PELLET BOILER
K11
August, 2016
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 2
We thank you for the trust that you’ve shown us by purchasing the K11 furnace. We ask that you read the instructions for use before attempting to install and use your K11 pellet
boiler. The combustion devices (hereinafter referred to as the “pellet boiler” or the “boiler”) built by
PETRIČ d.o.o. (hereinafter referred to as the “K11”) are designed and tested in accordance with the safety requirements laid out in the applicable European directives.
The instructions are intended for the end-users, the installers and the authorized service personnel of the K11 pellet boiler.
If you have any doubts in connection with the instructions for use, or if you require any clarification, please contact the manufacturer or an authorized PETRIČ d.o.o. representative.
Printing out, translating or reproducing the instructions for use, even partially, may only be done upon obtaining an approval from the PETRIČ d.o.o. company.
The amount of carbon dioxide (CO2) formed by proper combustion of the wood biomass inside the boiler is equal to the amount that would be emitted during the natural wood decomposition process.
The amount of carbon dioxide (CO2) produced during the combustion or decomposition of the wood is the same as the amount of CO2 that the tree sequestered in its lifetime, turning it into oxygen and carbon.
By contrast, the use of non-renewable energy sources (wood char, heating oil, gas) emits vast quantities of CO2 that had been accumulated through millions of years, thereby contributing to the greenhouse effect.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 3
TABLE OF CONTENTS
1. THE PURPOSE OF THE INSTRUCTIONS FOR USE .................................................................................... 5
1.1. THE LABEL MEANINGS ........................................................................................................................... 5
2. COMPONENTS OF THE BOILER .................................................................................................................. 6
3. THE BASIC REQUIRED STANDARDS .......................................................................................................... 7
4. BOILER SAFETY ............................................................................................................................................ 7
5. RESPONSIBILITIES ....................................................................................................................................... 8
5.1. MANUFACTURER’S RESPONSIBILITY ................................................................................................... 8
5.2. USER’S RESPONSIBILITY ....................................................................................................................... 8
5.3. INSTALLERS’ RESPONSIBILITY.............................................................................................................. 9
6. PICKING THE BOILER UP; TRANSPORTATION AND INSTALLATION .................................................... 10
6.1. PICKING THE BOILER UP ...................................................................................................................... 10
6.2. TRANSPORTING AND MOVING THE PELLET BOILER ........................................................................ 10
7. INSTALLATION ............................................................................................................................................ 10
7.1. PLACEMENT ........................................................................................................................................... 10
7.2. WASTE MANAGEMENT ......................................................................................................................... 12
7.3. FLUE GAS EXHAUST ............................................................................................................................. 12
7.4. AIR SUPPLY ........................................................................................................................................... 15
7.5. ELECTRICAL GRID CONNECTION ........................................................................................................ 16
7.6. CONNECTING THE BOILER TO THE HEATING WATER CIRCUIT ...................................................... 17
8. FIRST START OF THE BOILER ................................................................................................................... 18
8.1. INSTRUCTIONS FOR PERSON, ANIMAL AND PROPERTY SAFETY .................................................. 18
9. SAFETY WARNING ...................................................................................................................................... 19
9.1. SAFETY PRECAUTIONS FOR THE MAINTAINERS .............................................................................. 19
9.2. SAFETY PRECAUTIONS FOR THE USER ............................................................................................ 19
10. INSTRUCTIONS FOR SAFE IGNITION AND CLEANING OF THTHE BOILER .......................................... 20
10.1. INSTRUCTIONS FOR SAFE IGNITION .................................................................................................. 20
10.2. REGULAR MAINTENANCE AND CLEANING OF THE BOILER ............................................................ 20
10.3. INSPECTION AND PARTS THAT REQUIRE MAINTENANCE ............................................................... 21
10.4. ADDITIONAL MAINTENANCE ................................................................................................................ 23
11. IMPORTANT SAFETY DATA ....................................................................................................................... 23
12. FILLING THE PELLET HOPPER .................................................................................................................. 24
13. FUEL ............................................................................................................................................................. 25
13.1. ACCEPTABLE FUEL ............................................................................................................................... 25
13.2. UNACCEPTABLE FUEL .......................................................................................................................... 25
13.3. PELLET STORAGE ................................................................................................................................. 25
14. THE CONTROLLER...................................................................................................................................... 26
14.1. Cautions ............................................................................................................................................... 26
14.2. Recommendations ................................................................................................................................... 26
14.3. Keypad .................................................................................................................................................... 27
14.4. Menu structure ......................................................................................................................................... 29
14.4.1. Navigating the menus ..................................................................................................................... 29
14.5. Setting the clock ...................................................................................................................................... 30
14.6. Setting the temperature ........................................................................................................................... 30
14.7. Setting the operating power ..................................................................................................................... 30
14.8. Setting the weekly programs ................................................................................................................... 31
14.9. Setting the fuel options ............................................................................................................................ 32
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 4
14.10. Changing the options’ settings ................................................................................................................. 32
14.11. Troubleshooting ....................................................................................................................................... 33
15. WIRING DIAGRAM ....................................................................................................................................... 35
16. INFORMATION REGARDING THE DESTRUCTION AND DISPOSAL OF THE BOILER ........................... 36
17. WARRANTY CONDITIONS .......................................................................................................................... 37
17.1. INSPECTION: .......................................................................................................................................... 37
17.2. WARRANTY TIME CONDITIONS: .......................................................................................................... 37
17.3. GENERAL WARRANTY CONDITIONS: .................................................................................................. 37
17.3.1. We declare the following: ............................................................................................................... 37
17.3.2. Claiming the warranty ..................................................................................................................... 37
17.3.3. The period of time that spare parts and service is guaranteed ....................................................... 37
17.3.4. The warranty does not cover damage due to the following: ........................................................... 37
17.4. THE COMPONENTS SUBJECT TO NORMAL WEAR AND THUS NOT COVERED BY THE
WARRANTY ............................................................................................................................................ 38
17.4.1. SERVICE WITHIN THE WARRANTY PERIOD .............................................................................. 38
17.5. THE COURT OF JURISDICTION ............................................................................................................ 38
18. MODEL K11 TECHNICAL CHARACTERISTICS ......................................................................................... 39
19. BOILER IMENSIONS AND CONNECTIONS ................................................................................................ 41
20. DECLARATION OF CONFORMITY.............................................................................................................. 42
21. CE LABEL ..................................................................................................................................................... 43
22. CONNECTION DIAGRAMS (hydraulic and electric) .................................................................................. 44
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 5
1. THE PURPOSE OF THE INSTRUCTIONS FOR USE
The instructions for use are meant to inform the user about the measures and the equipment required to ensure safe and proper operation of the combustion device.
Read and consider the contents of this booklet carefully. In order to properly install, use and maintain your boiler, you will need all the information contained in this booklet.
Store the instructions carefully and safely at a suitable location; you never know when you will need them. The instructions for use, maintenance and installation are considered an integral part of the pellet boiler unit.
In the case of the boiler changing ownership, the new owner must receive the instructions for use along with the boiler.
If the instructions for use get lost, you may request a new copy of the instructions from the manufacturer or from a person authorized by the manufacturer.
1.1. THE LABEL MEANINGS
DANGER:
An important instruction on how to prevent accidents, fatalities and property
damage.
DANGER DUE TO ELECTRICAL WIRING:
An important instruction on how to handle the electrical wiring of the boiler properly in order to avoid accidents, fatalities and property damage.
DANGER OF BURNS:
An important instruction on how to prevent burns.
