a great deal of heat in
both Oden AT and the object being tested. To avoid
unneccesary heating, you can:
•
Generate current only for brief intervals.
• Use the I/30 function .
Generating briefly
There are two easy ways to generate current for
brief intervals: a) using the <MOM ON>-button or
b) using the limited-time generation function. These
are described in this chapter in section 7.13 “Measuring operating limits”.
Using I/30 function
Connect Oden AT properly to the object being
1.
tested. See chapter 6 ”How to install and connect Oden
AT”.
2. Activate the I/30 function.
3. Press <ON+TIME>. The current is displayed
as ”XXXX/30”. XXXX represents the value
the current will have when the I/30-function is
released.
Adjust the current using the coarse adjustment
4.
buttons or the fine adjustment knob. The value
of the current will be presented on the display.
5. Shut off the current using the <OFF> button.
6. Deactivate the I/30 function.
7. Activate the HOLD function by pressing
<HOLD>.
8.
Press the <MOM ON>-button briefly.
9. Read the current presented on the display.
10. Use the <FINE> knob for fine adjustment of the
current.
1. Repeat, starting with step 8 above, until you
1
have set the desired current.
Note: The I/30-function is less accurate on non
linear test objects.
O d e n A T
7 H o w t o u s e O d e n A T
7.4 Setting times for limited-time
generation (MAX TIME)
If you want to generate current throughout a limited
time using the MAX TIME function, proceed as
follows:
1. Press <AUTO OFF> in order to light up the
MAX TIME lamp. The preset maximum generation time will appear on the display
2. Set the desired generation time by turning the
<CHANGE> knob. If you want the time expressed in another unit than the preset, you can
enter a new unit under the
TIMER menu head-
ing in the <SYSTEM> menu option.
MAX TIME
< 1.500s>
.
7.5 Continuous current generation
If you want to generate current for an unlimited
time, i.e. until you shut generation off manually,
proceed as follows:
1. Press <AUTO OFF> in order to turn off the
STOP INPUT and MAX TIME lamps.
2. Start generation by pressing <ON+TIME>.
3. Set the desired current using the coarse and fine
adjustment procedures.
3. Start generation.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
4 1
7 H o w t o u s e O d e n A T
4 2
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7.6 Getting maximum current from
Oden AT
Maximum output current is limited by the following:
• Impedance of the object being tested.
• Impedance of the current cables.
• Mains supply.
• Voltage drop in mains cables and other cables.
• Oden AT’s internal impedance
To obtain maximum current from Oden AT proceed
as follows:
•
Connect two or three current units together.
• If the object being tested has high impedance,
connect the current units in series.
If the object being tested has low impedance,
•
connect the current units in parallel.
Use short, heavy-gauge (thick) cables and
•
twisted cables, see fig 6.2.
7.7 Improving the resolution of
current settings
If you want to improve the accuracy of current settings, you can:
• Use a voltage that is as low as possible by (for
example): a) not connecting the current units
in series, b) using the high-current output even
when low currents are to be generated, or b)
connecting the low-current output for the lowest
voltage (0-30
current unit.
• Increase the impedance in the circuit, for instance use longer
cables.
V) if you are using a single type X
, lighter-gauge (thinner) current
• Make certain that the object being tested is con
nected properly (all connectors must be clean,
connected at the right places etc.).
-
O d e n A T
7 H o w t o u s e O d e n A T
7.8 Generating pulse trains
You can set Oden AT to generate a pulse-train (intermittent current generation at regular intervals, i.e.
pulse-pause-pulse-pause etc.). This will continue until you shut off generation, until a preset maximum
time (MAX TIME) is reached or until the condition
at the STOP INPUT is met.
1. Basic settings:
OPERATE: OFF
2. Set the desired current. See section 7.3 ”Setting
the desired current”.
Press the <APPLICATION> menu option.
3.
4. Turn the <CHANGE> knob until ”PULSES”
appears on the display and press <ENTER>.
Set the pulse duration (TIME ON) by turning
5.
the <CHANGE> knob and press <ENTER>.
TIME ON
7.9 Holding (freezing) measured
values
Press the <HOLD> button to activate the holding
(freeze) function. The function freezes a measured
value when a signal arrives at the STOP INPUT or
when the current is interrupted. When the hold function is activated the lamp in the HOLD button glows
steadily. As soon as the stop condition has been met,
the lamp in the HOLD button starts to flash.
The frozen values disappears when you start a new
current generation operation or press <RESET>.
< 1.000s T1 >
6. Set the desired between-pulse pause (TIME
OFF) by turning the <CHANGE> knob and
press <ENTER>.
Note: You can select the unit in which time is
to be expr
essed under the TIMER menu
heading in the <SYSTEM> menu option.
7. Press <ON+TIME> or <MOM ON> to start the
test. The word ”OPERATE” appears on the display indicating that Oden
18.50s
AT is generating.
OPERATE
800A5:OP
Note: The counter on the display (”:OP”) is
intended mainly for use when testing
sectionalizers. Each time the current is
interrupted the counter value increases
by one. The counter can count up to 127
pulses.
8. Generation stops when you press <OFF> or
release the <MOM ON>-button or when the
AUT
O OFF-conditions are met.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
4 3
7 H o w t o u s e O d e n A T
4 4
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
I2
I1
20A
200V
AMMETER 2VOLTMETER
Positive
direction
Red
(
+)
B
lack
(
-)
Load
Positive direction
Red
(+)
Black
(
-)
Load
Positive direction
I1
20A
200V
AMMETER 2VOLTMETER
20A
200V
AMMETER 2VOLTMETER
Red
(+)
B
lack
(
-)
Load
7.10 Measuring phase angle and
polarity
Oden AT can display the phase angle between the
current from Oden AT and a) the current (I2) passing
through Oden AT’s second ammeter (A-METER 2)
or b) the voltage (V) at the voltmeter input. Press
the <ESC>-button until the sign for degrees (”°”)
appears in the upper-left corner of the display.
Measuring current:
Current direction is defi
Fig 7.1
I1 is the reference current and the range is 0-360°.
ned as illustrated in fig 7.1.
Example:
Fig 7.4
Phase displacement caused by an inductive load.
Voltage lies 60° ahead of current. 60° appears on the
display.
The number of degrees that I2 is displaced ahead
of I1 appears on the display
Fig 7.2
.
Measuring voltage:
Current direction is defined as illustrated in fig 7.3:
Fig 7.3
I1 is the reference and the range is 0-360°. The
number of degrees that voltage (V) is displaced
ahead of I1 appears on the display.
O d e n A T
7 H o w t o u s e O d e n A T
7.11 Measuring Z, P, R, X, S, Q and
power factor (cos )
When Oden AT's voltmeter is activated you can
measure impedance (Z), active power (P), resistance
(R), reactance (X), virtual power (S), reactive power
(Q) and power factor (cos ϕ). You can scroll through
these quantities by pressing the <ESC>-key several
times. Scrolling is possible even if the measurement
is frozen.
300ms
800A0.558V
Standard: Time displyed on upper row.
Pressing the <ESC>-key once provides:
1.434 Z
7.12 Reading maximun current at an
operation
The highest current value showed on the display
at an operation is stored. Press <ESC> repeatedly
until a current value and the text "max" appears. The
maximum current value is updated every 1/3 sec.
800A0.558V
Continue scrolling to view the desired quantities.
0.866cos
800A0.558V
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
4 5
7 H o w t o u s e O d e n A T
4 6
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7.13 Measuring operating limits
There are three ways to measure operating limits:
• Normal generation. Used when there is little risk
for undesirable heating in the object under test.
•
Manually-controlled momentary injection.
• Limited-time generation. Used when you do not
want to expose the object under test to needless
heating.
Method 1: Normal injection; gradually increase in current.
In this method current is sent out continuously.
The current is gradually increased until the object
being tested operates. When this happens a) the
LATCHED lamp lights up, b) the current value is
frozen on the display and c) the current to the object
is interrupted.
When you are testing protective relay equipment
you can, as a next step, reduce the current and freeze
the displayed value to obtain information about the
drop-out function.
1.
Basic settings:
OPERATE: OFF.
CURRENT ADJUST: Lower than the tripping/
operating limit.
HOLD function:
AUTO OFF: STOP INPUT.
2. • For proteive relay equipment:
Set the stop condition to (for example):
• For breakers:
Set the stop condition to INT.
3. Start generation by pressing <ON+TIME>.
ON.