RECOMMENDATION:
A recommendation by the boiler manufacturer on how to improve the user’s experience in connection with the boiler, prolong the lifetime of the boiler, etc.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 6
2. COMPONENTS OF THE BOILER
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 7
3. THE BASIC REQUIRED STANDARDS
The boiler K11 was designed, manufactured and tested in accordance with EN 303-5: 2012. We took into account the directives and standards as follows:
EC Machinery Directive 2006/42/EC, EC Electromagnetic compatibility directive (EMC) 2004/108/EC EC Low voltage directive (LVD) 2006/95/EEC
Harmonised standards:
EN ISO 12100: 2011;
EN 60204-1: 2006;
EN ISO 13857: 2008;
EN 61000-6-3: 2007;
EN 61000-6-2: 2005;
EN 61000-3-3:2009;
EN 61000-3-2: 2006;
EN 61000-3-2: 2006 A1: 2009
4. BOILER SAFETY
The boiler K11 is tested according to standard EN 303-5:2012 and has passed all safety tests required by this standard. In addition to the safe operation controlled by the electronics are installed on the boiler additional safety components, which operate independently of the electronics. List of this components are given in Table
1.
Table 1: Additional safety components
Name
Failure
Function
Pressure switch 1
Blockage of the chimney Fan failure or fan blockage
Turn off dosing system
Safety relay
Uncontrolled continuous dosing
Turn off dosing system
Pressure switch 2
Open cumbustion chamber door
Turn off dosing system
Thermostatic switch STB
Overheating water
Turn off dosing system
Proper and safe operation of the boiler is the responsibility of the installer and the boiler user. Instructions for safe installation and use of the boiler are listed later in this “User manuals”.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 8
5. RESPONSIBILITIES
5.1. MANUFACTURER’S RESPONSIBILITY
By supplying these instructions, PETRIČ d.o.o. disclaims any civil or criminal liability arising directly or indirectly from the following:
An accident due to non-compliance with the standards and specifications laid out in these instructions.
Accidents due to disallowed and inappropriate operation by the user.
Accidents due to modifications and repairs that were not authorized by the manufacturer,
PETRIČ d.o.o. .
Poor maintenance.
Unforeseen situations;
Accidents due to the use of non-original or unsuitable spare parts.
5.2. USER’S RESPONSIBILITY
The user must observe the following during the operation of the boiler:
The boiler should only be operated by a suitably trained adult person who is familiar with the instructions regarding the boiler operation.
With the exception of the trained operator and the authorized boiler service personnel, or adults authorized by the service personnel, no other person should be allowed in the vicinity of the boiler.
The pellet boiler must be used according to the instructions laid out in the “Instructions for Use, Maintenance and Installation” and in compliance with all the local regulations valid at the site of the installation of the pellet boiler.
The boiler should be fuelled exclusively with wood pellets with the required properties, as specified later in the text.
Every time before starting the boiler, the operator must verify the electric power supply of the boiler and the sealing of the chimney and chimney connectors; the operator must also visually inspect the boiler to see if it’s in a suitable condition for start up.
Only remove the ash from the boiler when both the boiler and the ash are at the same temperature as the room where the boiler is installed (otherwise burns may occur).
Clean the boiler using non-flammable cleaning agents only.
The ash from the boiler should only be disposed of and stored in a non-flammable
container with a lid, in order to prevent ignition.
It is forbidden to keep or store flammable or explosive substances in the room where the boiler is installed.
The maximum permissible temperature of the water in the boiler is 80°C.
The minimum temperature of the water in the boiler during operation should not be lower
than 55°C, in order to prevent flue condensation in the boiler.
If there is a danger of explosion, fire or a gas leak, do not start the boiler.
When shutting the boiler off, observe the shutting off instructions later in the text; never
extinguish the boiler forcefully, such as by pouring or loading any kind of substance into any part of the boiler or the chimney connector.
Register the
boiler to concessionaires to implement the chimney
-
sweeping service
*User is obliged by the law to register the pellet boiler to chimney-sweeping service that review the device and chimney connector.
*depends of state
or local
law
.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 9
5.3. INSTALLERS’ RESPONSIBILITY
The installer’s responsibilities include:
Checking the pipes, the plumbing, the air supply and all the fixtures required for the installation of the pellet boiler.
Ensuring that the boiler is installed in compliance with the local regulations valid at the site of the installation.
The installer must check the following:
The type of the machine they are installing.
The suitability of the installation site of the unit, that is, the minimum acceptable size of
the room where the pellet boiler is to be installed.
The manufacturer’s instructions regarding the combustion device that pertain to the flue gas exhaust requirements.
The inner diameter of the chimney; the material used in its construction; whether it is straight, that is has a uniform surface; and that it is not obstructed.
The height and the vertical extension of the chimney.
Whether the chimney has a cap of suitable durability.
The sealing performance of the chimney connection from the boiler to the chimney.
The possibility of an external air inlet.
If the results of the checks mentioned above are positive, the installation may be commenced. Carefully follow the instructions supplied by the manufacturer, as well as the applicable safety and fire safety standards.
After the installation has been completed the installer must provide the buyer with the following:
The manufacturer’s Instructions for Use, Maintenance and Installation (if they’re not already included with the unit).
The documentation required by the applicable standards.
THE INSTALLER TAKES FULL RESPONSIBILITY FOR THE INSTALLATION.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 10
6. PICKING THE BOILER UP; TRANSPORTATION AND INSTALLATION
6.1. PICKING THE BOILER UP
Waiting to be picked up at the manufacturer’s premises, the boiler is fully packaged, protected with cardboard and plastic foil and set on a wooden base (a pallet) to facilitate transport. The Instructions for Use, Maintenance and Installation are inside the boiler.
6.2. TRANSPORTING AND MOVING THE PELLET BOILER
From the time of picking the boiler up, all the transportation and movements are done on your own responsibility. Take care of your safety when moving the boiler.
WHEN TRANSPORTING AND MOVING THE BOILER, YOU MAY ONLY USE
ACCESSORIES WITH SUFFICIENT LOAD BEARING CAPACITY. AVOID JERKY AND/OR SUDDEN MOVEMENTS OF THE BOILER.
7. INSTALLATION
The responsibility for the installation tasks performed on-site lies solely with the buyer. Before the boiler installation both installation place and chimney connection must be reviewed
and confirmed by the Chimney-sweeping service. Before beginning the installation, the installer must check all the safety standards required by
law and in particular the following:
That the norms regarding pellet boiler installations conform to the local, national and
European norms.
That the requirements in this document are observed.
That the plumbing and the air supply are suitable for the type of installation.
That no temporary electrical connections have been carried out using uninsulated
cables.
That the electrical system is properly grounded.
That personal protective equipment has been used throughout the process, along with
all the protections required by law.
That sufficient room is left to enable maintenance in accordance with these instructions (Figure 1).
7.1. PLACEMENT
When placing the boiler at the final location, consider the following:
If the walls and/or the floor in the vicinity are covered with a material that is not heat resistant, it is necessary to provide appropriate protection using non-flammable insulation.
Maintain a safe distance (c. 50 cm) between the pellet boiler and any furniture, appliances, etc.
In order to protect floors made of flammable materials, we recommend placing a metal sheet of 3 to 4 mm thickness underneath the boiler; it should exceed the boiler depth by at least 30 cm in the front.
Storing flammable substances in the room where the boiler is installed is forbidden.
The pellet boiler should be installed at least 50 cm away from the walls, in order to
ensure a sufficient supply of air and facilitate access in case servicing is required.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 11
Figure 1
If the pellet boiler is installed in a kitchen where there are other devices that are drawing air off (e.g. an exhaust hood, various vent fans, etc.) or in a room with other solid fuel combustion devices (e.g. a solid wood boiler, etc.), make sure that the volume of air supplied is sufficient for the safe operation of the combustion device.
If the flue gas exhaust is routed through the ceiling the penetration must be insulated with a non-flammable insulation membrane.
Once the boiler is positioned, it has to be levelled using levelling screws. Take care when considering the load bearing capacity of the floor; you have to take into account not only the boiler itself but also a hopper full of pellets and a boiler full of water!
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 12
7.2. WASTE MANAGEMENT
DISPOSE OF THE PACKAGING MATERIAL IN A WAY THAT KEEPS IT OUT OF REACH
OF CHILDREN. THE BAG, FOIL, POLYSTYRENE, ETC. PRESENT A RISK OF SUFFOCATION.
After the boiler has been installed, the remaining packaging materials should be handled in accordance with applicable local regulations valid at the installation site.
7.3. FLUE GAS EXHAUST
The flue gas exhaust must be implemented in accordance with the applicable regulations. Only stainless steel may be used for the flue gas exhaust. The flue gas piping must not be joined together with the exhaust pipes of any other combustion devices. Routing the flue gas exhaust into enclosed or semi-enclosed spaces, such as, for instance, a garage, a narrow passage or corridor, an underpass, or any other similar spaces, is not permitted. When the connection between the boiler and the chimney connector is made, the chimney expert should verify that the chimney connector has not been damaged or punctured and that it’s sealing properly. If the chimney connector is found unsuitable, its cladding has to be replaced with new, intact material and the connector must subsequently be re-approved by the relevant authority.
The flue gas exhaust should be grounded according to the applicable regulations.
(The ground connection implementation is dictated by the law). The ground connection must be independent from the boiler unit.
As regards the dimensions and the construction material, the chimney must be fully compliant with all the applicable standards valid in the area of installation.
Chimneys in poor condition and/or those constructed from unsuitable materials (asbestos, galvanized steel sheeting, etc., with rough or porous surface) contravene the law and endanger the operation of the boiler. The smoke may also be exhausted using a traditional chimney (see the figure below), provided that the following rules are followed:
The chimney’s state of maintenance is inspected. If the chimney is old, it is advisable to renovate it by inserting a stainless steel pipe, properly insulated with glass wool or vermiculite. To ensure proper maintenance and/or a suitable renovation, seek the help of a chimney sweeping service.
The smoke may only be routed directly into a chimney in cases where the chimney is at most 20 x 20 cm or 20 cm in diameter and equipped with an inspection opening.
If the chimney is larger than that, an appropriately insulated stainless steel pipe of sufficient diameter must be inserted.
For chimney diameter 20cm should be install the condensation drain or used the type of the chimney with condensation tank.
Make sure that the chimney connection is properly sealed.
Avoid contact with flammable materials (such as, for instance, partially burned wood stubs); in
any case, there must be flame-resistant protection.
Key:
A) Wind-proof protection cap B) Maximum dimensions 20 x 20 cm or 20 cm
diameter, maximum height 5-6 m C) O-ring D) Inspection opening E) Condensate drain F) The access gully
Figure
2
Due to the high efficiency of the boiler the flue gas temperature
at
the exit of the boiler are relatively low.
This may often occur the
condensation of the flue gases in the chimney. Modern
chimneys
are usually all equipped with condensation containers-tanks,
it
makes sense and is recommended over the gully to connect
with a
drain system.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 13
The diameter of the pipe depends on the power of the pellet boiler. This pellet boiler is designed for pipes of 100 mm diameter. If you need to use pipes of 120 mm diameter, mount a 100 mm diameter T­junction onto the boiler and then use a reducer Ø100/Ø120 mm.
Key:
A) Vermiculite and/or glass wool B) Aluminium pipes C) Cover plate
Figure
3
When using connectors between the pellet boiler and the chimney, you are required to use a T-junction with an inspection opening looking directly into the boiler, or an elbow with a cleaning hatch. A T­junction must facilitate collecting the ash that accumulates at the bottom of the pipe, as well as regular cleaning, without requiring the disassembly of the piping. The smoke in the chimney connector is under slight pressure, so it is necessary to verify that the ash cleaning cover is hermetically closed and that it remains so after every cleaning. Make sure that the assembly was carried out correctly and check the gasket condition.
It is recommended to avoid long horizontal runs of the pipes leading to the chimney. If this is not possible, the pipes should not slope downwards, but upwards, at an angle of at least 5%. A horizontal pipe run should not exceed 3 m in length.
It is not recommended to run a pipe directly from the pellet boiler to the chimney with a horizontal pipe longer than 1 m.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 14
SAFETY WARNING
The flue gas exhaust MUST NOT BE CONNECTED:
To exhaust ducts used by other combustion devices (boilers, stoves, fireplaces,
etc.).
To vent systems (caps, vent fans, etc.).
Using flexible piping.
The installation of draft control valves is forbidden!
Chimney connection using the 100 mm diameter pipe between the pellet boiler and the chimney should satisfy the following:
No more than 6 m in total length.
Every 90° elbow joint shortens the permissible maximum length of the chimney
connection by 1 m.
The length of the installed connector should be 3 m at most.
Every elbow should be equipped with a hatch to enable cleaning.
The joints between the pipe segments must be sealed.
When mounting the chimney connector to the boiler, keep it as short and stable as
possible.
The chimney connector pipes longer than 1 m should be fixed properly, so that they
do not loosen.
A chimney connector that is more than 1 m in total length should be fixed properly,
so that it does not loosen.
All the chimney connector parts have to be removable and have to enable interior
inspection.
The total draft depends primarily on the chimney, which must contain no obstructions, which include, for instance, constrictions and/or various angled connections. It is recommended to only use pipe elbows at an angle of 45° at most; it is better yet to use an angle of 30°.
In any case, it is imperative to ensure an initial vertical, straight pipe run of at least 1.5 m length, this is the only way to ensure proper removal of flue gases.
If the draft in the exhaust system is poor (numerous elbows, inappropriate termination, constrictions, etc.), this is due to the obstructions just listed. In such a case, the flue gas exhaust will not be optimal, necessitating the adjustment of the pellet boiler parameters in order to adapt the boiler operation to its exhaust system. This may only be carried out by an authorized person.
The system of flue gas exhaust from the pellet boiler works on the basis of negative pressure and the barely detectable pressure of the exhaust pipe. It is very important for the flue gas exhaust to be hermetically sealed.
It is necessary to analyse the layout and structure of the space where the chimney is located. In case it is routed through a wall and/or the roof, it has to be integrated properly and in accordance with fire safety standards; it also requires approval by the relevant authorities.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 15
7.4. AIR SUPPLY
The air from the room that is necessary for complete combustion must be replaced with fresh air, either through an opening in the wall, a slit in the boiler room door, or an open window. This will improve the combustion and ensure a lower pellet consumption.
It is advisable to perform regular inspections of the air supply ducts, as this is the only way to make sure that sufficient air is supplied to the combustion chamber.
To implement an external air intake or external air supply, you need a 110 mm diameter pipe with a maximum length of 10 m. Every 90° elbow joint shortens the permissible maximum length of the air supply line by 1 m; If the air supply pipe is longer than that, its diameter must be increased.
If a grate mounted on the facade is used, the opening for the draft has to be at least 100 cm². The opening for the fresh air supply must be equipped with a grill to protect it from rain, wind and insects. The opening must be made in the external wall of the room where the pellet boiler is installed (Figure 4).
Figure 4
DANGEROUS
It is forbidden to supply the air from a storage space containing flammable materials or a space where a fire might start.
If there are other combustion devices located in the same room, the volume of air supplied must be sufficient to support complete combustion in all the combustion devices.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 16
7.5. ELECTRICAL GRID CONNECTION
The combustion unit requires an electrical connection. Our pellet boilers are equipped with a medium temperature power supply cable. If the power supply cable is damaged and needs to be replaced, call our repair service.
DANGEROUS
Before you begin with the electrical connection, make sure:
The electrical wiring characteristics fit the requirements listed on the combustion device.
That the flue gas exhaust is grounded according to the applicable regulations and local
directives (the ground connection implementation is dictated by the law).
The power supply cable must never reach a temperature higher than 80° above ambient. If
you wish to connect the boiler directly to the electrical grid, insert a bipolar switch with contact point spacing of at least 3 mm, suitable for use with the required voltage and in compliance with applicable regulations. Yellow/green striped grounding cable must be interrupted with the switch. The bipolar switch must be accessible at all times, even after the boiler has been installed.