7. Start generation by pressing <ON+TIME> and
turn up the current until the protective relay
equipment operates (pick-up).
8. Turn down the current until drop-out occurs.
The value frozen when drop-out occurred is now
presented on the display
.
For protective relay equipment you can simplify the
procedure by testing both the pick-up and drop-out
functions with a single current generation operation.
This can be accomplished as follows:
Basic settings:
1.
OPERATE: OFF
CURRENT ADJUST: Lower than the tripping/
operating limit
HOLD function:
ON
AUTO OFF: Turn off the AUTO OFF
function (neither the STOP
INPUT nor the MAX TIME
lamp will be lit)
2. Select the stop condition:
3. Start current generation.
4. Increase the current until the protective relay
equipment operates (pick-up).
5.
Read the pick-up function value from the display
.
6. Press <RESET>.
7. Turn down the current until the protective relay
equipment drops out. You can now on the dis
play read the value that was frozen when dropout occurred.
Method 2: Manually controlled momentary
injection
4. Increase the current until operation occurs.
5. The value frozen when operation occurred is
now presented on the display.
Note! If the impedance of the object under test
changes during operation, you should use
the maximum cur
rent value during the
operation as pick-up value. Press <ESC>button to get the maximum value, see
section 3.1. MENU block.
The following apply only when testing protective
relay equipment:
6.
In order to measure the drop-out function,
change the stop condition to (for example):
Here, current is sent out as long as you hold down
the <MOM ON> button. This method is useful when
you do not want to expose the object being tested to
unneccesary heat.
1. Basic settings:
OPERATE: OFF
CURRENT ADJUST: Close to the operating limit
HOLD function: ON
AUTO OFF: STOP INPUT
2. • Foprotective relay equipment:
Set the stop condition to (for example):
• For breakers:
Set the stop condition to INT
O d e n A T
7 H o w t o u s e O d e n A T
3. Press <MOM ON> briefly. Note, however, that
current must be sent out for a period longer than
the operating time.
4. Read the current from the display.
5. Change the current setting somewhat.
6. Repeat, starting at step 3 above, until you find
the lowest current that provides operation.
Method 3: Limited-time generation
Here, current is sent out for a limited period of time
and interrupted when a present maximum time
(MAX TIME) is reached. This method is useful
when you do not want to expose the object being
tested to unneccesary heat. Section 7.4 “Setting
times for limited-time generation (MAX TIME)” in
this chapter explains how to set MAX TIME.
1. Basic settings:
OPERATE: OFF
CURRENT ADJUST: Close to the tripping/opera
ting limit
HOLD function :
AUTO OFF: Specify MAX TIME
2. • For protective relay equipment:
Set the stop condition to (for example):
ON
(choose a generation time
that is longer than the
operating time) and also
specify STOP INPUT
7.14 Measuring tripping/operation
times
Here, generation continues until the protective relay
equipment operates or the breaker trips. To avoid
unneccesary heating or operation of the object being
tested, the I/30-function can be used (see section 7.3
”Setting the desired current” in this chapter) while
the current is being adjusted.
1. Basic settings:
OPERATE: OFF
CURRENT ADJUST: Lower than the operating
limit.
HOLD function
AUTO OFF: STOP INPUT.
2. Set the stop condition to (for example):
3. Start generation by pressing <ON+TIME>.
4. Set the current at which the operating time is to
be measured. The current must exceed the oper-
ating limit by an ample mar
5. Turn off the current by pressing the <OFF>-button.
6.
Press <ON+TIME> again and wait until the stop
condition is met.
7.
Read the time and the current from the display.
ON.
gin.
• For breakers:
Set the stop condition to INT
3. Start injection by pressing <ON+TIME>.
4. Read the current on the display after generation
has stopped.
Change the current setting somewhat.
5.
6. Repeat, starting at step 3 above, until you find
the lowest current that provides operation.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
4 7
7 H o w t o u s e O d e n A T
4 8
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7.15 Instantaneous trip unit
measurement
You can test the instantaneous trip for breakers and
for protective relay equipment as follows:
• When you test the instantaneous pick-up you
can generate current by using the <MOM ON>
button.
pick-up without operating the overcurrent stage.
• You can also use limited-time generation (MAX
TIME) to obtain the desired generation time.
Manually-controlled momentary injection is described below:
Basic settings:
1.
OPERATE: OFF
CURRENT ADJUST: Close to the operating limit
HOLD function: ON
2. For protective relay equipment:
Set the stop condition to (for example):
This permits you to find the instantaneous
4. If neccesary readjust the current and inject
again. Repeat this until you have achieved the
desired current value. Deactivate the I/30 function.
5.
Inject until the test object operates and the operating time is presented on the display
.
• For breakers:
Set the stop condition to INT
3. Select a suitable current setting.
4. Press <MOM ON> briefly. The interval through
out which current is sent out must be shorter
than the overcurrent stage’
s tripping/operating
time.
5. Change the current setting somewhat and repeat,
starting at step 4 above, until you find the lowest
current that provides instantaneous pick-up.
When you test the instantaneous trip time make
the following settings. Use the I/30 function (described in section 7.3 “Setting the desired current”
in this chapter) while making current adjustments to
avoid undesired operation of the object being tested.
1.
Basic settings:
OPERATE: OFF
CURRENT ADJUST: Instantaneous operating
limit
HOLD function:
ON
AUTO OFF: STOP INPUT
• For protective relay equipment:
Set the stop condition to (for example):
-
• For breakers:
Set the stop condition to INT
3. Inject briefly using the <MOM ON>-button.
O d e n A T
7 H o w t o u s e O d e n A T
7.16 Selecting Oden AT
configuration and current cables
Introduction
Different applications have various requirements on
current and load time and the test objects have different impedance. The ODEN AT concept has three
types of current units and they can be connected in
series or in parallel. So there are good possibilities
to find a configuration that meet your requirements.
Examples of different applications:
• Up to 5 - 7 kA through 5 m current cables. Applications:
• > 10 kA through a low-impedance test object
placed close to ODEN AT.
Applications:
ers and joints.
• More than 100 V to push currents up to 400 A.
Applications: Primary injection through cables or
lines.
Continuous current generation.
•
Up to 2.5 kA
Up to 3.8 kA if test object has low impedance
and bars are used as current conductors.
Available systems
• Any system must have a control unit
• There can be 1, 2 or 3 current units in a system
• There are 3 different types of current units: S
(Standard), X (Extra output) and H (High current)
Test of outdoor apparatus.
Test of Low Voltage Circuit Break-
through 5-m current cables.
Test circuit impedance limits the current
The test circuit impedance Z consists of current cable
impedance and impedance of the test object. According to Ohms law I x Z volt is required to push current
I through the impedance. If voltage at ODEN AT
terminals is less, current will be lower than desired.
Note! Voltage is required to get current through
the impedance and you need to know the
impedance of the test cir
Please not only look at the maximum
rated current of the ODEN AT configuration. Y
ou must also check that the available voltage at ODEN AT’s output terminals (see chapter 11 Specifications) is
sufficient
to push current through the test
circuit.
The cur
rent capability is dependent on
the load time. You must also check in
the load time - current diagram that the
system can generate the desired current
for the required load time.
cuit.
•
All current units in a system must be of same
type
A system can be designed for either 240 V or
•
400 V mains supply
Altogether there are 18 different ODEN AT systems.
Furthermore, the current units can be connected in
parallel or series. In total there are 46 dif
ferent configurations available. Their specifications are present
in the chapter “Specification”.
The system designation indicates the number and
type of current units.
Example:
ODEN
AT / 2X
2 = Quantity of the current units
X =
Version of current units
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
4 9
7 H o w t o u s e O d e n A T
5 0
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7.17 How to succeed in selecting a
suitable ODEN AT system
Please follow the procedure below. It implies that
you first choose configuration and then suitable
current cables. At the end of this chapter you will
find two forms (Form 1 and Form 2) useful for the
procedure. Form 2.is for cases where you must use
a certain cable set (length, cross section or weight
restrictions).
Required information
•
Application
• Desired Current
• Desired load time
• Distance to the test object
• Is it possible to twist current cables
• Impedance and type of test object
• Mains voltage supply and its current capability
Distance to the test object
• Use as short cables as possible
Length (impedance) has a direct impact on maximum possible current. There is no reason to burn
power in unnecessarily long cables.
Impedance of the test object
Knowledge saves you from surprises
• Test object impedance has most impact at higher
currents and when current cables are short.