The machine operates on 220 V~, 50 Hz. Make sure that the electric cables are not routed
under the boiler, that they are far enough from hot surfaces and that they are not touching any sharp parts that could damage them. If the voltage supplied to the boiler is too high, the life expectancy of the electrical components is substantially reduced.
The pellet boiler must be connected to the electrical grid. The power supply cable for the boiler is marked “Napajanje”. The other cable is for the connection of the pump; it is marked “Črpalka”.
DANGEROUS
If the power supply cable is damaged, it needs to be replaced. Only an authorized person may replace it, and the connection of the boiler to the electrical grid may likewise only be performed by an expertly trained person! The electrical connection has to be easily accessible even after the boiler has been installed.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 17
7.6. CONNECTING THE BOILER TO THE HEATING WATER CIRCUIT
DANGEROUS
The connection of the boiler to the heating water circuit may only be performed by a suitably trained installer.
The joints and connections of the pipes should not leak (guaranteed water-tightness).
The connection should be carried out according to the following procedure (see chapter 19. and 22):
connect the cold water line of the heating water circuit to the connector marked “Hladna voda”;
connect the hot water line of the heating water circuit to the connector marked “Topla voda”;
the filling line for the boiler should be connected to the connector marked “Polnilni priključek”.
To assess connections for »hot« and »cold« water it is necessary to remove the service panel with keyboard »A« and then connect both line:
»Hot« water with connector »B«
»Cold« water with connector »C«
Connection is carried out through the side slots which have been previously removed. (See Figure 5)
Figure 5
Return w
ater protection system
For proper operation of the boiler, return water temperature should be min.55°C. This is achieved by using water protection system shown in Chapter 22 on page 44.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 18
8. FIRST START OF THE BOILER
The first
start of the boiler may only be performed by an authorized person;
otherwise, the warranty is voided.
After starting the boiler for the first time, an operation test of at least 30 minutes duration has to be performed.
8.1. INSTRUCTIONS FOR PERSON, ANIMAL AND PROPERTY SAFETY
We would like to inform the installer about some general guidelines that need to be followed, if the pellet boiler is to be installed correctly. Those are the standards required, but they are not sufficient; for more in-depth information, you have to read the rest of the Instructions for Use, Maintenance and Installation.
Connect the pellet boiler to the electrical grid;
do not allow children and animals to approach the boiler;
do not use any fuel other than high quality pellets;
inform all users about possible risks and dangers and teach them how to use the pellet boiler;
if the pellet boiler is set on a wooden floor, it is advisable to insulate it.
DANGEROUS
The pellet boiler operates by maintaining a negative pressure in the combustion chamber, so make sure that the flue gas exhaust is SEALED, BOTH THERMALLY AND AGAINST SMOKE EMISSION.
When the boiler has been ignited for the first time, part of the paint that the boiler is coated with evaporates*, so it is essential that you ventilate the room afterwards.
(*because of stabilization after the painting process)
Mandatory
measurement
of flue gases
emission
In the first start-up of the boiler it is mandatory to carry out emission measurements of flue gases which can be performed by an authorized service technician or the concessionaire for the chimney­sweeping services.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 19
9. SAFETY WARNING
9.1. SAFETY PRECAUTIONS FOR THE MAINTAINERS
Before complying with the safety regulations the maintainer must:
Always use safety devices and individual safety equipment in accordance with the 89/391/EEC directive.
Disconnect the electrical power supply before starting any work.
Always use suitable tools.
Make sure, before starting any work on the boiler, that both the boiler and the ash inside are
cold, especially before touching either.
CONSIDER THE BOILER UNUSABLE IF EVEN A SINGLE SAFETY DEVICE IS FAULTY, INCORRECTLY REPAIRED OR MALFUNCTIONING!
Make no changes of any kind, for any reason, except as allowed and/or approved by the manufacturer or an authorized person.
Always use original spare parts; do not wait for a part of the boiler to become worn before replacing it. Replacing a worn part before it breaks down helps prevent injuries due to a sudden break-down of a component; such injuries may seriously endanger persons and/or their property.
Check for any condensation that would suggest water infiltration or the cooling of flue gases. We recommend finding out the cause for the condensation, so that normal boiler operation can be re-established.
9.2. SAFETY PRECAUTIONS FOR THE USER
The space where the pellet boiler is to be located, or the installation site, must comply with local, national and European norms.
The pellet boiler is a combustion device. Certain external boiler surfaces may reach very high temperatures during operation.
The pellet boiler is designed to burn only wood pellets (pellets of 6 mm diameter and 30 mm length, with humidity content up to 10%).
Children must not approach the boiler during operation and play with it! When using the combustion device, comply with the following:
DO NOT approach and do not touch the combustion chamber door during the operation of the boiler, as there is a DANGER OF BURNS!
DO NOT approach and do not touch the chimney connection during the operation of the boiler, as there is a DANGER OF BURNS!
DO NOT clean any parts of the combustion device during the operation of the boiler!
Do not open the combustion chamber door during the operation of the boiler; proper
combustion requires the combustion chamber door to be hermetically sealed.
DO NOT remove ash during the operation of the boiler!
DO NOT allow children and animals to approach the pellet boiler!
OBSERVE THE REQUIREMENTS IN THIS DOCUMENT!
Use exclusively wood pellets compliant with the specifications laid out later in the text!
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 20
Observe the maintenance instructions!
DO NOT use the pellet boiler in case of incorrect operation or other abnormalities,
unusual sounds and/or suspicious malfunctions!
The combustion chamber contains rotating parts that can injure you!
DO NOT spill water over the boiler and do not use water to extinguish the flames in the
combustion chamber!
DO NOT lean on the boiler, as it might be unstable and tip over!
DO NOT use the pellet boiler as a support or fasten other objects to it!
DO NOT leave the hopper cover open!
DO NOT touch the painted parts of the boiler during its operation!
DO NOT use wood or wood char in the pellet boiler!
DO NOT use the boiler as an incinerator!
Always ensure complete safety!
10. INSTRUCTIONS FOR SAFE IGNITION AND CLEANING OF THE BOILER
10.1. INSTRUCTIONS FOR SAFE IGNITION
NEVER use heating oil, lamp oil or any other oil, nor any other flammable liquid to ignite the pellet boiler. Keep all such liquids far away from the boiler during its operation.
Make sure that the pellet boiler stands securely and that it doesn’t move. Verify that you have closed the combustion chamber door properly and that it is closed during the
operation of the boiler. Only vacuum clean the ash when the pellet boiler is cold. Do not use abrasive agents to clean the pellet boiler.
10.2. REGULAR MAINTENANCE AND CLEANING OF THE BOILER
The pellet boiler is equipped with an automatic heat exchanger scrubbing device and a device for automatic removal of ash from the combustion chamber. Despite the automatic ash removal we recommend regular inspection and, if necessary, cleaning of the combustion vessel or the chamber. It bears keeping in mind that ash is an insulator and that a poorly cleaned boiler will lead to higher pellet consumption, as well as a higher chance of malfunctions.
When using pellets that comply with the specifications laid out later in the text, the ash container needs to be emptied either once per month, or once per every 3-4 hoppers worth of pellets burned, but this is not a rule! The rate of ash accumulation in the boiler depends on several different factors, so we recommend paying special attention to the ash build-up after the commencement of boiler operation.
The use of a vacuum cleaner with a dust separator will simplify the cleaning of the ash from the boiler. Before starting any maintenance, including any cleaning, observe the following safety measures:
Safety warning
Always make sure that the pellet boiler and the ash within are cold! Turn off the pellet boiler before starting any work! Vacuum the ash from the combustion chamber whenever you empty the ash container; vacuum and carefully clean the combustion vessel whenever you empty the ash container
(only when the boiler is cold)
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 21
Figure 6 shows the combustion vessel or “cup”, which is where the pellet combustion takes place. When you restore the combustion vessel back to its place, make sure that it’s set down correctly; this is the only way to ensure the correct operation of the boiler.5
WARNING! Check the braided gasket under the rim of the combustion vessel for any damage. If the braided gasket is damaged, seek the help of an authorized service shop. If you need any clarifications, do not hesitate to call your installer.