•
Test object impedance is less important when
cable set is 5 meters or longer and only consists
of one or two cables each side.
impedance is the major part of the test circuit
impedance.
• Test object impedance can be measured. Inject an
AC current, measure voltage drop directly across
the object. Divide voltage by the current to get
the impedance (mΩ = V / kA).
If possible, current magnitude should be the
same as when testing the object. Some test objects saturate at high currents and measurement
at low currents will give a too high impedance
value.
Note! Do not use a DC - microhmmeter for
measuring. Y
ou will get a too low value
since the reactive part is excluded.
• Test object impedance can be estimated from
experience. Some examples:
Then cable set
a) Low Voltage air breaker rated 4 kA:
0.09 - 0.2 mΩ
b) Low Voltage circuit breaker rated 630 A:
0.3 - 1mΩ
c) Outdoor breaker pole or disconnector:
0.2 - 0.5 mΩ
In general test objects rated for higher currents have
lower impedance
Regarding current transformers, the impedance in
the secondary circuit has a direct impact on the impedance. Shunting secondary circuits not included
in the test reduces but some users dislike to do that.
For out-door current transformers current cable
impedance is usually the problem, not impedance of
.
the CT
Procedure
1. Available mains supply
Should a 240 V version or a 400 V version be used?
400
• requires less input current
• has higher current capability at short duration
Note! There is a 400 V version which also can
240
• has in some cases higher continuous rating
See further chapter 3, section ”Mains power supply”.
2. Load time - Current & Output Voltage - Current
• Check Time-Current and Voltage-Current dia
• If no configuration meets the requirements there
3
. Calculate maximum allowed test circuit impedance
Test circuit impedance = Output voltage / Current
(mΩ = V / kA)
4. Calculate maximum allowed cable set impedance
Subtract test object impedance from test circuit
impedance.
(Simplification. Both cable set and test object are
inductive)
V version or 480 V 60 Hz version
load
operate at 240 V (r
educed output voltage) provided that the mains system has
a neutral
V version
-
grams in the chapter ”Specifi
cations”. Select a
configuration that fulfils Time-Current requirements and has reasonably high output voltage.
is no reason to proceed. However please check
your requirements once more. Do you really
need the current magnitude and the length of the
cables?
O d e n A T
7 H o w t o u s e O d e n A T
5. Select current cables / conductors
You know the length. Select from tables in chapter
3, ”Current cables and conductors”.
•
Impedance may not exceed maximum allowed
value. It should be as low as possible but cable
set should not be unnecessarily clumsy or heavy
• Impedance can be reduced by:
a) twisting cables since it reduces the reactance.
Important!
b) using sets with more cables
c) using several cable sets in parallel.
This is
especially useful when current units are used in
parallel.
• At continuous or long term load:
Check that the current per cable not will be too
2
high (a 120 mm
cable can withstand 350 A
continuously). If so, use a set with more cables in
parallel.
• Weight. Overhead test object must be able to
carry the weight of the cable set. Divide weight
by 2 to get load at one side of the test object or
check if the cables can be supported by other
method.
•
Solid bars can be a better solution than cables at
high currents and short distances.
that the cable set will become rather heavy.
d) Continuous or long injection time.
(for instance at heat run)
First you must check that cable set has suffi
.
number of cables that current through a single
cable does not become too high.
6 Check input current
Again, to avoid surprises. ODEN
AT is like a
transformer, high output power requires high input
current. Your mains supply must be able to supply
the current.
See also Chapter 6, section 6.10 "Mains power supply” and Chapter 1
1, ”Specifications” for informa-
tion how to calculate.
Current calculation example
Q: Output voltage is lower than test circuit imped-
ance x current? What is the highest possible current I can get?
A: Draw a line in the voltage versus current diagram
representing the impedance. The highest possible
current is where impedance line crosses the voltage graph. See diagram below
.
cient
If distances to test object terminals are different,
•
using a set with different cable lengths can reduce impedance.
This also makes twisting easier
5. Rules of thumb
a) Distance max. 1 meter
, current 5 - 15 kA
(For example Low Voltage Circuit Breaker testing)
Minimise cable impedance. Weight is a minor prob-
lem. Use cable set with many cables in parallel
or bars.
b) Distance 5 meters or more, current max 3 kA
and
time max. 10 seconds:
(For instance at outdoors Current
Transformer
testing)
Since current is moderate and load time is short, it is
possible to use a cable set that is not too clumsy
.
One or two cables in parallel each side is sufficient in many cases, especially if it is possible to
twist the cables.
c) Distance 5 meters or more and current > 3 kA:
(for instance outdoor Current
Transformer test-
ing)
Low impedance must be given highest priority in
order to get the desired current.
This means many
cables in parallel. Unfortunately it is unavoidable
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
5 1
7 H o w t o u s e O d e n A T
5 2
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
Example: An ODEN AT/3H with units in series is
used and test circuit impedance is 1.2 mΩ. The line
should start at 0 kA, 0V. Multiply 1.2 mΩ by for instance 10 kA to get another point (10 kA, 12V) and
draw the line between the points. Highest possible
current for an ODEN AT/3H with units in series
(graph 3Hs) is 5.6 kA.
O d e n A T
7.18 Examples
Example 1, Current Transformer
Conditions:
Current 3 kA
Cables can be twisted
Injection time 10 seconds
CT impedance 0.4 mΩ
Current cable length 5 meter
Mains voltage 400 V
2. Selected output configuration
ODEN
3 kA for more than 10 seconds and has 4.0 V
output voltage.
3. Maximum allowed test circuit impedance
3.9
4. Maximum allowed cable set impedance
1.3 mΩ - 0.4 mΩ = 0.9 mΩ
AT 1/S is a possible choice. It can supply
V / 3 kA = 1.3 mΩ
7 H o w t o u s e O d e n A T
5.
Select current cables
A
cable set for 5 meter with 3 x 120 mm2 cables
has the impedance 0.8 mΩ if the cables are
twisted. Weight at each side of the test object is
3 x 21.2 kg.
6. Input current
46
A
Tip If you consider 3 cables each side
being clumsy, an ODEN AT 2/S with units
in parallel can be chosen. Output voltage
at 3 kA is 5 V and maximum test cable
impedance is 1.6 m . Two cable sets
is enough since their impedance is
1.1 m.
ODEN AT/1S (graph 3) 3kA at > 10 seconds
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
5 3
7 H o w t o u s e O d e n A T
5 4
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
Example 2, Low Voltage Circuit Breaker
Conditions:
Current 7 kA
Cables can not be twisted Injection time 5
seconds Breaker impedance 0.15 mΩ
Current cable length 0.5 meter
Mains voltage 240 V.
2. Selected output configuration
ODEN
kA for more than 5 seconds and has 3.6 V output
voltage.
3. Maximum allowed test circuit impedance
3.6
4. Maximum allowed cable set impedance
0.51 mΩ - 0.15 mΩ = 0.36 mΩ
5. Select current cables
Set GA
ance approx. 0.5 mΩ with untwisted cables. 2
of these sets (one for each current unit) gives
impedance 0.25 mΩ. However, even better is to
take two sets of GA – 12305. It will give better margins and less heating in the cables. Short
cables are inexpensive and not heavy.
6. Input current
175
AT 2/S with units in parallel can supply 7
V / 7 kA = 0.51 mΩ
-12205 is 0.5 meter long and has imped-
A
Example 3, Low Voltage Circuit Breaker
Conditions:
Current 15 kA
Cables can not be twisted
Injection time 5 seconds
Breaker impedance 0.1 mΩ
Distance 0.5 meter
Mains voltage 400 V
2. Selected output configuration
ODEN
15 kA for more than 5 seconds and has 2.7 V
output voltage.
3. Maximum allowed test circuit impedance
2.5
4. Maximum allowed cable set impedance
0,17 mΩ - 0,1 mΩ = 0.07 mΩ
5. Select current cables
0.07 mΩ is hardly possible with standard cable sets. Copper bars where the conductors with
opposite current directions are close together
should be used.
6. Input current
136
AT 3/H with units in parallel can supply
V / 15 kA = 0,17 mΩ
A
O d e n A T
7 H o w t o u s e O d e n A T
Form 1
Selection of configuration & cables
See explanations in chapter 7, ”Selecting ODEN AT system and current cables”
Required information:
• Desired Current ______ A
• Desired load time ______
• Distance to the test object (Please check how short cables you can use) ______ m
• Can current cables be twisted? ______
• Test object type / impedance (not always necessary) __________________ / ______m
Available mains voltage and its current capability ______ V ______ A
•
1. Should a 240 V or a 400 V version be used?
V version: Sometimes higher continuous rating 240 V
240
400 V version: Higher short time current, lower input current 400 V
2. Select ODEN AT configuration
Check Time-Current and Voltage-Current diagrams in chapter ”Specifications”
Select a configuration that fulfils Time - Current requirements and has reasonable
high output voltage.
Configuration ______________
Series
Parallel
Output voltage ______________V
Ω
3. Calculate maximum allowed test circuit impedance
est circuit impedance = Output voltage / Current (mΩ= V / kA) ______mΩ
T
4. Calculate maximum allowed cable set impedance
Subtract test object impedance from test circuit impedance ______mΩ
5.
Select current cables / conductors
See chapter ” Current cables and conductors”
Number of sets ______
Impedance of all sets ______m
Check input current
6.
See chapter 3 ”Mains power supply”or chapter1
Input current _______A
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
Cable set ______mΩ
Ω
1 ”Specifications”
5 5
7 H o w t o u s e O d e n A T
5 6
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
7 H o w t o u s e O d e n A T
Form 2
Selection of configuration when
using a certain cable set
Use this form when you must use a certain cable set. See explanations in chapter 7, ”Selecting ODEN AT
system and current cables”
• Test object type / impedance (not always necessary) __________________ / _____ m
•
Available mains voltage and its current capability ______ V ______ A
1. Select current cables / conductors
See chapter 3, “Current cables and conductors”
2. Impedance of the test object
Most important at high currents and if current cables are short
3. Calculate test circuit impedance
T
est circuit impedance = cable set impedance + test object impedance. _____ mΩ
4) Calculate required output voltage
Required voltage =
Test circuit impedance x Current (V = mΩ x kA) ______ V
Cable set ______________________ mΩ
_____ mΩ
Ω
5) Select ODEN AT configuration and system voltage
Now you know required output voltage, load time and desired current.
Select a confi
See diagrams in chapter 11 ”Specifications”.
400 V version: Higher short time current, lower input current 240 V
240 V version: In some cases higher continuous rating 400 V
Configuration_________________
Series
Parallel
6. Check input current
See chapter 3, ”Mains power supply”or chapter11, ”Specifications”.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
guration that fulfils both Voltage-Current & Time-Current requirements.
5 7
7 H o w t o u s e O d e n A T
O d e n A T
5 8
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
8 A p p l i c a t i o n e x a m p l e s
8 Application examples
This chapter explanis step-by-step how some specific objects are tested. The following are discussed:
• Testing a low-voltage circuit breaker
• Testing the turns ratio of a current transformer
• Testing the polarity of a current transformer
• Measuring the resistances of breakers and electri
cal connections (microhmmeter testing)
• Testing a direct acting recloser
• Testing a sectionalizer
• Testing a ground grid
8.1 Testing a low-voltage breaker
The following sections explain how to test a lowvoltage breaker. Start by measuring the overcurrent
stage’s tripping limit and the tripping time. Then
measure the tripping limit and tripping time for the
instantaneous unit.
-
Measuring the tripping limit (normal generation):
Current is generated continuously and gradually
increased until the breaker trips.
trips the current shown on the display is frozen
and the current is interrupted. When current first is
generated for a load (while the current is being set),
Oden AT adapts itself so that all subsequent generation operations start at the current’s zero-cross-over
points. This ensures minimized transient DC offset
when the injection is initiated.
1. Basic settings:
OPERATE: OFF
CURRENT ADJUST: Lower than the tripping
limit
HOLD function:
AUTO OFF: STOP INPUT
2. Set the stop condition to INT.
ON
When the breaker
3. Start generation by pressing <ON+TIME>.
4. Increase the current until tripping occurs (the
LATCHED lamp lights up).
5. The current value frozen when tripping occurred
can now be read from the display.
Note: You can read out the highest current
value during an operation by pr
<ESC> repeatedly until "max" appears
after a current value. This value should
be used for test objects whose impedance changes during the operation.
Measuring the tripping time:
1.
Set the current to an ample margin above the
tripping limit. The procedure is described in
section 7.3. Use the I/30 function (step 2 to 6 in
section 7.3) if you want to set the current without operating the breaker
Note: Disable the INT-function when you are
using I/30.
.
essing
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
5 9
8 A p p l i c a t i o n e x a m p l e s
6 0
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
2. Settings:
HOLD: ON
AUTO OFF: STOP INPUT
STOP INPUT: INT
3. Start generation by pressing <ON+TIME> or
<MOM ON>.
4.
Read the time and the current presented on the
display.
Instantaneous trip unit measurement:
When you test the instantaneous pick-up you can
provide a manually-controlled momentary current
injection by pressing the <MOM ON> button.
This
permits you to find the instantaneous trip unit’s lowest operating current without tripping the overcurrent stage.
1. Basic settings:
OPERATE: OFF
CURRENT ADJUST: Close to the tripping limit
HOLD function: ON
2. Set the stop condition to INT.
8.2 Testing the ratio of a current
transformer
This test determines whether or not a current transformer has the correct ratio. During the test, current
is injected into the primary side of the current trans-
, and the current in each secondary winding is
former
measured using Oden AT’s second ammeter (A-ME
TER 2).
WARNING
Make certain that you observe all applicable safety r
associated with dielectric strength on the
secondary side. The secondary side of
the transformer must be closed during
the injection!
Basic setting:
1.
OPERATE: OFF
AMMETER1, UNIT: AMPERE
2. Connect the Oden AT output to the primary
terminals on the current transformer.
egulations and precautions
-
3. Select a suitable current setting.
4. Press <MOM ON> briefly. The time throughout
which current is generated must be shorter than
the overcurrent stage’
s tripping time. You can
also use limited-time current generation (MAX
TIME). See section 7.13 "Measuring operating
limits".
5. Change the current setting somewhat and repeat
from step 3 above until you find the lowest current that provides tripping of the instantaneous
trip unit.
In order to measure the instantaneous trip time
proceed as follows:
1.
Increase the current to an ample margin above
the tripping level.
Start an injection and read the time on the dis-
2.
play
.
3. Connect Oden AT’s second ammeter (A-ME
TER 2) input to the current transformer winding
that is to be tested. Make certain that this winding is not connected to any other circuit.
4.
Activate A-METER 2 in the <V/A METER> menu
option under the "A-METER 2" menu heading.
5. Select "A-METER 2 NOM I" and set the nominal
secondary current for the current transformer
.
You might, for example, set it to 5 A.
6. Select "A-METER 2 UNIT", and then select
“CT ratio".
7.
Press <ON+TIME>.
8. Set the desired primary current, whereupon both
the primary current and the actual ratio will appear on the display
.
Example:
A injected into a transformer with a ratio of
1000
5000/5.
5.107s
1.00kA5000/5 A
Note: Another method to measure the ratio be-
tween primary and secondary current is
to set the unit for ammeter 1 to "I1/I2".
Do not however try to combine the two
methods!
O d e n A T
20A
200V
AMMETER 2VOLTMETER
Red
(+)
Black
(
-)
Current transformer
P1(H1)P2(H2)
S1(X1)
S2(X2)
8.3 Measuring the polarity of a
current transformer
You can conduct a polarity test to determine whether
or not the current direction in a current transformer
is correct.
In this test it is to be verified that the terminal S1
(X1) on the secondary side is positive relative to
terminal S2 (X2) when terminal P1 (H1) on the primary side is positive relative to terminal P2 (H2).
8 A p p l i c a t i o n e x a m p l e s
1.
Basic setting:
OPERATE: OFF
2. Connect the one of the output terminals on Oden
AT’s which is marked with a dot (·) to P2 (H2)
on the primary side of the CT.
3. Connect the other output terminal to P1 (H1).
4. Connect the one of A-METER 2:s terminals
which is marked with a dot (·) to S2 (X2) on the
secondary side of the CT
.
5. Connect the other terminal of A-METER 2 to S1
(X1).
6.
Activate Oden AT’s second ammeter
(A-METER 2) under the "A-METER 2" menu
heading in the <V/A
METER> menu option.
7. Press the <ESC>-button (normally twice) until
the sign for degrees ("°") appears in the upperleft corner of the display
.
8. Press <ON+TIME>.
9. Turn the current up until the a stable phase-angle
appears on the display.
Fig 8.1
DANGER
Never ever make this hookup while current is being generated. If you do, you
may be exposed to dangerously high
voltages.