In no case will the manufacturer be held liable for any damage caused by a third party.
Figure 6
The combustion chamber must always be emptied of any remains from the pellet combustion. Never put the pellets that did not burn back into the pellet hopper or into the ash container.
10.3. INSPECTION AND PARTS THAT REQUIRE MAINTENANCE
CHECK THE FOLLOWING POINTS TO VERIFY THAT THE PELLET BOILER WORKS PROPERLY. THIS WAY ITS EFFICIENCY AND THEREFORE THE HEAT OUTPUT WILL BE HIGHER:
Make sure that the pellet boiler and the ash within are cold.
Table 2 shows the parts that require maintenance, who is responsible for the maintenance and the maintenance time interval.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 22
Table 2: The list of parts requiring maintenance
Part requiring maintenance Maintainer Time interval
Combustion vessel (cleaning) Owner
Every time the pellet hopper is
filled
Combustor – opening the hatch Owner
Every time the pellet hopper
is filled
Combustion vessel walls Owner
Every time the pellet hopper
is filled
Combustion vessel door (sealing assessment, the assessment of the braided gasket condition)
Owner
Every time the pellet hopper
is filled
Ash container door (sealing assessment, the assessment of the braided gasket condition)
Owner
Every time the pellet hopper
is filled
Emptying the ash containers Owner
Once per every 3-4 hoppers
worth of pellets burned
(depending on the pellet quality)
The heat exchanger scrubbing mechanism Service personnel Annually
Flue gas fan Service personnel Annually
Chimney connector Owner Annually
Whenever you load the hopper, check the combustion chamber (Figure 5). Ash and soot may build-up on the combustion vessel, potentially blocking the holes, which serve as the combustion air supply! In case of blockage, clean the holes and use the hatch under the combustion vessel to remove combustion debris from the burner itself. The debris falls into the lower part of the combustion chamber, where the auger expels it into the ash container.
The combustion chamber door sealing and ash container door sealing is insufficient, if the door is too easy to close (no resistance is felt when closing the door).
The gasket inserted in the slot on the combustion chamber door and on the ash container door eventually ceases to function properly. We recommend that you check the gasket performance before or after the heating season and that you call an authorized service shop in case of damage to any of the gaskets. The gasket must ensure a hermetical seal of the combustion chamber door and of the ash container door. Poor combustion results otherwise.
The chimney flue, the chimney itself and the chimney cap need to be inspected and cleaned at the specified intervals. Seek the help of your chimney sweeper for a professional job.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 23
10.4. ADDITIONAL MAINTENANCE
Your pellet boiler is a heat generator used with wood pellets. Once a year it requires special maintenance performed by the authorized personnel.
Tasks that have been described in the previous chapter are best performed when the heating season is over. Their intent is to check and ensure the flawless operation of all the components.
11. IMPORTANT SAFETY DATA
The vendor is available for sending you any data you may need. A correct installation of the combustion device, performed in accordance with the instructions, is important to prevent poor operation, danger and fire risk.
The pellet boiler operation is based on negative pressure in the combustion chamber, so you must always make sure that the chimney connection seals well.
In case of a fire in the chimney, it is essential that people and animals leave the room. Immediately afterwards, the electricity must be disconnected using the master switch or plug (only if it can be done at no risk), and then the fire brigade must be called.
For reasons of proper operation and safety of the pellet boiler, you must not use small pieces of chopped-up wood.
Do not use the pellet boiler as an incinerator.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 24
12. FILLING THE PELLET HOPPER
The boiler has a 180 kg pellet hopper built in. Before starting to fill the hopper, open the lids (Figure 7). There is a safety grid on the top of the hopper; place a pellet bag on the grid, open it and pour the pellets into the hopper. Always fill the hopper up to the top of the safety grid, which is c. 12 bags.
When pouring the pellets, take care that bag scraps or other objects that could obstruct or block the pellet dispensing system do not end up in the hopper.
After filling up the hopper, close the lids. Do not place any objects onto the hopper lids. The grid on the top of the hopper also has a safety function, so it should never be removed without a reason! (Figure 7a, 7b and 7c)
Figure 7
Figure 7a
Figure 7b
Figure 7c
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 25
13. FUEL
13.1. ACCEPTABLE FUEL
The pellet boiler is designed to use wood pellets exclusively. Since there are various types and dimensions of pellets on the market, it is important that you procure pellets that do not contain impurities. Make sure that only compact pellets that are not dusty/friable are used. Ask your pellet provider for suitable pellets. Correct operation of the boiler depends on the type and quality of the pellets.
Use exclusively wood pellets with a maximum diameter of 6
mm and a maximum
length of 30 mm that comply with one of the standards valid in the EU (EN 14961) or alternatively pellets of EN plus A1 quality class.
13.2. UNACCEPTABLE FUEL
The use of any fuel other than that listed in the chapter 13.1 is not allowed. The manufacturer is not to be held liable in any case for any damage due to the use of poor quality
pellets, nor for poor operation of the boiler due to the poor quality of the pellets used.
Using pellets of lesser quality decreases the combustion efficiency, which leads to increased emissions and fuel consumption. Using pellets of lesser quality likewise lowers the boiler efficiency. Using pellets of lesser quality necessitates more frequent cleaning of the parts of the boiler that are in contact with the flue gases.
13.3. PELLET STORAGE
Pellets should be stored in a dry place that is not too cold. Cold and humid pellets (with a temperature of around 5°C) reduce the thermal output and necessitate cleaning the boiler more frequently.
THE PELLETS SHOULD NOT BE STORED IN THE VICINITY OF THE PELLET BOILER. Store them at least half a meter (0.5m) away.
Pouring sawdust into the hopper may block the pellet dispensing system.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 26
14. THE CONTROLLER
14.1. Cautions
Exposure to water and other liquids
Do not expose the product to water, cleaning agents, solvents or other liquids, because they may damage the electronics, leading to impaired operation or product malfunction, thereby representing a danger to life.
Every contact with water or some other liquid can damage the electronics, leading to impaired operation or product malfunction, thereby representing a danger to life.
End-user’s responsibility
The user of the boiler is responsible for ensuring that the boiler is in a flawless state before starting it. Before starting the product, the user has a duty to check the following:
that there are no pellets in the combustion vessel prior to ignition;
that the chimney works properly.
Empty battery
If the controller battery is depleted and the power goes out, the control software restarts the system, when the power supply is re-established.
14.2. Recommendations
Setting the current time
Note that at the first start, it is necessary to set the current time, so that the weekly timer can activate the heating system on the desired schedule. We recommend frequent checking of the set time on the controller.
Cleaning
Clean the keypad by gently wiping it with a dry cloth. To remove greasy stains, use cloth that is lightly moistened with a mild detergent.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 27
14.3. Keypad
Figure 8: Keypad
Keypad cleanliness
To ensure proper operation, the keypad must be clean. Stains (greasy fingerprints, for instance) can interfere with the operation.
At the top of the Fumis ALPHA keypad, there are alarm, timer and menu indicators.
The screen shows the set values or the actual values of the currently selected menu. The buttons are used to navigate the menu and operate the Fumis ALPHA control system.
Table 3 describes the keypad buttons in more detail.
The Fumis ALPHA keypad is equipped with a buzzer that emits sound signals for feedback when you use the keypad. The following sound signals are available:
A short, high-pitched tone: beeps when you navigate the menu and change the settings
A longer, low-pitched tone: sounds when an invalid operation is attempted (pressing the wrong
button)
A longer, high-pitched tone: can indicate a warning, sounding at a volume you can set arbitrarily; it can also indicate an error, in which case it sounds at full volume. For a description of the warnings and errors, see chapter 14.11 on page 33.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 28
Table 3: Buttons on the Fumis ALPHA keypad
Button Description
The On/Off button is used to turn the system on and off and clear errors and warnings. Press and hold the button for 1 second.
Use the menu buttons (the left and right buttons) to navigate the top level of the menu structure. The currently selected menu is indicated by the corresponding indicator at the top of the keypad. These buttons are also used in the adjustment mode.
The adjustment buttons (the plus and minus buttons) are used to navigate the submenus and to increase/decrease the values in the adjustment mode, when the selected value is blinking.
The “Confirm” button is used to enter the adjustment mode and to confirm the set values, or for the selection of additional submenus.
The “Cancel” button is used to abort changes and for exiting the submenus. By pressing and holding this button for more than 3 seconds, the code of the most recent warning or error is displayed.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 29
14.4. Menu structure
Figure 9: Menu structure
Note
The Fumis ALPHA menu structure depends on the configuration and the additional options. Figure shows the entire menu structure with the full set of entries. Depending on the chosen configuration, some of the entries may not be available. Such an entry is excluded from the menu and the numbering of the submenus changes accordingly.
The values shown on the screen are for presentation purposes only and may not reflect actual values.
14.4.1. Navigating the menus
To navigate the top level menu, use the left and right arrow buttons. The screen displays the setting for the first entry in the corresponding submenu.
To move up or down the submenus, use the plus and minus buttons. The menu structure shown in the picture is inverted; in reality, the submenus are directed upwards. To make navigating the submenu easier, the corresponding sequential number of a submenu entry is briefly shown on the screen, in parentheses.
To change settings in the menu, press the “Confirm” button in order to enter the adjustment mode for the selected setting. The displayed setting blinks. To change the value, use the plus and minus buttons. To change the values in the adjustment mode by steps, use the left and right arrow buttons. When you are finished, press the “Confirm” button in order to save the settings and leave the adjustment mode. The screen displays the value of the menu you have just adjusted.
The screen displays the set value or the actual value, depending on the setting. For example, when setting the temperature, enter the desired temperature. When you leave the adjustment mode, the screen starts
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 30
displaying the actual temperature (which might not equal the value you set). When adjusting the fuel quality setting, the screen displays the set value.
To enter the third level submenu, press the “Confirm” button and use the plus and minus buttons to move from entry to entry. The process of changing the settings is the same as in the second level submenu.
To leave the adjustment mode without saving the changes, press the “Cancel” button. This button is also used to go one level upwards in the menu. For instance, if you are editing the Program 3 in the weekly periods, press the “Cancel” button to cancel the changes and return to Program 3. By pressing the “Cancel” button, you move to the “Nastavitev programov” (Setting the programs) submenu, then to the “Ura” (Clock) submenu and finally to the “Moč delovanja” (Operating power) submenu, which is part of the “Moč” (Power) top-level menu (the first entry in the menu structure).
14.5. Setting the clock
The Fumis ALPHA keypad enables you to set the exact time and date. To display the current time, use the left and right arrow buttons to move to the “Ura” (Clock) menu. The
screen displays the current time. To set the clock and date in the “Ura” (Clock) menu, press the “Confirm” button. The clock value begins
to blink. Use the plus and minus buttons to set the hour. Afterwards, press the right arrow button, so that the minutes value starts blinking, and set it. Press the right arrow button again and set the date in the same way. Set the date in the dd.mm.yyyy form. Then press the right arrow button and set the day of the week. Set the sequential number of the day; 1 means Monday, 7 means Sunday. Use the “Confirm” button to save the time and date settings.
14.6. Setting the temperature
The Fumis ALPHA controller allows two ways of setting the desired temperature:
using the weekly time period programs;
setting the temperature manually.
Using the weekly programs, you can completely automate the operation of your heating system; there is almost no need for any further intervention. For more information, see chapter 13.11 on page 33.
The temperature can be set or changed manually. If you use the weekly programs, you can temporarily override the programmed settings this way. The program settings are reset when the conditions set in the timer are met (for instance, the stop time is reached and the system switches off).
If you want to see the current temperature, go to the “Temperatura” (Temperature) menu. The current temperature is displayed on the screen.
To set the desired temperature, press the “Confirm” button in the “Temperatura” (Temperature) menu. The screen shows the target temperature in adjustment mode (the setting is blinking). You can use the plus and minus buttons to raise or lower the temperature. When you are finished, confirm the new value using the “Confirm” button. After confirming, the screen displays the current temperature again.
14.7. Setting the operating power
The Fumis ALPHA controller automatically regulates the operating power of your heating system. The settings can be overridden and the operating power changed, whether to reach the target temperature quicker, or to save fuel. The operating power setting affects the pellet dispenser and fan setting.
The operating power setting represents the highest operating power of the heating system. When the target temperature is reached, the operating power is automatically lowered. Example: if you select the operating power value “3”, your combustion device will modulate (based on the desired temperature) its power within the range of 1 to 3.
If you want to check the currently set operating power, navigate to the “Moč” (Power) menu. The current operating power setting is displayed on the screen.
For faster heating you can raise the operating power. Press the “Confirm” button in the “Moč” (Power) menu. The screen shows the operating power setting in adjustment mode (the setting is blinking). You can use the plus and minus buttons to raise or lower the operating power. When you are finished, confirm
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 31
the new value using the “Confirm” button. The screen then shows the newly set operating power. The output power is increased by speeding up the pellet dispenser and the fan.
To save fuel and energy, you can decrease the operating power. The pellet dispenser and the fan work slower and it takes a longer time to reach the target temperature.
14.8. Setting the weekly programs
The Fumis ALPHA controller allows you to set the weekly operation programs in order to automate the combustion system operation. You can set six different programs and select up to three of them for every day of the week. The program defines the time when the heating system starts, the time when it stops and the desired temperature during the period of operation.
To set the program, navigate to the “Ura” (Clock) menu and use the plus button to find the “Nastavitev programov” (Setting the programs) submenu. The screen shows (3). Press the “Confirm” button to select Program 1; the screen shows (P1). Press the “Confirm” button to enter adjustment mode. The starting hour of the heating system in the selected program (P1) starts blinking. Use the plus and minus buttons to set the starting hour. Then press the right arrow button. The starting minute of the heating system starts blinking. Set the desired starting minute. Press the right arrow button and use the same procedure to set the desired stopping time of the heating system. Then press the right arrow button and set the desired temperature for the set time period. Press the “Confirm” button to save the changes. Repeat the procedure for the rest of the five programs.
Example:
Program 1 Program 2 Program 3 Program 4 Program 5 Program 6
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
5:00 9:00 6:00 23:00 10:00 13:00 12:00 16:00 15:00 23:00 19:00 23:00
70⁰C 70⁰C 70⁰C 70⁰C 70⁰C 70⁰C
To set the program for each day of the week, navigate to the “Ura” (Clock) menu and use the plus button to find the “Programi po dneh” (Programs - day by day) submenu. The screen shows (4). Press the “Confirm” button to select Monday; the screen shows (d1). Press the “Confirm” button to enter adjustment mode. The value for the 1. program is blinking. Use the plus and minus buttons to select the desired first program. Then press the right arrow button. Use the plus and minus buttons to select the desired second program. Then press the right arrow button. Use the plus and minus buttons to select the desired third program. Press the “Confirm” button to save the changes. Repeat the procedure for the other days of the week.
Example:
To turn the weekly programs on or off, navigate to the “Ura” (Clock) menu and find the “Aktivacija časovnika” (Timer activation) submenu. Press the “Confirm” button and select ON or OFF. If you turn the timers off, set the heating system operation manually.
Program overlap: If the programs overlap each other, the program with the higher number takes precedence (e.g.: P2 has
a higher priority than P1; P4 has a higher priority than P3, P2 and P1; P6 has a higher priority than P5, P4, P3, P2 and P1).