10. If the phase angle is close to 0° or 359° the
polarity is correct. If the phase angle is 180°, the
polarity is incorrect.
1
1. Press <OFF>.
12. Move the cables used for A-METER 2 to the
other secondary windings and check them in the
same way
A sample hookup is shown in fig 8.1.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
.
6 1
8 A p p l i c a t i o n e x a m p l e s
6 2
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
8.4 Measuring the resistances of
breakers and electrical connections
(microhmmeter testing)
You can measure the resistance of a breaker or an
electrical connection by changing Oden AT’s settings for microhmmeter testing.
WARNING
You must make cer tain that all general
safety precautions are taken. See chapter 1 "Safety pr
also make certain that all local regulations which govern work with high-voltage
equipment are complied with.
WARNING
Before you connect Oden AT to a breaker,
you must make certain that the breaker
is closed and grounded on one side.
WARNING
Do not measure on outdoor High Voltage
Circuit Breakers due to risk for capacitively coupled currents. It could cause
danger and/or damage.
WARNING
If generated current must pass through
the current transformer, the protective
relay system must be blocked so that it
cannot trip unintentionally.
ecautions". You must
5. Turn the <CHANGE> knob until "MICROHMMETER" appears on the display. Then press
<ENTER>.
Oden
AT will now automatically configure itself for
microhmmeter testing as follows:
The voltmeter is set to the lowest range.
•
• The ammeter range is set to "AUTO".
Activate HOLD .
6.
7. If you want limited-time generation, activate
MAX TIME and set the desired maximum gen
eration time.
Press <ON+TIME> and set the desired current .
8.
9. Current and
Time
Current3.15kA50
µΩ values are displayed. Example:
60.31s M
Resitance
in microohms
10. To return Oden AT to normal use, press the
<APPLICATION>-button and then turn the
<CHANGE> knob until "NORMAL USE" appears on the display. Press <ENTER> and Oden
AT will be reset for normal use.
-
If you are measuring the resistance of an object that
has high core losses, the measured resistance will
be in error
. Highly inductive objects can also lead to
erroneous readings.
The accuracy is best when the current and voltage measurement operates at more then 50% of the
measurement range.
1.
Connect the Oden AT current cables and sensing cables between the Oden
AT voltmeter and
the breaker. The cables in each cable set should
run as close to each other as possible, i.e. there
should be as few openings as possible where
magnetic disturbances can get in and cause trouble.
2. Turn on Oden AT.
3. Basic setting:
OPERATE: OFF
4. Press the <APPLICATION> menu option.
O d e n A T
8 A p p l i c a t i o n e x a m p l e s
8.5 Testing a direct acting
automatic recloser
Setting the currrent and testing the pick-up level is
done in the same way as when testing low voltage
circuit breakers, see section 8.1. Press <ESC> to obtain the maximum current during a test for reclosers
that change their impedance.
At time tests Oden AT will generate current until <OFF> is pressed or until a preset maximum
generation time is reached.
pleted the following measurements are stored and
displayed:
• Number of operations (number of times the current is interrupted).
•
The total accumulated time taken by the reclosing cycle (i.e. from the recloser
last trip).
• The trip and reclosing times.
The current at the first four trip operations.
•
The showed value is the average of the current at the
beginning and the end of the operation.
After the cycle is com-
’s first trip to its
6. Generation stops when you press <OFF> or when
the preset limited-time generation period (MAX
TIME) is reached.
Total time
to OFF
Actual current0A3:OP
10.00sRECL.
Number of
operations
7. Display shows:
8. If you press <ENTER> the test results will be
dumped via the serial-port, see appendix 1.
9.
Press <ESC> to get more information on the
display:
Total recl.
1)
time
First trip
pulse985ms T139A
1) Displayed provided generation continued until
lock-out
9.015sTot3:OP
Current at
T1
Time test
1. Set the current, <APPLICATION> should be set
to "NORMAL", see 8.1.
2. Press the <APPLICATION> menu option.
3. Turn the <CHANGE> knob until "TEST RECLOSER" appears in the display window and
then press <ENTER>. Oden
AT will now work
as a recloser test equipment.
Note: Range for A-METER1 will automatically be
changed to "LOW".
The HOLD featur
e is not active in TEST
RECLOSER.
4. If you prefer limited-time measurement, activate MAX
TIME and set the desired maximum
generation time.
5. Press <ON+TIME> or <MOM ON> to start the
test.
Oden
AT now generates current continuously while
the direct acting automatic recloser trips and closes
alternately
. For each time the current is interrupted,
the number of operations ("OP" on the display) is
increased by one on the display. Oden AT stores
the trip (opening) times and reclosing times and the
currents that prevailed when each trip and reclosing
took place.
-
10. More information on the display can be seen by
turning the <CHANGE>-knob.
11. Press <ON+TIME> to start a new test.
12. To return Oden AT to normal use, press the
<APPLICATION>-button and then turn the
<CHANGE>-knob until "NORMAL USE" ap-
ears on the display. Press <ENTER>.
p
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
6 3
8 A p p l i c a t i o n e x a m p l e s
6 4
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
8.6 Testing a sectionalizer
You can test a sectionalizer by making appropriate
changes in Oden AT’s settings. Here Oden AT sends
out a preset sequence of current pulses corresponding to those that would be obtained from a directacting automatic recloser. After the cycle is completed, the following are stored and displayed:
• The number of current pulses until lockout
(number of times the current is interrupted).
•
The total accumulated time (i.e. from the reclos-
’s first trip until its last trip).
er
• The trip times and the reclosing times.
• The current at the first four trip occations.
Prior to the test 4 different
- T4) and the reclosing time (R1 - R4) can be set.
Note: After pulse T4 and R4 a pulse T5 and a
pulse R5 will be generated. T5 and R5
ar
e identical to T1 and R1. Use the "MAX
TIME" function to limit no. of pulses.
puls-duration times (T1
9. If you press <ENTER> the results will be
dumped via the serial-port, see appendix 1.
10. Press <ESC> to get more information.
Total acc.
time
Duration
of pulse
T1214ms T138A
9.786Tot2: OP
Current at
T1
11. Scroll with the knob to get the times for R1, T2,
R2 etc.
12. Press <ON+TIME> to start a new test .
13. To return Oden AT to normal use, press the
<APPLICATION>-button and then turn the
<CHANGE>-knob until "NORMAL USE" appears on the display
. Press <ENTER> .
1. Set the desired current, see section 7.3 "Setting
the desired current" for details.
2.
Press the <APPLICATION> menu option.
3. Turn the <CHANGE> knob until "
SECTIONAL-
IZER" appears in the display window, and then
press <ENTER>.
Set the time for T1 with the <CHANGE>-knob
4.
and press <ENTER>.
5.
Set the times for R1, T2, R2 etc. in the same
way and press <APPLICATION> .
6. If you want to use limited-time generation, acti
vate MAX
TIME and set the desired maximum
generation time.
7. Press <ON+TIME> or <MOM ON> to start the
test.
8.
Generation stops when you press <OFF>, release the <MOM ON>-button or when the preset
MAX
TIME has been reached.The display
shows:
-
Total time
to OFF
Actual current0A2:OP
10.00sSECT.
Pulses until
lockout
O d e n A T
8.7 Testing a ground grid
The best method of testing the integrity of a ground
grid is the High Current Method. An Oden AT
equipped with a current unit of type X is very suitable for this kind of tests. Here is a brief description
of how such tests is conducted with Oden AT.
A current of 300 A is to be injected between one
reference ground electrode (usually the grounding
point for a transformer) and the ground to be tested.
One criterium that must be met before a ground
network can be approved is that at least 50% of the
total current injected between points passes through
the ground network. Moreover the voltage drop
must not exceed 0.1V/meter
Connect the output you intend to use for measurement (the 30
V output on a type X current unit for
example) to the injection points. Then, in addition,
connect the voltmeter input to the injection points.
.
8 A p p l i c a t i o n e x a m p l e s
1. Basic settings:
OPERATE: OFF
Voltmeter: Activate it in the <V/A ME
T
ER> menu option
HOLD function: ON
2. Set Oden AT to generate 300 A, and allow the
current to flow for about three minutes.
3. Then measure the portion of the current that
flows through the ground network and the
portion that proceeds via other routes using a
clamp-on ammeter
.
4. Read the voltmeter. The voltage drop must not
exceed 0.1 V/meter.