DAN/URA 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 [d1] - ponedeljek [d2] - torek [d3] - sreda [d4] - četrtek [d5] - petek [d6] - sobota [d7] - nedelja
M
onday
Tuesday
Wednesd
ay
Thursday
Friday
Saturday
Sunday
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 32
14.9. Setting the fuel options
Fuel autonomy must be reset manually. When you fill up the empty hopper (up to the level marked “polno” (full) in the hopper), press the “Confirm” button to set the fuel autonomy to FULL. The screen shows how much fuel is left in the hopper, in terms of the remaining burning time (in days or hours). When the fuel reaches the warning level, the screen shows LO (empty). When the hopper is completely empty, the fuel autonomy is set to OFF and on the user interface, the (Ni goriva - No fuel) icon lights up. Fill up the hopper and set the fuel autonomy to FULL. If you refill the hopper before it’s completely empty, don’t forget to reset the fuel autonomy to FULL, but be careful that you fill the hopper up to the level marked “polno” (fuel); otherwise, the fuel autonomy will be shown incorrectly.
14.10. Changing the options’ settings
In the “Nastavitve” (Settings) menu you can set various options, such as keypad locking, keypad lighting brightness in stand-by mode, the display in stand-by mode, the buzzer volume and manual dispenser activation (optional); you can also check the time until scheduled maintenance (optional; read-only).
To change the options settings, navigate to the “Nastavitve” (Settings) menu. Use the plus and minus buttons to navigate the submenus. To change a value, press the “Confirm” button and use the plus and minus buttons to set the value appropriately. When you are finished, press the “Confirm” button to save the changes.
The “Zaklepanje tipkovnice” (Keypad locking) submenu enables keypad lock in order to prevent changing the settings accidentally. If the keypad is locked, you can view the settings and current values, but you can not change them (except to unlock the keypad). The “Zaklepanje tipkovnice” (Keypad locking) submenu offers the following options:
OFF: the keypad is not locked; all the buttons are active
Lo: changing the settings is disabled (the “Confirm” button is inactive)
Hi: changing the settings is disabled and so is the turning the system on/off (you can only return
to the “Lo” or “OFF” state)
Keypad locking
We recommend that you lock the keypad during the cleaning of the user interface or if there is a possibility of children without adult supervision tampering with the combustion device.
The “Svetlost-stanje pripravljenosti” (Brightness - stand-by mode) submenu allows you to save energy by lowering or even disabling the keypad lighting in stand-by mode. When you touch the keypad, its lighting level is increased to the default value.
The “Prikaz-stanje pripravljenosti” (Display - stand-by mode) submenu offers the following options:
OFF: The keypad remains in the menu that was selected most recently.
“Možnost 1” (Option 1): the keypad exits the selected menu and alternately displays the current
temperature, the fuel autonomy (optional) and the time. If the “Avtonomija goriva” (Fuel autonomy) option is set to OFF, or if your heating system doesn’t have the ability of displaying the autonomy, this entry is skipped.
“Možnost 2” (Option 2): the keypad exits the selected menu and switches to the “Temperatura” (Temperature) menu. The screen displays the current temperature.
“Možnost 3” (Option 3): the keypad exits the selected menu and switches to the “Ura” (Clock) menu. The screen displays the current time.
“Možnost 4” (Option 4): the keypad exits the selected menu and switches to the “Avtonomija goriva” (Fuel autonomy) menu (optional). If this option is set to OFF, or if your heating system doesn’t have the ability of displaying the autonomy, the keypad switches to the “Temperatura” (Temperature) menu.
The “Glasnost piskača” (Buzzer volume) allows changing the volume of the sound signals the keypad emits on button presses.
The “Ročni vklop dozirnika” (Dispenser - manual activation) (optional) allows manual activation of the dispenser. The dispenser will work for a short while and then stop. You can use this option to clean or empty the dispenser, or you can use this functionality before the first ignition, when the dispensing system is completely empty.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 33
The “Čas do vzdrževanja” (Time until maintenance) submenu (optional) shows the days remaining before you will have to have a trained service person perform the regular maintenance and inspection of your heating system. This value (in days) is read-only and can only be changed by authorised service personnel.
14.11. Troubleshooting
The Fumis ALPHA keypad shows warnings about the errors that can occur during the heating system operation. The indicator lights warn you about problems. In case of a warning, the light blinks; in case of an error, the light stays on. In case of a warning, the heating system continues to operate, whereas in case of an error, the operation of the heating system may be seriously impaired and experts should be contacted.
Every warning and error has a code, so you can identify the problem. To show the code, press and hold the “Cancel” button. If there is no data, the screen displays ----.
Warning Cause / Solution
Warning: The “Ni goriva” (No fuel) alarm is blinking
Cause: When the hopper is nearly empty, the warning is triggered.
Solution: Refill the hopper.
Code: A001 Warning: The “Ni goriva” (No fuel) alarm
stays on
Cause: When the hopper is empty, the warning is triggered.
Code: ----
Solution: Refill the hopper. Reset the “Avtonomija goriva” (Fuel autonomy) option to Full.
Warning: The “Ččenje” (Cleaning) alarm is blinking
Cause: The flue gas temperature has reached a level where the combustion device starts to automatically lower the operating power.
Code: A003
Solution: Turn the combustion device off and contact an authorised service shop, requesting a preventive inspection/cleaning of the heat exchanger before starting the combustion next time.
Warning: The “Ččenje” (Cleaning) alarm stays on
Cause 1: The combustion chamber, the chimney or the heat exchanger is/are dirty and have to be cleaned. There may be too much ash or unburned pellets in the combustion chamber; the chimney and/or the heat exchanger may be clogged with soot.
Code: ----
Solution 1: Check and clean the combustion chamber, or get a chimney sweeper to clean your chimney, or have authorised service personnel clean the heat exchanger.
Cause 2: You have turned the combustion device on and then off again (using the on/off button) before it transitioned from the ignition phase to the normal operation phase. Blowing-out is performed (if it is activated).
Solution 2: If the fuel in the combustion chamber of the device is burning, wait until it finishes burning and the combustion device stops completely. Before starting the combustion next time, make sure that the combustion chamber is completely empty and press the on/off button twice (first to clear the alarm and then to turn the combustion device on again).
Warning: The “Vzdrževanje” (Maintenance) alarm is blinking
Cause: The internal battery of the Fumis ALPHA controller is almost empty. The heating system can operate normally.
Code: A004
Solution: Call an authorised service person and have them replace the battery. Do not attempt to replace the battery on your own.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 34
Warning: The “Vzdrževanje” (Maintenance) alarm is blinking
Cause: The fan speed sensor (if the fan in your combustion device is so equipped) is faulty. The heating system can operate normally.
Code: A005
Solution: Call an authorised service person.
Warning: The “Ččenje” (Cleaning) and
“Vzdrževanje” (Maintenance) alarms are blinking
Cause: The “Čas do vzdrževanja” (Time until maintenance) counter shows, in hours, the time left before you will be required to perform the regular inspection of your heating system. The counter counts down time, shown in hours; when it reaches 0, the “Vzdrževanje” (Maintenance) alarm starts blinking. The counter value is read-only and may only be changed by authorised service personnel.
Code: A002
Solution: Call an authorised service person.
Warning:
The “Vzdrževanje” (Maintenance) alarm stays on
Cause: The heating system has malfunctioned and does not operate. The possible causes are:
Code E001: Keypad malfunction
Code E002: IR communication malfunction
Code E003: RF communication malfunction
Code E004: MB communication malfunction
Code E101: Combustion-related malfunction or
excessive water temperature
Code E105: NTC2 malfunction
Code E106: NTC3 malfunction
Code E107: TC2 malfunction
Code E108: Safety switch malfunction
Code E109: Pressure switch malfunction
Code E110: NTC1 malfunction
Code E111: TC1 malfunction
Code E112: Excessive fuel temperature
Code E115: General malfunction
Solution: Write down the error code and call an authorised service shop.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 35
15. WIRING DIAGRAM
Instructions for Use, Maintenance and Installation Pellet boiler PP27 A – G3
© Petrič d.o.o. / august 2016 36
16. INFORMATION REGARDING THE DESTRUCTION AND DISPOSAL OF THE BOILER
The responsibility for the destruction and disposal of the pellet boiler lies exclusively with the owner of the boiler; the owner must act according to the safety and environmental protection laws valid in the country of their residence.