-
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
6 5
8 A p p l i c a t i o n e x a m p l e s
O d e n A T
6 6
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
9 T r o u b l e s h o o t i n g
9 Troubleshooting
9.1 General
Problem: No current is sent out from
Oden AT
• Check miniature circuit breaker F2.
• Overheating may have triggered the thermal
protection. The thermal protection resets itself
automatically after Oden AT cools down.
• Check the connections to the object being tested.
If a breaker is being tested, check to see that it is
closed.
•
Check the connection between control unit and
current unit.
For series connection, check that a series connec-
•
tion cable is being used and is connected prop-
.
erly
Problem: Not possible to switch on
Oden AT. The display is dark.
• Check the fuse F1 (located on the left side of the
control unit).
• Check that the mains cable is plugged in properly
and that mains voltage is present.
Problem: Generation stops immediately or
after half a cycle.
Possible causes:
• Stop condition is set to INT and F2 is off.
Remedy: Close F2.
Stop condition is set to INT and the output circuit
•
is open.
Remedy: Change stop condition or close output
circuit.
Stop condition is set to INT and the output cur-
•
rent is just a few percentage of the measurement
range of ammeter 1, see 1
Remedies: Increase the current, decrease INTlevel or use range or output with lower current
rating.
1.8.
Problem: Generation does not stop when
the breaker opens.
• Zero offset need to be calibrated, see section
10.2 ”Calibration of offset”.
Problem: Unexpected value on Ammeter
1.
Possible cause: Improper settings in the OUTPUT
block on the control panel.
Remedies:
•
Select HIGH I if the high-current output is used.
• Select 0-30/60 V if the low-current output on a
type X current unit is used.
Select PARALLEL if the current units are con-
•
nected in parallel or if you only have one current
unit connected.
Select SERIES if the current units are connected
•
in series.
Possible cause: "SERIES" is selected in the OUT-
block and unused current units are connected
PUT
to the control unit.
Remedy: Disconnect unused current units.
Possible cause: Oden AT is set for DC-Measure-
ment while
will be approx. 10%).
Remedy: Select proper setting for DC-Measurement
(submenu system).
Possible cause: The test object has higher impedance than expected.
Remedies: Increase the voltage applied from Oden
A
T by connected the current units in series or use
the low-current output if you have a type X current
unit.
AC is generated or vice versa. (Fault
Problem: The miniature circuit breaker F2
or the mains supply fuse trips.
Possible cause: High inrush current due to remanence.
Note Connecting cur
decrease the measurement ranges.
P r o g r a m m a E l e c t r i c A B
P - B H 0 2 E R 1 0 0
Z
rent units in series will
Remedies:
1. Disconnect all current units
2. Set the <FINE> knob in the CURRENT
block to 40 %
ADJUST
6 7
9 T r o u b l e s h o o t i n g
6 8
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
3. Press <ON+TIME> and turn the knob up to 100%
and then down to 0%.
4. Connect one current unit. No load should be connected to it.
5. Press <ON+TIME> and set the <FINE> knob to
100%.
6. Slowly increase the COARSE adjustment to its
maximum.
7. Press <OFF> and set the COARSE and FINE
adjustments to 0.
8. Connect next current unit without any load connected and repeat the procedure from step 5.
•
If problem appears at step 6, try with loading
some current from the unit.
•
If problem appears at step 6 for the second and
third current unit, proceed with only the newly
added current units connected.
9.2 Error messages
You can encounter the following error messages on
the display:
Current units
Message: ”Type X curr unit not installed”
Cause: You have selected 0-30/60 V in OUTPUT
in order to measure current from the low-current
output, but there is no low-current output on the current unit.
Remedy: Cancel the 0-30/60
current unit having a low-current output.
Message: ”Curr units have diff settings”
Cause: In OUTPUT, you opted to measure current
from the 0-30/60 V low-current output when the
switches on the current units are set differently
Remedy: Make certain the switches on the current
units have the same settings.
V setting or connect a
Message: ”Curr units are of diff types”
Cause: You have connected different types of current units.
Remedy: Connect current units of the same type.
O d e n A T
9 T r o u b l e s h o o t i n g
9.3 Measurement errors
Problem: No reading on voltmeter and ammeter 2.
Possible cause: The instrument is not activated.
Remedy: Activate the instrument in the <V/A-ME-
TER> menu option if its indicator lamp is not lit.
Problem: Time ”0.000s” is displayed but
generation continues.
Possible cause: The stop condition is met but
AUTO OFF is not activated.
Remedy: Press <RESET> if you want the generation time displayed.
Problem: ” ——- A or ——-V” is displayed.
Cause: Because the measurement time was too
short, the HOLD function cannot present any frozen
readings or there was not enough time for a range to
be selected automatically.
Problem: Unexpectively long trip-time
while testing instantaneous trip on a circuit breaker.
Remedy: Increase INT-level or use range or output
with higher current rating.
Remedy: Increase the measurement time or select a
fixed range.
Problem: ”——- OFA or OFV" is displayed.
Cause: The magnitudes of the input signals are too
great for the fixed preset range or the AUTO range
does not have time to function properly for highspeed cycles. (”OF” = Overflow)
Remedy: Carry out a new measurement or select a
fixed range.
Problem: ”AMP2=0A AMP1=0A”is displayed.
Cause: Because the measurement current is 0, no
ratio can be calculated.
Remedy: Generate current.
Problem: ”**** A”is displayed.
Cause: Ammeter cannot present measured values
for the generated current because:
• Current units are of different types.
• Current unit unknown because it is uncalibrated.
Remedy: Connect same type of current units or calibrate the current unit.
P r o g r a m m a E l e c t r i c A B
P - B H 0 2 E R 1 0 0
Z
6 9
9 T r o u b l e s h o o t i n g
O d e n A T
7 0
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
1 0 C a l i b r a t i o n
10 Calibration
10.1 General
You can calibrate the zero levels (offset) for ammeter 1, ammeter 2 and the voltmeter. The timer
in Oden AT is crystal controlled and requires no
calibration, but can be checked against an external
timer.
The instruments used for calibration should have a
verified high accuracy
The control unit and the current units must be calibrated together
your Oden AT system once a year, but also if a new
current unit is added to your system or if the system
has been exposed to extreme variations in ambient
temperature.
Regarding calibration of the scale factors we recommend that it is done at 2/3 of the measurement range
or at 2/3 of the highest rated current for your Oden
A
T-system (see output specifications in chapter 11).
You can however calibrate at other values. If accuracy at a certain value is important you can calibrate
at this value instead.
. It is recommended that you calibrate
.
10.2 Calibration of offset
The zero-offset for ammeter 1, ammeter 2 and the
voltmeter is calibrated.
1. Make sure that no current units are connected to
the control unit and that the input for ammeter 2
is open.
Short circuit the voltmeter input (i.e. the voltage
2.
should be 0 V).
3. Press the <SYSTEM> button.
4. While simultaneously pressing the but
tons <ESC> and <ENTER>quickly turn the
<CHANGE> knob clockwise until "CALIBRA-TION" appears on the display. Press <ENTER>
to confirm.
5.
Choose ”Zero-offset” and press <ENTER>.
6.
Calibration of zero-offset is done automatically.
-
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7 1
1 0 C a l i b r a t i o n
7 2
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
10.3 Calibration of scale factor,
ammeter 1
Scale factor, range LOW
1. Press the <AMMETER> menu-option and
change the range to ”LOW”. Press <ENTER> to
confirm, then press <AMMETER> to leave the
menu.
2. Connect a reference ammeter to the current output.
Note: If a current transformer is used, make
sur
e that it is applied at least 0.5 meter
from any bend of the current conductor.
Other conductors shall not be closer than
0.5 meter from the current transformer.
3. Activate the HOLD-function by pressing
<HOLD>. The lamp in the HOLD-button lights
up.
4.
Press the <MOM ON> button and adjust the
current until the calibration value (about 2/3 of
maximal current, see chapter 1
section 11.2 -11.5) appears on the reference ammeter. Release the <MOM ON> button when the
value is adjusted.
1 Specifications,
10.4 Scale factor for the I/30function.
1. See that the I/30-function is turned off.
2. Activate the HOLD-function by pressing
<HOLD> (the LED in the button lights up).
3.
Press the <MOM ON> button and hold it down
for a second. The LED in the HOLD-button
should start flashing.
4. Note the current value for ammeter 1 that is
displayed on the display.
5. Activate the I/30-function.
6. Press the <MOM ON> button and hold it down
for a second. The LED in the HOLD-button
should start flashing.
7. Press the <SYSTEM> menu option.
8. While simultaneously pressing the but
tons <ESC> and <ENTER>quickly turn the
<CHANGE> knob clockwise until "CALIBRA-TION" appears on the display. Press <ENTER>
to confirm.
9.
Choose ”AMMETER 1” and press <ENTER>.
”I/30” is displayed in the upper right corner of
the display
.
-
Note: The lamp on the <HOLD>-button should
be flashing.
5.
Press the SYSTEM menu option.
6. While simultaneously pressing the buttons <ESC> and <ENTER>quickly turn the
<CHANGE> knob clockwise, until "CALIBRA-TION" appears on the display. Press <ENTER>
to confirm.
7.
Choose ”AMMETER 1” and press <ENTER>.
8.
Turn the <CHANGE> knob until the current
value on the display matches that on the reference ammeter
. Press <ENTER> to confirm the
calibration.
Scale factor, range HIGH
1. Press the <AMMETER> menu-option and
change the range to ”HIGH”. Press <ENTER>
to confirm and then <AMMETER> to leave the
menu.
2. The rest of the procedure is the same as step 2
- 8 in the ”LOW”-range.
10. Turn the <CHANGE> knob until the current
value on the display matches the value from the
previous measurement in step 4. Press <ENTER> to confi
rm the calibration.
The I/30 function is intended only for use at coarse
adjustment of high currents and gives only an approximate indication.
O d e n A T
1 0 C a l i b r a t i o n
10.5 Calibration of scale factor,
ammeter 2
Scale factor, range 0 – 2 A
1. Press the <V/A METER> menu option, select
”AMMETER 2” and press <ENTER>.
2.
Select the ”0 – 2 A”-range and press <ENTER>.
Press <V/A
3. Connect an AC current source and a reference
AC ammeter to the AMMETER 2 input.
4. Adjust the current from the AC current source to
1.3 A (2/3 of the full range).
5. Activate the HOLD-function.
6. Press the <MOM ON> button and hold it down
for a second. The LED in the HOLD-button
should start flashing.
7. Press the <SYSTEM> menu option.
8. While simultaneously pressing the but
tons <ESC> and <ENTER>quickly turn the
<CHANGE> knob clockwise until "CALIBRA-TION" appears on the display. Press <ENTER>
to confirm.
METER> to leave the menu.
-
10.6 Calibration of scale factor,
voltmeter
Scale factor, range 0 – 0.2 V
1. Press the <V/A METER> menu option, select
”VOLTMETER” and press <ENTER>.
2.
Select the ”0 – 0.2 V”-range and press <ENTER>. Press <V/A
3. Connect a DC voltage source and a reference
DC voltmeter to the VOLTMETER input.
4. Adjust the voltage from the DC voltage source
to about 0.133 V (2/3 of the full range).
5. Activate the HOLD-function.
6. Press the <MOM ON> button and hold it down
for a second. The LED in the HOLD-button
should start flashing.
7. Press the <SYSTEM> menu option.
8. While simultaneously pressing the but
tons <ESC> and <ENTER>quickly turn the
<CHANGE> knob clockwise until "CALIBRA-TION" appears on the display. Press <ENTER>
to confirm.
METER> to leave the menu.
-
9.
Choose ”AMMETER 2” and press <ENTER>.
10.
Turn the <CHANGE> knob until the current
value on the display matches that on the reference ammeter
. Press <ENTER> to confirm the
calibration.
Scale factor, range 0 – 20 A
1. Press the <V/A METER> menu option, select
”AMMETER 2” and press <ENTER>.
2.
Select the ”0 – 20 A”-range and press <ENTER>. Press <V/A
3. The rest of the process is just the same as for the
0 – 2 A-range, follow step 3 to 10. Calibrate at
13 A (2/3 of the full range).
METER> to leave the menu.
9.
Choose ”VOLTMETER” and press <ENTER>.
10.
Turn the <CHANGE> knob until the voltage
value on the display matches that on the reference ammeter
. Press <ENTER> to confirm the
calibration.
Scale factor, ranges 0 – 2 V, 0 – 20 V and
0 – 200 V
1. Press the <V/A METER> menu option, select
”VOLTMETER” and press <ENTER>.
2. Select the range that should be calibrated
(0 – 2
V, 0 – 20 V or 0 – 200 V) and press <ENTER>.
Press <V/A METER> to leave the menu.
3. The rest of the process is just the same as for the
0 – 0.2 V range, follow step 3 to 10. Calibrate at
about
2/3 of the full range; 1.333
range, 13.33 V for the 0 – 20 V range and
133.3 V for the 0 – 200 V-range.
V for the 0 – 2 V
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7 3
1 0 C a l i b r a t i o n
10.7 Resetting to preset
(standardized) calibration values
Instead of regular calibration a resetting function
can be activated that will set the calibration values
to a set of preset and standardized values. This will
give an accuracy of about 1%. Resetting can never
replace a regular calibration where accurate and
traceable reference instrument are used, but is a
quick and simple method of solving the problem of
having no calibration values at all. Resetting must
always be followed by a calibration of the zero-offset, which is a part of the regular calibration procedure.
It is possible to combine resetting and calibration;
first perform a reset and then calibrate the ranges for
which required instruments and sources are available.
The ranges that can not be calibrated will then
use the standard calibration values.
O d e n A T
Note: When a reset is performed, ALL settings,
values and parameters will be set to pr
eset default values. This also implies the
settings stored in Oden AT’s memories,
which will be lost if a reset is performed.
Performing a reset
1. Press down the <RESET> button while Oden AT
is switched on.
7 4
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
O d e n A T
1 1 S p e c i f i c a t i o n s
11 Specifications
11.1 General
Specifications are valid for an ambient temperature of +25°C and
nominal input voltage. The specifications are subject to change
without further notice.
System designation
An ODEN AT-system consists of a control unit an one, two or three
current units. There are three different versions of the current units:
S-unit (standard), X-unit (extra 30/60 V outlet) and H-unit (high current). The system designation indicates the number and version of
current units included.
Example: ODEN AT/2X
X = Version of current unit (S, X or H
Environment
CE-marking
General
Display
2 = Number of current units
Application fieldThe instrument is intended for use
Temperature
Operating0°C to +50°C (+32°F to +122°F)
S
torage & transport -25°C to +55°C (-13°F to +127°F)
Humidity5% – 95% RH, Non-condensing.
LVDLow Voltage Directive 73/23/ EEC am.
EMCEMC Dir
Mains voltage• 240 V AC 50/60 Hz
Mains inletIEC 60309-2, 63 A
ower consumptionThe power consumption for Oden AT
P
Input currentOutput current x open circuit voltage
ProtectionThe output transformer has a built-in
Dimensions
Contr
ol unit AT570 x 310 x 230 mm
ent unit S, X H570 x 310 x 155 mm
Curr
eight
W
Control unit AT25 kg (55 lbs)
ent unit S42 kg (92.6 lbs)
Curr
ent unit X45 kg (99.3 lbs)
Curr
ent unit H49 kg (108 lbs)
Curr
TypeLCD
Available languagesEnglish, German, French, Spanish,
in medium-voltage substations and
industrial environments.
by 93/68/EEC
ective 89/336/EEC am. by
91/263/EEC, 92/31/EEC and 93/68/
EEC
• 400 V AC 50/60 Hz
• 480 V AC 60 Hz
The mains voltage must be between
-14% and +10% of the nominal input
voltage stated
depends on the generated output
ent, see sections 11.2, 11.4 and
curr
11.6 for details.
/ input voltage
thermal cut-out, and the primary
side is protected by a miniature
circuit breaker
(22.4” x 12.2” x 9”)
(22.4” x 12.2” x 6”)
Swedish.