The destruction and disposal of the pellet boiler may be assigned to a third party, if the party has a licence or an authorisation to dispose of and destroy the materials in question.
INDICATION: You must, in any case, observe and follow the laws valid in the country where the pellet boiler is installed.
WARNING All the parts that are dismantled in order to be destroyed, have to be removed properly:
remove all the electrical components;
separate the battery from the controller;
dispose of the controller battery into suitable waste containers in a way compliant with the
applicable normatives;
the boiler core should be disposed of or sold as scrap iron.
WARNING A discarded pellet boiler in an accessible location presents a serious hazard for people and
animals. The owner of the boiler is always responsible for any resulting damage.
When the boiler is destroyed, the CE marking, the Instructions for Use, Maintenance and Installation and other documents associated with the boiler should be destroyed along with it.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 37
17. WARRANTY CONDITIONS
17.1. INSPECTION:
In order for the warranty to be valid, as noted in the EEC directive 1999/44/E (42/2002), the user must carefully observe the instructions contained in this document; in particular the following:
The pellet boiler must be used according to its capabilities and pursuant to the conditions contained in the instructions for use.
The pellet boiler should be maintained diligently and consistently.
All the safety measures should be observed, in accordance with applicable laws.
Any tampering with the product should be avoided.
Only original spare parts should be used.
17.2. WARRANTY TIME CONDITIONS:
The warranty for all of our products is valid for 24 months from the date of the first start, provided that an authorised service person performed the regular service inspection 12 months from the first start date, at the latest.
17.3. GENERAL WARRANTY CONDITIONS:
17.3.1. We declare the following:
In the warranty period, the product will perform flawlessly, provided that it is used as intended and in accordance with the included Instructions for Handling and Maintenance.
That during the warranty period the PETRIČ d.o.o. company will, through authorised service shops, resolve all the malfunctions and faults that cause the device to not operate as intended, within 45 days from a written report of the malfunction or fault.
That the product, if not repaired within the previously specified period, will, upon the owner’s request, be replaced with a new one; the warranty period will be prolonged by the repair time.
That the warranty conditions are guaranteed by an authorised service shop with a signature and a stamp on the issued warranty statement.
17.3.2. Claiming the warranty
The warranty is valid under the following conditions:
The buyer has a valid document (a receipt) issued by the seller.
The combustion device was installed by a qualified and/or trained person who had evaluated if the
device was suitable for the technical characteristics of the system at the installation site, and that the installation was compliant with the requirements stated in the instructions.
The pellet boiler is used according to the instructions for use.
The warranty claim is made with the seller, where the device was purchased. When reporting the malfunction, supply an exact description of the malfunction - fault.
17.3.3. The period of time that spare parts and service is guaranteed
the period of guaranteed service and spare parts provision for proper operation of the device is 7 years from the date of the first start;
in case the model K11 is replaced, we guarantee spare parts for your product for the 3 following years;
after 7 years, the spare parts will still be provided, but they may only be obtainable in colour schemes different from those of your product.
17.3.4. The warranty does not cover damage due to the following:
Weather, chemical and electro-chemical effects, lightning strikes, natural disasters, inappropriate use of the product, inadequate maintenance, modifying the product or tampering with it,
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 38
unsuitability or inefficiency of the chimney, or other causes that are not due to the product itself, such as an improper or unsuitable installation.
The burning of materials other than those of the type specified in these instructions.
Any damage caused by/during the transport unless Petric d.o.o. is also the carrier, the product
should be thoroughly inspected on delivery. In case it is found to be damaged, the seller should be immediately notified and the damage must be recorded on the delivery note or the docket.
If the start was performed by a company who had not obtained a suitable authorisation for our products.
If the product was tampered with or serviced by an unauthorised person.
If the user did not observe the instructions for use and maintenance.
If faults or malfunctions occur on the K11 heating device because of the malfunctioning of
equipment by other manufacturers.
The responsibility of the PETRIČ d.o.o. company is limited to the delivery of the device. The unit must be installed properly, in accordance with the manufacturer’s instructions, as well as in compliance with applicable laws. The installation has to be performed by qualified personnel, selected by the manufacturer or by the representative/dealer1 (and/or under their supervision and on their responsibility), who takes on the entire responsibility for the final installation and the eventual correct operation of the installed product. In case these conditions are not satisfied, the PETRIČ d.o.o. company is in no way responsible.
1
Representative/dealer means any natural or legal person authorised to sell articles to the end-users of this warranty.
NOTE
PETRIČ d.o.o. shall not be liable for any damage or consequences, even in case of those arising from a replacement of a malfunctioning component of the boiler.
If any components break down or stop working properly during normal use, they are to be replaced.
17.4. THE COMPONENTS SUBJECT TO NORMAL WEAR AND THUS NOT COVERED BY THE WARRANTY
Any components break down or stop working properly during normal use, they are to be replaced. The components subject to normal wear and thus not covered by the warranty are:
Gaskets and cast-iron parts that do not demonstrate any faults that could be due to a production error;
Discolorations, cracks and small changes in dimensions are not considered to be a justified reason for rejection, as they are a consequence of the natural material characteristics.
Ignition plug.
Combustion vessel.
17.4.1. SERVICE WITHIN THE WARRANTY PERIOD
PETRIČ d.o.o. deals with warranty-related problems only through their authorised personnel.
17.5. THE COURT OF JURISDICTION
The Court of Nova Gorica has the competence for the settlement of disputes. In case of spare parts replacement, the warranty is not prolonged. The PETRIČ d.o.o. company shall not be liable for the reimbursement of the costs incurred during the
period of time that the boiler was not operational.
The PETRIČ d.o.o. company shall no be liable for mistakes in the instructions. We retain the right to make modifications without prior notice.
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 39
18. MODEL K11 TECHNICAL CHARACTERISTICS
Output
Minimum Nominal
*Thermal output (kW)
9,15 32,97
*Efficiency (%)
91,5 92,8
Hourly pellet consumption (kg/h)
2,1 7,45
CO emissions (at 10% O2) [mg/m3]
345 72
Average flue gas temperature [°C]
62,8 126,1
Flue gas mass flow [kg/s]
6,5 16,2
Boiler class according to EN 303-5:2012
5
Boiler resistance at T=20°C [mbar]
33
The boiler water temperature setting range [°C]
70 - 80
Minimum return water temperature [°C]
55
Chimney connector
Ø100 mm
Water connections
DN25 (1˝)
Weight
~ 315 kg
Fuel
Wood pellets
Pellet hopper
~ 280 litres (~ 180 Kg)
Hopper opening dimensions
600 mm x 950 mm
Burning time with a full hopper at nominal power
24,2 h
Water volume in the boiler
~ 85 litres
Chimney draft
0.11 mbar
Power supply
230 V~
Frequency
50 Hz
Highest use of electricity during boiler operation
31W 72W
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 40
Highest use of electricity at boiler ignition
341 W
Electrical energy consumption in stand-by mode [W]
2 W
Noise pollution
50 B(A)
*Values measured in testing laboratory
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 41
19. BOILER IMENSIONS AND CONNECTIONS
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 42
20. DECLARATION OF CONFORMITY
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 43
21. CE LABEL
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 44
22. CONNECTION DIAGRAMS (hydraulic and electric)
22.1. General connection diagram
Return water protection
Hydraulic boiler connection must be implemented with return protection system.
It must must be ensured that return water temperature is never lowet than 55°C!
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 45
22.2. An example of the boiler connection
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 46
22.3. Electrical connection diagram of the boiler
There are two cables at the back of the K11 boiler. A white cable, marked “230V~”, is connected to one of the customer’s electrical outlets, while the cable marked črpalka” or “pump” is connected to the pump for the protection of the boiler return line.
BOILER K11
Instructions for Use, Maintenance and Installation Pellet boiler K11 Type; PP27 A – G3
© Petrič d.o.o. / august 2016 47