Measurement section
Ammeters
Measurement method AC, true RMS
Inaccuracy1% of range ±1 digit
Ammeter 1
Ranges0 – 4800 A / 0 –15 kA
0 – 9600 A / 0 – 30 kA
0 – 960 A / 0 – 3 kA
Ammeter 2
Ranges0 – 2.000 A / 0 – 20.00 A
Maximum current20 A (The input is not protected by
Dielectric withstand Galv
a fuse)
anically isolated
Voltmeter
Measurement method AC, true RMS
Ranges0 – 0.2 V
Inaccuracy1% of range ±1 digit
esistance (Rin)
Input r
Dielectric withstand2.5 kV
, 0 – 2 V, 0 – 20 V,
0 – 200 V, AUTO
240 k (range 0 – 200 V)
24 k (other ranges)
Timer
PresentationIn seconds, mains frequency cycles
Ranges0.000 – 99999.9 s
uracy±(1 digit + 0.01% of value)
Inacc
or hours and minutes
0 – 9999 cycles
0.001s – 99 h 59 min
For the stop condition in INT-mode
1 ms shall be added to the specified
ement error.
measur
Stop input
Max. input voltage250 V AC / 275 V DC
Phase angle
Range0 – 359º
Resolution1º
uracy±2º (For voltage and current read-
Acc
ings that ar
selected range)
e higher than 10% of the
Z, P, R, X, S, Q and power factor (cos )
For these measurements the result is calculated using two or three
items. The accuracy depends on the errors for the items included
(U, I and sometimes ).
Imax
Stores highest current value that exists ≥100 ms
INT-level
Threshold indicating that current is interrupted, can be set to 0.7 or
2.1% of range for Ammeter 1
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7 5
1 1 S p e c i f i c a t i o n s
7 6
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
11.2 Output specifications for 240 V
Oden AT systems at 50 Hz
Specifications are valid at nominal input voltage and
ambient temperature +25 oC, (77 oF) and with the
current adjustment set to 100%. The specified times
refer to the maximum loading time during a single
load period, they are not valid during repeated use.
Important
Exceeding the currents and load times
specified could cause damage to the
equipment.
The specifi
output terminals. The voltage drop in the current cables and connections between current units in series
is not included.
OUTPUT HIGH I, Oden AT systems for 240 V at 50/60 Hz operation
Load time
1 1 S p e c i f i c a t i o n s
Current (kA)
Oden AT/3S, units in SERIES 1 Oden AT/3H, units in SERIES 6
Oden AT/2S, units in SERIES 2 Oden AT/2H, units in SERIES 7
Oden AT/1S 3 Oden AT/1H 8
Oden AT/2S, units in PARALLEL 4 Oden AT/2H, units in PARALLEL 9
Oden AT/3S, units in PARALLEL 5 Oden AT/3H, units in PARALLEL 10
Note: The curves for systems with type S units
are also valid for systems equipped with
units of type X.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
7 9
1 1 S p e c i f i c a t i o n s
8 0
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
OUTPUT HIGH I, Oden AT systems for 240 V
3 S or X units in series
2 S or X units in series
1 S or X unit
3 S or X units in series
3 S or X units in parallel
2 S or X units in parallel
2 S or X units in series
1 S or X unit
* Voltage between the output terminals.
3 S or X units in parallel
2 S or X units in parallel
O d e n A T
1 1 S p e c i f i c a t i o n s
3 H units in series
2 H units in series
3 H units in parallel
1 H unit
3 H units in series
2 H units in series
2 H units in parallel
1 H unit
* Voltage between the output terminals.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
3 H units in parallel
2 H units in parallel
8 1
1 1 S p e c i f i c a t i o n s
8 2
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
1
1
2
2
4
1
0
20
40
1
2
4
1
0
20
40
1
2
3
8
7
seconds
m
inutes
h
ours
100
200 300 400
500
600
700
800 900
10
00
1100 12
00
13
00 1400
15
00
16
00
17
00
18
00 1900
2000
4
5
6
OUTPUT 0-30V/60V, Oden AT systems for 240 V at 50/60 Hz operation
Load time
Oden AT/3X 60 V, SERIES 1
Oden AT/2X 60 V, SERIES 2
Oden AT/3X 30 V, SERIES 3
Oden AT/1X 60 V range 4
Oden AT/2X 30 V, SERIES 5
Oden AT/1X 30 V range 6
Oden AT/2X 30 V, PARALLEL 7
Oden AT/3X 30 V, PARALLEL 8
Current (A)
O d e n A T
OUTPUT 0-30V/60V, Oden AT systems for 240 V at 50 Hz operation
1 1 S p e c i f i c a t i o n s
Output voltage* (V)
Oden AT/1X 30 V range 1
Oden AT/2X 30 V, PARALLEL 2
Oden AT/3X 30 V, PARALLEL 3
Oden AT/1X 60 V range 4
Oden AT/2X 30 V, SERIES 5
Oden AT/3X 60 V, PARALLEL 6
Oden AT/3X 30 V, SERIES 7
Oden AT/2X 60 V, SERIES 8
Oden AT/3X 60 V, SERIES 9
Current (A)
* Voltage between the output terminals.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
8 3
1 1 S p e c i f i c a t i o n s
8 4
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
11.4 Output specifications for 400 V
Oden AT systems at 50 Hz
Specifications are valid at nominal input voltage and
ambient temperature +25°C, (77°F) and with the
current adjustment set to 100%. The specified times
refer to the maximum loading time during a single
load period, they are not valid during repeated use.
Important
Exceeding the currents and load times
specified could cause damage to the
equipment.
The specifi
output terminals. The voltage drop in the current cables and connections between current units in series
is not included.
OUTPUT HIGH I, Oden AT systems for 400 V 50/60 Hz and 480 V 60 Hz
Load time
1 1 S p e c i f i c a t i o n s
Current (kA)
Oden AT/3S units in SERIES 1 Oden AT/3H units in SERIES 6
Oden AT/2S units in SERIES 2 Oden AT/2H units in SERIES 7
Oden AT/1S 3 Oden AT/1H 8
Oden AT/2S units in PARALLEL 4 Oden AT/2H units in PARALLEL 9
Oden AT/3S units in PARALLEL 5 Oden AT/3H units in PARALLEL 10
Note: The curves for systems with type S units
are also valid for systems equipped with
units of type X.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
8 7
1 1 S p e c i f i c a t i o n s
8 8
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
OUTPUT HIGH I, Oden AT systems for 400 V
3 S or X units in series
2 S or X units in series
1 S or X unit
3 S or X units in series
3 S or X units in parallel
2 S or X units in parallel
2 S or X units in series
1 S or X unit
* Voltage between the output terminals.
3 S or X units in parallel
2 S or X units in parallel
O d e n A T
1 1 S p e c i f i c a t i o n s
3 H units in series
2 H units in series
1 H unit
3 H units in series
3 H units in parallel
2 H units in parallel
2 H units in series
1 H unit
* Voltage between the output terminals.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
3 H units in parallel
2 H units in parallel
8 9
1 1 S p e c i f i c a t i o n s
9 0
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
1
1
2
2
4
1
0
20
40
1
2
4
1
0
20
40
1
5/6
2/3
8
7
seconds
m
inutes
h
ours
100
200 300 400
500
600
700
800 900
10
00
1100 12
00
13
00 1400
15
00
16
00
17
00
18
00 1900
2000
4
OUTPUT 0 – 30 V/60 V, Oden AT systems for 400 V 50 Hz
Load time
Current (A)
Oden AT/3X 60 V, SERIES 1
Oden AT/2X 60 V, SERIES 2
Oden AT/1X 60 V range 3
Oden AT/3X 30 V, SERIES 4
Oden AT/2X 30 V, SERIES 5
Oden AT/1X 30 V range 6
Oden AT/2X 30 V, PARALLEL 7
Oden AT/3X 30 V, PARALLEL 8
O d e n A T
OUTPUT 0 – 30 V/60 V, Oden AT systems for 400 V 50 Hz
1 1 S p e c i f i c a t i o n s
Output voltage* (V)
Oden AT/1X 30 V range 1
Oden AT/2X 30 V, PARALLEL 2
Oden AT/3X 30 V, PARALLEL 3
Oden AT/1X 60 V range 4
Oden AT/2X 30 V, SERIES 5
Oden AT/3X 60 V, PARALLEL 6
Oden AT/3X 30 V, SERIES 7
Oden AT/2X 60 V, SERIES 8
Oden AT/3X 60 V, SERIES 9
Current (A)
*) Voltage between the output terminals.
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
9 1
1 1 S p e c i f i c a t i o n s
9 2
O d e n A T
P r o g r a m m a E l e c t r i c A B
Z
P - B H 0 2 E R 1 0 0
11.6 Output specifications for 480 V
Oden AT systems at 60 Hz
Specifications are valid at nominal input voltage and
ambient temperature +25°C, (77°F) and with the
current adjustment set to 100%. The specified times
refer to the maximum loading time during a single
load period, they are not valid during repeated use.
Important
Exceeding the currents and load times
specified could cause damage to the
equipment.
The specifi
output terminals. The voltage drop in the current cables and connections between current units in series
is not included.